Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.1 CrAccepted-AOC C 2488 SUSHANT LOK PHASE 1 GURGAON 122001 HARYANA | GURUGRAM | HARYANA | 122001 | ₹38.1 Cr | L1 | Accepted-AOC Being lowest and reasonable |
| 2 | L2₹39.0 CrRejected-Finance | ₹39.0 Cr | L2 | Rejected-Finance Not being lowest |
| 3 | L3₹39.8 CrRejected-Finance 421 4TH FLOOR TOWER A 2 SPAZE ITECH PARK SECTOR 49 SOHNA ROAD GURGAON | GURUGRAM | HARYANA | 122001 | ₹39.8 Cr | L3 | Rejected-Finance Not being lowest |
| 4 | L4₹40.8 CrRejected-Finance A 2 45 JANAKPURI NEW DELHI 110058 | NEW DELHI | NEW DELHI | DELHI | 110058 | ₹40.8 Cr | L4 | Rejected-Finance Not being lowest |
| 5 | L5₹41.1 CrRejected-Finance K 99 LGF KALKAJI NEW DELHI 110 019 | NEW DELHI | SOUTH EAST DELHI | DELHI | 110019 | ₹41.1 Cr | L5 | Rejected-Finance Not being lowest |
Tender Value
₹31.4 Cr
EMD Value
₹15 L
Closing Date
12 Apr 2025, 6:00 pmClosed
CE Delhi Zone
HQ CE Delhi Zone Delhi Cantt-10
PROVN OF ADVANCE CENTRE FOR OPTHALMIC SCIENCES AND VISUAL SCIENCES AT AH (RR), DELHI CANTT (SPL WK)
2024_MES_680784_4
CEDZ/TOKEN-07 OF 2024
Open Tender
Civil Works
548 days
Delhi Cantt
As per tender documents
10 documents required · 10 mandatory
₹3,000
GE E/M RR Hospital
₹15 L
Yes
26 Jul 2025
8 Mar 2025
14 Apr 2025
8 Mar 2025
12 Apr 2025
29 Mar 2025
8 Mar 2025 - 15 Mar 2025
Amount
Lump sum price worked out by the contractor for Schedule 'A' Section-I (Bldg Work) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-II (Site Clearance) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-III (Exacavation and Earth Work) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-IV (Internal Electric supply) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-V (Internal Water Supply) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-VI (Fire Alarm) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-VII (Lightening Protection) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-VIII (External Water Supply) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-IX (External Electric Supply) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-X (Fencing and Gate) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XI (Sewage Disposal) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XII (Area Drainage) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XIII (Rain Water Harvesting) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XIV (Road and path) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XV (Hot Water Supply, geyser) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XVI (Hot Water Supply, Solar) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XVII (Summer Appliances) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XVIII (Lift) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XIX (Fire Fighting) (Ref pre priced Schedule attached seperately)
Description of Work / Item(s)
Amount
INTERNAL ELECTRIC SUPPLY S & F Blanking plates for modular cover plate
S & F Decorative wall light made up of high grade engineering plastic material suitable for 9 W LED lamp B22 base including fixing accessories complete all as specified and directed.
Supply, Installation, Testing and Commissioning of ceiling recessed mounting LED SKY Lights luminaire, Printed Customised design (design as per approval by GE), 600 mm x 600 mm, (2' x2'), 36 Watts, luminaire should be made of single piece deep drawn CRCA housing with fully diffused PC/PS diffuser for general lighting. The LEDs used should have a color consistency SDCM≤5, CRI ≥ 80 and CCT 6500K, ≥ 110 lumen / watt, 50,000 burning hrs, PF ≥0.95, Surge Protection 3.5KV. The LED Luminaire & it's driver both should be BIS registered & shall be of the same make/manufacturer as that of LED luminaires complete all as specified and directed.
Supply and fix modular Telephone socket outlet on the existing modular plate & switch box including connections but excluding modular plate etc as required on site complete all as specified and directed
Supply and fix modular RJ 45 Internet socket outlet for Cat 6 on the existing modular plate & switch box including connections but excluding modular plate etc as required on site complete all as specified and directed
Supplying, installation, testing and commissioning of Passive Infrared (PIR) technology based occupancy sensor having high performance, non regulating programmable type, suitable for connected load upto 10Amp, for mounting height up to 2.8 mtr and for 5 m diameter coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required.
Supplying, installation, testing and commissioning of Passive Infrared (PIR) technology based occupancy sensor with day light dimming (lighting level shall be regulated as per availability of natural day light in an area along with occupancy detection.) having high performance, regulating programmable type, suitable for connected load upto 10Amp, for mounting height up to 2.8 mtr and for 5 m diameter coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required.
Design, manufacture, supply , installation, inspection, handling, assembling, affecting proper connections, testing and commissioning of Main L.T. Panel, Indoor type, floor mounting, dust & vermin proof, front operated construction, enclosure class - IP54/42 with the following Specifications :- (a) 800 A, 4P, 50 kA, EDO, ACB - 01 (Incomer, Tfr-01) (b) 800 A, 4P, 50 kA, EDO, ACB - 01 (Incomer, Tfr-02) (c) 1600 A, 4P, 50 kA, EDO, ACB - 01 (Incomer, DG) (d) 1600 A, 4P, 50 kA, EDO, ACB - 01 (Bus Coupler) (e) 800 A, 3P, 50 kA, MDO, ACB - 01 (O/G) (f) 630 A, 4P, 55 kA, TMD, MCCB - 02 (O/G) (g) 400 A, 4P, 36 kA, TMD, MCCB - 03 (O/G) (h) 250 A, 4P, 36 kA, TMD, MCCB - 01 (O/G) (i) 200 A, 4P, 36 kA, TMD, MCCB - 02 (O/G) (j) 160 A, 4P, 36 kA, TMD, MCCB - 02 (O/G) (k) 100 A, 4P, 25 kA, TMD, MCCB - 03 (O/G) (l) 63 A, 4P, 25 kA, TMD, MCCB - 03 (O/G) (m) 63 A, DP, 10 kA, MCB - 03 (O/G) (n) Fan & Filter - 04 Nos Note : (a) Detailed Specification has been uploaded along with the tender documents at Annex 'C' and is the part of BOQ for all purposes. (b) All acccessories included in the panel cost such as MCCB, MCBs, ACB , rotary handles, and its accessories & metering etc. The panel should be got inspected / tested in the factory premises from the Engineer-in-charge / consultant before brought at site after approval of all drawings of the panel.
Supply , installation and testing Capacitor Panel, floor mounting, dust & vermin proof, complete all as per specifications and accessories mentioned at Technical Specifications :- (a) 630 A, TPN, 36 kA, TMD, MCCB - 01 (b) Capacitor Bank, 50 KVAR - 04 Nos (c) Capacitor Bank, 25 KVAR - 03 Nos (d) Fan & Filter - 04 Nos Note : (a) Detailed Specification has been uploaded along with the tender documents at Annex 'D' and is the part of BOQ for all purposes. (b) All acccessories included in the panel cost such as MCCB, MCBs, rotary handles, and its accessories & metering etc. The panel should be got inspected / tested in the factory premises from the Engineer-in-charge / consultant before brought at site after approval of all drawings of the panel.
Supply , installation and testing of LT Panel, indoor type (for Lift), floor mounting, dust & vermin proof, complete all as per specifications and accessories mentioned at Technical Specifications :- (a) 200 A, 4P, 36 kA, TMD, MCCB - 01 (I/C) (b) 63 A, 4P, 25 kA, TMD, MCCB - 06 (O/G) Note : (a) Detailed Specification has been uploaded along with the tender documents at Annex 'E' and is the part of BOQ for all purposes. (b) All acccessories included in the panel cost such as MCCB, MCBs, rotary handles, and its accessories & metering etc. The panel should be got inspected / tested in the factory premises from the Engineer-in-charge / consultant before brought at site after approval of all drawings of the panel.
Supply , installation and testing of LT Panel, indoor type (for light load), floor mounting, dust & vermin proof, complete all as per specifications and accessories mentioned at Technical Specifications :- (a) 100 A, 4P, 25 kA, TMD, MCCB - 01 (I/C) (b) 63 A, 4P, 25 kA, TMD, MCCB - 01 (O/G) (c) 40 A, 4P, 25 kA, TMD, MCCB - 05 (O/G) Note : (a) Detailed Specification has been uploaded along with the tender documents at Annex "F' and is the part of BOQ for all purposes. (b) All acccessories included in the panel cost such as MCCB, MCBs, rotary handles, and its accessories & metering etc. The panel should be got inspected / tested in the factory premises from the Engineer-in-charge / consultant before brought at site after approval of all drawings of the panel.
Supply , installation and testing of LT Panel, indoor type (for UPS load), floor mounting, dust & vermin proof, complete all as per specifications and accessories mentioned at Technical Specifications :- (a) 100 A, 4P, 25 kA, TMD, MCCB - 02 (I/C) (b) 100 A, 4P, ATS Switch - 01 (c) 63 A, 4P, 25 kA, TMD, MCCB - 02 (O/G) (d) 40 A, 4P, 25 kA, TMD, MCCB - 05 (O/G) Note : (a) Detailed Specification has been uploaded along with the tender documents at Annex 'G' and is the part of BOQ for all purposes. (b) All acccessories included in the panel cost such as MCCB, MCBs, rotary handles, and its accessories & metering etc. The panel should be got inspected / tested in the factory premises from the Engineer-in-charge / consultant before brought at site after approval of all drawings of the panel
Supply , installation and testing of LT Panel, indoor type (for Power load), floor mounting, dust & vermin proof, complete all as per specifications and accessories mentioned at Technical Specifications :- (a) 200 A, 4P, 36 kA, TMD, MCCB - 01 (I/C) (b) 63 A, 4P, 25 kA, TMD, MCCB - 05 (O/G) (c) 40 A, 4P, 25 kA, TMD, MCCB - 02 (O/G) Note : (a) Detailed Specification has been uploaded along with the tender documents at Annex 'H' and is the part of BOQ for all purposes. (b) All acccessories included in the panel cost such as MCCB, MCBs, rotary handles, and its accessories & metering etc. The panel should be got inspected / tested in the factory premises from the Engineer-in-charge / consultant before brought at site after approval of all drawings of the panel.
Supplying, installation, testing and commissioning of Street light control panel, outdoor type with the following :- (a) MCCB 100 A, 4P, 25kA, TMD - 01 No (Incomer) (b) MCB 40 A, 4P, 10 kA - 04 Nos (O/G) (c) MCB 32 A, 4P, 10 kA - 03 Nos (O/G) (d) MCB 32 A, DP, 10kA - 02 Nos (O/G) (e) Contactor 63 A, 3P - 01 Nos (f) Digital timer (Astronomical type) for auto on /off - 01 Nos Note : (a) Detailed Specification has been uploaded along with the tender documents at Annex 'I' and is the part of BOQ for all purposes. (b) All acccessories included in the panel cost such as MCCB, MCBs, rotary handles, and its accessories & metering etc. The panel should be got inspected / tested in the factory premises from the Engineer-in-charge / consultant before brought at site after approval of all drawings of the panel.
Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Bus Trunking, 1600 Amps, 50 kA SC for 1 Sec, (3L+N+PE), with Multi Layer Class-F Insulation, 100% N, Totally enclosed with 1.6mm thick GI Sheet, Dust & vermin proof with IP-55 (Indoor Type) Ingress Protection, incl 90 degree bends / elbows etc, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. Make : LK / Legrand / Sudhir- Schneider / ABB / C&S
Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Bus Trunking, 630 Amps, 50 kA SC for 1 Sec, (3L+N+PE), with Multi Layer Class-F Insulation, 100% N, Totally enclosed with 1.6mm thick GI Sheet, Dust & vermin proof with IP-55 (Indoor Type) Ingress Protection, incl 90 degree bends / elbows etc, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. Make : LK / Legrand / Sudhir- Schneider / ABB / C&S
Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Bus Trunking, 400 Amps, 35 kA SC for 1 Sec, (3L+N+PE), with Multi Layer Class-F Insulation, 100% N, Totally enclosed with 1.6mm thick GI Sheet, Dust & vermin proof with IP-55 (Indoor Type) Ingress Protection, incl 90 degree bends / elbows etc, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. Make : LK / Legrand / Sudhir- Schneider / ABB / C&S
Supplying, installing, connecting to existing Air Insulated Compact Type bus trunking/ rising mains, testing and commissioning of 1600 Amps, 50 kA SC for 1 Sec, capacity End Feed Unit for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCCB / ACB (but without MCCB / ACB) complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. Make : LK / Legrand / Sudhir- Schneider / ABB / C&S
Supplying, installing, connecting to existing Air Insulated Compact Type bus trunking/ rising mains, testing and commissioning of 630 Amps, 50 kA SC for 1 Sec, capacity End Feed Unit for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCCB / ACB (but without MCCB / ACB) complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. Make : LK / Legrand / Sudhir- Schneider / ABB / C&S
Supplying, installing, connecting to existing Air Insulated Compact Type bus trunking/ rising mains, testing and commissioning of 400 Amps, 30 kA SC for 1 Sec, capacity End Feed Unit for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCCB / ACB (but without MCCB / ACB) complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. Make : LK / Legrand / Sudhir- Schneider / ABB / C&S
Supplying, installing, connecting to existing Air Insulated Compact Type bus trunking / rising mains, testing and commissioning of 200 Amps, 15 kA SC for 1 Sec, capacity Plug In / Tap Off Box for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCCB (but without MCCB) complete etc. as required. Make : LK / Legrand / Sudhir- Schneider / ABB / C&S.
Supplying, installing, connecting to existing Air Insulated Compact Type bus trunking / rising mains, testing and commissioning of 125 Amps, 15 kA SC for 1 Sec, capacity Plug In / Tap Off Box for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCCB (but without MCCB) complete etc. as required. Make : LK / Legrand / Sudhir- Schneider / ABB / C&S.
Supply and lay XLPE Cable, 35 Sqmm, 4 core, insulated screened PVC bedded, galvanised steel strip or wire armored, electric power cable (heavy duty) 1100 volts grade with stranded Copper conductor complete all as specified and directed
Supply and lay XLPE Cable, 16 Sqmm, 4 core, insulated screened PVC bedded, galvanised steel strip or wire armored, electric power cable (heavy duty) 1100 volts grade with stranded Copper conductor complete all as specified and directed
Supply and lay XLPE Cable, 10 Sqmm, 4 core, insulated screened PVC bedded, galvanised steel strip or wire armored, electric power cable (heavy duty) 1100 volts grade with stranded Copper conductor complete all as specified and directed
Supply and lay XLPE Cable, 2.5 Sqmm, 2 core, insulated screened PVC bedded, galvanised steel strip or wire armored, electric power cable (heavy duty) 1100 volts grade with stranded Copper conductor complete all as specified and directed
Supplying and making end termination with brass compression gland and aluminium lugs of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade, for 4 X 10 sq. mm (25mm)
Supplying and making end termination with brass compression gland and aluminium lugs of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade, for 4 X 16 sq. mm (28mm)
Supplying and making end termination with brass compression gland and aluminium lugs of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade, for 4 X 25 sq. mm (28mm)
Supplying and making end termination with brass compression gland and aluminium lugs of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade, for 3½ X 35 sq. mm (32mm)
Supplying and making end termination with brass compression gland and aluminium lugs of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade, for 3½ X 50 sq. mm (35mm)
Supplying and making end termination with brass compression gland and aluminium lugs of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade, for 3½ X 70 sq. mm (38mm)
Supplying and making end termination with brass compression gland and aluminium lugs of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade, for 3½ X 300 sq. mm (70mm)
Supplying and laying of DWC HDPE pipe, 63 mm dia (OD-63mm & ID-51mm nominal), ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required
Supplying and laying of DWC HDPE pipe, 90 mm dia (OD-90mm & ID-76mm nominal), ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required
-Blank-
S & F cable junction box 200 x 160 x 98mm in size made out of thermoplastic sheet having IP 65 protection for out door installation fixed with 4 way bakelite cable terminals with one MCB SP 6 Amps to be fixed inside the box including 03 Nos polynide gland with check nut (M-32 - 3 Nos) fixed on pole with flat iron clamps of size 25 x 3mm, nuts, bolts, washers etc., including two coats of synthetic enamel paint over a coat of redoxide zinc chrome primer for iron clamps complete all as specified and as directed by Engineer-in-Charge.
Supply errection and testing of post top Modem 40 watt decorative spun aluminium housing with power LED,s and extruded aluminium heat sinks. A UV stbilized PC/PMMA diffuser is provided for glare free lighting with high visual comfort. Available in 3000k/6000k
Supply and errection of 4000 mm Decorative pole with cast iron embellishment at bottem & middie with designer cast aluminum ribbed design double arm bracket.Pole is made of mild steel & galvanized complete with service window containing 6-amp MCB ,4- Way connector.
INTERNAL WATER SUPPLY Supply & fixing Over head shower 200 MM DIA/square single flow ( ABS body chrome plated with grey face plate) with rubit cleaning system and flow restrictor 6.0 LPM at 3 bar pressure and with CP Shower arm 250 mm long with wall flange complete all as specified and directed.
Supply & fixing health faucet (ABS Body) mild steel chromium plated suitable for 15mm dia pipe with 1.25 metre long flexible tube and ABS wall hook including making conection and fixed in position complete all as specified and directed.
Supply & fixing towel rail 600 mm long CP brass fixed with and including cromium plated brass screws and wooden/ plastic cleats complete all as specified and directed.
S&F Liquied soap dish of CP brass fancy type fixed with, including cromium plated brass screws and wooden/ plastic cleats complete all as specified and directed.
S&F Towel ring of CP brass fixed with and including Chromium plated brass screws and wooden/plastic cleats complete all as specified and directed.
S&F glass corner shelf assembly cosisting of 5.5 thick sheet glass, shelf 30x30 CM corner with chromium plated bracket guard and railing necessary CP fiting complete all as specified.
Supply & fixing Urinal spreader of CP brass with and including cromium plated brass screws and wooden/ plastic cleats all as specified.
Supply & fixing luxury Towel Rack of CP brass with and including cromium plated brass screws and wooden/ plastic cleats all as specified.
Supply & fixing luxury WHB Mixer of CP brass including all fitings all as specified directed.
QUE MANAGEMENT SYSTEM - QMS PATIENT CALL SYSTEM Supplying, installation, testing and commissioning of QMS as specified below complete with racks, patch panel, active components, cabling outlet, back boxes , cable pilling etc. Token display 4 Inch 3 digit - COUNTER DISPLAY Used to call a registered Token No - Display - Bright 7 Segment Digit Size - 2 Inches, No of Digits - Total 4 (3 Digits red color for token and 1 Digit green for counter), Interface - Wired Rs485 or Wireless 865 Mhz RF. Power Supply - 12V DC
Token calling unit - Used to announce called token no in human voice in two predefined languages English and Hindi. Interface - Wired Rs485 or Wireless 865 MHz RF. Power Supply - 12V DC
Media converter - MEDIA CONVERTER. All counters shown on LED tv screen with current token no. Connectivity :- 1x full size HDMI , 4x USB 2.0 , LAN Screen Size LED SMART TV 24"inch - 65"inch. Wireless RF /Rs485 connection interface. Input voltage - 230 AC, 50Hz
Supply & laying Cat 6 wire
Supply and installation RJ45 outlets in existing backbox
Supply & laying of 20mm PVC Conduit
Supply and installation of GI backbox for RJ45 outlets
Supply and installation 2 Module Back Box
Token Dispenser unit 58 mm paper width with direct thermal printing method type. Interface RS232-C and print speed of 50mm/sec and mechanical lifetime of minimum 50km. Sheet metal with Vinyl enclosure of approx size 77X77X44mm with LCD display of alphanumeric 16 characteristic, 2 lines with backlight with wireless 865 MHZ RF and 230V AC, 50 Hz
FIRE ALARM SYSTEM Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required
Supply, Installation, Testing & Commissioning of Addressable Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance complete all as specified and directed
Supplying, installation, testing & commissioning of addressable fire control module complete as required
Supplying, installation, testing & commissioning of fault isolator complete with base as required
Supply, installing, testing and commissioning of Addressable Relay Module for AHU, Access Control, Lifts, Staircase Pressurization, Fire Suppression & other Third Party Outputs. The relay module shall provide contact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance complete all as specified and directed
Supply, installation, connecting, testing and commissioning of Addressable Hooters cum strobe min. 80 db output and 110 candelas complete with modules. The strobes shall be synchronised for better evacuation.
Supplying, installation, testing & commissioning of fire fighter phone jack complete as specified and directed
Supplying, installation, testing & commissioning of fire fighter telephone handset complete as specified and directed Note for item No 64 to 73 : Make - Ansul-Tyco / Notifier/ Rux / JCI(IFC) / Nohmi / Gamewell / Honeywell
Supplying & laying of 2 x 1.5 sqmm fire survival armoured cable, 600 / 1000 V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete all as specified and directed. Make : Polycab/ RR Kabel/ Paramount/ Parasheild/ Derwiser
Supplying, installation, testing & commissioning of 6W ceiling speaker complete as required Approved Makes : Actis / Honeywell / Bosch (Persadio)
Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required. Approved Makes : Actis / Honeywell / Bosch (Persadio)
Supply, Installation, Testing & Commissioning of 1X500W Class-D Amplifier with 2 independent channels and can provide automatic re-settable overcurrent, overload, overheating, overvoltage, under-voltage and DC protection. Approved Makes : Actis / Honeywell / Bosch (Persadio)
Supplying and Laying of 2 C X 1.5 Sqmm multi stranded twisted shielded FRLS Copper cable. Approved makes : Polycab/ RR Kabel/ Paramount/ Parasheild/ Derwiser
TELEPHONE, INTERCOM & TV CONDUIT
Supply, Installation, Testing & Commissioning of Pure IP at core server Based voice solution with 04 Port Voicemail ,04 Port FXS ,04 Port FXO ,1 PRI Trunk lines (30 Ch) Circuit with CLIP Facility ,47 IP users License ,01 Nos. IP Operator Console, 100 Party Conference ,Speed Dial, Music on Hold , Internal/ External ring difference ,Call Barring, Call Pickup, TEC should be with GR Number, - Should Support Redundant server in active-Active mode. Approved Makes: Tadiran/Arista /Polycom/Toshiba/ Aeonix/Nexxus
Supply, Installation, Testing & Commissioning of Type 1 IP Phone 1 VoIP account , Full duplex speaker phone, IPV6, 2xLAN, PoE . Approved Makes: Tadiran/Arista /Polycom/Toshiba/ Aeonix/Nexxus
Supply, Installation, Testing & Commissioning of Type 2 IP Phone with 2 Voip accounts, 2 Lines , HD Voice,Graphic LCD display with backligh. Approved Makes: Tadiran/Arista /Polycom/Toshiba/ Aeonix/Nexxus
Supply & Fixing Rigid non-metallic PVC conduit 25 mm dia exclusive of boxes (junction / terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc
Supply and fixing of Modular White cover plate with frame, 2 module complete all as specified and directed
Supply and fixing of Modular metal flush box 1/2 module complete all as specified and directed
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required for Telephone Socket outlet
DG SET
Supply, installation, testing and commissioning 500 KVA SILENT D.G. SET WITH INBUILT SYNC PANEL AND LOAD MANAGER 415 Volts, 3 phase, along with AMF cum Synchronization Panel in-built and integrated inside canopy, PRIME Rated DG set rated at 1500 RPM, Radiator Cooled with associated accessories, having 10% overload capacity for 1 Hour in every 12 Hrs of operation as per relevant ISO. DG set along with Acoustic enclosure shall be provided and mounted on the common base frame and Genset shall be suitable to transport from one place to another without dismantling the Acoustic Enclosures. Genset shall be provided with inbuilt Fuel tank, mounted at the base frame of the Genset and all the specifications have been mentioned in PS Note: (a) These DG Set must be suitable for parallel operation and share equal load i..e. percentage impedence of both alternators of DG set must be same. (b)The DG Set and all accessories / fittings shall conforming to relevant IS with latest amendments. (c) Completion of the work shall be issued after precommisioning of DG Set inspection by Testing Officer. Necessary diesel, tools and equipment shall be provided by the contractor for testing / precommsioning without any extra cost.
NURSE CALL SYSTEM
Supply, Installation, Testing & Commissioning of Main Display with 3 x 3 FND (3 digits X 3 displays), 20 call memory - Calls are stored from the 1st place (top left) - 2nd place (top right) - 3rd place (bottom right) . from the 4th calls are hidden in order (till 47 calls). If the cancel button is pressed from Call Point, the responding call is deleted regardless of the order of the call . If Cancel Only button is pressed, the 1st call is deleted, then the 2nd call display takes the place of the 1st call, the 3rd call display takes the place of the 2nd call and the hidden 4th call takes the place of the 3rd call. Make - Solt Memory :last 20 calls ,22 different sound, 7 Segment Alphanumaric Display,power Adaptor With 12 V/1.5 Amp DC power complete all as specified and directed
Supply, Installation, Testing & Commissioning of software for PC Monitoring to display active calls on the computer screen and play different sound based on call type, different background colours for different call types complete with one PC with Windows 11 with speaker and working USB complete all as specified
Supply, Installation, Testing & Commissioning of Call-cancel - 6 buttons (5 call / 1 cancel or 3 call/3 cancel)..BK-black, Whwhite .transmit a radio signal for a distance of up to Indor up to 30 to 50 meters & open site 100 meters . They can work Lithium Coin Battery ( 3 V) up to 18 month without changing the batteries complete all as specified and directed.
Supply, Installation, Testing & Commissioning of cabled push-button 2X : call/cancel, 3X : 3 call/cancel With come spiral Cable & Push Button for tension free use .with required cable length as needs.
Supply, Installation, Testing & Commissioning of Repeater - Transceiver (Receiver & Transmitter) max. output 10mW . Extending the signal range .Easy configuration .Avoid duplication of the same calls .Register up to 999 call buttons. Unit power Adaptor With 12 V/1.5 Amp DC power complete all as specified and directed
Supply, Installation, Testing & Commissioning of Call / Cancel button (Transmitter) with pull-string(1 m) for Toilet Unit complete all as specified and directed.
Supply, Installation, Testing & Commissioning of Mounting cover for fixing SB6 series call points to the wall complete all as specified and directed.
SIGN BOARD
Supply and fixing of hospital sign boards of different types and size i.e. illuminated and others for depiction of various wards, deptts, centres, services and other locations in the hospital including day and night signs and patient guidance system.
LIGHTENING PROTECTION
Supply, installation, testing and commissioning of Lightning Strike counter for counting the number of lightning strikes without any power supply. The Counter should be mounted on the Down Conductor. Make: ERICO, FURSE OR OBO.
Supply, installation, testing and commissioning of OBO make Encapsulated Class B+C surge arrester (V25-B+C) for three phase four wire system with nominal discharge current(In as per IEC 61643-1) 30KA (for 8/20ms) & Impulse current 7KA(for 10/350ms) per pole between phase to neutral. & 50KA (8/20ms) current for neutral to earth. Maximum continuous operating voltage should be 320V. Response time (ta) should be less than 25ns for phase to neutral. Voltage protection level should be less than 900V at 5KA (8/20ms) for phase to neutral & 1.2KV for neutral to earth.
Supply, installation, testing and commissioning of OBO make Encapsulated Class C surge arrester (V20-C) for three phase four wire system with nominal discharge current(In as per IEC 61643-1) 20KA (for 8/20ms) between phase to neutral & 50KA (for 8/20ms) between neutral to earth. Maximum continuous operating voltage is 320V. Response time (ta) should be less than 25ns for phase to neutral. Voltage protection level should less than 1.3KV at 5KA (8/20ms) for phase to neutral & 1.2KV for neutral to earth.
60KVA/60KW Online Modular UPS Supply, Installation, Testing and Commissioning of minimum 60KVA/60KW or Higher rating True - On - Line, Energy Efficient, configuration double conversion UPS with DSP (Digital Signal Processor) / Microprocessor Based Control System using IGBT Based Technology and High Switching Frequency PWM (Pulse Width Modulation) with PFC controlled IGBT Rectifier with Active Power factor Correction (APFC). The Design of the UPS shall be Modular Type with Decentralized parallel Architecture. and the Power Module shall be upto 20KW Range to achieve high redundancy. UPS should be in N+1 mode for redundancy purpose so that at least one Module should be spare apart from 60KW capacity. In case of Overloading due to any reason the Total Load shall be transferable to Mains Source without affecting the working condition of equipment which are operational. Modular UPS with HOT Swappable Power Module upto 20Kw (No Module shall have different Rating it means all Modules shall be of same rating). The detailed specifications are mentioned in PS Note : (a) The UPS and all accessories / fittings shall conforming to relevant IS with latest amendments.
SUMMER APPLIANCES
Supply, installation,commissioning of Water Purifier having filtration capacity 50 LPH having purification stages RO+UV+UF+TDS technique compelete all as specified and directed
Supply installation,commissioning of refrigerator electric driven single phase capacity 465 Ltr smart inverter compressor, BEE star rating compelete all as specified and directed
(a) Electrically operated with electric motor AC 415 Volts, 3 Phase 50 HZ of suitable capacity as per IS (efficiency class equivalent to IE 2) and operating gearless box with independent main sheave rim. (b) Electric cabling and wiring in FRLS copper cable including all necessary PVC conduits ISI marked of suitable size (c) Micro processor based VVVF type main controller with closed loop system. (d) Car position indicator in car all fixture in SS face plate (both insided/out-side). All buttons should be with brail marking and luminous. (e) Provn of travelling cable with copper conductor FRLS of suitable size & core or required wiring to intercom speaking & other accessories. (f) Inbuilt ARD (Automatic Rescue Device) with maintenance free batteries operated to bring the car cage to the nearest floor level in case of power failure, which includes power failure of one or more phase. Emergency light and at least one fan inside the lift car shall be operational till the rescue operation and an audio and visual indicator shall be provided inside car to alert the persons trapped inside that they are being rescued. (g) Provision of governor and governor rope of suitable size, buffer springs as per manufacture's design, car cabin having powered doors and inspection box at top of the car cabin, compact high efficiency drive combined with suspension Traction Media Technology. Grooved Belt and alongwith belt monitoring device which can ensure to prevent from any breakage of beltwire rope and taking elevator nearest landing. (h) Provision of safety guarding equipments such as 02 Nos pit switches controller, guarding pit, pulley, guarding pit ladders, facia plate to cover free space between car cabin and hoist way & switches. (j) Door sensor not less than 74 beam, 2D infra red full length (k) Provision of fire man switch complete at ground floor fitted in box including SS face plate. (l) Provision of "Press and Speak" system to be connected with lift complaint cell compatible with exchange. Provision of Automatic call registration in case of breakdown.
(m) Do's & Don’ts chart on stainless steel to be installed inside the car cabin. (n) A three Pin plug socket with switch for hand lamp shall be fitted on top of the lift car for use by person working there on. (o) Provn of 40 mm SS handrail on three side of the lift. (P) Provn of 40 mm SS handrail on three side of the lift. (q) Provn of RCCB/RCBO in SS enclosure.
Supply and fix lift electrically operated microprocessor controlled complete with power driven automatic stainless steel (SS) sliding doors and having SS car enclosure ,suitable to carry 20 passengers (1360 kg) at a speed of 1.5 m/sec to serve 5 floors (G+4) including automatic rescue device all as specified as per the description below:-
(a) Electrically operated with electric motor AC 415 Volts, 3 Phase 50 HZ of suitable capacity as per IS (efficiency class equivalent to IE 2) and operating gearless box with independent main sheave rim. (b) Electric cabling and wiring in FRLS copper cable including all necessary PVC conduits ISI marked of suitable size (c) Micro processor based VVVF type main controller with closed loop system. (d) Car position indicator in car all fixture in SS face plate (both insided/out-side). All buttons should be with brail marking and luminous. (e) Provn of travelling cable with copper conductor FRLS of suitable size & core or required wiring to intercom speaking & other accessories. (f) Inbuilt ARD (Automatic Rescue Device) with maintenance free batteries operated to bring the car cage to the nearest floor level in case of power failure, which includes power failure of one or more phase. Emergency light and at least one fan inside the lift car shall be operational till the rescue operation and an audio and visual indicator shall be provided inside car to alert the persons trapped inside that they are being rescued. (g) Provision of governor and governor rope of suitable size, buffer springs as per manufacture's design, car cabin having powered doors and inspection box at top of the car cabin, compact high efficiency drive combined with suspension Traction Media Technology. Grooved Belt and alongwith belt monitoring device which can ensure to prevent from any breakage of beltwire rope and taking elevator nearest landing. (h) Provision of safety guarding equipments such as 02 Nos pit switches controller, guarding pit, pulley, guarding pit ladders, facia plate to cover free space between car cabin and hoist way & switches. (i) Door sensor not less than 74 beam, 2D infra red full length (j) Provision of fire man switch complete at ground floor fitted in box including SS face plate. (k) Provision of "Press and Speak" system to be connected with lift complaint cell compatible with exchange. Provision of Automatic call registration in case of breakdown.
(l) Do's & Don’ts chart on stainless steel to be installed inside the car cabin. (m) A three Pin plug socket with switch for hand lamp shall be fitted on top of the lift car for use by person working there on. (n) Provn of 40 mm SS handrail on three side of the lift. (o) Provn of transparent space for highlights the imp instructions and Mobile Nos. (p) Provn of RCCB/RCBO in SS enclosure.
Supply and fixing 6 sqmm 4 core copper conductor PVC insulated sheathed cable complete all as specifed and directed.
Supply and fixing sheet metal enclosure loadline DB VTPN, 4 way, double door in as incomer, IP-43 dust and vermin proof, vertical type suitable for MCCB as incomer duly fixed on wall on angle iron frame in and including following items complete all as specifed and directed:- (i) MCCB 100 Amps, TPN, 25KA, 50Hz, 415 volts with Thermal magnetic release-01 Nos (ii) RCBO, 40 Amps, 300mA, 4 pole-02 Nos (iii) MCB, 25 Amps, 10 Ka, TPN-01 Nos(Spare)
AIR CONDITIONING
Water Cooled Screw Chilling Machine with VFD Supply, Installation, Testing and Commissioning of 150 TR Water cooled screw type Single/ Multi Compressor, Single/ Multi Ref. Circuit water chilling machine with unit mounted VFD each having a capacity as given hereunder at chilled water inlet/outlet temperature of 54°F / 44°F, Fouling Factor 0.0005 FPS and condenser water inlet/outlet temperature of 90°F / 97.5.4°F Fouling Factor 0.001 FPS, suitable for operation on factory charged suitable refrigerant for screw type machine each comprising of the following complete as per specifications Chilled Water Flow 360 GPM & Condenser Water Flow 600 GPM. (a) Screw type compressor semi hermetic complete with automatic capacity control safety switches, forced feed lubrication system (b) The semi hermetic compressor should be mono/ twin type. Capacity control range of compressor shall be from 25% to 100% (c) Suitable capacity squirrel cage induction motor with class 'B'/'H' insulation suitable for operation on 415 +- 10% volts 50Hz, A.C. supply. (d) 1 No. suitable capacity Variable frequency drive for the above compressor motor complete with ammeter with CTs, over load protection, under voltage protection, protection against phase reversal & independent single phase preventers etc complete as required Necessary drive arrangement. 1 set - Lubrication device consisting of automatic electric oil pump, oil cooler, head tank, oil strainer, and automatic pressure regulating valve, oil heater, oil heater thermal switch etc. as per specifications. 1 No. - Matching shell and tube water cooled condenser of M.S. shell and integrally finned copper tubes with Max Pressure Drop of 3 mtrs 1 No. - matching shell & tube flooded type chiller for screw type units of MS shell and copper tubes with Max. Pressure Drop of 5 mtrs
1 Lot - Refrigerant piping fittings, valves and accessories to inter connect compressor, condenser, chiller and expansion valve. 1 set - Microprocessor based control panel complete with accessories as per specifications. Lot - Refrigerant line accessories comprising of safety valves, angle valve, liquid line indications, liquid level control etc. Lot - Water flow switches at outlet of condenser & chiller, water drain, air purge valves, thermometers and pressure gauges wherever required. Lot - Suction line and chiller factory insulated with minimum 19mm thick polyvinyl nitrile rubber insulation complete as required. Lot- Frame work for mounting the above condenser, chiller compressor and motor with base plate complete with anti-vibration pads/springs. Lot- Initial/first charge of refrigerant gas & compressor oil. Lot- RCC / cement concrete foundation for the chilling unit. Screw type chilling machine described above, as per specifications and complete in all respects for the operating parameters as given under. The evaporator and condender shall have with Even pass system only . OEM & compressor shall be of same make The evaporator and condender shall have ASME Stamping
The Chillers shall be in accordance with AHRI /AHRI Certified and must be compatible with BMS system Minimum COP should be 5.9 for water cooled screw chillers . The IPLV of VFD chiller should not be more than 0.38 KW/TR . Maximum IKW/ TR at operating conditions 0.68 KW/TR. The IPLV of VFD chiller should not be more than 0.39 KW/TR . Country of Origin : Indian/ Imported. Chiller 150TR (Actual Capacity) (2 W + 1S) Chiller must comply at least ECBC+ 2017 Note : The above 1 no chiller shall be got tested at AHRI certified test bed in OEM factory for 4 load points at (100%, 75%, 50% & 25%)the cost of the agency/ firm. The machine shall be accompanied with the 4 point test report duly certified by the OEM. No payment shall be released without the same.
Primary Chilled Water Pump for chillers Supply, installation, testing and commissioning of PN16 rated Vertical Inline Split Coupled (with rigid aluminium alloy coupling between pump shaft and motor shaft) single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications. Casing (Volute) - Ductile Iron. Impeller - 316 Stainless Steel - Statically and Dynamically Balanced Casing Gasket - Confined Non Asbestos Fiber Pump Shaft - SS 316. Flush Line - Braided Stainless Steel Mechanical Seal - Outside Balanced Water Flow Rate: 360 USgpm Head : 18 m WC Motor Type - Parmanent Magnet Motor , Efficiency Class - IE5,Pump Effi minmum 80% and having rated capcity 5.5 KW All the VFD should display the dynamic head & flow rate of the pump using inputs from ultrasonic flow meter and digital pressure gauge or using sensorless algorithms,( 1 flow meter and 2 pressure gauges to be supplied for each VFD driven pump). Pump manufacturer to supply Ultrasonic flow meter and digital pressure gauges along with the pumps supplied or can display individual flow and head of each pump using sensorless algorithms. VFD screen should be touch screen All pump shall be provided with embedded software and hardware for wireless remote performance managements with an initial one-year subscription for IOT service as described below. a) Web access to monitor data (flow, head, vibration, pump in hand, dead head, & other important electrical data) b) Analyzed out in the form of alerts for preventive maintenance. c) Energy Report & raw data available to download
Secondary Chilled Water Pumps for Chillers and Energy efficient HWGs Supply, installation, testing and commissioning of PN16 rated Vertical Inline Split Coupled (with rigid aluminium alloy coupling between pump shaft and motor shaft) single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications. Casing (Volute) - Ductile Iron. Impeller - 316 Stainless Steel - Statically and Dynamically Balanced Casing Gasket - Confined Non Asbestos Fiber Secondary water pump(2W+1S) Pump Shaft - SS 316. Flush Line - Braided Stainless Steel Mechanical Seal - Outside Balanced Motor Type - Parmanent Magnet Motor , Efficiency Class - IE5 Pump Efficiency minmum 80% and having rated capcity 7.5 KW Water Flow Rate: 360 USgpm Head : 20 m WC All the VFD should display the dynamic head & flow rate of the pump using inputs from ultrasonic flow meter and digital pressure gauge or using sensorless algorithms,( 1 flow meter and 2 pressure gauges to be supplied for each VFD driven pump). Pump manufacturer to supply Ultrasonic flow meter and digital pressure gauges along with the pumps supplied or can display individual flow and head of each pump using sensorless algorithms.VFD screen should be touch screen All pump shall be provided with embedded software and hardware for wireless remote performance managements with an initial one-year subscription for IOT service as described below. a) Web access to monitor data (flow, head, vibration, pump in hand, dead head, & other important electrical data) b) Analyzed out in the form of alerts for preventive maintenance. c) Energy Report & raw data available to download
Microprocessor Based Pump Logic Controller for Secondary water pumps SITC of Separate ( not as apart of VFD )Microprocessor based variable pump logic controller in IP 54 protection, to control following nos. Pumps. Suitable to operate on sensorless /Transmitters, interfacing amongst all components and compatibility of I/O signals etc Should be Modbus RTU/ BACnet enabled for communicating with BMS & RS-485 serial communication with Pump VFD. The staging of pumps should be based on efficiency (not on capacity) to ensure minimum operating cost. Power Rating: 230 V/ 1 ph/ 50 Hz Display: Minimum 4.3" backlit LCD Hand-Off-Automatic (H-O-A) control Secure front cabinet door with lock and key UL Listed and CSA Approved Remote or local start/stop mode of operation. 2-level (field and factory) password security Remote zone signals, zone faults, zone setpoint and active control zone
CONDENSOR WATER PUMPS Supply, installation, testing and commissioning of PN16 rated Vertical Inline Split Coupled (with rigid aluminium alloy coupling between pump shaft and motor shaft) single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications. Casing (Volute) - Cast Iron. Impeller - 316 Stainless Steel - Statically and Dynamically Balanced Casing Gasket - Confined Non Asbestos Fiber Pump Shaft - SS 316. Flush Line - Braided Stainless Steel Mechanical Seal - Outside Balanced Condensor water pump (2W+1S) Water flow rate 360US GPM Head :18 m Motor Type - Parmanent Magnet Motor , Efficiency Class - IE5 Pump Efficiency minmum 80% and having rated capcity 11 KW All the VFD should display the dynamic head & flow rate of the pump using inputs from ultrasonic flow meter and digital pressure gauge or using sensorless algorithms,( 1 flow meter and 2 pressure gauges to be supplied for each VFD driven pump). Pump manufacturer to supply Ultrasonic flow meter and digital pressure gauges along with the pumps supplied or can display individual flow and head of each pump using sensorless algorithms.VFD screen should be touch screen.
COOLING TOWER Supplying , installation, testing and commissioning of Induced Draft counter flow Fibre glass-reinforced Cooling Towers (2 cell) CTI Certified in accordance with the technical specification, Drawings and Schedule of Quantities. Tower shall be vertical , Induced Draft counter flow type in fibre-glass reinforcement plastic construction , complete with statically and dynamically balanced axial flow type fan, TEFC induction motor with efficiency class IE3, surface and spray section , eliminators , steel supports. The tower shall be CTI certified and meet energy efficiency per ECBC 2017 standards. The tower shall be complete in all respects inlcuding but not limited to base frame, mounting, Isolating devices, tanks, drift eleminator, make-up quick fill arrangement, overflow and drain connections with necessary valves and suitable inspection ladder, access arrangement for cooling tower interior, steel/ masonary supporting structure, anti-vibration mountings etc and other accessories as mentioned in the specifications. The Unit shall be complete in all respect and shall be factory tested with reports submitted. The scope of work shall include Lifting, shifting & positioning of cooling tower at location shown on drawing. The dB levels shall be less than 80 dB(A) at 3 m distance. VFD - The variable frequency drive(s) shall be pulse width modulation (PWM) type, microprocessor controlled design. VFD shall be capable of operating in voltage ranges of 240V or 415 V +/- 10% AC, three phase; at frequencies of 48 to 63 Hz. VFD shall be factory fitted and unit mounted. The Cooling tower shall be capable to communicate effectively with BMS on open protocal modbus/Bacnet. WBT : at 83º F WB Approach : 2.77º C Maximum Hot water IN : 97.5 ºF Hot water OUT : 90ºF Drift loss < 0.005% Water flow : 600 USGPM Heat Rejection Capacity : 2340000 BTU/hr (2W + 1S)
AIR HANDLING UNITS Supply, install, testing and commissioning of all weather Smart Air handling unit for OT with the following specifications: - Supplying, installing, testing and commissioning of AHRI/Eurovent Certified’ 50 mm thick double skin construction Floor Mounted Air Handling Units comprising of following parameter of - Casing Strength- D1 or equivalent, Thermal Bridiging Factor - TB2or equivalent, Thermal Transmittance - T2 pr equivalennt, Casing Air Leakge - L1 or equivalent, Fillter By pass Factor- F9 or equivalnet. Outer skin will be 0.8mm thick pre-coated GI & inner skin will be 0.8mm thick plain Aluminium. LOWER TIER- WITH Min.30% FRESH AIR ARRANGEMENT INTAKE SECTION - Fresh Air intake section with GI louvers require to access the pre filter and EAC filter.Primary Filter Section - Pre filter section will be fixed along with EAC filters ( To maintainn PM 2.5 level upto desired level) to work as a primary filteration.Coil Section- Coil section require with multi row deep chilled water & DX coil section with 2 row deep hot water coil. Sufficient space is require between both the coils for maintenance. Both coils will be on working condiiton togather. DX coil require with 3/8 inch IGT tube. Tube thickness must not be less than 0.5mm.UVGI require for both chilled water & DX coil with running hour meter. Hot water coil require after DX coil. Chilled water coil require Eurovent Certified’ Chilled water/Hot water coil Geometry must not be less than 31.75mm*27.5 mm and for DX coil 25.4mm*22mm or as per OEM standard Coil casing & its blank off require in SS-304 construction.Thyristor based ultrasonic humidifier required in AHU to maintain humidity along with 2 row deep hot water coil EC fan Section -The Fans must required in (N+1) mode . The minimum efficiency class of the motor shall be equivalent to IE5. The motor shall be Permanent magnet external rotor motor with integrated electronics and suitable for continuous operation. The speed of the motor shall be varied with an external 0-10V/ PWM control signal. The fan in totality shall be of most efficient type so that the power Consumption and noise level is minimal. The motor shall be minimum IP54 protection class. Fan must be AMCA certified.Fine Fiter Section - EU-7 Rigid media type filter section require after fan section.Supply Air Damper require in AL construction.
UPPER TIER- In take Section - Return intake section require to connect retrun air duct and to acess pre and fine filter. Filter Section - Pre (Eu-4) & fine filter ( EU-7) with rigid media filter require for return air.EC fan Section - The minimum efficiency class of the motor shall be equivalent to IE5. The motor shall be Permanent magnet external rotor motor with integrated electronics and suitable for continuous operation. The speed of the motor shall be varied with an external 0-10V/ PWM control signal. The fan in totality shall be of most efficient type so that the power Consumption and noise level is minimal. The motor shall be minimum IP54 protection class. Fan must be AMCA certified. Exhaust Air Damper Require in AL construction. 1. Fan operation status 2. Chilled water valve operation status 3. AHU Airflow (CFM) 4. AHU power consumption Controller shall also have fire trip alarm compatibilty to shut AHU in case of signal from fire panel. Instrumentation Kit to be provided to give out the following option 1. Supply air temperature / RH Sensor 2. Return air temperature / RH Sensor 3. Fresh air temperature Sensor 4. Chilled water in temperature Sensor 5. Chilled water out temperature Sensor 6. DP switch across filter for filter clog 7. Touch screen display-Min.7'' 8. DPT 9. UVGI status 10. CO2 Sensor The other than above following features/facilities are also required in AHU : 1) High efficiency air filtration for supply and extract air 2) Capable to control room air temperature and relative humidity throughout the year 3) Variable fresh air supply for OT/procedure room requirements.
4) Self-contained (controller) is an independent system, which is under the direct control of the authorised personnel where room temperature, relative humidity, room positive-negative pressurization levels etc. can be maintained. 5) Enabled to maintain positive or negative pressure per the requirement for the occupied area by providing independent supply air and exhaust air fans with inverter driven motor. 6) PLC unit (MICROPROCESSOR CONTROLLING SYSTEM) controls. 7) Enabling unit to work on positive pressure/negative pressure with the help of PLC as per the instructions of the Engineer-in-charge or as per the requirements supports Aseptic conditions in the operation theatre as well as in surroundings which is the foremost requirement for any medical operation. . System shall have provision to adjust the respective pressure (positive and negative Pressure) along with all required sensors etc. AHU's shall be provided with thermal brake profile & Pre-coated GI canopy (if required at site) and all dampers shall be of motorised type From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring (upto 10mtr) from Terminal Box to multiple direct drive motors provided by AHU vendor.All AHU shall be provided with factory fitted Electrical in AHU Casing (as per approved list of makes and specifications).
The desired rating of AHU shall be as follows: CFM TYPE SP CHW CC/TR HW CC DX CC/TR Exhaust CFM (±5%) 3500 FM 125 8 RD/8 2 RD 4/6 RD/9.6 700
CFM TYPE SP CHW CC/TR HW CC DX CC/TR Exhaust CFM (±5%) 4000 FM 140 8 RD/10 2 RD 4/6 RD/11.2 800
CFM TYPE SP CHW CC/TR HW CC DX CC/TR Exhaust CFM (±5%) 4400 FM 125 8 RD/11 2 RD 4/6 RD/11.2 880
CFM TYPE SP CHW CC/TR HW CC DX CC/TR Exhaust CFM (±5%) 4700 FM 125 8 RD/12 2 RD 4/6 RD/12.8 940
CFM TYPE SP CHW CC/TR HW CC DX CC/TR Exhaust CFM (±5%) 6100 FM 125 8 RD/12 2 RD 6.0 RD/17.6 1220 Note : For AHU 6100 CFM HEPA filters are required at Discharge and shall be included in the cost of AHU. Design of Plenum need to be submit by contractor for approval.Approval to be provided by GE
Floor Mounted AHU's
CFM TYPE SP CC /TR 5500 FM 80 6.0 RD /12
CFM TYPE SP CC /TR 7000 FM 80 6.0 RD /17
CFM TYPE SP CC /TR 8000 FM 80 6.0 RD /20
CFM TYPE SP CC /TR 8600 FM 80 6.0 RD /20
CFM TYPE SP CC /TR 9000 FM 80 6.0 RD /22
CFM TYPE SP CC /TR 10000 FM 80 6.0 RD /25
CFM TYPE SP CC /TR 11000 FM 80 6.0 RD /25
Ceiling Suspended AHU
Supplying, installing, testing and commissioning of factory built Eurovent Certified’ weather Proof Ceiling Suspended double skin type air handling units with thermal break profile made of 32 +-2 mm thick panels consisting of pre plasticized G.I casing made of thickness 0.6 mm outside layer and sheet of thickness 0.6mm inside layer with polyurethene foam (PUF) CFC Free insulation of density 40+-2 kg/m3 factory injected between them by injection moulding machine,extra min13mm thick acoustic insulation of opencell nitrile rubber with 0.8mm AL perforated sheet complete with blower section with blower DIDW backward/Forward curved centrifugal fan for CS AHU's, 4/6 row deep cooling coil, with aluminium finned copper tubes (tube thickness not less than 0.5mm), Filter section with 50 mm thick box type pre filter & microvee filter on common frame. , belt/Direct drive package with TEFC drive motor(IE-3) suitable for 415 ± 10% volts, 50 Hz, 3 phase, A.C supply,Mixing box with Aluminium Anodised Extruded dampers at fresh and return air cutouts.,drain connections with drain valve, stainless steel drain pan, thermometers and pressure gauge at the inlet and outlet of cooling coil, necessary vibration isolation arrangement etc ,The Unit shall have UVGI system AHRI/Eurovent Certified’ complete as per specifications of following capacity:
CFM TYPE SP CC /TR 1300 CS 65 6.0 RD /3.5
CFM TYPE SP CC /TR 1600 CS 65 6.0 RD /4.0
CFM TYPE SP CC /TR 1800 CS 65 6.0 RD /4.0
CFM TYPE SP CC /TR 2500 CS 65 6.0 RD /6.0
CFM TYPE SP CC /TR 5000 CS 65 6.0 RD /12.5
CFM TYPE SP CC /TR 5000 CS 65 6.0 RD /14
CFM TYPE SP CC /TR 1600 CS 110 6.0 RD /4.0 with HEPA filters at discharge
ENERGY EFFICIENT AIR SOURCE HOT WATER GENERATOR/HEAT PUMP Supply, Installation, Testing and Commissioning of electrically operated modular type Air Source Hot Water Generator/Heat Pump of following nominal capacity having Controller and Thermostat so that required qty. of hot water is generated at required temperature with nominal variation, including necessary electrical panel with automatic Controls including inlet and outlet connections and suitable for outdoor installation. The equipment shall be capable of operation from -10 to 43 Deg C DB ambient temperature Suitable Nos & suitable capacity squirrel cage induction motor with class 'F' insulation suitable for operation on 380 ~ 415 volts, 50 Hz, A.C. supply. Suitable Nos. & suitable capacity starter as per manufacturer's design First charge of R410 A refrigerant and oil duly charged at factory 1 No. - Matching Air Cooled condenser with copper tubes and aluminium fins 1 Set - Control panel with display comprising of Controls. It shall also be equipped with protection and monitoring devices such as H/L Pressure switch/ Thermal and Current Overload Protector 1 Lot - DP/ Flow switches at inlet and outlet water drain & air purge valves, wherever required. Lot- suction line and required insulation Lot-frame work for mounting the above with base plate complete with antivibration pads/ springs Nominal Heating capacity : 120 KW(40KW X 3 Nos or any other combination) ; modules shall operate in master slave combination with automatic run time equalization between the modules. Nominal Hot water producing rate: 2580 L/H Nominal Water Flow Rate : 20.64 m3/hr Max Power Input: 26.13 KW Air Source HWG as Above
FAN COIL UNITS (Standard) Supply,Installation , testing and commissioning of fan coil units of specified capacities and air flow as per the specifications , complete with auxillary drain pan. Fan coil unit shall be supplied with approved make of factory fitted adequately sized insulated (with nitrile foam) PICB motorized valves , insulated brass ball valves-one with Y strainer, and the other without Y strainer complete with room thermostat for fan speed control ,copper pipe connections with brass fittings, associated conduiting and wiring between the thermostat . wiring with 3 pin socket plug , U-trap in drain pipe connection near FCU , 3 speed switch , fire retardant double canvas connections , 3/4 row deep hydronic coil , three speed motor , washable filters , Stainless steel drain pan insulated with 13 mm aluminium faced nitrile rubber. Fan coil unit shall be suitable for 220 ± 10 volts , 50 Hz cycle single phase power supply , maximum RPM of motor shall be 960. The Unit shall be complete with insulated FCU assembly for each unbit comprises of on / off type PICB etc.. FCU shall be provided with extended drain pan covering the covering the connection with 13mm nitrile rubber insulation. Cost of fan coil unit shall be inclusive of approved make room thermostat (heating and cooling, with fan speed control), and associated MS conduiting and wiring etc.between the thermostat and PICB , for a standard length of approximately 5-7 M per fan coil unit. Providing and fixing in position the following Fan Coil units complete with all valves and accessories as described above.
400 CFM, 1.0 TR and 3 R.D Cooling Coil
600 CFM, 1.5 TR and 3 R.D Cooling Coil
800 CFM, 2 TR and 4 R.D Cooling Coil
1000 CFM,2.5 TR and 4 R.D Cooling Coil
1200 CFM,3.0 TR and 4 R.D Cooling Coil
Supply, installation, testing & commissioning of the following Conduits complete as per tender specification. Supplying, laying and fixing rigid PVC conduits of 25mm dia N.B.complete with all accessories. [ For only inside shafts]
Flexible PVC conduit of 25 mm dia N.B.
Rigid PVC conduit of 25 mm dia N.B.
Temperature and RH sensor and adjuster package. Supply,install-(grout),test and commission micro-processor based Room temperature, humidity sensor and remote adjuster package within a MS housing -wall ,suitable for mounting, and having a stainless steel cover plate.This package shall have a temperature and humidity display - red 2" high LED character for operation rooms , and other critical areas. Sensor, adjuster (Snap acting humidistat/Proportional thermostat- Microprocessor based) and displayer package, as described above.
EXPANSION TANK SITC of MS Expansion tank of size 1.0 m x 1.0 m x 1.0 m height made of 3 mm thick MS sheet complete with vent and drain connection, quick fill with float valve and control valve etc. as required. Litres duly insulated with fire retardant quality expanded polystrene moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete in all respecte.The tank shall be insulated with the approved method of insulation, and shall be complete with water make-up connection and system .The expansion tank will be supplied,Non return Valve and interconnecting piping. 1000 Ltr . Open Expansion Tank duly insulated and with all accessories.
CHILLED WATER PIPING
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping plumbing inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.),cut to required length, and installed with welded joints (USE RECTIFIER AS SPECIFIED), duly insulated with fire retardant quality expanded polystrene moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints repairing of damage to building etc. as per specifications and as required complete in all respect. Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. (Insulation Make : Beardsell, Lloyed)
200 MM Pipe DIA with 75 mm Thick Insulation
150 MM Pipe DIA with 75 mm Thick Insulation
125 MM Pipe DIA with 50 mm Thick Insulation
100 MM Pipe DIA with 50 mm Thick Insulation
80 MM Pipe DIA with 50 mm Thick Insulation
65 MM Pipe DIA with 50 mm Thick Insulation
50 MM Pipe DIA with 50 mm Thick Insulation
40 MM Pipe DIA with 50 mm Thick Insulation
32 MM Pipe DIA with 50 mm Thick Insulation
25 MM Pipe DIA with 50 mm Thick Insulation
20 MM Pipe DIA with 50 mm Thick Insulation
SITC of Insulated VALVES/CONTROLS - PN-16
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.
200 MM DIA
150 MM DIA
125 MM DIA
100 MM DIA
80 MM DIA
65 MM DIA
50 MM DIA
40 MM DIA
32 MM DIA
Motorized BUTTERFLY VALVE with C I body ,SS disc, O - ring & Min.PN 16 pressure rating,Conformingto BS5155, IS13095. with P-I55 actuator as specified.
150 MM DIA
125 MM DIA
80 MM DIA
65 MM DIA
BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.
125 MM DIA
100 MM DIA
80 MM DIA
65 MM DIA
50 MM DIA
32 MM DIA
NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified.
125 MM DIA
80 MM DIA
65 MM DIA
SITC Water Flow Switches (Brass body) BMS Compitable
SITC Auto Air Vent Valve 1/2"
SITC 6" StemType Thermometers (0 To +50OC)
SITC Pressure Gauge 4" Dial (0 To 6 Kg/CM2)
2-way Control valve with modulating type actuator (PICV) for AHU's 2-way pressure independent balancing cum control valve, self adjusting type for chilled water with electrical actuator. Valve shall be globe type design, with Linear as per VDI/VDE 2173 characteristics. Body material shall be brass(till 32mm) or grey/nodular cast iron (40mm & above)with P/T ports. All working parts like stem & spring shall be in SS and the travelling stroke for the control valves will not be change, no matter the pre-setting the flow rate in the pre-setting rings. The actuator versions should be directly mounting on valves without any adjustments. All the electrical actuator shall be operated through 24 VAC and should be modulated through control signals 0-10 VDC, 4-20 mA, or 0-1000 ohms The actuators should have stroke position indication and manual override mean to manual open and close the actuators when commissioning. The max differential pressure range at least 600 for DN15 ~ DN50 and > DN65 is 700 kPa. Max. Pr. Drop across valve : 40kPa Makes:- Siemens,Danfoss,oventrop
32mm Threaded (8-17)USGPM
40mm Threaded (17-41)USGPM
50mm Threaded (41-50)USGPM
50mm Flange Type (50-70)USGPM
125mm Flange Type (308-484)USGPM
2-way Control valve with ON/OFF type actuator (PID Valve) for FCU's 2-way pressure independent balancing cum control valve self adjusting type for chilled water with electrical actuator. Valve shall be globe type design, with Linear as per VDI/VDE 2173 characteristics. Body material shall be Dezincification resistant hot-pressed brass. All working parts like stem & spring shall be in SS and the travelling stroke for the control valves will not be change, no matter the pre-setting the flow rate in the pre-setting rings The actuator versions should be directly mounting on valves without any adjustments. All the electrical actuator shall be operated through 230 VAC, ON/OFF type and shall be in close position in case of power fail. The max differential pressure range at least 600 for DN15 ~ DN32 Max. Pr. Drop across valve : 40kPa Makes:- Siemens, Danfoss, oventrop
20mm Threaded (2.5-5)USGPM
25mm Threaded (5-8)USGPM
Brass Ball Valves SITC of Brass Ball Valves of dia 40mm with Strainer
SITC of Brass Ball Valves of dia 40mm without Strainer
SITC of Brass Ball Valves of dia 32mm with Strainer
SITC of Brass Ball Valves of dia 32mm without Strainer
SITC of Brass Ball Valves of dia 25mm with Strainer
SITC of Brass Ball Valves of dia 25mm without Strainer
CONDENSOR WATER PIPING Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends,tees etc.but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:-(i)The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. (ii) For under ground pipe : The pipe will be covered by applying 2-4mm thick Tarfelt sheet with required Adhesive ,Accessories etc
250 MM DIA
200 MM DIA
150 MM DIA
VALVES/CONTROLS - PN-16 without Insulation , Make :Advance, Sant,Honeywell Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.
250 MM DIA (Gear Box type)
200 MM DIA (Gear Box type)
Motorized BUTTERFLY VALVE with C I body ,SS disc, O - ring & Min.PN 16 pressure rating,Conformingto BS5155,IS13095. with P-I55 actuator as specified. 200 MM DIA
BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. 200 MM DIA
150 MM DIA
2-way Control valve with modulating type actuator (PICV) for AHU's 2-way pressure independent balancing cum control valve, self adjusting type for chilled water with electrical actuator. Valve shall be globe type design, with Linear as per VDI/VDE 2173 characteristics. Body material shall be brass(till 32mm) or grey/nodular cast iron (40mm & above)with P/T ports. All working parts like stem & spring shall be in SS and the travelling stroke for the control valves will not be change, no matter the pre-setting the flow rate in the pre-setting rings. The actuator versions should be directly mounting on valves without any adjustments. All the electrical actuator shall be operated through 24 VAC and should be modulated through control signals 0-10 VDC, 4-20 mA, or 0-1000 ohms The actuators should have stroke position indication and manual override mean to manual open and close the actuators when commissioning. The max differential pressure range at least 600 for DN15 ~ DN50 and > DN65 is 700 kPa. Max. Pr. Drop across valve : 40kPa Makes:- Siemens,Danfoss,oventrop 150mm Flange Type (484-704)USGPM
Y- STRAINERS (PN-16) Providing and fixing in position the following Insulated Y-Strainers 200 mm
POT- STRAINER(PN-16) Proiding and Fixing of Pot strainer with drain valve complete in all respect of following dia 250 mm
NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation as specified. 200 MM DIA
SITC Water Flow Switches (Brass body) complete with copper control wiring at chiller outlet of each machine
SITC Pressure Gauge 4" Dial (0 To 6 Kg/CM2)
SITC 6" StemType Thermometers (0 To +50OC)
AUTO AIR VENT Supply, installation ,testing and commissioning of Auto Air vents,at the specified locations in the chilled water piping , alongwith isolation ball valves, as per approved makes Auto air vent with isolating ball valves (15 mm dia)
CONDENSATE DRAIN PIPE Providing and fixing and in position the following CPVC pipes (Min. Thickness 3.0mm) for condensate drain duly insulated with minimum 6.0 mm 'O' Class Nirile rubber & duly secured with adhesive tape as per specification ,cut to required length and installed with all joints , including the necessary fittings. (For all the AHU/FCU units upto the main header in the shaft dor vertical risers
65 mm dia
50 mm dia
40 mm dia
32 mm dia
25 mm dia
AIR SIDE WORKS Factory fabricated Duct-GI duct Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required and shall also confirm to the BIS specifications.The duct shall be fabricated at site for to make Collors/bends/plenums/suit pieces Only.
0.63mm (24 gauge) GSS
0.8mm (22 gauge) GSS
1.0mm (20 gauge) GSS
1.25 mm (18 gauge) GSS
Site fabricated Duct-GI duct Supply, installation, balancing and commissioning of Site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required and shall also confirm to the BIS specifications
0.63mm (24 gauge) GSS
0.8mm (22 gauge) GSS
1.0mm (20 gauge) GSS
1.25 mm (18 gauge) GSS
Factory Fabricated Duct - AL duct Supply,Fabrication , Installation and testing of sheet metal ducts in accordance with the approved shop floor drawings and specifications , and shall also confirm to the BIS specifications. The hardware shall be chrome plated or of stainless steel.All lateral and transverse joints shall be sealed with silicon based mastic sealant.
Aluminum Sheet thickness - 0.80 mm
Aluminum Sheet thickness - 1.00 mm
Aluminum Sheet thickness - 1.25 mm
Grilles/Diffusers Providing and fixing of Extruded aluminium supply and return air grilles/diffusers/ louvres with dampers, supply air plenum etc. duly powder coated as per specifications and drawings.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills as per specifications
Supplying, fixing testing commissioning of Return/Supply air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.
Supplying, fixing testing commissioning of aluminium Collor dampers as per specifications
Supplying, Fixing,testing and commissioning of fire dampers with 120 minute fire rating in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
Fire damper
Actuator
GI Volume control dampers for ducts
AI Volume control dampers for ducts
Fresh Air/Exhaust Air Louvers Supply, Installation, Testing and Commissioning of extruded aluminium louvres with frame bird screeen 50 mm pre-filter with frame, mounting arrangement etc. as per specifications and drawings.
Fresh Air/Exhaust Louvers
Supply,Installation,Testing and commissioning of doble layer canvas connection with 1/2 hr. fire rating as per specification.
MECHANICAL INSULATION DUCT LINE ACOUSTIC TREATMENT Supply, Installation, Testing and Commissioning of Acoustic lining inside ducts/plenum using open cell nitrile rubber foam having microban anti-microbial/ anti fungal product protection and of 160-180 kg / m³ density as per ASTM D3575, class 1 ratingn As per BS476,PART-7, cut to required sizes and to be stuck to the inside of duct surfaces with adhesive as approved by the manufacturer. (Rubber based solvent). as per specifications
15mm thick sound board for Floor Mounted AHU's
10mm thick sound board for Ceiling Suspended AHU's
DUCT LINE THERMAL INSULATION (Inside Conditions) SITC of Physically / Chemically crosslinked polyethylene foam, with factory reinforced alupet foil facing, ANTI MICROBIAL/ANTI FUNGAL,HFC & CFC free , Negligible VOC level with Class O fire properties,with very low fire propagation of < 5.5 and passing E-84 at < 25/50, as per technical specification, the density of the foam should be not less than 25-30kg/m3 and the maximum thermal conductivity K should be 0.032W/mK@ 23 Deg C , the permeability resistance factor u shouldn't be less than 14000. The product shall have temperature range of –20oC to 115oC
13 mm thick
DUCT LINE THERMAL INSULATION (Outside Conditions exposed to sun) Physically / Chemically crosslinked polyethylene foam, with factory laminated heavy duty and ultra tough multi-layered composite aluminium foil facing, with puncture resistance of >400N and Class O fire properties as per BS 476 Part BS 476 Part 6 & 7 and as per the tender technical specification and density of the foam should be not less than 25 - 30 kg/m3 and maximum thermal thermal conductivity K should be 0.032W/mK@ 23 Deg C & the permeability resistance factor u shouldn't be less than 97000.
25 mm thick
ASSOCIATED ELECTRICAL WORKS The rates for the distribution boards from the Breakers and instruments shall also include the following : A) Wiring for light / Fan points with 1.5 sq. mm PVC insulated copper conductor 1100 Volt grade stranded flexible FRLS wires of approved make in 1.6 mm thick 25 mm dia MS conduit including cost of providing & fixing saddles, hangers, supports,cutting chases and filling chases for recessed conduiting, and including the cost of providing and fixing a 6 amp 240 Volt Modular Plate type switches of approved quality, colour, make and design with moulded cover plate in zinc chromate passivated MS box and including the cost of running 1.5 sq. mm PVC insulated copper earth wire for loop earthing etc. complete B) TPN ACB’s / MCCB’s shall mean 3 pole ACB’s / MCCB’s with adequate size of neutral link C) All MCB’s shall be of minimum 10 KA breaking capacity or as metioned in BOQ. D The breaking capacity of MCCB’s are mentioned panel wise. All MCCB’s shall be with thermal magnetic microprocessor releases as per BOQ and following i. MCCB rating upto 250 Amps with thermal magnetic releases ii. MCCB above 250 Amps with microprocessor releases. E) All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic. F) Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993 i. IP 42 for indoor panels. ii. IP 55/IP65 for ODU panel. G) All MCCB’s shall be provided with operating mechanism for door interlock H) All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.
I) Providing cable clamps / supports within distribution boards cable alley. J) Current density of aluminium shall be 1sq mm for 1.0 Amps for rated current of bus bars. K) Model, current capacity location and frame size of switchgear shall be written inside of the panel doors with paint / permanent marker as approved shop drawings / site requirment L) All meter shall be digital type. M) Current Transfomer shall be resin cast. N) All Panel Shall be BMS Compitable O) In All panels Each starter should have remote control compatibilty and interlocking facilities including auto manual switch, NO/NC contacts for control and must have auto manual operation suitable to take signal from fire alarm panel for automatic operation of fan in case of fire. All smoke /vent. fan panel the starters shall have suitable facility to operate with fire sensing control modules. Main Electrical Panel (CPRI Approved OEM at leat 70 K) Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of following LT panels fabricated out of 14 guage for load bearing and 16 gauge for non load bearing CRCA sheet steel in cubical formationwith reinforecment of suitable size angle iron and channel T iron flats. All steel material used in the construction of panels shall be powder coated. A solid busbar shall be provided at the bottom of the panel with two connecting eyes for termination. The boards shall be suitable for 415 volts, 50 Hz, 3 phase , 4 wire supply system. All the hardware used in the fabrication of the panel shall be galvanized with zinc passivation. The panel shall be compartmentalized to accommodate one feeder in each compartment. A vertcal cable alley of suitable width shall be provided to serve on or two vertical feeder sections. Also the opening between the busbar chamber and the feeder section shall be shrouded with bakelite / hylam sheet with min.3 mm thickness.
The panel drawing shall be approved before taking up the fabrication and Shall have compitable BMS requirment. Plant Room Panel 1 no.1600 amp EDO ACB 65 KA with Microprocessor release alonwith protection of S/c, E/F, etc Multi Function Digital Meter class 1.0 Accuracy Schnieder series 64XX or equivalent of the same model in Elmeasure/ HPL/Reputed with CTs of the desired rating as per the load. Phase indicating lights RYB with control fuses. Breaker ON/OFF/TRIP indicating lights. Bus Bars 2000 amp TPN Aluminum Bus Bar with heat shrinkable insulation colored sleeves. Outgoings 3nos. 250-320 amp, MCCB, 50 KA with Rotary operating handles for Chiller 3 nos. MPCB for 6 KW or as per the rating of the Chilled water pumps by the Chiller Manufacturer (2Working + 1Standby) for primary Chilled water Pumps without starter as VFD to be available on Chilled water pump side with Digital Ampere Meter Class 1.0 with CT of suitable rating 3 nos. MPCB for 7.5 KW or as per the rating of the Chilled water pumps by the Chiller Manufacturer (2Working + 1Standby) for Secondary Chilled water Pumps without starter as VFD to be available on Chilled water pump side with Digital Ampere Meter Class 1.0 with CT of suitable rating 3 nos MPCB for 11 KW or as per rating of the Condenser water pump without starter as VFD to be available on cond water pumps side with O/L Digital Ampere Meter Class 1.0 with CT of suitable rating
3 nos MPCB for 7.5 KW x 1nos or as per the rating of manufactrer specifications for the cooling towers without starter as VFD to be available on cond fan motor side with O/L Digital Ampere Meter Class 1.0 with CT of suitable rating 3 nos MPCB for 2.5 KW x 1nos or as per the rating of manufactrer specifications for the cooling towers without starter as VFD to be available on HWG/HP pumps side with O/L Digital Ampere Meter Class 1.0 with CT of suitable rating 2 nos MPCB upto 5 KW or as per rating of the Monsoon Re-heating pump and the Star Delta starter with Contactors as per the Cordination chart with O/L Relay, S/D Timer and SPP (1 working + 1 Standby) with Digital Ampere Meter Class 1.0 with CT of suitable rating 6 nos MPCB upto 12 KW or as per rating of the Heat pumpHWG and the Star Delta starter with Contactors as per the Cordination chart with O/L Relay, S/D Timer and SPP (5 working + 1 Standby) with Digital Ampere Meter Class 1.0 with CT of suitable rating 2 nos MPCB upto 36 KW or as per rating of the HWG for Monsoon Reheating and the Star Delta starter with Contactors as per the Cordination chart with O/L Relay, S/D Timer and SPP (1 working + 1 Standby) with Digital Ampere Meter Class 1.0 with CT of suitable rating 3 nos DP MCB 16Amps 10 KA for supplying to various control equipment 1 Nos MCCB upto 200 Amps for VRV/VRF sub Panel 1 Nos, spare space for MCCB upto 100 Amps
Sub Panel for AHU Motors up to 5.5 KW SITC of Wall mounted sub panel boards for AHUs, Blower with switch, starters, lamps inter connections, current operated single phase preventer, A/M switch etc. as per specifications and drawings and as required. 1.0 with CT of suitable rating RYB Indicators 2 Nos. Push Buttons On/Off 1No. single phase preventor 1 nos. DOL starter with Power contactor and MPCB as incomer of the starter with SPP with Digital Ampere Meter Class 1.0 with CT of suitable rating 1 No MCB DP 2 nos. 6 A or suitable, MCB for UVC (if required)
Sub Panel for AHU above 5.5 KW to 15 KW SITC of Wall mounted sub panel boards for AHUs, Blower with switch, starters, lamps inter connections, current operated single phase preventer, A/M switch etc. as per specifications and drawings and as required. 1 Nos. 32-63 Amps TP+NL MCCB 25 KA ICU=ICS=100% with Terminals, ROM and necessary accessories with Mutlifunction Meter Class 1.0 with CT of suitable rating RYB Indicators 2 Nos. Push Buttons On/Off 1No. single phase preventor 1 nos. Star Delta starter with Power contactor and MPCB as incomer of the starterwith SPP with Digital Ampere Meter Class 1.0 with CT of suitable rating 1 No MCB DP 2 nos. 6 A or suitable, MCB for UVC lamp (if required)
SITC of Wall mounted sub panel boards for VRF/VRV switch, starters, lamps inter connections, current operated single phase preventer, A/M switch etc. as per specifications and drawings and as required. 1Nos 160 A incomer feeder 3Ph. Digital Voltmeter, Cl-1.0 - SIF96 x 96 R-Y-B Phase Indicating Lamps 220V AC - LED Type (set) Neutral link Overload relay ,timer,multimeter Indication lamp for R,Y,B phase CT/PT ,Auxillary Contact MCCB TPN 63 A - 03 A MCCB TPN 63 A 02 + 01 (spare) Unloading at site, placement of Panel on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned Panel.
CABLING (POWER) Power Cabling and Earthing Supply, installation, testing & commisioning of Aluminum/CU conductor cables PVC sheathed, armoured cables of 1.1 KV grade with termination glands and GI earthing, identification tags, clamps and saddles etc.
3.5C x 185 Sqmm (Al. Conductor)
3.5C x 120 Sqmm (Al. Conductor)
4.0C x 25 Sqmm (Al. Conductor)
4.0C x 16 Sqmm (Al. Conductor)
4.0Cx10 Sqmm (Cu Conductor)
4.0Cx 06 Sqmm (Cu Conductor)
4.0Cx04 Sqmm (Cu Conductor)
2.5 Cx04 Sqmm (Cu Conductor)
8 Cx1.5 Sqmm (Cu Conductor)
Y - STRAINER (PN-16)of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.
Control Cabling Supply, installation, testing & commisioning of Copper conductor , PVC insulated, PVC sheathed armoured cable of 1.1 KV grade (Which is Interconnecting wiring for the fire alarm system with the AHU and the smoke dampers / actuators etc.
3C x 1 Sqmm
Supply, Laying, testing and commissioning of FRLS XLPE armoured cables for Electrical Power and controls from MCC/LSCP/PDB to respective Equipments with earthing, clamped on surface or on cable trays, structural supports and cable supports provided. The scope includes End Termination of cables with Double Compression type Brass Cable Glands and Copper Lugs, clamping of cables by ready made G.I. spacers, saddles or clamps fabricated out of GI. strip 3 mm thick, treasing and Clamping of Cable on cable tray or surface, supply of all clamping materials and hardware etc., providing cable tags made out of aluminium/PVC laminated strip and 75x20 mm in size with cable number and size punched on it. Cable tags shall be tied to cables at every 20 meter interval and at both the ends. MS Powder Coated Junction Boxes with Bolted type terminals of suitabel size shall be provided near all Fan Motors for termination of armoured cables.
4C x 6 Sqmm Copper Cable for Axial fans
4C x 2.5 Sqmm Copper Cable for Axial fans
Supplying and installing following size of perforated G.I. cable trays, G.I. bends with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with suitable suspenders including G.I. bolts & nuts, painting of suspenders etc. complete as required.
50 mm x 100 mm x 50mm x 1.6mm. Thickness
50 mm x 150 mm x 50mm x 1.6mm. Thickness
50 mm x 200 mm x 50mm x 1.6mm. Thickness
50 mm x 300 mm x 50mm x 1.6mm. Thickness
50 mm x 450 mm x 50mm x 1.6mm. Thickness
Under Deck Insulation Providing & Fixing Underdeck Insulation with 50 mm thick TF Quality EPS of Density 20 Kg/M3 fixed to slab with good quality Black CPRX Compound. 28Gwirenet shall be tightened arround insulation so as avoid any kind of sagging, Ends of net shall be overlapping at least 25mm. Overlaps shall be screwed with galvanized screws to avoid rusting
SITC Central Control panel in ACs plant room containing various indications and control for the AC system comprising of 3 Nos chiiling unit,3 Nos pumps,3 Nos cooling tower, 6 Nos HWG ,3 Nos HWG pumps,35 Nos AHU/CSU with test push button facility The pannel shall be fabricated from minimum 1.6 thick M.S powder coated sheet of approved design.The AC module of the Central Control shall have the following accessories . Status Indication lamp(ON,OFF) for each compressor for each chilling machine and all pumps Push button & Indication lamps for remote start &stop and status indication for each of the AHUs Push Button & Indication lamps for remote start & stop and status indication (ON,OFF & fault) for each of the 3 Nos cooling tower motor and low level indication for each of 3 Nos cooling tower Hooter & Flashing lamps to indicate operation of any safety/shut down with necessary contractors, accept,reset, and test push button complete all as specified
VRV/VRF Systemfor OT's VRV/VRF ODU UNITs Supply, installation, testing and commissioning of Variable Refrigerant Flow modular type air-conditioning system suitable for Cooling & Heating both by multiple scroll/DC Twin rotary compressor controlled by individual inverters for each compressor complete with indoor and outdoor units with individual wired and wireless /wired remote controller for indoor units and centralized controller, interconnecting refrigerant piping, full charge of refrigerant gas (R-410A) & oil, control cabling and fittings etc. as per details given in specifications and having following items. The out door units shall be suitable for 3 phase 4 wire system, 415V + 10 %, 50 Hz AC supply and indoor shall be suitable for Single phase 220-240V, 50 Hz AC supply.Vendors are allowed to quote only Japanese & Indian brands makes for outdoor units Outdoor Units Supply, installation, testing & commissioning of Modular type outdoor units equipped with highly efficient multiple scroll/ DC twin rotary compressors fully inverter controlled (individual inverter for each compressor) i.e. changes its speed in accordance to the variation in cooling loads, special heat exchanger, low noise condenser fan, auto check function for connection error, auto address setting and capacity as mentioned below including all hardware & accessories & including full charging of R-410A refrigerant gas complete i/c powder coating complete as per specifications. The units should be with necessary weather protection coating. The coating should be done before bringing the units to site. Out door units shall be provided with MS stand of suitable size duly painted with corrosion resistant paint suitable for outdoor application including supply, installation, testing and commissioning of centralized remote control system for monitoring the parameters of entire system from a centralized location. All the units shall be provided with built-in microprocessor control panel, for automatic operation and capacity control, Refrigerant Cooled PCB, Automatic Refrigerant charge function.
All compressor shall have inverter technology i.e. outdoor units shall have all inverter based compressor. All units are Cooling & Heating both with Eco Friendly Refrigerant (R-410a). Unit should deliver 100% capacity without deration upto 43°C Ambient Temperature.Operating Outdoor Ambient Temperature Range Cooling 10°C to 56°C & for Heating -5°C to 24°C. VRF Installation work to be executed by OEM or OEM Authorised Vendor Only. The bidder is required to submit MOU certificate from the OEM duly signed and stamped for back to back support & Capacity Deration Rating Chart from OEM. Variable refrigerant flow modular type air- conditioning system suitable for Cooling/Heating by inverter driven capacity control compressor Outdoor unit having minimum COP 3.5 at 100% and minimum 6.5 at 50% Load, at 35 deg C ambient temperature in cooling conditions (To crosscheck COP orginal data sheet to be provided from OEM). Insurance of Units ,Unloading at site, placement of Outdoor Units on the foundation,stands, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned VRF/VRV by OEM. Refrigerant topup or charge must be included in quoted price. Note: (a) The civil foundations reqd shall be made by the tenderer. (b) The mentioned load of chiller unit is minimum and the chiller unit must attain the tonnage load after deration .Contractor is at liberty to procure next higher standard capacity at no extra cost.
AHU Expansion KITs
SITC of Required AHU KIT for connection the cooling coils with the VRF/VRV outdoor unit complete with expansion valve,sensors,wired remote controller & PCB etc. to run the AHU as required for OT AHU's
SITC Central Controller compatibale with BMS
PIPING Refrigerant Piping 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 13 mm thick insulation
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 13 mm thick insulation
22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
34.9 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
NOTE:- 1)The Copper Piping & Piping Circuit should be with Minimum Number of joints, which shall be attained by : (i) Using One End Expanded Tubes (ii) Bending the tubes instead of using elbow joints wherever 90 degree bending is required. (2) Piping should be routed at site in such a manner, that brazed joints in the refrigeration piping are kept to a minimum. (3) The makes of tube fittings shall be same as that of tubes. (4) The thickness of fittings used shall be same as that of the pipe.
Control Cabling Providing & fixing control cum transmission wiring/ Control Cabling of 2 core x 1.5sq. mm copper in suitable conduits between indoor and out door unit & indoor unit & its remote controller.
SITC of Strip heaters along with all kind of thermostats ,internal wiring, hanging arrangments, cut out in ducts (if required), making banks of heaters as per AHU's/Area requirments, complete in all respect Strip heater 3.0 KW
Primary Heat pump/HWGs water PUMPS Supply, installation, testing and commissioning of PN16 rated Vertical Inline Split Coupled (with rigid aluminium alloy coupling between pump shaft and motor shaft) single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications. Casing (Volute) - Cast Iron/ Ductile Iron. Impeller - 316 Stainless Steel - Statically and Dynamically Balanced Casing Gasket - Confined Non Asbestos Fiber Pump Shaft - SS 316. Flush Line - Braided Stainless Steel Mechanical Seal - Outside Balanced Motor Type - Parmanent Magnet Motor , Efficiency Class - IE5. Pump having rated capcity 2.2 Kw All the VFD should display the dynamic head & flow rate of the pump using inputs from ultrasonic flow meter and digital pressure gauge or using sensorless algorithms,( 1 flow meter and 2 pressure gauges to be supplied for each VFD driven pump). Pump manufacturer to supply Ultrasonic flow meter and digital pressure gauges along with the pumps supplied or can display individual flow and head of each pump using sensorless algorithms.VFD screen should be touch screen All pump shall be provided with embedded software and hardware for wireless remote performance managements with an initial one-year subscription for IOT service as described below. a) Web access to monitor data (flow, head, vibration, pump in hand, dead head, & other important electrical data) b) Analyzed out in the form of alerts for preventive maintenance. c) Energy Report & raw data available to download Heat pump Water Pump ( 2W+1S ) Water Flow Rate: 95 USgpm Head : 18 m WC
SITC of BMS computer station having computer processor 2.6 Ghz along with the enclosure. The processor must be processor-7th gen intel Core TM i5 processor (2GHz) and 16 GB DDR4 RAM or higher with two hard drives-Solid State Drive 512GB + 1TB Hard Drive. Along with Graphic Card-NVDIA G and screen monitor of 27 inches for the SCADA work station system complete all as specified and directed. Must be accompanied by all peripherals such as mouse, keyboard, firewell etc with dedicated UPS supply having 30 minutes of backup.
Supply, installation, Testing and Commissioning of Building Management System server software. Must have user customizable dashboards and SLD (without any coding/scripting) Reporting must be user-configurable and changeable. Utility like billing reports must be supported. Multi-site data viewing within same interface from all sites to single server system must be accessible over LAN and must have adequate security with dual factor authentication with username/password alongwith OTP on email. All device communication with the third party system with must be secured using TLS/SSL encryption. System must work without any need of static IP. No static IP will be provided for any location. All screen development must show at least the basic monitoring, automation and controlling functionality for VRF, AHU and the logic to operate both within the actual layout of the building. Periodic reporting shall be enabled according to the format decided by the engineer-in-charge. All runtime/development licenses must be included in the above for creation and maintenance of the system.
FIRE FIGHTING SYSTEM
Providing and fixing fire hose cabinet of size 1000 x 1650mm weather proof fabricated from 18 SWG MS sheet with double front central opening partially glazed with 4mm thick glass with locking arrangement duly painted suitable to house incl 2x15Mtr (two length) of RRL house and hose reel drum with coupling, Branch pipe one firemans axe, first aid hose reel and hydrant outlet complete all as directed.
M&L for road cutting of average size 0.30m x 0.60 m for laying of MS pipe, incl excavation, returning filling in, spreading, levelling well ramming in layers, soling with broken boulders/stones, WBM 7.5 cm thick coarse aggregate received from dismantling the existing road, premix capeting 25mm thick using ready mix patch repair work, complete all as specified & directed.
Supply and fixing of Automatic air-vent having 15mm end connections complete all as specified and as directed.
Providing and fixing 6 kg capacity Multipurpose dry chemical powder (ABC) type (IS-15683) fire extinguishers consisting of welded MS cylindrical body fabricated from 1.6 mm MS sheet internally protected with anticorrosive treatment and hydraucally tested. Extinguisher externally painted with red enamel and fixed to wall with bracket complete with initial filled/charged all as specified and as directed.
Providing and fixing CO2 type fire extinguisher of 3 Kgs capacity with steel cylinder with a discharge valve and confirming to IS : 15683. Extinguisher shall be painted with red enamel apint and fixed to wall with bracket complete all as specified and as directed.
Providing and fixing 9 Ltr capacity Foam type (IS-15683) fire extinguishers consisting of welded MS cylindrical body fabricated from 1.6 mm MS sheet internally protected with anticorrosive treatment and hydraucally tested. Extinguisher externally painted with red enamel and fixed to wall with bracket complete with initial filled/charged all as specified and as directed.
Supply, installation, testing and commissioning of powder coated of Siemens grey of approved colour compartmentlised cubicle MV Panel fabricated out of 14 SWG thick CRCA sheet steel suitable for operation on 415 Volts, 50Hz, 3 Phase 4 wire AC supply . The panel shalll be indoor free standing, floor mounting, dust and vermin proof type, adeqate size cable alley with front operated rotary handles for MCCB's complete with gland plates, lifting hooks, ventillating louvers, busbars, Inter connections, earthing, labelling electrical , as per specification and drawings, suitable for termination of cables as per single line diagram including. supply and fixing of following switchgear and accessories complete as required. A separate earth copper bus bar of size 25 mm x 5 mm to be provided throughout the length of the panel. The Panel should be extendable type. (Make of panel, Tricolite, International Switchgear, Embit ,ETE Electrogears). Having CPRI test certificate breaking capacity 70 KA and ISO 9001-2008.
ENCLOSURE & ACCESSORIES Fabrication in 2.0 mm.CRCA Sheet Powder Coating in Siemens Gray Shade, Cable Entry will be Top & Bottom Suitable for Cable ,Lock, Rubber Gasket, hardware etc. BUS BAR & HARDWARE 200A. Aluminium Main Bus Bar,Load wise Sub Feeder Bus Bar Colour Coated Heat Shrink Bus Bar sleave Nut-Bolt,Washer ,Hardware etc. WIRING & ACCESSORIES Power & Control Wiring will be (ISI 1100V) flamc smoke FRLS PVC Single Core Copper Wire,Copper Lugs, PVC Sleeve, Ferruels Numbers, Hardware & Labour etc. Note:- The All acccessories included in the panel cost such as MCCBs, MCBs, ACB , rotary handles, Spreader link and its accessories & metering etc. The panel should be got inspected / tested in the factory premises from the Engineer-in-charge / consultant before brought at site after approval of all drawings of the panel. INCOMER FEEDER : 160A MCCB INCOMER FEEDER 160A 4P 25kA MCCB - Thermal Magnetic with O/L, S/C Rel. Rotarty Operating Handle Spreader Links with Phase Barriers (Set of 8) 06A SP 10kA MCB - Curve "C" ( For Control) 3Ph. Digital Voltmeter, Cl-1.0 - SIF96 x 96 R-Y-B Phase Indicating Lamps 220V AC - LED Type (set) Neutral Link OUTGOING FEEDER : 50HP STAR-DELTA STARTER OUTGOING FEEDER : 1 No 100A, 3P, 55kA, MCCB for Motor Starter Protection Rotarty Operating Hand Spreader Links with Phase Barriers (Set of 6)
MAIN BUS BAR : 160A TPN Aluminium Bus Bars - Electrolytic Grade E-91E grade AL. Horizontal, Vertical, Input & Output Links of SMG Bus Bar Supports, Colour Coded PVC Heat Shrinkable Sleeves Earth Bus across the width of the panel ENCLOSURE & ACCESSORIES: Estmd. Size of Panel: MS Cabinet (2/1.6mm - CR-3.15 D-Grade) with Base Frame Mounting Plates, MS Channels, Partitions & Gland Plates EPOXY Powder Coated Paint (Min. 60Microns) after Seven Tank Pre-treatment Process Hardware and Accessories - Nuts, Bolts, Washers - Plain & Spring Door Hinges (Aluminium Die Cast), Steel Door Locks Neoprene Rubber Gaskets -"D" Type, Rubber Gromet Transparent Polycarbonate Sheet for covering live parts + Fly Nut + Handle "I" Lifting Hooks with Plain & Spring Washer and Bolts Inscription Name Plates, Danger Plates, Legends, Lock / Unlock Sticker Braded Copper Wires for Feeders Door Eathing with Thimbles Wiring & Accessories : PVC Wires, Ferrules Thimbles PVC Channels, Terminal Strips, End Plates, Dressing Other Wiring Accessories. Materials for Wiring, Buttons, Tie Sticker. Note:The system shall be designed for operation automatically so that as and when water is drawn from the system through any hydrant, the pumps will operate automatically and feed water in to the system. However once a fire pump starts working, it will be stopped only manually (except jockey pump) or on account of any fault or non-availability of power supply to electrical pumps The control system shall be designed to provide the following sequence of operation:
SITC of Fireman Axe
Supply and fix foot valves without bypass arrangement vertical installation flanged type for iron pipe of dia 150mm as per ISI4038 incl taking out old unservicable valve complete all as specified.
SITC of test drain assembly complete 25mm dia
Supply and fix Master Control Unit along with connected items complete all as specified and directed by Eng-in-charge
Supply and fix pressure switch complete all as specified and directed by Eng-in-charge
Supply and fix 1.5 sqmm 3 core copper cable for pressure switch complete all as specified and directed by Eng -in-charge
Linear pneumatic heat detection tube for automatic fire detection and suppression system made by special modified Polyamide (PA)- CE APPROVED
HOT WATER SUPPLY SOLAR
Fabrication of stand and ladder arrangements for cold water storage tank from MS angle iron of size 50 x 50 x 6mm and 3.15 mm thick MS base plate incuding one red oxide primer coat and two finishing coats of synthetic enamel paint
M&L GI tubing 25 mm bore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc, in new or old position fixed complete to walls & ceiling or laid in floors/ trench complete all as directed.
MGPS Supply, Installation, Testing & Commissioning (SITC) of BSI Kite Mark Certified Copper Pipes : It should be confirm and meets with BS:EN:13348:2016 copper pipes: All medical grade degreased copper pipes. Medical Grade Copper pipes manufactured from Phosphorous de-oxidized non-arsenical copper to BS:EN: 1412:1996 grade CW 024A ( Cu-DHP) manufactured to metric outside diameters and having mechanical properties in accordance with BS:EN: 13348:2016, Degreasing of pipe shall be such that there is less than 20 mg / m2 (0.002 mg / cm2) of hydrocarbons on the degreased surface when tested by the method specified BS: EN: 13348:2016 complete all as specified and directed.
(a) SITC of BSI Kite Mark Certified Copper Pipes of 54mm.
(b) SITC of BSI Kite Mark Certified Copper Pipes of 42mm.
(c) SITC of BSI Kite Mark Certified Copper Pipes of 28mm.
(d) SITC of BSI Kite Mark Certified Copper Pipes of 22mm.
(e) SITC of BSI Kite Mark Certified Copper Pipes of 15mm.
SITC of Line Ball Valves: It should fully complies and meets with the requirements of the HTM 02-01 / NFPA -99 Recomendations All ball valves as per BS 1057 are rated at 400 psig, as well as full vacuum ( 29.9" Hg). Valves go from full ON to full OFF by turning the vinyl-gripped valve handle 90 ° Locking-type handles may be ordered separately when required. Copper tubing is factory installed to help prevent valve seat damage during soldering. Main and riser valves are not required to be installed in a box unless specially noted or required. It should be duly CE markd with 4 digit notified body number or UL /ETL listed whereever applicable. All line valves - Supplied with a mechanism to enable the unit to be locked in the fully closed or fully open position complete all as specified and directed
(a) SITC of Line Ball Valves of 54 mm size with pipe stub on both sides
(b) SITC of Line Ball Valves of 42 mm size with pipe stub on both sides
(c) SITC of Line Ball Valves of 28 mm with pipe stub on both sides
(d) SITC of Line Ball Valves of 22 mm with pipe stub on both sides
(e) SITC of Line Ball Valves of 15 mm with pipe stub on both sides
SITC of Area Valve Service Units for 5 gas services Service : It should fully complies and meets with the requirements of the HTM 02-01 or NFPA 99. Bidder must submitted third party CE certification I UL listed along with tender documents. Self attested certificate not valid. Adopter having opening by quarter turn of handle. The valve should be pneumatically tested as per BSEN 1057 for twice the working pressure and degreased for medical gas service before supply. Valve boxes should be equipped with components for shutting off and supervising individual /parts of central systems in hospital, laboratories and the like. They should be allowed the ward staff to allow isolating of the areas for maintenance and repair work. The pressure monitoring of the distribution system is done by pressure gauges. In case of emergency the door can be glass break opened or by un-locking using the key.
Area Alarm for 5 Gas service: It should fully complies and meets with the requirements of the HTM 02-01 standards or NFPA-99 Standards recomendations and standards mentioned under these recomendations or applicable. . It shall be provided with a copy of the certificate of origin. Area Alarms are designed to include all necessary displays, factory wiring, transformers and circuitry requiring only 230 VAC primary powers. Internal voltage should be stepped down to S VDC and 1S VDC for control circuit Power. Voltage to external pressure or vacuum transducers should be 1S VDC. The Area Alarm should have digital display facility. Area alarm panels should be modular in design. Each gas monitored should have a light Emitting Diode (LED) display to continuously indicate actual line pressure. A vertical series of LED's should further indicate relative line pressure. The LED should show Normal pressure at SO psi. Apart from Normal it should also show low risk of 40 PSI as low-pressure and 60 psi as high. High risk of 30 psi as low pressure & 70 psi as High pressure. The back box should contain factory installed copper tube extensions 6" Long, 3/8" ID (1/2"0D) , to accept installer furnished lines form the medical gas system. Each inlet tube should accept gas - specific DISS fittings for transducers, to prevent cross-connection. The power supply should be installed in the back box Power supply should include an on I off rocker switch and a fuse holder. The audible alarm tone should pulsate, 90 dBa at 2 meters. The audible signal should be cancelled only by the alarm silence button or fault correction. The display should remain illuminated to indicate the presence of the alarm condition. The alarm should automatically reset with the correction of the fault condition. Should a new alarm occur while the panel is silenced, the audible alarm should reactivate. The area alarm should store the last four alarm conditions in memory at the alarm panel. These conditions can be indicated by using the buttons on the alarm panel control module complete all as specified and directed
SITC of Area Valve Service Units for 3 Service : It should fully complies and meets with the requirements of the HTM 02-01 or NFPA 99. Bidder must submitted third party CE certification I UL listed along with tender documents. Self attested certificate not valid. Adopter having opening by quarter turn of handle. The valve should be pneumatically tested as per BSEN 1057 for twice the working pressure and degreased for medical gas service before supply. Valve boxes should be equipped with components for shutting off and supervising individual /parts of central systems in hospital, laboratories and the like. They should be allowed the ward staff to allow isolating of the areas for maintenance and repair work. The pressure monitoring of the distribution system is done by pressure gauges. In case of emergency the door can be glass break opened or by un-locking using the key.
SITC of Area Alarm for 3 Gas service: It should fully complies and meets with the requirements of the HTM 02-01 standards or NFPA-99 Standards recomendations and standards mentioned under these recomendations or applicable. . It shall be provided with a copy of the certificate of origin. Area Alarms are designed to include all necessary displays, factory wiring, transformers and circuitry requiring only 230 VAC primary powers. Internal voltage should be stepped down to S VDC and 1S VDC for control circuit Power. Voltage to external pressure or vacuum transducers should be 1S VDC. The Area Alarm should have digital display facility. Area alarm panels should be modular in design. Each gas monitored should have a light Emitting Diode (LED) display to continuously indicate actual line pressure. A vertical series of LED's should further indicate relative line pressure. The LED should show Normal pressure at SO psi. Apart from Normal it should also show low risk of 40 PSI as low-pressure and 60 psi as high. High risk of 30 psi as low pressure & 70 psi as High pressure. The back box should contain factory installed copper tube extensions 6" Long, 3/8" ID (1/2"0D) , to accept installer furnished lines form the medical gas system. Each inlet tube should accept gas - specific DISS fittings for transducers, to prevent cross-connection. The power supply should be installed in the back box Power supply should include an on I off rocker switch and a fuse holder. The audible alarm tone should pulsate, 90 dBa at 2 meters. The audible signal should be cancelled only by the alarm silence button or fault correction. The display should remain illuminated to indicate the presence of the alarm condition. The alarm should automatically reset with the correction of the fault condition. Should a new alarm occur while the panel is silenced, the audible alarm should reactivate. The area alarm should store the last four alarm conditions in memory at the alarm panel. These conditions can be indicated by using the buttons on the alarm panel control module complete all as specified and directed.
Supply and installation of Oxygen BPC single type pipe line flow meter with humidifier bottle including pressure gauge, flow adjuster, screw cap, pressure reducing valve, safety vlave complete testing and commissioning all as directed by Engr-in-Charge.
Supply and fix Nitrous oxide liner and the tube including connected items all as directed by Eng -in-charge
Supply and fix Theatre vacumm unit incl Theater vacuum unit shall be Analog type regulator with gauge (size 2 and 1/2 inches) with gauge accuracy + 1% of full scale color coded range. The unit shall have 3-Mode High feature and equipped with push to set technology which shall automatically establish vacuum. Limit with each vacuum level setting. The vacuum unit shall have a precision in the critical care range (0-200mm hg) and should provide fast adjustment with turns of the knob up to full wall vacuum thus should instantly facilitate regulated and continuous suction for tracheal and pharyngeal airway management, surgical procedure and continuous drainage which shall facilitate unrestricted full time vacuum for emergency .This unit shall consist of suction bottle/Jar of capacity 2000 ml with suction cannula and all connected items. The unit shall be equipped with Positive Pressure Relief Valve to protect patient and unit both in case if accidentally connected to pressurized gas (O2, Air etc) all as directed by Engr-in-Charge.
Supply and fix Ward vacumm unit incl Vacuum Jar capacity 600 ML with vacuum regulator including connected items all as directed by Engr-in-Charge.
M&L for decorative bed head panel with outlet for Oxygen/Vacuum/Med Air/Nitrous and with outlets & for 4 gases matching prob , 06 Nos 15 Amp point incl. switch and socket including all connected accessories i.e BPC flow meter /humidifier bottle/Vacuum jar /Oxygen flow meter but incl oulets points with matching probe as per HTM 02-01 or NFPA 99 CE certified / UL listed etc all as directed by engr-in-charge.
Supply, install & testing high pressure tubing as per HTM 02-01 or NFPA 99 CE certified / UL listed for oxygen, vacuum, Air all as directed by engr -in-charge.
SITC of oxygen manifold with 8 Nos pigtail pipes for 4 +4 cylinders and non return valves The oxygen cylinder manifold should comprise of two cylinder Banks which can accommodate 8 cylinders in each Bank (means 4+4) complete with copper tail pipes with bull nose fittings of RH External threading suitable for cylinder valves conforming to IS 3234 (Oxygen service) and Cylinder support system. Manifold should be suitable to withstand a pressure of 140 Kg/cm2, along with high pressure copper annealed tail pipes with Brass adapter suitable for Oxygen Cylinders and manifold. High pressure copper tail pipes, made of high pressure copper pipe of size 1/4" I. D. x 15 swg. Note: Free standing modular mounting frame of suitable size deemed in the quoteed rate.
SITC fully automatic oxygen control panel as per HTM-2022/02-01 The control panel should be capable with auto switch over facility when ever required with all required fittings and accessories required for noramal running of the system. Gas Manifold should be fully automatic, self- shifting to reserve bank on exhaustion of the service bank without interruption of gas delivery to the system. Critical connections should be gas specific, non- interchangeable and should be designed to eliminate gas supply error. The manifold control system should supply a flow of 2000 L/ Min at 50 psi. The dual line regulator/single vent Medical Gas Manifold control unit should include right and left header bars and pigtails for the appropriate medical gas. The installed system should automatically switch over to the reserve bank when the primary bank is depleted. When the depleted cylinders are replaced with full cylinders the system should automatically reset itself in preparation for the next bank change. The primary side bank in use and the remaining side bank on reserve. This designation should automatically change from left to right and right to left as each bank is depleted and, in turn, refitted with full gas cylinders.
SITC of Oxygen Manifold Emergency for 8 cylinders, The oxygen cylinder manifold should comprise of two cylinder Banks which can accommodate 8cylinders in each Bank (means 4+4) complete with copper tail pipes with bull nose fittings of RH External threading suitable for cylinder valves conforming to IS 3234 (Oxygen service) and Cylinder support system. Manifold should be suitable to withstand a pressure of 140 Kg/cm2, along with high pressure copper annealed tail pipes with Brass adapter suitable for Oxygen Cylinders and manifold.Top frame comprising of high pressure copper pipes of size 1/2" I. D. x 15swg with high pressure brass fittings made of high tensile brass and connections through non- return valves. High pressure copper tail pipes, made of high pressure copper pipe of size 1/4" I. D. x 15 swg. The copper tail pipes are fitted to the individual non return valves of the cylinder manifold for easy removal of cylinders without disturbance to system operation
Supply,Installation,Testing and Commissioning of N2O Fully Automatic Manifold Control Panel.The fully automatic N2O control panel should comply with HTM02-01/NFPA99C/EN/DIN/ISO7396-1 STANDARD.It should have import /manufacturing license from Central licensing Authority or State licensing authority of CDSCO for the product and copy of valid license should be submitted.The manifold assembly should provide two stages of pressure regulation. A single stage primary regulator,one for each cylinder bank should be used to initially reduce cylinder pressure and two single stage pressure regulators should be provided in the control cabinet for final delivery pressure regulation.One delivery pressure regulator in service and one should be ready for service in a Stand by mode.The Manifold control panel should be digital ,fully automatic type and switches from“ Bank in Use”to“Reserve bank“ with out fluctuation in delivery supply line Pressure.Change over should be performed by electrically /pneumatically operatedvalves contained in the control cabinet. In the event of an electrical power failure (incase of electrically operated) the valves should automatically open to provide a nuninter rupted gas flow.The mani fold should not requireany manual resetting or adjustments after the replac ements of the depleted cylinders. The Control Panel shall include two pressure relief valves,one high pressure approx. 200psi and one low pressure approx.75psi.
SITC of Oil free Air Compressor with compressed air plant complete package unit total capacity 2 x 450 LPMor next higher The system should be designed minimum duplex to deliver total plant capacity (running +standby) as specified in the BOQ to the hospital and associated equipment, one vertical ASME Tank and one control panel. The entire system including the receiver should be mounted on a common structural steel stack base. The only field connections required would be system intake, exhaust and power connection at the control panel. All components should be completely prepiped and pre-wired to single-point service connections. All interconnecting piping and wiring should be completed and operationally tested at the site of manufacturer.The medical air compressors should be of oil free screw/scroll technology air-cooled design. Connecting rod and bearings should be packed with lifetime lubrication and sealed Each compressor should be belt driven by a suitable HP, 3 phase, 50 cycle, 415 volt, ODP NEMA construction motor. Slide bases for convenient belt tension adjustment and totally enclosed OSHA approved belt guards should be provided. The system should include individual compressor inline intake filters, discharge check valves of bronze construction, safety relief valves, bronze intake and discharge flexible connectors, solenoid unloaders, isolation valves, air cooled after coolers for each compressor, high discharge temperature shut down switches on each cylinder, pressure control switches, as well as copper tubing with shut-off cock for gauge and switches. The system should include a 120 gallon or as per site rrquirement pressure storage tank of ASME construction rated for 200-PSI MWP service. The tank should be equipped with a pressure gauge, safety relief valve, 3-way by-pass; gauge glass and automatic electronic tank drain with manual override. The inside of the tank should be coated for rust protection with a two component coating which provides a hard, durable lining.
All the status monitoring of the pump can be connected to the Master Alarm. The system should also include the following: Factory installed 5 micron pump inlet filters to promote longer life. The medical plant should be manufactured under in ISO 13485 quality management system. The plant should be fitted with filters. There should be a vacuumreceiver of 1000 ltr capacity. One bacterial filter with secretion bottle having end connection of 2 inch. Electrical control panel.
S&F hospital sign bd of different types and size for MGPS i.e. illuminated and others for depition of various wards, deptts, centres, services and other locations in the hospital incl day and night signs and patient guidence system. Note:-All items should be duly CE marked with 4 digit notified body number or HTM 02-01 or NFPA 99 / UL listed.
SOLAR PHOTOVOLTAICS SYSTEM (SPV) Supplying, erecting, installing, testing and commissioning of Grid connected Rooftop Solar Photo-voltaic (PV) plant of 50 KWp, incl mounting structures, PV output, at STC comprising of following sub-components and meeting the specifications as given here-in-after:- Note - (a) cumulative capacity of inverter shall be 50 KW. Design structural drawings of module mounting structure along with design calculations shall be submitted by the contractor duly vetted from MNRE approved organisation / NIT / IIT / Govt Research Institute. The cost of same shall be deemed to be included in this item. (b) Minimal technical requirements / standards for SPV systems /plants to be deployed as per MNRE are mandatorily to be complied within the design. Some of these are narrated here-in-after. For other details website of MNRE may be referred. (c) The detailed specifications are mentioned in particular specification.
EXTERNAL WATER SUPPLY
Supply and lay ductile iron Spun (Socket Spigot) pipe including specials, class " K-9", 100mm, laid in trenches complete all as specified and directed by Eng-inchargre.
Supply and lay ductile iron Spun (Socket Spigot) pipe including specials, class " K-9", 150mm, laid in trenches complete all as specified and directed by Eng-inchargre.
Material and labour for fixing including jointing and testing of cast iron butterfly Valves as per BS EN 593 (BS 5155) IS 13095 Body Cast Iron S:210 FG 260 Disc Ductile Iron IS 1865 Gr 400/15(Epoxy coated)stem SS ASTM A 276 type 410 seat nitrile /EPDM Rubber Ends Water type to suit mounting bteween flanges drilled to IS 1538 100 mm class pn16 with hand lever operated & above with gear operated complete all as specified and directed by Eng-inchargre.
Material and labour for fixing including jointing and testing of cast iron butterfly Valves as per BS EN 593 (BS 5155) IS 13095 Body Cast Iron S:210 FG 260 Disc Ductile Iron IS 1865 Gr 400/15(Epoxy coated)stem SS ASTM A 276 type 410 seat nitrile /EPDM Rubber Ends Water type to suit mounting bteween flanges drilled to IS 1538 150 mm class pn16 with hand lever operated & above with gear operated complete all as specified and directed by Eng-inchargre.
Material and labour for fixing including jointing and testing of cast iron butterfly Valves as per BS EN 593 (BS 5155) IS 13095 Body Cast Iron S:210 FG 260 Disc Ductile Iron IS 1865 Gr 400/15(Epoxy coated)stem SS ASTM A 276 type 410 seat nitrile /EPDM Rubber Ends Water type to suit mounting bteween flanges drilled to IS 1538 80 mm class pn16 with hand lever operated & above with gear operated complete all as specified and directed by Eng-inchargre.
M&L for DI/CI/GI fittings i.e bends,teees,union etc all as specified and directed by negr-in-charge.
M&L for cutting of existing DI/MS pipeline of 150/100 mm dia bore/size in position for insertion of 01 No tee of required size and bore connecting pieces/flanged/socketed/spigoted of suitable bore and making run lead/flanged joint complete all as specified and directed.
M&L for road cutting of average size 0.30m x 0.60 m for laying of MS pipe, incl excavation, returning filling in, spreading, levelling well ramming in layers, soling with broken boulders/ stones, WBM 7.5 cm thick coarse aggregate received from dismantling the existing road, premix capeting 25mm thick using ready mix patch repair work, complete all as specified & directed.
EXTERNAL ELECTRIC SUPPLY
Supply, installation, testing and commissioning of distribution net work, 11 kv outdoor compact Sub Station totally factory assembled (non walk in type) consisting of RT2 RMU type, 1 No. 11KV/433V, 500 KVA with Mineral Oil type transformer, 1 set of LT device as under. Approved Makes- Schneider/ ABB/ Siemens Note: (a) The CSS and all accessories / fittings shall conforming to relevant IS with latest amendments. (b) Completion of the work shall be issued after precommisioning of CSS inspection by Testing Officer. Necessary tools and equipment shall be provided by the contractor for testing / precommsioning without any extra cost
Cable route indicator made out of stone patties size 10cmx15cmx60cm in lengths duly engraved and painted with (HT Cable) with projection of 30 cm above ground level and 30 cn grouted in foundation includingg PCC foundation etc complete all as specified and directed.
SEWAGE DISPOSAL
RCC Septic tank conventional type design to carry sewage and sludge water ecxavation in any type of soil , PCC 1:4:8 in foundation and RCC M-30 Design Mix in walls base slab and Roof slab including Beam and vent saft complete with effective depth of 1.5 mtr and overall depth of 3.00 mtr for 150 users
Sockage well 3.60 mtr dia and 6.00 mtr effective depth in any type of soil , foundation in PCC 1:3:6 ,walls of hony comb massonary with top ring of M-25 concrete including intersepting chamber and screen chamber made of brick massonary, RCC cover slab in M-25/SFRC cover ,interconnecting pipe/RCC /DWC complete filled with brick bats, coplete all as.
RAIN WATER HARVESTING
M& L for drilling 300 dia bore hole by DTH cum Rotary at any depth below the ground level below the ground level any kind of rock/soil upto 100 m depth including disposal of surplus soil to a distance of not exc 50 m all as specified and directed.
M&L for perforated 250 mm dia UPVC pipe of pressure rating 10 Kg/Sqcm fixed to wall/ceiling/floor all as specified.
MODULAR OT & LIGHT
-Blank-
-Blank-
Supply, Installation, Testing and Commissioning of Surgeon Control Panel : It should be designed to cope with changing technology and equipment in operating environments. Control panel should be user friendly and ease of operating and maintaining purpose. It should be flush to wall touch screen application for operating theatres, protected by a glass surface that enhances its features and performance in a critical environment of an operating room, coplanar to the finish panel (with the exception of the panels with metallic finish. Touch Screen Surgeon Control panel is recessed box kit for screen 32" approx. 1 x Hardware and software kit for touch screen, with PC intel NUC, PLC and software. 1 x Capacitive touch screen 32" approx size with full HD resolution. It should have IPS alarm and memory for fault status report. The control panel should have feature for On and off and dimming of LAF Light, Peripherial Lights. The control panel should have feature for On and off of OT LED Ceiling Light. The control panel shall accommodate digital clock and the elapsed time display. The control panel should medical gas alarm low pressure display. The control panel should have temperature, humidity and HEPA filter indicator display. Make : Getinge / Stryker / Drager / Western India Electromedical Systems Pvt Ltd / Magnatek Enterprises.
Supply, Installation, Testing and Commissioning of Double arm moveable Pendant for Anesthetist wih following specification :- (a) The Pendants should comply with NFPA 99C/HTM 02-01/DIN. The support arms should be extremely robust and revolve on high quality bearings, so that the pendant head glides smoothly and quickly to any desired position. (b) Double moveable arms (any combination) with total coverage of min 1800mm and 330 deg. Horizontal movements for each arm. Vertical movement should be motorized and the arm height should remain to a height greater than 6.5 feet above floor level. (c) Weight carrying capacity of the arm should not be less than 180 Kg. should have electromagnetic/pneumatic brakes. (d) Each arm should be capable of 300-340 degrees of rotation, which can be easily adjusted to suit the desired mode of operation. (e) The pendant should be European CE Certified or US FDA or BIS approved. (f) The Pendant Service Heads should be modular with minimum 800mm head. The heads should be capable of accepting a range of shelves, infusion poles, electrical switch / sockets, gas outlets other accessories as asked intender. The Pendant Heads should support the range of Physiological Monitor Mounting Solutions. (g) The Pendant Service Heads should be supplied with medical gas terminal units and 5/15 or 6/16 Amps hybrid Sockets (h) Double arm pendant anesthesiologist: Each pendant should be supplied with outlets and probes as mentioned below :- (i) Oxygen outlets - 02 Nos, (ii) Vacuum Outlest - 02 Nos, (iii) Nitrous Oxide - 01 Nos, (iv) Air (4 bar) outlets - 2 Nos (v) AGSS Outlest - 01 Nos, (vi) Electrical Sockets - 10 Nos, (vii) Adjustable Shelf with two rails one on each side - 03 Nos, (viii) IV Fluid Pole with 4 hooks - 01 Nos, (ix) Data Socket RJ-45 - 02 Nos Note : Pendant Supplier should provide cutouts for Patch panes in intefrated OTs. Anaesthettist pendant shouldd havee NIST connectioon for aall gases to connect the MGPS System. Make : Getinge / Stryker / Drager / Western India Electromedical Systems Pvt Ltd / Magnatek Enterprises.
Supply, Installation, Testing and Commissioning of Double arm moveable Pendant for Surgeon wih following specification :- (a) The Pendants should comply with NFPA 99C/HTM 02-01. The support arms should be extremely robust and revolve on high quality bearings, so that the pendant head glides smoothly and quickly to any desired position. (b) Double moveable arms (any combination) with total coverage of min 1800mm and 330 deg. Horizontal movements for each arm. Vertical movement should be motorized and the arm height should remain to a height greater than 6.5 feet above floor level. (c) Weight carrying capacity of the arm should not be less than 180 Kg. Should have electromagnetic/pneumatic brakes. (d) Each arm should be capable of 300-340 degrees of rotation, which can be easily adjusted to suit the desired mode of operation. (e) The pendant should be European CE Certified or US FDA or BIS approved. (f) The Pendant Service Heads should be modular with minimum 800mm head. The heads should be capable of accepting a range of shelves, infusion poles, electrical switch / sockets, gas outlets other accessories as asked intender. The Pendant Heads should support the range of Physiological Monitor Mounting Solutions. (g) The Pendant Service Heads should be supplied with medical gas terminal units and 5/15 or 6/16 Amps hybrid Sockets (h) Each pendant should be supplied with outlets and probes as mentioned below :- (i) O2& MA4 -1Nos each, (ii) Vacuum Outlest - 02 Nos, (iii) Air (7 bar) outlets - 01 Nos, (iv) CO2 Outlets - 01 Nos (v) Electrical Sockets - 10 Nos, (vi) Adjustable Shelf with two rails one on each side - 03 Nos, (vii) Data Sockets RJ-45 - 02 Nos, (viii) IV Fluid Pole with 2 hooks - 01 Nos (pole should be capable of stacking 4 nos of syringe pumps, (ix) Nitrous Oxide - 01 Nos Note : Pendant Supplier should provide cutouts for Patch panes in intefrated OTs. Surgeon pendant should have NIST connectioon for all gases to connect the MGPS System. Make : Getinge / Stryker / Drager / Western India Electromedical Systems Pvt Ltd / Magnatek Enterprises.
Supply, Installation, Testing and Commissioning of Camera which should be mounted on light head for displaying real-time images during surgery with a Coaxial camera chip of 1.28 CMOS or more than with 2.10 Megapixels capability with at least 12X Digital Zoom and 30X Optical Zoom. Full HD 1080p (1920x1080) image capture and external recording. Camera control should have function like Zoom In / Out, White Balance, Focus In / out, Auto, Aperture In / out, Freeze. All function of HD camera should be controllable through Andriod Tablet PC / voice control & touch Panel. It should be in HD formats 1080i: 1920 x 1080 pixels / 60 frames / sec. Minimum Object distance 10 mm to 1200 mm. Focal Length 4.3 to 129 mm. Shutter Speed 1/1-1/10000 (22 Steps). Signal Noise Ratio 50Db. Output 3G HD-SDI, SMPTE 424M and 292M. Light and Integrated Camera should have a control through Touch Panel of the control equipment placed inside the operating room complete all as specified and directed
Supply, Installation, Testing and Commissioning of HD LED Flat Panel Monitor (Only for non-integrated MOTs) : (a) It shall be 30”-32” medical grade high definition progressive scan flat-panel monitors with wall mounted to support high definition / HDTV progressive scan images and shall be able to support and display DVI / HDTV, RGBHV, S-video, composite video signals. Aspect ratio 16:9/16:10. Resolution: 1920x1080 or better. It shall meet IP54 regulations. (b) The flat panel shall be ready with the cables for integration of high definition digital (DVI/HDTV), RGBHV (high resolution), SVHS (S-video), composite video signals to travel from the various sources of video like endoscopic camera, room camera, in-light camera, high definition flat panel monitors, while assuring native resolution / signal.
Supply, Installation, Testing and Commissioning of Medical Recording Device with 5 inch touch screen preview of Video Recording and Archiving Device to capture HD photo (up to 1920x1080p) and medical session video recording (up to 1080p 60Hz). The system should simultaneously record to the 2 terabyte internal hard disk drive and an external USB flash drive. It should record 2 sources at once and play back 1 or 2 sources from the same video file. Files to be recorded through a Software for Digitizing and Archiving Data through a password protected to send images in HD-SDI Video Inputs. Simply Use Web Browser interface to access Data on Computer or Tablet Video Recording upto1080P at 60Hz. System controls can be managed using the touch screen and buttons on front of the unit.Should be suitable for storing HD videos from ultrasound, digital X-ray, endoscopic, laparoscopic and other compatible diagnostic and surgical imaging systems.
Supply, Installation, Testing and Commissioning of Integrated Wiring from OT"s to Head of Department and Confrence Room for streaming the live video from OTs cameras
Supply, Installation, Testing and Commissioning of X-Ray View Panel : The system should electrical safety codes for high & low voltage system. The theatre is to be equipped with a 2-plate X-Ray viewing screen. It should be designed to provide flicker free luminance for the film viewing purpose. It should be installed flushed with the theatre wall for hygienic and ease of cleaning purpose. The X-Ray viewing screen should be designed for the purpose of front access. The X-Ray viewing screen should be illuminated by 2 pieces of high frequency fluorescent lamps and the dimming is controlled by the usage of dimming ballast with the PCB that is mounted inside the box. Size of the unit should be not less than 940 mm width x 640 mm height x 50 mm depth. It should be CE compliance under medical devices directive class-1. Copy of CE certificate must be submitted.
S&F Distribution Board double Door made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating and IP43 & IK09 protection, consealed/ surface, TPN 8 way, 415 volts with bus bar rating 200 Amps, dust and vermin proof with and including of MCB TPN 63 Amps and MCB SP 6-32 Amps etc and making all necessary connections complete all as specified and directed.
S&F Distribution Board double Door made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating and IP43 & IK09 protection, consealed/ surface, TPN 6 way, 415 volts with bus bar rating 200 Amps, dust and vermin proof with and including of MCB TPN 63 Amps and MCB SP 6-32 Amps etc and making all necessary connections complete all as specified and directed.
Supply, Installation, Testing and Commissioning of Operation Threatre (medical grade) Isolation Panel system as per specifications mentioned below: The panels shall be isolated panel system only, having critical (isolated) and non-critical circuits. Both circuits shall be monitored on the building management system. The monitoring parameters shall include On/Off status, load monitoring and shall generate alarms if any critical parameters such as isolation is anomalous. The panel shall enable electrical shock protection: according the IEC 60364-7-710 standard the solution is in compliance with the group 2 location through isolation transformer and associated monitoring system. The system shall be according the IEC standard, the switchgear is energy by 2 separate sourcing. The “Main incomer supply” is coming from the UPS system. The “Safety incomer supply” is coming directly from the other part of the main low voltage switchgear. An automatic change over shall transfer the energy sourcing from the “Main incomer supply” to the “Safety incomer supply” in case of outages in less than 30ms. The Utility and Genset sourcing should limit by 15 seconds at least any potential outage to re-energise the Main and Safety incomers. The wiring shall be in compliance with the recommendations of IEC 60364-4-4-44, IEC 61000-6-2 and IEC 61000-6-3. It shall be possible for the protective devices to be controlled by the maintenance staff, without risk of direct c
The power and communication circuit routing shall be completely separate. Pulse energy meters with inbuilt CTs shall be provided with incomers to the panel for getting the energy consumption data for operation theatre The system should be able to locate faults in case of tripping Communication auxiliaries, for communicating ON/OFF/Trip status shall be provided with all MCBs, RCCBs, RCBOs used for protection. The status shall be available over Modbus TCP/IP network. Smartlink or equivalent shall be used for communicating the status of protection devices. The System Controller shall transfer all data to BMS room, shall include suitable number of DI/DOs to control and monitor the panels. The controller has 01 Nos. isolated RS 485 communication port, 1 Nos. Ethernet communication port with 10BASE-T/ 100BASE-TX, support : Modbus master/slave, BACnet, MBUS and DNP 3.0 protocols, and shall conform to ANSI/ISA 12-12-01, CSA C22.2 No 142, CSA C22.2 No 213, EN/IEC 61131-2:2007 standards, 230VAC with inbuild 4G modem and has DIDO Capability for adding upto 256 DI/DOs/AI/AOs. The controller sends data with TLS encryption and the data on controller shall be encrypted. The controller shall be able to store data till it is received by the BMS room to avoid any data loss. The system shall have the following components: 63A, FP, Isolator, Complies to IEC/EN 60947-3- 2Nos Contactor 60A, FP AC-1 duty 230V 50/60Hz for 10 KVA- 2Nos Mechanical interlock for LC1 D60- 1No. On delay Timer 2C/O, 230V AC- 1No. Miniature circuit breaker ACTI 9, C60, 2 poles, 2A, C Curve - 2Nos Polybloc 160A 1P - 2Nos Miniature circuit breaker ACTI 9, C60, 2 poles, 2A, D Curve- 1No. AC Residual Current Circuit Breaker, 40A, 100mA- 1No. Digital VAF Meter With RS 485 Modbus Port- 1No. Current transformer 40/5A Class 1 10VA- 3Nos CT Shorting Links- 3Nos
Auxiliary contact, 1 OC- 6Nos Multiclip distribution block- 1No. Miniature circuit breaker ACTI 9, C60, 2 poles, 4A, C Curve- 1No. Universal Power Supply 24V DC 5A- 1No. Miniature circuit breaker ACTI 9, C60H-DC, 500Vdc, 2A, 2 poles, C Curve- 1No. IMD Vigilohm IM20-H a positive safety 220/240V AC, 50H- 1No. Current transformer 50/5A class 3 for cable - 1No. Insulation Fault detectors (12 channel)- 1No. Sensor Vigilohm TA30- 6Nos Miniature circuit breaker ACTI 9, C60, 2 poles, 16A, C Curve- 6Nos Auxiliary contact, 1 OC- 6Nos Multiclip distribution block, 4P, 80A, 1 row- 1No. Smart Link Modbus TCP/IP Communicating I/O Module- 1No. Field Controller with Bacnet, Modbus, DNP3.0, MBUS protocols- 1No. Prefabricated Cables, Long: 870mm- 1No. 15KVA Isolation Transformer 3Phase, 415V/220 V AC- 1No. Prisma Panel Type Tested IEC 61349- 1No.Or equivalent of above
OT FLOORING AND STICHED PVC M&L for SS 304 wall panelling in OT complex incl necessary GI profile formwork along the periphery & GI intelocking section with base runner framework with following Specifications: - The wall panel will consist of sandwiched wall panels. Front side of the panel shall be SS 304 sheet, 0.8 mm thick & back side PPGL sheet, 0.5 mm thick with core consisting of rigid polyurethane PUFF with 40 Kg/cum density. Standard panels shall have an overall thickness of 50mm to 60mm. The self-supporting internal walls are constructed with PPGL frame work. Partition to partition connections shall be maintained with precision with PPGL profiles that create uniform seams. No welding shall be allowed. It shall have minimum number of junctions. The Partition seams shall be sealed by silicone with a perfectly flush finishing. Stainless steel plate shall be finished to fine grain surface, and treated properly to take antifungal paint. Paneling shall be easy to maintain, durable, antistatic/conductive and fire retardant. Angular corners shall be made with a 130°-140° angular modular element with the same finish of the wall panels. Note :- Necessary openings if any required at site shall be provided by the contractor for fixing of switch boards / panels / equipment etc. and unit rate quoted shall be deemed to be inclusive of this aspect. Make/Manufacturer :Western India Electromedical Systems Pvt Ltd / Tanvi Enterprises/ Magnatek Enterprises/ Lifewise Healthcare.
M&L for Toughened glass wall panelling in OT complex incl necessary GI profile formwork along the periophery & GI intelocking section with base runner framework with following Specifications: - The wall panel consist of high quality 8mm thick back printed toughened glass. The printed toughened glass will use UV multicolor printing technology with PU glass coating . Front side of the panel shall be 8mm thick back printed toughened glass & back side PPGL sheet, 0.5mm thick with core consisting of rigid polyurethane PUFF with 40 Kg/cum density. Standard panels shall have an overall thickness of 50mm to 60mm. The wall panel should E section frame work with a sealed and PUFF insulated with 40 Kg/sqm density. Standard panels shall have an overall thickness of 50mm to 60mm. The self supporting internal walls are constructed with an interior of PPGL frame work. Partition to partition connections are maintained with precision with PPGL profiles that create uniform seams. The Partition seams are sealed by silicone with a perfectly flush finishing. PUF insulation material is sandwiched between the skin layers and sealed from the exterior by the PPGI frame work. (a) Panel Thickness: 50 mm to 60mm with inner skin is of Toughened Glass (8mm) and outer skin 0.5 mm PPGL thick sheets. Note :- Necessary openings if any required at site shall be provided by the contractor for fixing of switch boards/panels/equipment etc. and unit rate quoted shall be deemed to be inclusive of this aspect. Make/Manufacturer :Western India Electromedical Systems Pvt Ltd / Tanvi Enterprises/ Magnatek Enterprises/ Lifewise Healthcare.
M&L for SS 304 ceilling panelling in OT complex with following specifications:- Standard ceiling partitions with composite construction of SS 304 sheet of 0.8mm thick from side back sie 0.5mm thick PPGI sheet for construction of wall panel. The wall panel should E section frame work with a sealed and PUFF insulated with 40 Kg/sqm density. Standard panels shall have an overall thickness of 50mm. The self supporting internal walls are constructed with an interior of PPGI frame work. Partition to partition connections are maintained with precision with PPGI profiles that create uniform seams. The partition seams are sealed by silicon with a perfectly flush finishing. PUF insulation material is sandwiched between the skin layers and sealed from the exterior by the PPGI frame work. (a) Type:- Walkable (b) Panel thickness: 50mm with inner SS 304 (0.8mm) and outer skin 0.5mm PPGI thick sheets. Make/Manufacturer: Western India Electromedical Systems Pvt Ltd. Note:- Necessary openings if any required at site shall be provided by the contractor for fixing of switch boards/panels/equipment etc and unit rate quoted shall be deemed to be inclusive of this aspect. Make/Manufacturer: Western India Electromedical Systems Pvt Ltd/ Tanvi Enterprises/Magnatek Enterprises/Lifewise Healthcare
Supply installation testing commissioning of anodised clip on type covering for the entire wall to wall and wall to ceiling. 3D internal/external corner covers. Covering of return air ducting lines inside OT. Material to be used for covering should be SS-304. Make/Manufacturer: Western India Electromedical Systems Pvt Ltd/ Tanvi Enterprises/Magnatek Enterprises/Lifewise Healthcare
Supply, Installation, Testing and commissioning of hermatically sealed automatic sliding doors: Size 1500mmX2100mm, MOC: SS 304 Hermatically sealed sliding door designed to fit flush into the wall on both sides. Door operations: Automatically operated door. The door runs on nylon wheels within an aluminium extrusion track, for smooth effortless sliding. Track- Aluminium anodised profile-90x110mm, Door blade-60mm with both side SS 304, Door panel insulation: PUF insulation 48mm @ 40Kg/m3, Controls & Safety features: Microprocessor based electronic automation for door controlling the direction of movements, acceleration and speed of the door, with a low noise level pulse generator motor. It includes a photocell for user's safety, Radar hand switch & foot switch. With 2mm Accessories-Vison Panel size 300mmx300mm, The lock can be locked and unlocked both sides by means of a euronom cylinder and should have hermatic sealing designed & tested on hermatically sealing an over pressure of 100 Pa. The air tightness should be 99.997% airtight. The door should be designed in consultation with doctors/Architects and technical bureau who design operation theaters and clean rooms. Make/Manufacturer: Western India Electromedical Systems Pvt Ltd/Meta Flex/Ribbon/Geze
Supply, Installation, Testing and commissioning of hermatically sealed automatic sliding doors: Size 1000mmX2100mm, MOC: SS 304, Hermatically sealed sliding door designed to fit flush into the wall on both sides. Door operations: Automatically operated door. The door runs on nylon wheels within an aluminium extrusion track, for smooth effortless sliding. Track- Aluminium anodised profile-90x110mm, Door blade-60mm with both side SS 304, Door panel insulation: PUF insulation 48mm @ 40Kg/m3, Controls & Safety features: Microprocessor based electronic automation for door controlling the direction of movements, acceleration and speed of the door, with a low noise level pulse generator motor. It includes a photocell for user's safety, Radar hand switch & foot switch. With 2mm. Accessories-Vison Panel size 300mmx300mm, The lock can be locked and unlocked both sides by means of a euronom cylinder and should have hermatic sealing designed & tested on hermatically sealing an over pressure of 100 Pa. The air tightness should be 99.997% airtight. The door should be designed in consultation with doctors/Architects and technical bureau who design operation theaters and clean rooms. Make/Manufacturer: Western India Electromedical Systems Pvt Ltd/Meta Flex/Ribbon/Geze
Supply and installation of storage unit in OT area 200x120x35cm deep having two shelves and Mounted flush wall with and including following:- (i) Each modular OT and passage area shall have flush mounted storage units. (ii) The storage is made of 0.8mm thick SS 304 on both side. (iii) shutter width of 45x50mm with a sealed & PUFF insulated with 40 Kg/Sqm density. (iv) The numbers of selves are 4 at the equal-distance. (v) View glass of size: 250mm x 1300mm x 5mm Thick (vi) Masonry work: Any masonry work required for installation of storage unit is included. Make/Manufacturer: Western India Electromedical Systems Pvt Ltd/ Tanvi Enterprises/Magnatek Enterprises/Lifewise Healthcare
FLOOR MOUNTED AUTOMATIC SURGICAL SCRUB -2 BAY Floor Mounted Scrub Sink “ are constructed of 1.2 thicknesses, type 304 stainless steel with horizontal and vertical corners coved to ¼” radius. Front corners are to be welded and all welds ground and polished to MAT finish. Sinks shall have sloping basin to eliminate back splash. Each station shall be equipped with 1.5” stainless steel drain. Outer enclosure is constructed of 18 gauge stainless steel. Quality Requirement : - Material S.S 304-18 SWG - Scrub Dimension : 1300W X 883H X508D - Perfect Matt Finishing of product. - Operation -Automatic OR Foot operation - Taps- Jaguar Make- 2 No. - 2 liquid detergent container, Flashback and with nylon adjustable levelling bullets for legs. - Branded Piping Material using like Astral Pipe. - Easy to clean Surface . - Radius Chamber. Make/Manufacturer :Western India Electromedical Systems Pvt Ltd / Window Techs / Tanvi Enterprises/ Magnatek Enterprises/ CMP/ Lifewise healthcare
M & L for Magnetic writing board with duster Colour - Pure white Size : 600mm x 800mm MOC : Magnetic laminated board bonded with 10mm high density fibre board sheet with magnetic duster Thickness - 1.50 mm thick Make/Manufacturer :Western India Electromedical Systems Pvt Ltd / Window Techs / Tanvi Enterprises/ Magnatek Enterprises/ CMP/ Lifewise healthcare
Antistatic conductive vinyl flooring Compliant to standards: EN 1081/IEC 613404, EN 1815 & EN 12466, TVOC as per AgBB / DIBt Certifications, ISO 16000-6. Thickness 2.00mm, polyurethane reinforced ,scratch resistant, fire resistant, chemical resistant , slip resistant, anti-fungi & bacterial growth , dimensional stability ≤ 0.40%, static electrical charger < 2Kv,. Flooring should be seamless with perfectly curved flush- coving, resistant to mechanical stress and dynamic loads and having protection characteristic, Conductive Washable vinyl in Roll form. Flooring should be laid on epoxy based self-levelling compound. Make/Manufacturer :Tarket/Gerfloor/ HR Johnson /Floormaster/ Accord Floors
Doubled toughened glass window providing and establishing the view windows of size 1.00 m x1.00 m with following specifications: It should be provided with each operation theatre and should have double isolated fixed glazing with not less than 5 mm thick toughened glass on both sides with 12 mm air gap. Window frame should be of Stainless Steel of approved shape flush mounted with wall panelling should have dynamic control over amount of light and heat passed through the surfaces. Window (Size: - 1000 mm x 1000 mm) with both side glass with blinds sandwiched in between. The blinds should be openable from inside the O.T and shall be magnetic operated. The work should be executed as per the directions of Engineer–in-Charge.
AMIT ASSOCIATES (BID ID -3276682)
Ktech Engineer Builders Co. Pvt. Ltd (BID ID -3276968)
SOOD ASSOCIATES PVT LTD (BID ID -3277060)
MAHINDER PAL CONSTRUCTIONS PVT LTD (BID ID -3276734)
TRIVENI CONSTRUCTIONS (BID ID -3277002)
NAFREF ENGINEERS PVT LTD (BID ID -3277052)
MAHINDER PAL CONSTRUCTIONS PVT LTD (BID ID -3276734)
AMIT ASSOCIATES (BID ID -3276682)
SOOD ASSOCIATES PVT LTD (BID ID -3277060)
TRIVENI CONSTRUCTIONS (BID ID -3277002)
NAFREF ENGINEERS PVT LTD (BID ID -3277052)
Aalaya Engineering Project Private Limited (BID ID -3276573)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tenderdocument.rar
Tender Documents • 11.50 MB
Tenderdocument_2.rar
Tender Documents • 9.63 MB
BOQ.xls
BOQ • 1.09 MB
Tenderdocument_3.rar
Tender Documents • 30.87 MB
Tenderdocument_4.rar
Tender Documents • 30.65 MB
Download all tender documents and submit your bid