| 1.00 | Supply, installation, commissioning and testing, water cooled, sound proof silent type, turbo charged, diesel engine driven Generating Set for deriving 30 KVA (at 0.8 PF), 415V, 3 phase, 4 wire engine as per IS: 10001/10002 and alterator as per
IS: 13364, complete with relay panel for automatic starting on mains failure, control panels having meters in an integral acoustic enclosure as per recommendation latest CPCB-IV norms, comprising of the following:
Notes: Quoted rates shall deemed to include the following also:-
(i) Supply of T and P and normal spares ie., Bi-hexagonal ring spanner set of 12 pieces - 01 Set.
(ii) Fuel measurement gauge - 01 No, hand operated fuel lifting pump with steel pipe 40mm dia - 01 No, Hydro meter - 01 No, Set of fan belt, oil/ fuel filters initial filling of coolant (coolant-2liters).
(iii) Service maintenance manual along with cat part list and price list - 03 set each.
(iv) Make of Engine and Alternator will be got approved from AGE (I) Bhalra before placing the order.
(v) The DG set will be operated at 1150 mtr Altitude at Ramban.
(vi) The DG set should adhere to CPCB-IV norms.
(vii) All civil/ PCC work for foundation of DG set as per manufacturer recommendations shall deemed to be included in the quoted rate. | 1 | Each | 7,75,000 ₹7,75,000 Lowest | 7,75,000 ₹7,75,000 Lowest |
| 1.01(a) Diesel Engine. Diesel engine developing suitable BHP, 1500 RPM inclusive of the following standard accessories: (i) Radiator/ heat exchanger cooling system. (xiv) Battery charging generator. (ii) Spider coupling guard. (xv) Industrial silencer. (iii) Fly wheel. (xvi) Lubricant oil cooler. (iv) Fly wheel housing complete with starter gear ring and coupling. (xvii) Flexible pipe for silencer. (v) Fuel pipes. (xviii) Battery Volt meter. (vi) Air cleaner. (xix) Water temperature gauge, lub oil pressure gauge. (vii) Fuel and Lubricant oil filter. (xx) Engine hour meter and performance monitoring. (viii) By pass filter. (xxi) Display for fault. (ix) Coolant inhibitor. (xxii) Turbo charger. (x) Fuel pump. (xi) Water pump. (xii) Lubricant oil pump. (xiii) Self/electric starter. (b) ALTERNATOR : Synchronous alternator 3 Phase 4 wire, 50 cycles 1500 RPM, self excited, self regulated, brushless type, 0.8 PF, 415V, AC Supply, 30 KVA capacity, copper wound, complete including necessary tools, mounted on strong rigid steel fabricated base frame and directly coupled through flexible coupling with diesel engine, complete all as specified and directed. | |||||
| 1.02(c) AMF/ CONTROL PANEL : AMF Panel factory made of suitable capacity as per Original Equipment Manufacturer make and specification or as approved by OEM for DG Set of capacity 30 KVA of suitable size, indoor cubical type, front and back openable fabricated out of mild steel sheet 1.6mm thick grouted in floor with adequate PCC foundation and minimum consisting of following :- (i) Contactor of suitable size for 30 KVA DG Set. (ii) Copper bus bar of 63 amps x 3 ph+30 amps x 1 neutral suitable current rating and sensitivity relay set unit with auxiliary CTs. (iii) Electronic latch circuit with tripping indication. (iv) Re-set facilities. (v) 3 Phase MVR relay unit with single phase protection complete with 2 No NC auxiliary contacts. (vi) 3 Phase AVR relay unit complete. (vii) Self sequential starting relay unit 12 volts DC complete with alarm and power contactor. (viii) Electronic timer 220 volts for main contactor with 1 No NC auxiliary contactor. (ix) Electronic timer 220 volts for fuel cut off operation with 1 No auxiliary contactor. (x) Battery charging 2x12 volts 10 Amp complete with digital voltmeter and Amps meter, including trickle and boost charging, (xi) The AMF panel should have manual by pass arrangement too in case of failure of AMF panel. (xii) Digital type multifunctional meter to show KwH, Volt, Amp, Frequency, KVAH. | |||||
| 1.03(d) Fuel tank of capacity as per manufacturer recommendations. (e) Base frame made out of suitable channel duly reinforced and provided with adequate numbers of anti vibration pads to ensure minimum vibration as recommended by manufacturer. (f) Battery maintenance free of 12 volts DC 180 AH, or as recommended by the manufacturer, alongwith the connecting leads and battery stand as per recommendations of manufacturer. Make: EXIDE/ AMARON/ SU-KAM/ AMCO. (g) Acoustic enclosure with natural air circulation without loss of any power for ventilation fan. The enclosure shall be modular in construction with hinge. (h) Provision of PCC foundation as per manufacturer's design and drawing/ instructions. Foundation drawing will be vetted by AGE (I) Bhalra. (j) Accessories : All accessories and maintenance spares, battery with connecting battery leads and fastening, as per spare list with generator set, complete all as specified and directed. | |||||
| 2.00 | 1100 volts grade heavy duty cable with XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty ) with aluminium conductor cable of size 50 Sqmm 3.5 core, 1100 volts, grade laid in trenches/ fixed on walls or passing through pipe complete, complete all as specified and directed. | 330 | RM | 300 ₹99,000 Lowest | 330 ₹1,08,900 |
| 3.00 | Excavation in trenches in any type of soil soil not exc. 1.5 metre wide and not exc. 1.50m in depth for pipes and getting out, complete all as specified and directed. | 52 | Cum | 110 ₹5,720 | 90 ₹4,680 Lowest |
| 4.00 | Returning filling including spreading leveling watering and well ramming in layers not exc 25 cm in any type of soil, complete all as specified and directed. | 22 | Cum | 10 ₹220 Lowest | 10 ₹220 Lowest |
| 5.00 | Removing excavated material in ant type of soil not exc. 50 mtr and depositing where directed at a level not exc 1.5m above the starting point, complete all as specified and directed. | 30 | Cum | 20 ₹600 | 10 ₹300 Lowest |
| 6.00 | Sand cushioning to underground ground cable in layers of 23cm thick (8 cm before laying the cable and 15 cm thick after laying the cable) in trenches including watering and consolidation, complete all as specified and directed.
Note: Punned Thickness shall be measured and paid. | 20 | Cum | 700 ₹14,000 | 600 ₹12,000 Lowest |
| 7.00 | Supply and lay well burnt brick class B as protection to cable in cable trenches, complete all as specified and directed. | 3 | Per 1000 Nos | 7,000 ₹21,000 Lowest | 12,000 ₹36,000 |
Tender Value
₹12.6 L
EMD Value
₹25,220
Closing Date
17 Jun 2026, 6:00 pmClosed
CWE NAGROTA
HQ CWE NAGROTA PIN-901208 c/o 56 APO
PROVISION OF 01 X 30 KVA GENR WITH CONNECTED ITEMS AS STANDBY POWER REQUIREMENTS FOR SEWAGE TREATMENT PLANT UNDER AGE (I) BHALRA
2026_MES_767920_1
CWE/NGT-23/2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AGE (I) Bhalra
As per tender documents
8 documents required · 8 mandatory
₹500
AGE (I) Bhalra
₹25,220
Yes
10 Jul 2026
26 May 2026
20 Jun 2026
26 May 2026
17 Jun 2026
10 Jun 2026
26 May 2026 - 2 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installing, commissioning and testing, water cooled, sound proof silent type, turbo charged, diesel engine driven Generating Set 30 KVA (at 0.8 PF), 415V, 3 phase, 4 wire engine as per IS: 10001/10002 and alterator as per IS: 13364, complete with relay panel for automatic starting on mains failure, control panels having meters in an integral acoustic enclosure as per recommendation CPCB norms, comprising of the following:
Notes: Quoted rates shall deemed to include the following also:-
(i) Supply of T and P and normal space ie., Bi-hexagonal ring spanner set of 12 pieces - 01 Set.
(ii) Fuel measuement gauge - 01 No, hand operated fuel lifting pump with steel pipe 40mm dia - 01 No, Hydro meter - 01 No, Set of fan belt, oil/ fuel filters initial filling of coolant (coolant-2liters).
(iii) Service maintenance manual along with cat part list and price list - 03 set each.
(iv) Make of Engine and Alternator will be got approved from AGE (I) Bhalra before placing the order. | 1 | Each | 1.25 | ₹1.25 |
| 1.01 | (a) Diesel Engine. Diesel engine developing suitable BHP, 1500 RPM inclusive of the following standard accessories:
(i) Radiator/ heat exchanger cooling system. (xiv) Battery charging generator.
(ii) Spider coupling guard. (xv) Industrial silencer.
(iii) Fly wheel. (xvi) Lubricant oil cooler.
(iv) Fly wheel housing complete with starter gear ring and coupling. (xvii) Flexible pipe for silencer.
(v) Fuel pipes. (xviii) Battery Volt meter.
(vi) Air cleaner. (xix) Water temperature gauge, lub oil pressure
(vii) Fuel and Lubricant oil filter. gauge.
(viii) By pass filter. (xx) Speedo meter and engine running hours meter.
(ix) Coolant inhibitor. (xxi) Display for fault.
(x) Fuel pump. (xxii) Turbo charger.
(xi) Water pump.
(xii) Lubricant oil pump.
(xiii) Self/electric starter.
(b) ALTERNATOR : Synchronous alternator 3 Phase 4 wire, 50 cycles 1500 RPM, self excited, self regulated, brushless type, 0.8 PF, 415V, AC Supply, 30 KVA capacity, copper wound, complete including necessary tools, mounted on strong rigid steel fabricated base frame and directly coupled through flexible coupling with diesel engine, complete all as specified and directed. | - | - | - | - |
| 1.02 | (c) AMF/ CONTROL PANEL : AMF Panel factory made of suitable capacity as per Original Equipment Manufacturer make and specification or as approved by OEM for DG Set of capacity 30 KVA of suitable size, indoor cubical type, front and back openable fabricated out of mild steel sheet 1.6mm thick grounted in floor with adequate PCC foundation and minimum consisting of following :
(i) Contactor of suitable size for 30 KVA DG Set.
(ii) Copper bus bar of suitable current rating and sensitivity relay set unit with auxiliary CTs.
(iii) Electronic latch circuit with tripping indication.
(iv) Re-set facilities.
(v) 3 Phase MVR relay unit with single phase protection complete with 2 No NC auxiliary contacts.
(vi) 3 Phase AVR relay unit complete.
(vii) Self sequential starting relay unit 12 volts DC complete with alarm and power contactor.
(viii) Electronic timer 220 volts for main contactor with 1 No NC auxiliary contactor.
(ix) Electronic timer 220 volts for fuel cut off operation with 1 No auxiliary contactor.
(x) Battery charging 2x12 volts 10 Amp complete with digital voltmeter and Amps meter, including trickle and boost charging, Make : SU-KAM, AMCO, EXIDE or any other make as recommended by the manufacturer.
(xi) Volt meter 0-500 volts panel mounting of size 96mm square with selector switch digital type.
(xii) Amps meter 0-100 Amps with 3 Nos CTs, 400/5 and selector switch 96 mm square digital type.
(xiii) Frequency meter (45-55) Hz, 415 volt, 96mm square digital type.
(xiv) The AMF panel should have manual by pass arrangement too in case of failure of AMF panel. | - | - | - | - |
| 1.03 | (d) Fuel tank of capacity as per manufacturer recommendations.
(e) Base frame made out of suitable channel duly reinforced and provided with adequate numbers of anti vibration pads to ensure minimum vibration as recommended by manufacturer.
(f) Battery maintenance free of 12 volts DC 180 AH, or as recommended by the manufacturer, alongwith the connecting leads and battery stand as per recommendations of manufacturer.
(g) Acoustic enclosure with natural air circulation without loss of any power for ventilation fan. The enclosure shall be modular in construction with hinge.
(h) Provision of PCC foundation as per manufacturer's design and drawing/ instructions. Foundation drawing will be vetted by AGE (I) Bhalra.
(j) Accessories : All accessories and maintenance spares, battery with connecting battery leads and fastening, as per spare list with generator set, complete all as specified and directed. | - | - | - | - |
| 2 | 1100 volts grade heavy duty cable with XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty ) with aluminium conductor cable of size 50 Sqmm 3.5 core, 1100 volts, grade laid in trenches/ fixed on walls or passing through pipe complete, complete all as specified and directed. | 330 | RM | 1.25 | ₹412.5 |
| 3 | Excavation in trenches in any type of soil soil not exc. 1.5 metre wide and not exc. 1.50m in depth for pipes and getting out, complete all as specified and directed. | 52 | Cum | 1.25 | ₹65 |
| 4 | Returning filling including spreading leveling watering and well ramming in layers not exc 25 cm in any type of soil, complete all as specified and directed. | 22 | Cum | 1.25 | ₹27.5 |
| 5 | Removing excavated material in ant type of soil not exc. 50 mtr and depositing where directed at a level not exc 1.5m above the starting point, complete all as specified and directed. | 30 | Cum | 1.25 | ₹37.5 |
| 6 | Sand cushoning to underground ground cable in layers of 23cm thick (8 cm before laying the cable and 15 cm thick after laying the cable) in trenches including watering and consolidation, complete all as specified and directed.
Note: Punned Thickness shall be measured and paid. | 20 | Cum | 1.25 | ₹25 |
| 7 | Supply and lay well burnt brick class B as protection to cable in cable trenches, complete all as specified and directed. | 3 | Per 1000 Nos | 1.25 | ₹3.75 |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.18 MB
tender.pdf
Tender Documents • 0.52 MB
BOQ_859966.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .