Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹65.8 LAccepted-AOC 440 12 A 3 T G CIVIL LINES NEW HYDERABAD LUCKNOW UTTAR PRADESH 226007 | LUCKNOW | UTTAR PRADESH | 226007 | L1 | Accepted-AOC L1 | |
| 2 | Rejected-Technical 9TH FLOOR 920 WAVE SILVER TOWER SECTOR 18 NOIDA GAUTAM BUDDHA NAGAR UTTAR PRADESH 201301 | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201301 | - | Rejected-Technical Not Eligible | |
| 3 | Rejected-Technical | - | Rejected-Technical Not Eligible |
Tender Value
₹62.9 L
EMD Value
₹1.3 L
Closing Date
2 May 2020, 5:00 pmClosed
Suptd. Engineer Civil
CSIR-NBRI, Rana Pratap Marg Lucknow-226001
As per BOQ
2020_CSIR_47279_1
1/WKS/01/20-Gl
Open Tender
Civil Works
Item Rate
30 days
CSIR-NBRI, Rana Pratap Marg Lucknow
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
Director,CSIR-NBRI, Rana Pratap Marg Lucknow
₹1.3 L
30 Jun 2020
27 Apr 2020
4 May 2020
27 Apr 2020
2 May 2020
27 Apr 2020
Amount
Part-A
The Pre-fabricated modular construction is designed and constructed for exact size, easy field installation . The Pre-fabricated Clean Room will be a freestanding structure, constructed from composite free standing insulated special PPGI PUF panels with ANTI bacterial coating which will be Hard, Impact resistant, scratch resistant and having elastomeric properties The entire panel assembly will be Light weight having sound absorption and Heat insulating properties.The PANELS ASSEMBLY should be based on a special G I material which is having non corrosive chemical resistant fire reardant non warping properties ,the panels will be supported with galvanized steel/extruded aluminium structure which will be fabricated as per the site requirement. COMPLETE AS PER THE ENCLOSED TECHNICAL SPECIFICATIONS
A. TR PCR Room size in mm (4550x 3050) :- 55.68 Sqm
B. EXTRACTION Room size in mm (4550x 3610) :- 59.40 Sqm
C. LAB 3 Room size in mm (3910x 3610) :- 44.76 Sqm
D. Entrance Lobby area size in mm :-79.92 Sqm
E. Dirty Corridor area:- 79.92 Sqm
F. DE gowning area:- 18.90 Sqm
G. Shower and Gowning area:-36.63 Sqm
Total for above area =
Flooring seamless with perfectly curved flash-covings, resistance to mechanical stress and dynamic loads and having ESD / EMI (conductive) protection characteristics, 2mm thick, washable.
Tile based and membrane type control panel, mounted flush in the Clean room wall, comprising of the following: Membrane type
Pass Box
Hermetically sealing type of manual door having features strictly as per the Techincal specifications,
A. Size appx ( 1000mm x 2100 mm)
B. Size appx ( 750mm x 2100 mm)
C. Size appx ( 650mm x 2100 mm)
Combined Electrical panel for AIR SUPPLY UNITS and Air Extractor Units having main Incomer with Overload protection, Display and monitoring of Voltage and currect on indivdual Phases, Bus Bar base distribution, complete with MCCB, MCBs of sizes as per the requirement of Air Supply Units and Air Extractor Units.with automated time delayed start and stop function
Air Handling Unit( AIR Supply Unit) - Constructed out of 0.6mm Pre- coated GI Outer Skin and Inner Skin: 0.6mm Plain GI having total Panel thickness: 50mm thick injected with 40kg / cum density, CFC free PUF insulation, having Extruded Thermal Break aluminum profile frame work, its Material of Drain pan should be : 20G SS-304 with 12mm thick chemically cross linked fire retardant Polyurethane foam insulation, having Heavy Gauge GI Unit Base Frame. • DX COOLING COIL (R-410a Gas) should have GI Coil Casing, having Tube Material of Imported special grade copper tube, Tube Dia (inch/mm): 3/8” and 0.5mm Thickness of tube , having Header Material: Copper, It should have Special grade aluminum blue fins Chemical salt fog spray 1.5 times long life instead of plane aluminum fins alloy-sine wave and staggered pattern/ 0.13mm, Spacing of Fins should be 11-12, The air Suply Unit should have Face velocity across coil: 500 FPM Expansion of tubes for perfect bonding of copper tubes with fins should be Hydraulically, Pressuretested at 21 kg/sqcm (300psig) pneumatically dipped in water for 2 hours,Should have FAN and filter section completely as per the TECHNICAL Specifications.
Air Extractor Unit 4000 CFM Air Handling Unit( AIR Supply Unit) - Constructed out of 0.6mm Pre- coated GI Outer Skin and Inner Skin: 0.6mm Plain GI having total Panel thickness: 50mm thick injected with 40kg / cum density, CFC free PUF insulation, having Extruded Thermal Break aluminum profile frame work, having Heavy Gauge GI Unit Base Frame. FAN and filter sections comprising of advanced Oxidation Process UV light chamber and H 14 grade HEPA filter sections. TECHNICAL Specifications of AIR Extraction/Discharge UNIT. The exracted air volume should be greater than the Volume of air supplied to rspective rooms to achieve Negative Air pressure.
AIR COOLED Condenser unit - Nominal Cooling Capacity: 102000 Btu/Hr, 25704 K Cal/Hr , using Refrigerant: R22/R 407 C, Pure polyester Powder coated GI Steel housing, having Nominal Air Flow: 5780 CMH/ 3400 CFM.Hermetically sealed scroll compressor, Propeller type condenser fan, Microprocessor Based controller with LCD display, Non-woven polyester media enclosed by HDPE Mesh Filter
Recess mounted IP54 Protocol, non-hygroscopic peripheral lights having LED lamp and sigma - digital ballast
Air conditioning Work Outside the LAB by competent agency ( Ducting and insulation)
Electrical Wiring work inside the LAB
Air Handling Unit( For Dirty Corridor only) - Constructed out of 0.6mm Pre- coated GI Outer Skin and Inner Skin: 0.6mm Plain GI having total Panel thickness: 50mm thick injected with 40kg / cum density, CFC free PUF insulation, having Extruded Thermal Break aluminum profile frame work, its Material of Drain pan should be : 20G SS-304 with 12mm thick chemically cross linked fire retardant Polyurethane foam insulation, having Heavy Gauge GI Unit Base Frame. Should have FAN and filter section completely as per the TECHNICAL Specifications.
Part-B
MS Structure consisting of: (J Bar, Net Bolts, MS Base and Top Plates, MS Hollow Pipes Columns, MS Hollow Pipes Trusee and MS Hollow Pipes Perlins of various sizes ) Including Weilding , drilling , fitting , Machinines , Net Bolts , Anchor Fashners, J Hocks , MS Washers , Rivets and etc. complete With application of two codes of RED OXIDE Primer and Two Codes of Metal Paint
0.6mm PPGI Corrugated Roofing Sheet With Riges complete with rivets , Self tapping and self screw
Civil Works : Making Of MS Column foundations, consisting of Soft earth excavation, upto 1 meter deep, Bed compaction, making PCC Bed of 150 mm thickness, Casting of RCC foundation as per IS complete with Holes and provision for Fastening Bolts etc, refilling and side compaction of foundation including watering of foundation structure preiodically
Installation of Ceiling Mounted self propelled Non Motorized Mechanical Ventillators
Note:- Rates should be quoted inclusive of all Taxes, GST etc.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .