Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹45.4 LAccepted-AOC 9 EZRA STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹49.8 L+₹3.0 L (6.44%)Rejected-Finance | L2 | Rejected-Finance Not Being L1 | |
| 3 | Rejected-Technical | - | Rejected-Technical NO remarks in HQ CE A and N Zone WLR for the QE Sep 2022 |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
3 Nov 2022, 6:00 pmClosed
GE Minniebay
Junglighat PO Port Blair
ADDN ALTN AND SPL REPAIR TO BLDG NO P-112 P-121 AND PROVISION OF DIESEL GENERATOR AT MARCOS TEYLERABAD UNDER GE MINNIE BAY
2022_MES_552206_2
8176/E8
Open Tender
Civil Works
Item Rate
180 days
GE Minniebay
Please refer Tender documents.
10 documents required · 10 mandatory
₹500
GE Minniebay
₹96,000
Yes
4 Jan 2023
14 Oct 2022
5 Nov 2022
14 Oct 2022
3 Nov 2022
21 Oct 2022
14 Oct 2022 - 20 Oct 2022
Amount
M&L for 40mm thick Plain cement concrete type B-1, 1:2:4 (nominal mix) using 20mm graded stone aggregate for roof slab / roof padding including removing existing treatment etc complete all as specified and directed by Engr-in-Charge
M&L for 15mm thick screed on terrace or concrete surfaces in cement mortar 1:4 finished even and fair complete all as specified and as directed by Engr-in-Charge
Material and labour for APP modified waterproofing treatment over existing RCC roof slab with following specification including brushing off the surface to receive the treatment obtain the required surface complete as directed :- (a) Applying bituminous primer @ 1.2 kg/Sqm on the prepared dry roof surface. (b) Laying 4mm thick APP membrane Plain finish weight not less than 3 to 4 kg per sqm by torch application with minimum 10cm side lap and 15cm end lap.(c) Applying bituminous primer @ 1.2 kg/Sqm and applying one coat of bituminous aluminium paint at the rate of 0.3kg/sqm Note : The laying of membrane shall be got done through an authorized applicator of manufacturer of APP membrane. The quoted rate shall include the cost of taking down and refixing PVC storage tank in roof after the execution of roof treatment work.
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing) and rubbish off the premises complete all as specified and as directed by Engr-in-Charge.
M&L for vitrified coloured tiles(light shade)10mm thick premium quality (square/rectangular) polished, area of each tiles not exceeding 0.36 Sqm, in floors etc set and jointed in cement slurry and pointed in coloured cement to match over a screed bed of 15mm thick in CM 1:6 complete all as specified and as directed by Engr-in-Charge
M&L for vitrified coloured tiles(light shade)10mm thick premium quality (square/rectangular) polished, area of each tiles not exceeding 0.36 Sqm,as in vertical surfaces such as skirting, dado etc, set and jointed in ement slurry and pointed in coloured cement to match over a screed bed of 10mm thick in CM 1:4 complete all as specified and as directed by Engr-in-Charge
M&L non skid cermic coloured tiles 400 x 400mm and 8mm thick (square or rectangular) area of each tile exceeding 0.11 sqm but not exceeding 0.18sqm, in floor etc and jointed in neat cement slurry and pointed in white cement or coloured cement to match over a screed bed of 15mm thick in CM 1:6 complete all as specified and as directed by Engr-in-Charge.
All as per item No 7.00 above but as in vertical surfaces/skirting over screed bed of 10mm thick in CM 1:4 complete all as specified and directed by Engr-in-Charge
S&F glazed digital ceramic coloured tiles in vertical surfaces 300x450x7 to 8mm thick set and jointed in neat cement slurry and pointed in white or coloured cement to match incl cutting to required shape and size all as specified and as directed by Engr-in-Charge
Taking down chowkats or frames with shutter (without taking off shutters from the frame) n.exc 1.5 Sqm each complete all as specified and as directed by Engr-in-Charge.
S&F factory made solid PVC moulded door shutter, 28 to 30mm thick (stiles), with 2, 4, or 6 raised panel design with 2mm thick Moulded Prelaminated PVC Sheet on the front face & 2mm Plain colour PVC Sheet on back face, inside the frame work at site complete all as specified and as directed by Engr-in-Charge
S&F solid PVC door frame of size 50 mm x 47 mm made out of 5 mm plain colour PVC sheet reinforced with MS Square tube in opeing, complete all as specified and as directed by Engr-in-Charge.
S&F 100mm size stainless steel,butt hinges, extruded aluminium alloy with galvanised mild steel hinge pin, anodised and fixed, type B-21 complete all as specified and as directed by Engr-in-Charge.
Taking down cement plaster of any description on brick or stone walls or concrete surfaces including raking out joints, hacking for key all as specified and as directed by Engr-in-Charge.
M&L for rendering 5mm thick in CM 1:3 on fair faces of block masonry or concrete surfaces in ceiling complete all as specified and directed by Engr-in-Charge.
M&L for rendering 15mm thick plaster in CM (1:4) on block wall or concrete surfaces finished even & fair complete all as specified and as directed by Engr-in-Charge.
M&L for rendering 15mm thick plaster in CM (1:6) on block or concrete surfaces finished even & smooth complete all as specified and as directed by Engr-in-Charge.
M&L for prepartion of newly plastered surface and applying two coats of oil bound distemper over a coat of primer complete all as specified and as directed by Engr-in-Charge.
M&L for preparation of newly plastered surface and applying two coats of acrylic emulsion weather coat premium quality antifungal exterior emulsion over a coat of primer complete all as specified and directed by Engr-in-Charge.
M & L for preparation newly plastered ceiling surfaces and applying two coats of oil bound distemper over a coat of alkali resistant primer complete all as specified and as directed by Engr-in-Charge.
M&L for prepartion of old surfaces of wall and applying one coat of acrylic emulsion weather coat premium quality antifungal exterior emulsion complete all as specified and directed by Engr-in-Charge.
M & L for complete removal of existing treatment on wall surfaces, and applying two coats of oil bound distemper over a coat of chalk whiting over a coat of primer complete all as specified and as directed by Engr-in-Charge
M & L for preparation of old plastered ceiling surfaces and applying one coats of oil bound distemper complete all as specified and as directed by Engr-in-Charge..
S & F Aluminium anodised Handle, of extruded section Fabricated Type of size 150mm long complete all as specified and as directedby Engr-in-Charge.
S&F 300mm long Aluminium alloy, anodised, sliding door bolt with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections complete all as specified and as directedby Engr-in-Charge.
Demolition of cement concrete in ground floor and pavings nexc 15cm thickness (below or above ground level) complete all as specified and as directedby Engr-in-Charge.
M&L for Plain cement concrete 1:3:6 type C1 (nominal mix) using 20 mm graded stone aggregate as in flooring/ hard standing/Path/plinth protection and similar works finished even and fair complete all as specified and as directed by Engr-in-Charge.
M & L for coloured chequered cement concrete tiles 30 cm x 30cm x 25 mm thick, set and jointed neat cement slurry and pointed with coloured or grey cement match with pigment, over and including 20 mm thick screed bed or bedding layer in CM 1:6 etc complete all as specified and as directed by Engr-in-Charge.
S & F PVC Rotational moulded polyethylene water storage tank ISI marked Double layered (Cylindrical Vertical with closed top) of 1000 litre capacity including tank nipple, bends, sockets, couplet all fitting required at site complete all as specified and all as directed by Engr-in-Charge.
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, MCB's pendants, regulators, sockets, light fitting etc. removing materials against schedule of credit and making good disturbed surfaces of walls, floors, etc complete all as specified and as directed by Engr-in-Charge..
M&L for point wiring with 1.5 Sqmm (nominal area) PVC FRLSH unsheathed multistrandard copper conductor PVC insulated 1100 volt single core cable drawn through concealed/surface and including rigid steel conduit medium grade ISI marked minimum 25mm size and its accessories complete along with 1.5 Sqmm FRLSH unsheathed multistrandard copper conductor but in green colour as continuous earthing wire and connecting to common earth dolly completely concealed ,ceiling/roofs with and including 1.2 mm thick MS sheet terminal boxes duly fabricated flush mounting in the wall for mounting switches,switch socket combinations fan regulators etc., as required with 3 mm CRCA sheet metal enclosure box as per required size complete all as directed at site for the following:-
One light /fan point controlled by one way switch complete all as specified and as directedby Engr-in-Charge.
All as per item No 31.00 above but with 2.5 Sqmm single core multi stranded unsheathed FRLS copper conductor for one three pin socket 15/16 Amps on independent board including continuous earth wire PVC FRLSH insulated 1.5 Sqmm copper conductor to common earth dolly complete complete all as specified and as directed by Engr-in-Charge.
All as per item No 31.00 above but with 4 Sqmm single core multi standard FRLSH copper conductor for one three pin socket 15 Amps on independent board/metal clad socket for AC point including continuous earth wire PVC FRLSH insulated 4 Sqmm copper conductor to common earth dolly complete all as specified and as directed by Engr-in-Charge.
M&L for Sub main wiring complete with 2 x 1.5 sqmm, single core, multi stranded copper conductor FRLSH PVC insulated and sheathed cable 1100 volts grade, drawn in 25mm enamelled steel conduit on surface/concealed (as required) along walls roofs etc including 1.5 sqmmm size PVC FRLSH insulated unsheathed copper earth continuity conductor to common earth and connecting to earth dolly including taking down old unsv wiring complete all as specified and as directedby Engr-in-Charge. Note : (i) All three wire/cable (phase, neutral and earth) should be run through for each individual circuit from the DBs. (ii) Three run of cable and one run of conduit shall be measued as one unit
S&F in replacement LED tube light 2x16W flame proof type FLP-WP, CMRI certified recommended for gas/vapour group of IIA & IIB, Zone 1 & 2 and IP 65 protection with die cast alluminum hosing with heat resistant toughened glass with LED tube light fixture with driver, holders, connectors etc. complete with all accessories prewired and including connecting up with three core flexible copper conductor cable drawn through steel enamelled flexible conduit with suitable size complete all as specified and directed by Engr-in-Charge. Make : M/s Sudhir Cat Part No SAI/FF/3004 or equivilant makes mentioned in list of makes
S&F in repair LED light 1x 8W flame proof type FLP-WP, CMRI certified recommended for gas/vapour group of IIA & IIB, Zone 1 & 2 and IP 65 protection with die cast alluminum hosing with heat resistant toughened glass with LED tube light fixture driver, holders, connectors etc complete with all accessories prewired and including connecting up with three core flexible copper conductor cable drawn through steel enamelled flexible conduit with suitable size with suitable size complete all as specified and as directedby Engr-in-Charge. Make : M/s Sudhir Cat Part No SAI/FF/3004 or equivilant makes mentioned in list of makes
S&F in repair bulk-head fiting flame proof type 2 x26 W LED FLP-WP, CMRI certified recommended for gas/vapour group of IIA & IIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED light fixture driver, holders, metalic conduit connectors etc complete with all accessories prewired and including connecting up with three core flexible copper conductor cable drawn through steel enamelled flexible conduit with suitable size with suitable size complete all as specified and as directedby Engr-in-Charge. Make : M/s Sudhir Cat Part No SAI/BH/3006 or equivilant makes mentioned in list of makes
Supply & Fix flame proof Exhaust fan , 380 mm Sweep 240 volt,1440 RPM,Opal. White/brown.CMRI certified recommended for gas/vapour group of IIA & IIB, Zone 1 & 2 and IP 65 protection with die cast alluminum hosing including making hole suitable size for fixing 380 mm sweep exhaust fan making good distribution and after fixing exhaust fan flap cover to be fixed on behind exhaut fan hole , louvers, wiremesh, nut bolts, metalic conduit, capacitors including all acessories complete all as specified and as directedby Engr-in-Charge. Make : M/s Sudhir Cat Part No SFI/01 or equivilant makes mentioned in list of makes
Supply & Fix flame proof ceiling fan , 1200 mm Sweep 240 volt, Single Phase. CMRI certified recommended for gas/vapour group of IIA & IIB, Zone 1 & 2 and IP 65 protection with die cast alluminum hosing, jerk free oscillation & smooth running comprising of high performance high speed motor for higher air delivery incl connecting up to the ceiling rose(flame pfoof) including all accessories, metalic conduit complete all as specified and as directedby Engr-in-Charge. Make : M/s Sudhir Cat Part No CF/193 or equivilant makes mentioned in list of makes
Supply & Fix flame proof wall mounted fan , 610 mm Sweep 240 volt, Single Phase. CMRI certified recommended for gas/vapour group of IIA & IIB, Zone 1 & 2 and IP 65 protection with die cast alluminum hosing, jerk free oscillation & smooth running comprising of high performance high speed motor for higher air delivery incl connecting up to the ceiling rose(flame pfoof) including all accessories, metalic conduit complete all as directed. Make : M/s Sudhir Cat Part No SFI/01 or equivilant makes mentioned in list of makes
Supply & Fix flame proof regulator 240 volt. CMRI certified recommended for gas/vapour group of IIA & IIB, Zone 1 & 2 and IP 65 protection complete all as specified and as directedby Engr-in-Charge. Make : M/s Sudhir Cat Part No SAI/CS/1050 or equivilant makes mentioned in list of makes
S & F in replacement of switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified and as directedby Engr-in-Charge. Make : M/s Sudhir Cat Part No SAI/RI/1050 or equivilant makes mentioned in list of makes
S & F in replacement of flame proof switch socket & plug combined in LM6 cable termination box in LM6, 16A, 250V, 2P+earth complete all as specified and as directedby Engr-in-Charge. Make : M/s Sudhir Cat Part No SAI/SS/1050 or equivilant makes mentioned in list of makes
S&F Flameproof junciton box 4 way complete all as specified and as directedby Engr-in-Charge. Make : M/s Sudhir Cat Part No SAI/JB/103 or equivilant makes mentioned in list of makes
S&F in replacement of metal ceiling rose, surface Mild Steel/Cast Aluminium 65 mm x 30 mm, 3 terminals complete all as specified and as directedby Engr-in-Charge.
S&F in replacement Flame proof Distribution box TPN 4 Way with category of protection double door type IP-65 factory made with tinned copper 200 Amps rated bus bar and earth link connector, fixed in wall/Panel with provision of 63amps MCB as incomer complete including part of job, CMRI certified recommended for gas/vapour group of IIA & IIB, Zone 1 & 2 and IP 65 protection with die cast alluminum hosing, including all fittings, suitable size of metalic flexible conduit complete all as specified and as directedby Engr-in-Charge. Note : TPN distribution board shall be fixed in the wall such that front cover shall be seen flush with the wall surfaces. Make : M/s Sudhir Cat Part No SAI/RI/1055 or equivilant makes mentioned in list of makes
S&F in replacement of Flame proof Distribution box SPN 8 Way with category of protection double door type IP-42 factory made with tinned copper 200 Amps rated bus bar suitable for MCBs and earth link connector,complete all as specified and as directedby Engr-in-Charge. Note : SPN distribution board shall be fixed in the wall such that front cover shall be seen flush with the wall surface. Make : M/s Sudhir Cat Part No SAI/RCP/1055 or equivilant makes mentioned in list of makes
Supply and fix in replacement of flame proof MCB Four Pole (Incomer) 63 Amps, 415 volts, 10 KA 'C' Curve CMRI certified recommended for gas/vapour group of IIA & IIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing, complete all as specified and as directedby Engr-in-Charge. Make : M/s Sudhir Cat Part No SAI/JB/1057 or equivilant makes mentioned in list of makes
Supply and fix in replacement of flame proof MCB TPN 32 Amps, 415 volts, 10 KA 'C' Curve CMRI certified recommended for gas/vapour group of IIA & IIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing, complete all as specified and as directedby Engr-in-Charge. Make : M/s Sudhir Cat Part No SAI/RI/1051 or equivilant makes mentioned in list of makes
Supply and fixing 240V, 10 KA 'C' curve flame proof miniature circuit breaker (MCB) of single poles and current carrying capacity upto 25 A. CMRI certified recommended for gas/vapour group of IIA & IIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing complete all as specified and as directedby Engr-in-Charge. Make : M/s Sudhir Cat Part No SAI/RI/1051 or equivilant makes mentioned in list of makes
Supply and fixing 240V, 10 KA 'C' curve flame proof miniature circuit breaker (MCB) of double poles and current carrying capacity upto 25 A. CMRI certified recommended for gas/vapour group of IIA & IIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing complete all as specified and as directedby Engr-in-Charge. Make : M/s Sudhir Cat Part No SAI/RI/1051 or equivilant makes mentioned in list of makes
Earthing complete with copper earth plate electrode 600 mm x 600 mm x 3.15 mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including 20x3mm copper strip electrode by means of bolts, nuts, check nuts & washers etc connected to DBs all as shown in electrical plate No.3 of SSR Part I of 2009 & as specified or indicated and testing on completion including excavation / earth work in any type of strata, PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab cover 50 mm thick in cement concrete ( 1: 2 : 4 ) type B 1 ( reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm), funnel with wire mesh, watering pipe of 20 mm bore medium grade,including GI protection pipe of 15 mm medium grade up to 7.5 meter length etc complete all as specified and as directedby Engr-in-Charge.
Supply install testing and commissioning of Silent Diesel Engine driven generating set 415 Volt (at 0.8 PF) 100 KVA 3 phase 50 Hz. 1500 RPM with accostic enclosure and canopy type (indoor use) made out of 14 gauge CRCA sheet without inbuilt AMF Panel and including all excavation PCC foundation(as per manufacture), anti vibration pads tamper standard control panel as per manufacture instructions as directed by manufacturer and conforming to latest CPCB norms. The DG set shall comprise of following : - (a) Alternator : Standard design alternator rated at 100 KVA net out put at site, self excited ,self regulated through an AVR, screen protected, revolving field, brushless design with permanent lubricated bearings with winding in each pole, insulation class H, voltage regulation ± 1.5 % of rated voltage 'No load to full load'. The alternator shall be in a position to generate supply with frequency regulation within ± 1 % tolerance and permissible overload of 10 % for one hour in 12 hrs continuous run and conforming to IS 13364. (b) Diesel Engine : Adequate capacity suitable for 100 KVA Alternator water cooled to drive independently the above alternator directly coupled through flexible coupling Six cylinder Four stroke direct injection cold starting 1500 RPM as per relevant IS, IS:10001/ 10002 BS 5514 with in overload capacity of 12hrs continuous running complete with standard accessories all as specified and required for site handling and operation generally the scope of accessories shall be as under :-
(i) Air intake system : Air intake manifold air cleaner. (ii) Exhaust system : Turbo charger SS Flexible bellow silencer complete with MS exhaust piping of minimum size 100 mm dia upto and outside the building covered with glass wool covered under aluminum foil of 28 gauge, adequate to exhaust without transferring vibration to building/walls. (iii) Coolant system : Engine water pump ,radiator with fan and fan belt. (iv) Lubricating system : Oil pump of suitable capacity, lub oil pump and lub oil filter. (v) Fuel system : Fuel injection pump 12/24 Volts (as per OEM recommendation) DC solenoid switch nozzle mechanical/electronic governor, replaceable fuel filter, fuel tank made of 14 SWG sheet with drain valve, air vent inlet and outlet connection, fuel supply piping from tank to pump & to engine including return of over flow fuel with level indicating arrangement duly marked in inches/Litres. Fuel tank should be of adequate capacity for 12hrs running at full load. (c) Starting system : 12/24 V DC self starter 12 V DC battery charging alternator, start & stop push button, ignitor key/ switch, Battery of reputed make of suitable capacity in changed condition with its copper leads of adequate size as per OEM recommendation. (d) Base frame: Common base plate with AVM pads for mounting the engine & alternator. (e) Engine mounted Instrument Panel fitted with and having digital display for following:(i) Start-stop switch with key,(ii) Water temperature indication,(iii) Lubrication oil pressure indication,(iv) Lubrication oil temperature indication,(v) Battery charging indication,(vi) RPM indication,(vii) Over speed indication,(viii) Low lub. Oil trip indication & (ix) Engine Hours indication
(f) Safety control : Lub oil pressure trip, High water temp trip & over speed trip. (g) Acoustic enclosure : Modular construction with the provision to assemble & dismantle easily at site, powder coated & stainless steel nut & bolts/external hardware, provision for filling fuel from outside the enclosure with locking arrangement, Sound proofing of enclosure with high quality rock wool /mineral wool The rock wool is further covered with fiber glass tissue & perforated sheet . A special residential silencer within the enclosure to reduce exhaust noise. Noise level 75 db (A) at 3 m distance. Make :Cummins Model No C100DSP or equivilant makes in Kirloskar/GREAVES/Mahindra (j) The following documents shall be provided with DG set: (i) O & M manual of Diesel Engine spare parts catalogue of Diesel Engine, test certificate of Diesel engine, Test cert of Diesel engine. Test certificate of Alternator, DG set complete. (ii) Standard testing of DG sets shall be carried out with 10 % overload for one hour (iii) All Civil work related to foundation as per manufactures recommendation will be carried out at no extra cost. (iv) Load bank, accessories, fuel required for 12 hours testing is to be provided by contractors will inclusive quoted rate. (v) Repair/Maint tools to be supplied with DG set are as under :- (i) STANLEY 91-931-12-Master Tool set-120 Pieces of Make : STANLEY (ii) Cutting pliers 10 " - 01 No
Supply & lay and testing of LT cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 Sqmm 3 1/2 core, laid in duct / fixed on wall/trenches all as specified and directed by Engineer-in-Charge.
Supply & lay of Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 110 mm and inner dia 95 mm polyethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable all as specified and directed by Engineer-in-Charge
Supplying and laying 80mm GI tubing medium grade ISI marked for cable protection in trenches/duct/fixing to pole/wall or in such similar position of 80mm bore complete all as specified and directed by Engineer-in-Charge.
Excavation in soft loose soil not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out including forming of bottom for laying cable all as specified and directed by Engineer-in-Charge
Returning filling soft & loose/hard & dense soil including spreading leveling, watering and well ramming in layers n exc 25 cms all as specified and directed by Engineer-in-Charge..
Removal of excavated material n.exc 50 mtrs and depositing where directed at a level n.exc 1.5 mtrs above the starting point all as specified and directed by Engineer-in-Charge.
Excavation in hard / dense soil Including road/PQC cutting etc not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out incl forming of bottom for laying cable all as specified and directed by Engineer-in-Charge.
Design, Supply, installing testing and commissioning factory fabricated out door type totally enclosed CPRI approved as per IEC-61439-1 LT cubical panel board shall be compartmentalized, suitable size with busbar shall be made of high conductivity high strength E91E aluminium alloy and capable of carrying the rated current, conforming to relevant IS and protection class IP-65 ,dust,vermin and weather proof fabricated out of 3.15mm thick CRCA sheet duly powder coated ,mounted on 40x40x5mm MS angle iron frame,duly welded in shape and coated with two coats of synthetic enamel paint of approved colour over a coat of redoxide primer including necessary grouting of legs 300mm deep in ground in PCC 1:4:8 type D2 using 40mm graded stone aggregate ,panel base to be 500mm above ground level with suitable compartments for controls and Monitors including cable glands for incoming and outgoing cables, suitable engraved white on black name plates and identification labels of metel for all switchboard, locking arrangement,including accomodating, supply and fixing the following accessories/items including necessary internal panel wiring with suitable size of Copper wire PVC insulated & sheathed multi stranded complete all as specified and as directed by Engr-in-charge including Supply and fixing the following :-
Earthing complete with GI earth electrode of size 60cmx60cmx6mm buried directly in ground vertically at a depth not less than 2.25 meter below normal ground level with top edge of earth plate at a depth not less than 1.5 meter below normal ground surrounded from all sides by 15 CM thick and packed layer of charcoal dust and common salt filling in alternate layers cleaned connected to and including GI earth strip 25 x 4 mm size up to 7.5 mtr by means of bolts, nuts, check nuts and washers made of galvanised iron and protected light grade 20 mm bore for watering and including funnel wire mesh, RCC pit cover 50 mm thick and PCC chamber pit with PCC 1:3:6 type C-2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 meter) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 all as specified and directed by Engineer-in-Charge.
Usha Builders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .