EXECUTIVE ENGINEER (E)
ELECTRICAL DIVISION-3 SIRI FORT, BEHIND GARGI COLLEGE NEW DELHI-110049
SITC of VRF/VRV system in Gym at Siri Fort Sports Complex.
2026_DDA_930371_1
45/EE/ELD-3/DDA/2026-27
Open Tender
Electrical Works
Percentage
90 days
As per Tender Document
Please refer Tender documents.
16 documents required · 16 mandatory
₹0
₹95,813
ELECTRICAL DIVISION-3/DDA
14 Oct 2026
14 Oct 2026
23 Oct 2026
14 Oct 2026
22 Oct 2026
15 Oct 2026
15 Oct 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying, Installation, replacement(i/c rebate of old item), Testing & Commissioning of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling/heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s),minimum two compressors (with individual separate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condenser fan shall be capable to operate at different speed with respect to load.The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39°C. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter connections etc. as required. (For capacity <40 kWr ISEER 7.4, Capacity > 40 and <70 ISEER 7.5, Capacity > 70 ISEER 7.6 for Super ECSBC Building). - (DSR Item: 31.3.3)
Outdoor unit: 22 X 4 = 88 HP Outdoor unit: 12 X 1 = 12 HP | 100 | HP | 21,009 | ₹21,00,900 |
| 2 | Supply, Installation,replacement(i/c rebate of old item), testing and commissioning of following minimum capacity and external high static pressure VRF/VRV ceiling mounted ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, other necessary supports etc., suitable for operation on single phase AC supply 230V±10%, 50Hz complete as required. The unit shall have automatic force shut down provision in case of fire on receiveing signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. Ductable Type : - 8 TR - (DSR Item: 31.12.4) | 8 | Nos. | 82,635 | ₹6,61,080 |
| 3 | Supply and Installation of Remote controllers (Corded) for operation of indoor units (MR) | 8 | Set | 16,215 | ₹1,29,720 |
| 4 | Supply, installation, testing & commissioning of Ceiling Suspended Treated Fresh Air Unit. (MR)
1300 CFM (For Gym Area) | 1 | No. | 1,27,650 | ₹1,27,650 |
| 5 | Supply, installation, testing & commissioning of AHU Kit for TFA for 1300 CFM Ceiling Suspended Unit. (MR) | 1 | Set | 33,120 | ₹33,120 |
| 6 | Supply, Installation, Testing and Commissioning of variable refrigerant flow distribution couplings with insulation for refrigerant piping 'Y' Joints in copper piping. (DSR Item: 31.13.1) | 9 | Nos. | 4,535 | ₹40,815 |
| 7 | Refrigerant Piping
Supply, Installation, replacement(i/c rebate of old item), Testing and Commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRF/VRV system, complete with fittings, with suitable adjustable ring type hanger supports, jointng/brazing including accessories insulated with XLPE Class O tubular insulation/with Class O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specification etc as required: (DSR-2025-31.14)
12.7 mm dia (OD) (soft drawn) with tube thickness 1.2 mm with 19mm thick insulation | 65 | Mtr. | 472 | ₹30,680 |
| 7.1 | 15.86 mm dia (OD) (soft drawn) with tube thickness 1.2 mm with 19mm thick insulation | 95 | Mtr. | 597 | ₹56,715 |
| 7.2 | 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19mm thick insulation | 90 | Mtr. | 717 | ₹64,530 |
| 7.3 | 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19mm thick insulation | 50 | Mtr. | 877 | ₹43,850 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.05 MB
NIT45.pdf
Tender Documents • 4.63 MB
BOQ_977724.xls
BOQ • 2.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .