Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹85.9 LAccepted-AOC | L1 | Accepted-AOC OK | |
| 2 | L2₹92.4 L+₹6.5 L (7.58%)Rejected-AOC 306 SHIV BARI MARG PANCHVATI NAGAR BATHINDA 151001 PB | BATHINDA | BATHINDA | PUNJAB | 151001 | L2 | Rejected-AOC OK | |
| 3 | L3₹1.1 Cr+₹19.7 L (22.9%)Rejected-AOC | L3 | Rejected-AOC OK |
Tender Value
₹80 L
EMD Value
₹1.4 L
Closing Date
22 Aug 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE AF Bhisiana
CWE AF BHISIANA
CWE(BHI)/BHI-13/2022-23
2022_MES_529236_2
CWE(BHI)/BHI-13/2022-23
Open Tender
Civil Works
Item Rate
180 days
AF Bhisiana
AS PER COVER 1
6 documents required · 6 mandatory
₹1,000
Yes
GE AF Bhisiana
₹1.4 L
Yes
29 Sept 2022
26 Jul 2022
24 Aug 2022
26 Jul 2022
22 Aug 2022
10 Aug 2022
26 Jul 2022 - 2 Aug 2022
60 days
Amount
S & F Energy saving ceiling fan 1200 mm sweep with double ball bearing with 5 star rating alongwith 5 amp flush type switch fixed in existing phenolic laminated sheet for ON/OFF ceiling fan white color with ISI marking complete including provision of three core copper wire of suitable size, connected from ceiling rose to fan, complete all as specified and as directed.
S & F stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc, complete all as specified and as directed.
S & F Energy saving ceiling fan 1400 mm sweep with double ball bearing with 5 star rating alongwith 5 amp flush type switch fixed in existing phenolic laminated sheet for ON/OFF ceiling fan white color with ISI marking complete including provision of three core copper wire of suitable size, connected from ceiling rose to fan complete all as specified and as directed.
S & F stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc, complete all as specified and as directed.
Supply , install , Testing & commissioning of Transformer floor mounted capacity 100 KVA ,step down, outdoor type11/0.433 KV,50Hz, AC double wound core type copper wound ,oil immersed ,air naturally cooled with external cooling tubes, transformer delta connection on HV side and star connection on LV side in accordance with vector symbol DyN-11 ( vector group 4) and having tapping of ± 7.5% in equal step of 2.5 % changed by means of auto on load tap changing arrangement. The voltage regulation shall be as per IS including first fill of transformer oil as per IS-335 and including all fittings /accessories as specified in SSR Part -1 and IS -1180 the transformer should have cable box on LT side and brass bushing on HT side. The limit of temp rise after continuous full load run as specified in SSR part-I and IS -2026 shall be suitably adjusted to suit the maximum ambient temp prevailing at site all as specified (i) 01 No Cable box on LT side consisting of 03 Nos porcelain bushing with bushing brass rods and nuts washers and cable glands of suitable for reception of cable LT 1100 Volt grade XLPE insulated heavy duty including gland joint complete.(ii) HV bushing with arching horn on 11 KV side.(iii) Oil Conservator with filter type drain valve and oil level gauge.(iv) Dehydrating Breather with first filling of Dehydrating Agent .(v) Explosion Vent.(vi) THERMOMETER Pocket(vii) Two Earthing Terminal on tank body to facilitate fixing of 32x6mm GI strips.(viii) One No Thermometer Dial Type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature gauge : Max reading painted (ix) Rating plate with terminal marking plate. (x) Oil level gauge. (xi) Oil drain filter valve. (xii) Oil filling port on top cover with plug.(xiii) Air release valve/plug (xiv) 4 Nos plain solid cast steel detachable rollers.(xv) Shut off valve between conservator and bucholz relay. (xvi) First fill of transformer oil conforming to relevant IS and tested upto 60 KV dielectric strength.(xvii) Inspection cover.
(xviii) Lifting lugs and jack lifting pad support. (xix) Bi-directional plan / flanged rullers. (xx) Explosion vent with double diaphragm and sight glass. (xxi) Silica gel breather or with connecting pipe, first fill of dehydrating agent. (xxii) Hand hole of sufficient size to assess the interior of the tank.(xxiii) Cover lifting eves. (xxiv) Double float bucholz relay with trio and alarm contacts. (xxvi) Rail section and channel embedded in foundation of suitable size in and including PCC 1:3:6 type C-I plate form size 3.0x2.5x1.0 Mtr. Including ramp and necessary earth work and excavation as directed. (xxv) Oil temp indicator of approved range, including shutt of valve between conservator and main tank.(xxvi) Winding temp indicator of approved range ,including shutt of valve between Conservator and main tank. (xxvii) Drain valve with threaded adaptor. (xxviii) Filter valve with threaded adaptor. (xxix) Sample valve. (xxx) Extra bushing for neutral outside the LV side. Note: 1. The oil temperature and winding temperature gauges shall be housed on a MS box shall be 0.6Mx0.6Mx0.3M with hinged door and having glass 3 mm thick front side of the box and provision for entry of cables and compression glands. 2.Contractor shall arrange for factory visit for GE/EIC/or his Rep to check theabove Note : The rate shall be included for making cable connection for HT/LT side from Transformer to existing taping point.
All as per item No 05 above but 75 KVA Capacity.
M & L for earthing complete with galvanised steel steel earth plate electrode 600x600x6mm thick burried directly in ground (earth pit not less than 2.25 mtrs deep below nominal ground level) with top edge of the plate not less than 1.5 mtrs below nominal ground level connected to galvanised strip 32x6 mm by means of bolts, nuts, check nuts and washers of GI all as shown in electrical plate No 3 of SSR Part I connected to earthing test point and testing on completion. all as specified and as directed. Note:- the cast of excavation and earth work PCC pit and PCC cover with handle, funnel & watering pipe, wiremesh,charcoal dust and common salt and earth strip up to 7.5 mtrs long shall be deemed included in the unit rate for earthing, complete all as specified and as directed.
M&L for cable jointing kit for 11 KV (earthed) grade cable for outdoor termincatioon heat shrink type joint complete with jointing materila and accessories suitable for 3 core XLPE armoured aluminium conductor cable pf size 120 to 185 sqmm , complete all as specified and as directed.
M&L for cable jointing kit for 11 KV (earthed) grade cable for outdoor termincatioon heat shrink type joint complete with jointing materila and accessories suitable for 3 core XLPE armoured aluminium conductor cable pf size 50 to 95 sqmm, complete all as specified and as directed.
Supply & Laying of , LT UG XLPE insulated 1100 volt grade heavy duty electric cables with aluminium conductor , cross sectional area 150 sqmm 3.5 core(From Existing panel to proposed pnl), complete all as specified and as directed.
Supply and Laying , LT UG XLPE insulated 1100 volt grade heavy duty electric cables with aluminium conductor , cross sectional area 70 sqmm 3.5 core (From Main panel to AC Panel), complete all as specified and as directed.
Supply and Laying , LT UG XLPE insulated 1100 volt grade heavy duty electric cables with aluminium conductor , cross sectional area 35 sqmm 3.5 core (From panel to AHU), complete all as specified and as directed.
M & L for earthing complete with galvanised steel steel earth plate electrode 600x600x6mm thick burried directly in ground (earth pit not less than 2.25 mtrs deep below nominal ground level) with top edge of the plate not less than 1.5 mtrs below nominal ground level connected to galvanised strip 25x4 mm by means of bolts, nuts, check nuts and washers of GI all as shown in electrical plate No 3 of SSR Part I connected to earthing test point and testing on completion. all as specified and as directed. Note:- the cast of excavation and earth work PCC pit and PCC cover with handle, funnel & watering pipe, wiremesh,charcoal dust and common salt and earth strip up to 7.5 mtrs long shall be deemed included in the unit rate for earthing, complete all as specified and as directed.
Material and labour for PCC 1:3:6, type C-1, using 20mm graded stone aggregate for road cutting / making plith for transformer where required and fair finishing to exposed surfaces without using extra cement including necessary form work, complete all as specified and as directed.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure, complete all as specified and as directed.
Supply fix and test Cable tray perforated of 150 mm width, 50 mm height and of 14 Gauge powder coated including coupler plate, bends, angle iron 40x 40x 5 mm size at suitable distance for support with wall etc , complete all as specified and as directed.
Dismantling of U/S XLPE cable any size from plant and Cable Tray and deposited in MES stoe for reuse. The cost shall be included Transportation & T&P , labor etc, complete all as specified and as directed. Note :- The cost shall be inclusive Making good surface and with exisitng surface using PCC1:3:6 PCC work
Dismantling of Existing LT / Control panel from Existing plant or any other location and deposited in MES store. The cost shall be included Transportation & T&P , labor etc, complete all as specified and as directed. Note :- The cost shall be inclusive Making good surface and with exisitng surface using PCC1:3:6 PCC work
Supply and laying 100 mm bores of tubes light grade' galvanised with all fittings and fixed complete laid in trenches/wall and ceilin or laid in floors, complete all as specified and as directed.
M & L for excavation in trenches, not exc 1.5 m wide and not exc. 1.5 m in depth for foundation and getting out hard/dense soil , complete all as specified and as directed.
M & L for returning filling in including spreading, levelling, watering and ramming in layers not exceeding 25 cm thick with earth obtained from excavation, complete all as specified and as directed.
M & L for removal of surplus soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 mtr above the starting point , complete all as specified and as directed.
M&L Fazilka sand as in sand cushioning to under ground cable including punning down, complete all as specified and as directed.
Supply and laying reinforced precast concrete cable cover, class LV, type 1, flat size 250 mm x150 mm x 40 mm, complete all as specified and as directed.
Dismantling of cement concrete/Brick wsorks in ground floors and paving exceeding 15 cm thickness (below or above ground level). The cost shall be included Removing of dismantling PCC Material at site and deposited out of air force stn Bhisian Minimum distance 2000 mtr away from site, complete all as specified and as directed.
Labour for Disconnecting the existing 100/80 mm DI/GI pipe ,suction and delivery end of any type from the existing pipe in under ground and supply and fixing with new pipes of various material and sizes of pipe given in schedule , all as specified and directed. Note The cost of included for fitting like , bends, Tee, Union, Socket, Mechanical Joint, Nipple etc of any size required to connect fro existing pipe to new proposed pipe. The cost of also included excavation required to cutting of pipe.
Material and labour for construction of valve pit chambers of size 750mm X 750mmX 700mm (internal dimensions) as under provided with 10 cm thick PCC 1:4:8 type D2 as in foundation over 15 cm thick hard core, 23 cm thick brick walls built in cement mortar 1:4, 15 mm thick internal plaster including top of floor, externally upto 150 mm below GL in CM 1:3 finish even and smooth without using extra cement, 4 mm thick MS sheet cover with 40 x 40 x 6 mm MS angle frame fixed in PCC 1:2:4 type B1 coping with 25 x 6 mm flat iron hold fasts, hinges, handles, locking arrangements and applying 2 coats of synthetic enamel paint over acoat of red oxide primer to all steel surfaces and 3 coats of white wash to internal surfaces of chamber including excavation and earth work in any type of soil and removing of surplus soil to a distance not exceeding 50 m , complete all as specified and as directed.
Supply and laying 50 mm bores of tubes 'medium grade' galvanised with all fittings and fixed complete laid in trenches, complete all as specified and as directed.
Supply and fix Gate valve, 50 mm with iron wheel head, screwed both ends for iron pipe and fixed , complete all as specified and as directed.
Supplying and laying 25 mm bores of tubes 'medium grade' galvanised with all fittings and fixed complete laid in trenches, complete all as specified and as directed.
S & F rotational moulded polyethylene water storage tanks ISI Mark of capacity 5000 Ltrs 3 layers (cylinderical vertical with closed top threaded type white colour ) hoisted and fixed in position including inlet and out let connection all as specified and directed.
S & F rotational moulded polyethylene water storage tanks ISI Mark of capacity 500 Ltrs 3 layers (cylinderical vertical with closed top threaded type white colour ) hoisted and fixed in position including inlet and out let connection, complete all as specified and as directed.
Supply & fix 25 mm (FLOAT VALVE ) ball valves high pressure of PTMT with epoxy coated Aluminium rod and high density plastic ball screwed for iron pipe and fixing with, complete all as specified and as directed.
Supply and fix Gun-metal, globe or gate valves 25 mm dia with iron wheel head, screwed both ends for iron pipe and supply fixed new one, complete all as specified and as directed.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure, complete all as specified and as directed.
M&L for Brick work with sub class 'B' old size bricks, straight or curved on plan exceeding 6 mtr mean radius built in CM 1:4 complete in surface channel etc, complete all as specified and as directed.
Dismantling of existing foundation of water / Cooling tower / pump / compressor / LT panle made out of Brick wsorks / PCC in ground floors and paving exceeding 15 cm thickness (below or above ground level). The cost shall be included Removing of dismantling PCC Material at site and deposited out of air force stn Bhisian Minimum distance 2000 mtr away from site, complete all as specified and as directed.
M&L for Cement plaster 1:4 rendering 10mm thick on fair faces of brick work or concrete surfaces and or deduct to/form the rates for each 5mm thickness over or under 10mm thick, complete all as specified and as directed.
Material and labour for PCC 1:3:6, type C-1, using 20mm graded stone aggregate under pipe line as anchor blocks at the places where required and fair finishing to exposed surfaces without using extra cement including necessary form work complete all as specified for making foundation of water storage tanks, complete all as specified and as directed.
M & L for excavation in trenches, not exc 1.5 m wide and not exc. 1.5 m in depth for foundation and getting out hard/dense soil, complete all as specified and as directed.
M & L for returning filling in including spreading, levelling, watering and ramming in layers not exceeding 25 cm thick with earth obtained from excavation, complete all as specified and as directed.
M & L for removal of surplus soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 mtr above the starting point, complete all as specified and as directed.
M & L for sub main wiring (concealed) complete with two single core 4 Sqmm FR PVC insulated unsheathed stranded copper conductor cable drawn through in and including 25 mm dia rigid non-metallic PVC heavy duty conduit and conduit accessories including 4 Sqmm FR PVC insulated unsheated stranded copper earth cable connected to common earth dolly complete and including cutting chasing in walls for concealed wiring using machine cutting and making good the disturbed surface all as specified and directed by EIC. Note: 3 run of 4 sqmm & one run of PVC conduit shall be measured as single unit, complete all as specified and directed. Note: The disturbed surface of wall for surfacce box wiring shall be make good by applying cement plaster, putty and colour wash etc matching with the existing surfaces. The rate for point wiring shall be deemed to include the costof making good.
Supply and install invertor based split AC with cordless remote of capacity 02 TON ,(Copper coil) electric driven single phase , 230 volts, 5 star rating including all accessories like brackets, rubber tubing , copper tubing as required at site, gas charging , with auto filter clean technilogy etc including testing and commissionin with as per norms of BEE and making good to the disturbed surface to match the existing surface, complete all as specified and directed. Note :- All cooling /condensing coil should be copper material
Supply and install Voltage stablizer coppper winding automatic digital type operation single phase naturally air cooled indoor type & designed for input variation between 90 Volt to 250 Volt with output voltage stablized at 230 Volt with accuracy of (+/-)2.5 percent of capacity 5KVA, complete all as specified and directed.
Supply and fix sheet metal enclosure with socket plug top single pole and neutral enclosure with a two pin and earth plug and socket with one single pole MCB 20 Amps, complete all as specified and directed.
Supply and fix new copper tubes of size 3/8 inch for suction line including rubber tube insulations of same size for fixing AC, complete all as specified and directed.
Supply and fix new copper tubes of size 5/8 inch for suction line including rubber tube insulations of same size for fixing AC, complete all as specified and directed.
Supply and fix PVC rigid conduit pipe ISI Mark 25 mm dia including all accessories and necessary saddles with fixing screws, gutties etc, complete all as specified and directed.
Supply and fix split AC stand of outdoor unit suitable for 1.5/2 ton including necessary fixing arrangement. Such drilling holes in wall, anchoring in wall, nut , bolts etc, complete all as specified and directed.
SCROLL CHILLER - WATER-COOLED (2 working + 1 standby) Supply, Installation, Testing and Commissioning of water-cooled scroll chiller with single/multi compressors, comprising of Hermetic compressors / Screw/Scroll compressor, DX Evaporator, shell & tube condenser, suitable expansion device, suitable for operation on R-407C refrigerant and complete in all respects, as required of 11 TR actual cooling capacity. Water Temperature IN - 54 deg F Water Temperature OUT - 44 deg F Fouling Factor - 0.0005 FPS Condenser: Water Temperature IN - 90 deg F Water Temperature OUT - 97.5 deg F Fouling Factor - 0.001 FPS. Water flow rate through Chiller - 70GPM Water flow rate110 LPM (29 GPM through Condenser - Note: - Next higher capacity of chiller can be supplied within overall cost quoted Note:- Suitable arrangement of platform and connected accessories for installing chiller unit with anti-vibration pads and as per OEM instructions.
Cooling Tower Supply, installation,commissioning and testing of induced draft top discharge counterflow type FRP Cooling tower suitable capacity of 11 TR AC plan with a adequate quantity of Cellulose pad (Rectangular/Roundbottle shape) with FRP body and base, the cooling tower is with water spray headers, Cooling tower Fills with adequate quantity of cellulose PVC fibers in plastic form as per OEM recommendation, fan with motor, supporting baseframes, FRP basin with integral louvers and drift eliminators complete with hot water basin either fitted with spray nozzles or having self rotating sprinklers, 1 no axial flow type fan-direct driven or driven through reduction gear box with TEFC induction motor withgood efficiency , suction screen, make-up quick fill arrangement, overflow and drain connections and suitable inspection ladder to access arrangement for cooling tower interior, Range: 4.5 Deg. C/ 7.5 Deg. F Condenser water inlet/outlet temp-90-97 Deg F Wet Bulb Approach: 2.78 Deg. C/ 5 Deg. F Capacity of cooling tower-33TR
Electric Hot Water Generator Supply, installation, testing and commissioning of electrical Hot water Generator of vertical construction equipped with sufficient number of flanges and electric emersion heaters. The pressure vessel shall be constructed as per ASME standards and insulated on all sides with 50 mm thick fiberglass with 0.6mm Aluminium cladding as per specifications.The hot water generator shall be equipped with all automatic and safety controls such as manual reset, high temperature water cutout, step controller, on/off switch, pilot light,low water cut off and other controls as per manufacturers recommendations.All basic controls and terminals shall be located in an integral control cabinet factory wired and tested. The hot water generator shall be suitable for 415 volts, 50 Hz, 3phase power supply.The entire hot water generator shall be factory assembled and tested. 45 kW Hot Water Generator as described above Water ‘in’ temperature‐ 45 Deg C Water ‘out’ temperature‐ 50 Deg C
Chilled Water Pumps Supplying, erection, testing and commissioning of chilled water centrifugal pump set capable of delivering 59GPM /223LPM of water against a head of 20mtr. Each pump shall comprise of following as required as per specifications. and as located shown on drawing.(1w+1s) End pump shall be monoblock type and top discharge complete with 5HP sq cage induction motor with mechanical seal bronze impeller suitable for 400/3ph/50hz supply.the motor pump shall be insulated with pipe line material.
Condenser Water Pumps Supplying, erection, testing and commissioning of condenser water centrifugal pump set capable of delivering 88GPM of water against a head of 15mtr. Each pump shall comprise of following as required as per specifications. and as located shown on drawing.(1w+1s) End pump shall be monoblock type and top discharge complete with 3HP sq cage induction motor with mechanical seal bronze impeller suitable for 400/3ph/50hz supply.
Hot Water Pumps: Supplying, erection, testing and commissioning of hot water centrifugal pump set capable of delivering 34GPM /128LPM of water against a head of 20mtr. Each pump shall comprise of following as required as per specifications. and as locatedshown on drawing.(1w+1s) the centrifugal pump shall be coupled to 3hp (1450 rpm) motor with steel base and shall be insulated with pipe line insulation material.with mechanical seal bronze impeller suitable for 400/3ph/50hz supply.the motor pump shall be insulated with pipe line material. Note for Item no 3.12, 3.13 & 3.14: a) Head calculation shall be submitted by contractor for approval by GE. No price adjustment shall be carried out for variation of plus/minus 5 meters. b) DIscharge calculation shall be submitted by contractor for approval by GE. No price adjustment shall be carried out for variation of plus/minus 10%
AIR HANDLING UNITS Supply, Installation, Testing and Commissioning of factory-built Floor standing double skin type air handling units capacity of 6000cfm with thermal break profile made of 25 mm thick panels consisting of pre-plasticized G.l. casing of thickness 0.8 mm outside and 0.8 mm thick Gl sheet inside layer with CFC-FREE P.U. insulation of density 42 (+5%) kg/m3 factory injected between them by injection moulding machine, complete with Direct Driven plug fan of 65 mmWG static pressure. The unit shall consist of 4/6 rows deep of cooling coil and 2 row deep heating coil section with cooling coil as per requirements (not limited to listed below) with aluminium finned(12FPI) copper tubes thickness not less than 0.41 mm), filter sections with 50 mm thick washable synthetic-type Pre-filters having efficiency 90% down to 10 micron, Fine filters having efficiency 99% down to 5 micron, VFD operated motor (Flame-proof) and panel suitable for operation at 415 ± 10% volts, 50 Hz, 3 phase A.C supply, complete with drain connections with drain valve, Insulated stainless steel drain pan, necessary vibration isolation arrangement, flexible duct connector etc., complete blower sections as per following capacities: (a) 20 G SS Drain pan, drain connection. (b) Fine filter should be located after the fan in the direction of air flow. (c) The AHU should have space for humidifier. (d) VFD panel with VFD (quantified separately), necessary control arrangement to switch off the fan in case of fire, indicating lamp & all safety precautions in a flame-proof powder-coated Gl enclosure with necessary power and control cable as required.
Supplying, Installing, Testing and Commissioning of Ultrasonic Humidifier, CAP 9.0 LPH complete with stainless steel tank with float valve, water makeup, overflow and Drain Connection along with suitable arrangement of Inlet/ out let HDPE piping, size of pipe as per OEM Recommendation. Out let connection from Humidifier to Duct and Inlet from Water storage tank to humidifier. The transducer shall be interlocked with float switch, supplied with humidifier, and humidistat with necessary supports by MS structural steel II required, hangers, clamp supports from walls, floors and ceiling with painting with one coat of primer and two coats of paint to supports of MS work.
Supply and lay M S Pipes heavy grade with all fittings laid in floors or fixed to walls and ceilings (with necessary clamps, vibration isolators and fittings ) complete of following sizes :-
50 mm dia
65 mm dia
Supplying, Laying/ Fixing, Testing and Commissioning of following nominal sizes of chiller/hot water. Water piping (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with 25 mm thick closed cell class 'O' Nitrile Rubber elastomeric insulation of density 40-55 kg per cubic metre, thermal conductivity of 0.037 W/mK at 20 degrees Celsius mean temp, and minimum water diffusion resistance of 7000 using manufacturer's recommended 'rubber-based adhesive in a blend of solvents. Nitrile rubber will be covered with a three-layered aluminium cladding thickness of 1 mm and of metallic finish having aluminium as an intermediate layer and UV protection, as per manufacturer's instructions, complete in all respects. Note:- The pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes of sizes above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. sheet for pipes up to 350 mm dla. and from miniumum 7mm thick MS sheet for pipes of 400 mm dia and above.
50 mm dia
65 mm dia
Condenser Water pipe Condenser Water pipeSupply and lay M S Pipes heavy grade with all fittings laid in floors or fixed to walls and ceilings (with necessary clamps, vibration isolators and fittings) complete of following sizes :-
32 mm dia
40 mm dia
50 mm dia
65 mm dia
Valves & fittings Supply, installation, testing and commissioning of following sizes PN-10 butterfly valves insulated in position complete with flanges,bolts, nuts gaskets etc. and conforming to specification complete of following sizes :-
40mm dia
50mm dia
65mm dia
Supply, installation, testing and commissioning of following sizes ball valves insulated in position complete with flanges,bolts, nuts gaskets etc. and conforming to specification complete of following sizes :-
25mm dia
32mm dia
Supply, Installation, testing and commissioning of motorised 3 way modulating insulated Control valves complete with electrical actuator, 50 mm dia, heavy duty PN 10 cast iron body with nylon coated S.G. iron disk, water sealant lining, stainless steel shaft, control lever with thermostat, control wiring, accessories if any like transformer etc.. Insulation shall be as per the connected chilled water piping, complete all as specified as directed.
Supply, installation, testing and commissioning of following sizes PN-10 non return insulated valves in position complete with all requirement. and conforming to specification complete of following sizes :-
32mm dia
50mm dia
65mm dia
Supply, installation, testing and commissioning of PN-10 Y-strainer duly insulated as per specifications. Strainer shall have CI/bronze body & bronze mesh complete of following sizes :-
32 mm dia
50 mm dia
65 mm dia
Expansion Bellow Providing and fixing expansion bellows with control rods/ Spacer in pipe connections to equipment of the following sizes:
32 mm dia.
50 mm dia.
65 mm dia.
Supply, installation, testing and commissioning of OEM recommendation sizes pressure gauges in the chilled water lines with gate valves conforming to technical specifications, complete all as specified and directed.
S & F Industrial type mercury in glass industrial type thermometers with gun- metal/brass conduction isolating valve complete with all accessories as required, complete all as specified and directed.
Supply, installation, testing and commissioning of flowswich in the chilled water lines conforming to specification, complete all as specified and directed.
Supply installation testing and commissioning of one soft makeup water tank for purpose of cooling set makeup water pvc tank of 5000 ltrs. capacity ,associated Gi piping network with required quick fill valve ,overflow connection and valves .the price shall include staging of tank on a masonary /steel frame work of 2mx2mx1.2m(H) etc as per site requirement, complete all as specified and directed.
Supply, Installing, Testing and commissioning of the following capacities PVC open Expansion tank with full XLPE foam insulated The tank shall be designed to absorb the expansion forces of heating/cooling system water while maintaining proper system pressurization under varying operating conditions. The system should include PRV , Airvent /isolation valve also. And complete as per technical specification.
chilled water expansion tank Capacity 500 ltr
Hot water expansion tank Capacity 100 ltr
12 mm thick xlpe insulation on tank
MS angle fram work /stand for chiller expansion tank including masonary /Rcc work such as cutting filling /finishing as per site requirement, complete all as specified and as directed.
MS angle fram work /stand for make up tank including masonary /Rcc work such as cutting filling /finishing as per site requirement, complete all as specified and as directed.
Condensate Drain Pipe Supply, Installation, Testing and Commissioning of PVC drain piping, complete High density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 fixed complete to walls, ceilings or in floors etc.with fittings, supports as per specifications and insulated with 6 mm thick closed cell polyethylene insulation as per specifications and drawings of following sizes :-
25 mm dia
32 mm dia
Make up water GI pipe 25 mm dia for cooling tower ,humidification tank .Pipe laid on floor or fixed to wall as required, complete all as specified and as directed.
AIR DISTRIBUTION SYSTEM Ducting Supply, fabrication, installation and testing of GSS ducting complete with flanges including necessary supporting arrangement with flexible connection in accordance with the approved shop drawings and as per the specifications of following sizes :-
24 G (0.63 mm)(0-750mm)
22 G (0.8 mm) (751-1500mm)
20 G (1.0 mm) (1501-2250mm)
Grilles/Diffuser Supplying, installing & testing of Powder coated Extruded aluminum supply air grilles with volume control damper. All grilles shall be Single louvered complete as per specification & drawings. ,complete all as specified and as directed.
Supplying, installing & testing of Powder coated Extruded aluminum return/exhaust air grilles without volume control damper. All grilles shall be Single louvered complete as per specification & drawings, complete all as specified and as directed.
Acoustic Lining of Ducts Supplying, installing & testing of ducts acoustic liningas per the specifications.The Acoustic lining material Open Cell Engineered Nitrile rubber for Acoustics , of Class-1 , Density 140-180Kg / m3, UL94 approved(HBF, HF 1 & HF 2) in accordance to UL 94,1996.Thermal conductivity of 0.047 W / ( M*K), Air Erosion Resistance test Confirming to ASTM Standard C 1071-05 (section 12.7). For application use low voc Adhesive. thickness 15 mm thick as per specification. [ for duct linear=15mm thk]
Thermal Insulation on Duct Supplying, installing of external thermal insulation on ducts with closed cell Nitrile Rubber Insulation 19 mm thick as per ASTM G797 standard Class “O” IMO A 653 (16), FM Global & UL 94 approved,density 40-55kg /m3. Temperature of -50 to 116 Deg C and Thermal conductivity of 0.036 W / m Deg K @ 0 deg C. water vapour permeability as per EN12086 (DIN 52615) , Moisture Resistance Factor >= 7000. And coated with 2coats of protective coating for exposed/external applications.For application use Low voc Adhesive K414 of 19 mm thick, complete all as specified and as directed. Note :- The suitable bypass arrangement from condenser pump to cooling tower will be made by the contractor to avoid of shutdown of plant due to blockage of scale guard.
Fresh Air Louvers Supplying, installing and testing of Fresh Air inlet louvers with volume control damper & bird screen in accordance with approved shop drawings and specifications.Aluminium extruded fresh air louver with VCD & Bird screen and filter, complete all as specified and as directed.
Canvas connection Supplying, fabricating, installing and testing of double canvas flexible connection for constructed of standard material as per the drawings/ specifications, complete all as specified and as directed.
Fire Damper Supplying, Fixing,testing and commissioning of fire dampers where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
Fire damper
Actuator
Cables XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, of following cross-sectional area :-
3.5 core 50 Sq mm Al
4core 10 Sq mm Al
4 core 6 Sq mm Al
Supply, installation, testing and commisioning of control cum transmission copper cable/wire of following sizes :-
2 core 1.5 sqmm control cable
3 core 1.5 sqmm control cable
Earthing Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc:-
25 mm x 4 mm GI strip
8 SWG GI WIRE
FLEXIBLE CONNECTIONS Supply, Installation, Testing and Commissioning of 65 mm dia flexible connector for following dia. pipe having PN 1.6 working pressure with anti-vacuum rings complete with flanges, nuts, bolts, seal etc.to be installed at chiller suction and discharge, complete all as specified and as directed.
FLEXIBLE CONNECTIONS Supply, Installation, Testing and Commissioning of 50 mm dia flexible connector for following dia. pipe having PN 1.6 working pressure with anti-vacuum rings complete with flanges, nuts, bolts, seal etc.to be installed at chiller suction and discharge, complete all as specified and as directed.
Material & labour for earthing with steel earth plate electrode 600 X 600X 6.00 mm thick buried directly in ground vertically at a depth not less than 2.25 meter below normal ground level with top edge of earth plate at a depth not less than 1.5 meter below normal ground level, earth plate surrounded from all sides by 15 cm thick packed layer of charcoal duct and common salt filling in alternate layers and electrode connections by using GI stip 25X 4 mm as earthing lead (upto the boby of the equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm dia GI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40 mm graded stone aggregate, including excavation and earth work in any type of soil, returning, filling in approved soil and disposal of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No. 3 of SSR 2009 (Part-I) complete all and as directed by engineer- in-charge.
S&F 50 MM dia BALANCING VALVE with BUILT-IN MEASURING FACILITY of Gun metal construction up to 50 mm dia. & cast steel/ ductile iron body up to 50 mm dia. as required having flanged construction with SS disc having long pitch with protruded out pipe insulation & suitable for PN 1.6 working pressure for condenser water circulation as required. The Ductile iron body shall be painted with one coat of Inorganic ethyl self-curing zinc silicate primer at 75 microns & a coat of Super High build epoxy MIO Coating cured with polyamide hardener at 150 microns & finally two coats of High Build Gloss Aliphatic Acrylic Polyurethane at 50 micron dry film thickness.
40 mm dia.
50 mm dia.
Supply, Installation, Testing and Commissioning of On-line, Non Chemical water treatment scale preventer system (suitable for 65mm dia. pipe) having flow rate 38 USGPM, complete all as specified and as directed. Note :- The suitable bypass arrangement from condenser pump to cooling tower will be made by the contractor to avoid of shutdown of plant due to blockage of scale guard.
M & L for Earthing complete with galvanised steel plate electrode, 600 x 600 x 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 mtrs deep below nominal ground level) with top edge of the plate not less than not less than 1.5 metres below nominal ground level connected to earthing lead of 4 mm dia galvanised iron or steel wire all as shown in SSR part I para No. 4 to the earthing test point all as specified and as directed. Note :- the cost of excavation and earth work PCC pit and CI cover funnel & watering pipe, wiremesh, charcoal dust and common salt shall be deemed included in the unit rate for earthing, complete all as specified and as directed.
Material an labour for fabrication for temporary shader of flate plate and fix framed work such as grills, gratings etc, with ends of bars shoulderd and / or riveted or forged into spikes, framed guard bars, barred iron doors, ladders , framed balusters, walk ways, railing, framework of water tanks , Bar protection of bolard light and similar work conforming to FE ,290. GDE E-165, complete all as specified and as directed.
Supply and fix chemical dehumidifier continuous operating complete, with heaters, ducting, electrical connection for 360 Cfm capacity, complete all as specified and as directed.
Taking down U/S & supply and fix GI duct of difference sizes made out of MS flat iron/GI Sheet of any size duly cutting , bending to shape required , welding as required for different size ducts deposit to MES store yard all as directed by engr by Engr-in charge.
Taking down of Existing false ceiling / frame carfully and refixing samen position after completion fabrication new duct given in sch, complete all as specified and as directed. Note : If false celing damged during dismantling or fixing of new duct the contractor will be replaced with new flase celing and holding celing frames and angles made out of iron / aliminium/GI material as existing size and colour without any extra cost.
M&L for Mkaing holes in wall or repair of pot holes in existing building wall for passing of duct / cables / pipe / cable tray Note: the distuebed surface of wall to passing of GI Duct/removing of existing duct shall be make good by applying cement plaster 1:4, and if required to fill with brick work 1:3:6 and applyin putty and colour wash etc matching with the existing surfaces, complete all as specified and as directed.
Supplying, fabricating and installing of following sizes of hot dip galvanized ladder type cable traysof size of 150 mm x 50mm x 1.6mm thick including horizontal vertical bends, reducers, tees, cross members and other accessories as required and duly installed from the ceiling/side walls with suitable sizes of channels/angles with anti-corrosion painting, full threaded Gl rods etc. complete as required & approved by the engineer-ln-charge.
The cost shall be included for in all respective item for Civil masonary/RCC works such as foundation/ platform for equipment , Pump, Motor , Hot water Generator, LT Panel , Expansion water tank , cooling tower , Chiller unit supporting for duct ,piping, and frames etc as required as per site.
M/s Luxmi Constructions
M/s Kataria Construction Company
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .