Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.3 CrAccepted-AOC A 14 INDUSTRIAL HOUSE INDERPURI NEW DELHI 1100012 | NEW DELHI | NEW DELHI | DELHI | 110012 | ₹13.3 Cr Quoted ₹13.7 Cr | L1 | Accepted-AOC Accept |
| 2 | L2₹14.8 CrRejected-AOC 143 INDUSTRIAL AREA PHASE II PANCHKULA HARYANA 134112 | PANCHKULA | HARYANA | 134112 | ₹14.8 Cr | L2 | Rejected-AOC Reject |
| 3 | L3₹15.9 CrRejected-AOC 322 AGGARWAL MODERN BAZAR C 33 LAWRENCE ROADS DELHI 110035 | DELHI | NORTH WEST DELHI | DELHI | 110035 | ₹15.9 Cr | L3 | Rejected-AOC Reject |
Tender Value
₹13.1 Cr
EMD Value
₹26.2 L
Closing Date
16 Aug 2023, 3:00 pmClosed
XEN M/GARH W.S MECH. DIVISION, NARNAUL
Executive Engineer M/Garh W.S. Mech. Divn., Narnaul, 123001
Replacement of 7 Nos. 150 Cs. VT Axial Flow Pump with 7 Nos. 650 HP Motor HT 3.3 KV at pump House MC-1 to MC-4 of M/Garh Canal having lift 23.02 in M/Garh W/S Mech. Division Narnaul
2023_HRY_300299_10
2814-25/9-A dated 21/07/2023
Open Tender
Pumps/Motors
300 days
XEN M/GARH W.S MECH. DIVISION, NARNAUL
Please refer Tender documents.
3 documents required · 3 mandatory
₹20,000
₹26.2 L
Yes
XEN M/GARH W.S MECH. DIVISION, NARNAUL
8 Dec 2023
28 Jul 2023
17 Aug 2023
28 Jul 2023
16 Aug 2023
28 Jul 2023
10 Aug 2023
Amount
Supply, Erection and commissioning of 150 Cs. existing V.T. axial flow pump having lift 23.02’ including delivery pipe & bend (MS IS 2062 Gr. Fe 410 WA) including flanges, welding, nut-bolts, siphon breaker valve as per site, erection & commissioning including any leftover item with epoxy coating paint both side as per specification approved by technical committee (Annexure-A).Including dismantling of old existing pump and shifting to store as directed. Providing & fixing by making required size /length at site in pair of MS cross Girder (ISMB) of size 500mmx200mm for foundation of 150 CS VT Axial Flow pump including supply,fixing & welding on both (top and bottom) side of ISMB through out length with MS flat of 200mmx25 mm thick. One end of ISMB shall be grouted into wall by making arrangement Of PCC block of suitable size as per weight of pump set of 150 Cs capacity and other end shall be welded with fixing of A.I. L- bracket and nut/bolts/washers etc into existing ISMB member. Including Material & Labour for applying primer coat with metal primer on new steel or iron work including preparation of surface and Material & labour for painting two coats excluding primer coat with ready mixed paint (Epoxy paint) for metallic surface in all shades on new steel or iron work. Taking down by cutting / welding the existing rusted/ old foundation girder for fixing new girder at site.MAKE: TATA/JINDAL/SAIL/VAIZAG.( 2 No. at PHMC-1, 2 No. at PHMC-2, 2 No. at PHMC-3, 1 No. at PHMC-4.)Providing & fixing by fabrication of pedestal frame structure vertically fixed on PCC Floor to support the M.S Bend of 150 Cs. VT Axial Flow Pump with wrought iron & mild steel (using angles, flats, square bars, tee & channels) ladders, grills, grating Frames, window guards iron doors openable or fixed stair case or parapet or any other type of railing, gates & tree guards etc. including cost of screws & welding rods or bolts & nuts complete fixed in position as per site requirement. Including Providing and fixing anchor bolt 20 mm dia N/S item 300 mm length (SS304) of suitable quantity, Providing and fixing anchor bolt 20 mm dia N/S item, 200 mm length (SS304) of suitable quantity, Appling priming coat with metal primer of approved make on new steel or iron work including preparation of surface and Painting two coats of approved make excluding priming coat with ready mixed paint (epoxy paint) for metallic surface in all shades on new steel or iron work. MAKE of Steel : TATA/JINDAL/SAIL/VAIZAG ( 31.34 Qtl. at PHMC-1, 31.34 Qtl. at PHMC-2, 31.34 Qtl at PHMC-3, 15.67 Qtl at PHMC-4.)
Supply and commissioning of Induction motor 650HP suitable for 150 cs. VT Axial flow pump having lift 23.02’ HP650, KW 485, RPM 495, Voltage 3.3KV., 3 phase, 50HZ, space heater 2 no 500 Wt, Bearing SKF/FAG as per specification approved by technical committee (Annexure-B). ( 2 No. at PHMC-1, 2 No. at PHMC-2, 2 No. at PHMC-3, 1 No. at PHMC-4.)
Supply Installation & commissioning of M.V feeder pillar VCB for 3.3 KV. ‘Supply with 1 No. incoming, 1600 Amp & 4 No. outgoing of 400 Amp. each motor panel. The VCB's shall be of Horizontal draw out type, Horizontal isolation with 26.2 KA fault level PT ratio 3300/110V, CT ratio 1600/5 for incoming 320/5 for outgoing with IDMT relay for over loaded fault/ earth fault. The auxiliary relay shall Pc No plus MC along with Amp meter having CT ratio as above. volt meter 1 No. for incoming along with minimum copper bus bars. the outgoing feeder shall also have Micro processor based motor protection relay with advance features of over loading, under loading dry, run, phase loss, phase revision, locked rotor, stalling etc and completed in all respect including all left over mist . Item that is power pack/ UPS & separate chemical earthing with capicator bank specification approved by technical committee. With 6 No. Bimetallic clamp 630 mm square as per specification approved by technical committee (Annexure-C). (MC-3=01 No , MC-5=01 No).
HT Cable 240 Sq mm, 3.3 KV, Three Core as latest ISI specification of approved make by technical committee.(MC-1=500mtr).
HT Cable 630Sq mm, 3.3 KV, Single Core as latest ISI specification of approved make by technical committee.(MC-2=500 Mtr).
Providing and fixing of lightening arrester with protection radius of 100 meter along with earthing arrangment as per proper specification for pump house building and as per site requirment.
Providing, Fitting & Fabrication including welding work of safety grating jal for fixing in bay kg gap of pumps inside pump house in different dimensions as per site requirement and as directed with material fabricated with MS Channel 150x75x5mm/100x50x5mm/75x40x5mm, MS flat 100x10mm/75x8 mm/35x6mm MS Angle 40x40x5mm/40x40x6, MS Chaquered sheet thickness 8 mm including Mason work, painting etc. Make:- Tata/ Jindal/Sail/Valzag. (Pump House MC-1 to MC-4)
Avon Engineering Company
M/s KRP Engineering Pvt. Ltd.