Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.2 CrAccepted-AOC 10 SHANTI VIHAR RUDRAPUR UDHAM SINGH NAGAR UTTARAKHAND 263153 | UDAM SINGH NAGAR | UTTARAKHAND | 263153 | ₹6.2 Cr | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹6.7 Cr+₹54.4 L (8.79%)Rejected-Finance | ₹6.7 Cr+₹54.4 L (8.79%) | L2 | Rejected-Finance Other than L1 |
| 3 | L3₹7.2 Cr+₹96.1 L (15.5%)Rejected-Finance | ₹7.2 Cr+₹96.1 L (15.5%) | L3 | Rejected-Finance Other than L1 |
| 4 | L4₹7.3 Cr+₹1.1 Cr (17.9%)Rejected-Finance | ₹7.3 Cr+₹1.1 Cr (17.9%) | L4 | Rejected-Finance Other than L1 |
| 5 | L5₹7.4 Cr+₹1.2 Cr (19.6%)Rejected-Finance | ₹7.4 Cr+₹1.2 Cr (19.6%) | L5 | Rejected-Finance Other than L1 |
Tender Value
₹5.4 Cr
EMD Value
₹6.0 L
Closing Date
8 Aug 2022, 6:00 pmClosed
Headquarter ,Chief Engineer Lucknow Zone,Lucknow .
Headquarter ,Chief Engineer Lucknow Zone,Lucknow Cantt PIN -226002
CONSTRUCTION OF 10 BEDDED ICU AND 30 BEDDED ACUTE WARD FOR OFFRs/JCOs/OR AT MIL HOSP UNDER GE (P) ALLAHABAD.
2021_MES_490965_4
CELZ/ALD/T-15 OF 2020-2021
Open Tender
Civil Works - Others
Lump-sum
450 days
GE (P) PRAYAGRAJ
As per tender documents
6 documents required · 6 mandatory
₹3,000
GE(P) Prayagraj
₹6.0 L
Yes
8 Sept 2022
11 Jun 2022
10 Aug 2022
11 Jun 2022
8 Aug 2022
26 Jun 2022
Amount
Sch 'A' Part-I (Building Work) Note : This schedule is pre-priced by MES and the pre-priced rate indicated are under Col. 5.
Total amount of Sch 'A' Part II (Site clearance, excavation and earth work)
Total amount of Sch 'A' Part III (Internal Water Supply )
Total amount of Sch 'A' Part IV (Internal Electrification)
Total amount of Sch 'A' Part V (Sewage Disposal)
Total amount of Sch 'A' Part VI (Fire Alarm System )
Total amount of Sch 'A' Part VII (Area Drainage)
Total amount of Sch 'A' Part VIII (Geyser)
Total amount of Sch 'A' Part IX (External Water Supply )
Total amount of Sch 'A' Part X (External Electrification )
Total amount of Sch 'A' Part XI (Lighting Protection)
Sch 'A' Part - XII (Miscellaneous Items) Note - This Schedule is not pre-priced by MES and the pre - priced rate indicated as "Rs 0.00 under col.5 siginifies this fact only.
INTERNAL ELECTRIFICATION Point wiring complete for One light/Fan/Exhaust Fan point controlled by one switch with PVC insualted and unsheathed FRLS cable 1.5 Sqmm (nominal area) ISI marked, multi-stranded copper conductor single core including ISI marked 20 mm dia PVC conduit medium grade concealed in wall and PVC conduit not less than 20 mm in roof / floor slab and ceiling, pressed GI concealed terminal boxes not less than 1.6 mm thick of required size and with top cover 3 mm thick of plastic laminated sheets of requied colour complete, including 1.5 Sqmm PVC, FRLS cable insulated unsheathed copper earth wire to the common earth and connecting to earth dolly, including colour coding of cable shall be Phase-red, Neutral-black and Earth- green with all accessories complete all as specified and directed. Note :- In case of roof/ceiling, heavy duty PVC pipe shall be used without any extra cost.
