Loading…
Loading…
Tender Value
₹57.8 L
EMD Value
₹1.1 L
Closing Date
15 Jul 2026, 9:00 am7d left
CWE (AF) Gwalior
HQ CWE (AF) Gwalior
RENEWAL/REPLACEMENT OF BER COOLING APPLIANCES AT TECH AREA AT AF STN GWALIOR
2026_MES_755963_2
86056/E8
Open Tender
Electrical and Maintenance Works
180 days
GE (AF) Tech Area
As per NIT and tender documents
8 documents required · 8 mandatory
₹1,000
GE (AF) Tech Area
₹1.1 L
Yes
1 Jul 2026
1 Jul 2026
22 Jul 2026
1 Jul 2026
15 Jul 2026
9 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply and fixing sheet metal enclosure triple pole and earth enclosure with three pin and earth plug with socket, 415 V, complete with one triple pole MCB of capacitry 32 amps complete all as specified and directed. | - | Each | - | - |
| 2 | Supply and fixing voltage stabilizer electronic type for automatic operation single phase naturally air cooled, indoor type, wall mounted for input variation between 170 V to 280 V with output voltage stabilized at 200V to 245 V with accuracy of + 1% and of capacity 5.0 KVA complete all as specified and directed | 21 | Each | - | - |
| 3 | Supply, install commissioning and testing of split type wall mounted Air Conditioner non inverter type units indoor/outdoor of capacity 1.5 TR (4500 K Cal / hr) single phase Non CFC / HCFC suitable for 230 volts + 10% , 50 Hz, AC supply complete with cordless remote control unit at any location with minimum 3 star rating and EER 3.2 and above including taking down carefully existing AC and depositing into AGE E/M Store yard complete with fittings.
Note : - (i) Copper pipe required for suction / discharge pipe line upto 3 mtr length shall be included in quoted rates and beyond 3 mtr will be measured and paid seperately under respective items of Schedule.
(ii) The contractor shall submit the original purchase voucher along with the warranty/guarantee certificate for the compressor while claiming payment in the RAR | 28 | Each Job | - | - |
| 4 | Supply, install commissioning and testing of split type wall mounted Air Conditioner non inverter type units indoor/outdoor of capacity 3 TR (9000 K Cal / hr) three phase Non CFC / HCFC suitable for 415 volts + 10% , 50 Hz, AC supply complete with cordless remote control unit at any location with minimum 3 star rating and EER 3.2 and above including taking down carefully existing AC and depositing into AGE E/M Store yard complete with fittings.
Note : - (i) Copper pipe required for suction / discharge pipe line upto 3 mtr length shall be included in quoted rates and beyond 3 mtr will be measured and paid seperately under respective items of Schedule.
(ii) The contractor shall submit the original purchase voucher along with the warranty/guarantee certificate for the compressor while claiming payment in the RAR. | 31 | Each Job | - | - |
| 5 | Supply, installation, commissioning of Window AC 1.5 TR with energey efficient compressor minimum 3 Star rating, white colour and working on Non -CFC Refrigerant, Non Inverter type, including making correct szie cutting into wall for insertion of window AC housing including taking down carefully existing AC and depositing into AGE E/M Store yard complete with fittings complete all as specified and directed.
Make : Blue Star Model No WID 518L or equivalent in Voltas, Carrier
Note :-The contractor shall submit the original purchase voucher along with the warranty/guarantee certificate for the compressor while claiming payment in the RAR. | 2 | Each Job | - | - |
| 6 | M & L for sub main wiring with two runs of single core 4 Sq.mm for phase and neutral conductor and one run of single core 4 Sq.mm as earth wire of multi stranded copper conductor FR-LSH PVC insulated unsheathed cable conforming to IS : 694 drawn through in & including PVC casing & capping with fixing accessories on wall / roof surface as per relevant IS standard not less than 25 mm width and all as complete specified and directed.
Note : Two run of single core PVC cable with one run of earth conductor and PVC casing & caping shall be measured and paid as one unit) | - | RM | - | - |
| 7 | Supply and fixing sheet metal enclosure double pole enclosure with a two pin and earth plug with socket, 240 V, complete with one single pole MCB of capacitry 20 amps complete all as specified and directed. | - | Each | - | - |
| 8 | M & L for sub main wiring with four runs of single core 6 Sq.mm for phase conductor and one run of single core 6 Sq.mm as earth continuity conductor of multi stranded copper conductor FR-LSH PVC insulated unsheathed cable conforming to IS : 694 drawn through in & including PVC casing & capping with fixing accessories on wall/roof surface as per relevant IS standard not less than 30 mm width and all as complete specified and directed.
Note : Four run of single core PVC cable with one run of earth conductor and PVC casing & caping shall be measured and paid as one unit) | - | RM | - | - |
| 9 | Supply and fixing copper tubing with of special annealed pressure copper of size 3/8" bore including insulation , clip complete all as specified and directed. | - | RM | - | - |
| 10 | Supply and fixing copper tubing with of special annealed pressure copper of size 5/8" bore including insulation, clip complete all as specified and directed. | - | RM | - | - |