Point wiring complete for One light point controlled by two way switches with PVC insualted and unsheathed FRLS cable 1.5 Sqmm (nominal area) ISI marked, multi-stranded copper conductor single core including ISI marked 20 mm dia PVC conduit medium grade concealed in wall and PVC conduit not less than 20 mm in roof / floor slab and ceiling, pressed GI concealed terminal boxes not less than 1.6 mm thick of required size and with top cover 3 mm thick of plastic laminated sheets of requied colour complete, including 1.5 Sqmm PVC, FRLS cable insulated unsheathed copper earth wire to the common earth and connecting to earth dolly, including colour coding of cable shall be Phase-red, Neutral-black and Earth- green with all accessories complete all as specified and directed. Note :- In case of roof/ceiling, heavy duty PVC pipe shall be used without any extra cost.
Point wiring complete for one 5 Pin 5 Amp switch Socket outlet point on an independent board, with PVC insualted and unsheathed FRLS CABLE 1.5 Sqmm (nominal area) ISI marked, multi-stranded copper conductor single core including ISI marked 20 mm dia PVC conduit medium grade concealed in wall and PVC conduit not less than 20 mm in roof / floor slab and ceiling, pressed GI concealed terminal boxes not less than 1.6 mm thick of required size and with top cover 3 mm thick of plastic laminated sheets of requied colour complete, including 1.5 Sqmm PVC, FRLS cable insulated unsheathed copper earth wire to the common earth and connecting to earth dolly, including colour coding of cable shall be Phase-red, Neutral-black and Earth- green with all accessories complete all as specified and directed. Note :- In case of roof/ceiling, heavy duty PVC pipe shall be used without any extra cost.
Point wiring complete for one 5 Pin 5 Amp switch Socket outlet point on same board, with PVC insualted and unsheathed FRLS CABLE 1.5 Sqmm (nominal area) ISI marked, multi-stranded copper conductor single core including ISI marked 20 mm dia PVC conduit medium grade concealed in wall and PVC conduit not less than 20 mm in roof / floor slab and ceiling, pressed GI concealed terminal boxes not less than 1.6 mm thick of required size and with top cover 3 mm thick of plastic laminated sheets of requied colour complete, including 1.5 Sqmm PVC, FRLS cable insulated unsheathed copper earth wire to the common earth and connecting to earth dolly, including colour coding of cable shall be Phase-red, Neutral-black and Earth- green with all accessories complete all as specified and directed. Note :-In case of roof/ceiling, heavy duty PVC pipe shall be used without any extra cost.
Point wiring complete with PVC insulated and unsheathed, FRLS cable 2.5 sqmm (nominal area) ,ISI marked, multi-stranded copper conductor single core including ISI marked 20mm dia PVC conduit concealed in wall and MS conduit in roof/floorslab excluding flush metal GI boxes complete,including 1.5 Sqmm,FRLS cable PVC insulated unsheathed copper earth wire to the common earth and connecting to earth dolly,including colour coding of cable shall be Phase-red,Neutral-black and Earth- green with all accessories and all as specified Note :- In case of roof/ceiling, only MS black sheet conduit ISI marked dia of coduit not less than 20 mm shall be used without any extra cost.
Supply and fixing Tele phone socket ,Modular, ISI marked complete all as specified and directed.
Supply and fixing Modular Metal Flush Box for 8 Module complete all as specified and directed.
S&F LED batten Tube light surface / wall mounted with specially designed powder coated aluminum housing, high optically efficient polycarbonate diffuser, in built electronic driver duly wired upto terminal block, power consumption <20W (4 FT 20 W), luminaire lumen >2000 lm, system efficiency of >120 lumens /W, with LED binning as per ANSI Bin C78.377A, photo biological safety report as per IEC624718 & electrical insulation class I, Ingress protection IP 20, colour rendering index CRI>80, temp range 0 to 450C, driver efficency>85%, power factor>0.9, THD <20% as per IEC 61000-3-2, colour temp -6500K, surge protection 2.5 KV, 50000 burning hrs (min) as per L70 criteria, two stages isolated constant current operated driver with range 150-270V AC and seafty extra low voltage safe level <60V DC as per IEC standard with LM70 & LM80 certification complete all as specified and directed
S&F LED batten Tube Light surface / wall mounted with specially designed powder coated aluminum housing, high optically efficient polycarbonate diffuser, in built electronic driver duly wired upto terminal block, power consumption <10W (2 feet 10 W) luminaire lumen >1000 lm, system efficiency of >120 lumens /W, with LED binning as per ANSI Bin C78.377A, photo biological safety report as per IEC624718 & electrical insulation class I, Ingress protection IP 20, colour rendering index CRI>80, temp range 0 to 450C, driver efficency>85%, power factor>0.9, THD <20% as per IEC 61000-3-2, colour temp -6500K, surge protection 2.5 KV, 50000 burning hrs (min) as per L70 criteria, two stages isolated constant current operated driver with range 150-270V AC and seafty extra low voltage safe level <60V DC as per IEC standard with LM70 & LM80 certification.complete all as specified and directed.
S&F LED Building security light fitting with aluminum pressure die cast housing, high purity PC Fresnel diffuser with silicon gasket for IP-65 protection, power consumption <20 W (14W) & luminaire lumen >2500 lm and system efficiency > 120 lm/W, in built electronic driver prewired upto terminal block with driver efficiency >85% power factor >0.95 as light source with toughened glass including two core flexible copper wire of 1.5 sq mm from ceiling rose to the connector of fitting, connection wires not to be more than 2.5 in length and made out of GI tubing 35/40 mm dia /suitable dia light grade bend to shape security light fitting with necessary MS clamp 25 mm wide and 6 mm in thickness in suitable length not more than 30 CM and max length of pipe 1.5 Mtr long with one code of anti corrosive primer and two coats aluminum paint including nuts, bolts and washers complete all as specified and directed.
S&F Mirror light Decorative ultra slim square profile liner LED lighting fixture with extruded polycarbonate body with Minimum 8 Watt & Maximum 11 Watt LED warm white in colour with a luminous efficacy of 120 lum/watt(min) with PF not less than 0.9 with LED binning as per ANSI Bin C78.377A, photo biological safety report as per IEC624718 & electrical insulation class I, Ingress protection IP 20, colour rendering index CRI>80, temp range 0 to 450C, driver efficency>85%, power factor>0.9, THD <20% as per IEC 61000-3-2, colour temp -6500K, surge protection 2.5 KV, 50000 burning hrs (min) as per L70 criteria, two stages isolated constant current operated driver with range 150-270V AC and seafty extra low voltage safe level <60V DC as per IEC standard with LM70 & LM80 certification.complete all as specified and directed.
S&F circular slim surface LED downlighter of 8 Watts with housing made up of die cast aluminum for better thermal management, high transmitivity non yellowing PMMA diffuser for better light output and uniform light distribution without glare, power consumption <10W, luminaire lumen>1000lm, driver and accessories to be prewired, CRI>70, LED efficiency > 120 lm/W photo biological safety report as per IEC624718 & electrical insulation class I, LED life with L70 criteries -37000 hrs colour temp >6000K, Ingress protection IP-20, ambient temperature 0 to 450C, driver efficiency >85%, THD<10% as per IEC 61000-3-2, power factor >0.95, surge protection 2.5 KV, two stages isolatated constant current operated driver with range 150-270V AC and safety extra low voltage safe level <60V DC as per IEC standard with LM79 & LM80 certification complete all as specified and directed.
S&F circular slim surface LED Decorative Wall mounting of 12 Watts with LED Bulb 12 watts complete Polycarbonate housing, globe type Glass protection with high transmitivity non yellowing PMMA diffuser for better light output and uniform light distribution without glare, power consumption <12W, luminaire lumen>1000lm, driver and accessories to be prewired, CRI>70, LED efficiency > 120 lm/W photo biological safety report as per IEC624718 & electrical insulation class I, LED life with L70 criteries -37000 hrs colour temp >6000K, Ingress protection IP-20, ambient temperature 0 to 450C, driver efficiency >85%, THD<10% as per IEC 61000-3-2, power factor >0.95, surge protection 2.5 KV, two stages isolatated constant current operated driver with range 150-270V AC and safety extra low voltage safe level <60V DC as per IEC standard with LM79 & LM80 certification complete all as specified and directed.
S&F Decorative wall mounting chrome finish 3 watts led fixture decorative LED wall bractive Glass protection with high transmitivity non yellowing PMMA diffuser for better light output and uniform light distribution without glare, power consumption <5W complete all as specified and directed.
S&F Decorative Pendent LED Lights 15 watts led fixture decorative type with flexible sprial extension copper conductor wire for better light output and uniform light distribution without glare, power consumption <18W complete all as specified and directed.
Supply and fixing Wall fan 400 mm sweep single phase 230V AC, five star rating and ISI marked alongwith ss fixing brackrt complete and connecting up the fan to ceiling rose including PVC insulated three core 23/0.0076 copper cable and suitable size of flexible conduit from 5 Amp socket to wall fan motor not less than 0.5 mtr long for connection complete all as specified and directed.
S&F MCCB 4 pole ,415 V ,AC fixed type 100 amps with breaking capacity 10 KA complete all as specified and directed.
S&F MCCB VTPN DB double door type, 415 Volts AC, with 200 amp rated bus bar of suitable size plate and common neutral link all enclosed in standard steel sheet flush mounting type factory fabricated ,powder coated complete with out MCCB and with enclosure blank plates for unused way suitable for 4 way complete all as specified and directed.
S&F MCB TP 63 Amps 'B" series,,10 KA 240 Volts ,AC complete all as specified and directed.
S&F MCB SPN 40 Amps 'B" series,,10 KA 240 Volts ,AC complete all as specified and directed.
S&F MCB SPN 16 Amps 'B" series,,10 KA 240 Volts ,AC complete all as specified and directed.
S&F MCB single pole 6- 32 Amp rating 'B' Series,10 KA 240 Volts,AC 50 Hz ,ISI marked complete all as specified and directed.
M & L Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground.(earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr. below ground level connecting to galvanised earth lead wire 4.0 mm dia as earth lead upto 7.5 meters long connected by means of bolts, check nuts and washers of GI and earth wire protected by provision of GI pipe medium grade, 15 mm bore including provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded crushed stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4Kg/Sqm) and frame of angle iron 40 x 40 x 3mm fixing with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge plate, common salt and charcoal filling, with fixing arrangement, funnel, wire mesh and earth work in hard / dense soil, returning filling in and removal of surplus soil to a distance not exeeding 50 mtr, all as per electrical plate No 3 of SSR 2009 Part-I and connection all as specified and testing on completion. Note: The cost of excavation and earth work, PCC pit and pit covers, funnel and watering pipe, wire mesh, charcoal dust and common salt,20/ 40mm dia, medium grade, GI pipe as protection to GI wire 4.0 mm as main earthing lead from earth electrode to main TPN MCCBs DB/MCB DB/ test point length not less than 7.5mtrs) shall be deemed included in the unit rate for earthing and testing complete all as specified and directed.
M & L Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground.(earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr. below ground level connecting to galvanised iron earth strip 25 x 4 mm as earth lead upto 7.5 meters long connected by means of bolts, check nuts and washers of GI and earth wire protected by provision of GI pipe medium grade, 15 mm bore including provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded crushed stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4Kg/Sqm) and frame of angle iron 40 x 40 x 3mm fixing with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge plate, common salt and charcoal filling, with fixing arrangement, funnel, wire mesh and earth work in hard / dense soil, returning filling in and removal of surplus soil to a distance not exeeding 50 mtr, all as per electrical plate No 3 of SSR 2009 Part-I and connection all as specified and testing on completion. Note: The cost of excavation and earth work, PCC pit and pit covers, funnel and watering pipe, wire mesh, charcoal dust and common salt,20/ 40mm dia, medium grade, GI pipe as protection to GI wire 4.0 mm as main earthing lead from earth electrode to main TPN MCCBs DB/MCB DB/ test point length not less than 7.5mtrs) shall be deemed included in the unit rate for earthing and testing complete all as specified and directed.
Supply and finxing Wall mounted Indoor LT panel board with CPRI Approved of suitable shape and size, 3 phase, 4 wire, 440 Volts AC supply, dust and vermin proof, floor block mounting type made out of 2.15 mm thick MS sheet with using 40mm x 40mm x 4mm angle iron with using two coats of synthetic enamel paint over a coat of red oxide primer with and including bus bars of capacity 400 Amp for phase 200 Amps for neutral complete all as specified and directed by Engr-in - Charge and the following : ( LT Panel-01 Near Stair case No -1 and No -2 Respectively ) INCOMING : (a) MCCB, 4 pole, 415 Volt AC supply, 250 Amps having breaking capacity Icu = 50 KA with adjustable load setting. - 01 No. (b) Digital panel meter for Amp,volt,KWH,PF and other parameters flush mounting of size 96 mm x 96 mm.-01 No. OUTGOING : (c) MCCB, 4 pole, 415 Volt AC supply,125 Amps having breaking capacity Icu = 50 KA with adjustable load setting. - 03 Nos. (d) MCCB, 4 pole, 415 Volt AC supply, 63 Amps having breaking capacity Icu = 25 KA with adjustable load setting. -1 No
INTERNAL WATER SUPPLY S& F CP Health faucet 15 mm bore with hook (hand spray) flexible pipe of min 1.50 metre length fixed complete all as specified and directed.
EXTERNAL ELECTRIC SUPPLY Supplying,design, loading, unloading, installing, testing and commissioning of Transformer 250 KVA step down, outdoor type, double wound copper, 3 phase, 4 wire, 50 Hz AC, oil immersed, natural air cooled with external cooling tubes having no load voltage ratio 11/0.433 KV (corresponding to principal tapping) winding delta connected on primary side (HV side) and star connected on secondary side (LV side) in accordance with vector symbol Dyn-11 (vector group-11) with natural brought out on LV side for earthing and having tapping on HV side for constant output so as to alter/vary secondary voltage by ± 7.5% in steps of 2.5% to be changed by means of manually operated "off load" taps changing gear. The limit of temperature rise after continuous full load run as specified in IS-1180 Part-1 (2b) shall be suitably adjusted to suit the maximum ambient tempearture of 48 degree Centigrade in HV/LV windings and 40 degree centigrade in oil as prevailing at site. The transformer shall confirm IS : 1180 and latest relavent IS and ECBC marked and shall comprise of the following :-
Oil conservator tank with filling holes and cap, filter type drain valve and oil level gauge.
Silica gel breather with connecting pipe and first fills of dehydrating agent.
Air release valve plug.
One cable box on LV side (secodary) consisting of 04 Nos porcelain bushings with nuts, washers & bushing rods with 01 cable gland suitable for reception of taking out one 3½ core, 240 Sqmm LT 1100 Volts grade cable including gland joints complete all as specified.
01 No. 100mm dial type thermometer vapour pressure type having rating 0-120 degree centigrade with max temp indicator and resetting device incuding max reading pointer washers etc.
Thermometer pocket on tank cover.
04 Nos Plain Solid CI detachable rollers.
Two number earthing termninals on tank cover to facilitate GI earth strip.
Rating plate and terminal marking plate.
Extra bushing for neutral outside the cable box brought on LV side.
First filling of oil conforming to IS and tested upto 50 KV/2.5 mm dielectric strength.
Lifting Lugs.
Oil drain valve with plug.
3 Nos Porcelain HV bushing with arching horns on HV side suitable for 11 KV complete bushing rods, nuts and washers etc.
(p) Explosive vent.
Note :-(i) Any other parts/items not specified above but have been considered essential for smooth and safe functioning of the transformer system shall be included in the items and are covered against the quoted rate.
(ii) certificate of di electric strength will be provided by contractor after initial filling of oil.
M&L for Transformer platform with standard specifications alongwith chain link fencing and gate complete all as specified and shown on drawing No TD-699 .
Supply and fix Outdoor automatic power factor correction (APFC panel) factory made of 125 KVAR capacity ready to use, design conforming to IS: 8623 rated for short circuit rating of 50KA, front openable and lockable by keys having louvers and air vent, gasket and totally vermin proof and suitable for 400-450 volts 3 phase 50HZ AC and housed in elegent enclousre fabricated from 3.14mm thick CRCA sheet with anti corrosive coating to achive power factor 0.9 to 0.99 and final powder coated in texture siemens grey RAL 7032 and directed by Engineer in charge and comprising for the following:-
Copper bus bar duly insulated with colour coated heat shrinkable sleeves and mounted on DMC/Epoxy insulator (size not less than 50 mm x 50 mm chronical type at a max interval of 500mm of not less than 1.5 times rated capacity.
A set of heavy duty capacitor type MPPH with 5 steps ( 2x12.5+2x25+50) each by using metalised polypropylene technology having total losses less than 0.5 KVAR output with over load and frequent switch capability conforming to IS-2834 IEC - 831. Capacitors should be provided with special sequential pressure sensitive disconnector.
MCCB four pole 400 Amp 25 KA capacity conforming to IS-13943 (Part-3) to ensure positive isolation from both side when the unit is off.
Suitable capacitor for each step shall be used and shall be provided with special in rush coil to limit the capacitor in rush contactor shall operate between 85% to 110% but not less than 60%.
The APFC Panel provided with two earthing terminal and it is connected through GI strip transformer earthing/panel earthing all as specified and directed.
All control wire shall be not less than 2.5 Sqmm multi stranded copper conductor and properly bunched/ tied, ferulled for proper identification and crimpled with adequated size of lugs. The cubicle will have a bottom support of channel of suitable size, duly coated with zinc metal coating. A detachable pre- drilled gland plate of thickness 3.0 mm thick, cold zinc metal coating shall be provided with at the bottom for entry for armoured cable with adequate size of glands. Manufacturer name plate with feeder details and danger plate shall be provided at suitable visible place.
PCC 1:2:4 type B-1 using 20 mm graded stone aggregate for grouting of APFC panel shall be provided as directed by Engineer-in-Charge.
Steel tubular swaged pole complete with MS base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55, 11 mtr long, all as specified and shown on drawings including the followings:- (a) Excavation in post holes in any types of soil, returning, filling, well ramming and disposal of surplus soil to a distance not exceeding 50m from the starting points. (b) PCC (1:4:8) type D2 using 40mm graded stone aggregate as in base. (c) PCC (1:3:6) type C2 using 40mm graded stone aggregate as in foundation (d) PCC (1:2:4) type B-1 using 20mm graded stone aggregate as in coping of size 300x300x300 mm including necessary form work (e) Painting of poles externally with one coat of bituminous paint (upto planting depth) and above plinth block concrete collar with two coat of aluminum paint over one coat of red oxide primer including preparation of surface . (f) The portion above coping shall be painted in alternation bands of black and yellow colour (each band of 30 cm wide) by two coats of super enameled paint upto 1.5m height
Supply and fix lightning arrestor expulsion/metal oxide type confirming to IS-3070 Part-I complete line discharge class-2, nominal discharge 5 KA & high discharge 65 KA assembly suitable for 11 KV including all clamps, nuts, bolts & washers and connecting to earth with 32x6 mm GI strip complete all specified and directed.
Supply, installing, testing and commissioning of Air break switch GOD (combined with dropout assembly with fuse carrier, fuse element mounted on insulator and steel frame), Single break, 11 KV rated voltage, Max system voltage, 11 KV, 50 C/S rated frequency, 200 Amp continous current rating max temp rise over contacts 35 degree centigrade, other current carrying parts max temp rise 50 degree centigrade, main contacts fixed / moving of tinned copper alloy, vertical loading arrangements (vertical mounting), Triple pole mechanically operated from ground, mounted on insulators 11 KV grade (09 Nos) operating handle, post insulators, high pressure heavy duty, operating rod made of 25 mm dia , GI medium grade pipe, MS clamps, bolts, nuts, and washers, locking arrangement with one pad lock 50 mm (Godrej / Navtal) with two keys including providing two coats of aluminium paint over a coat of red oxide Zink chrome primer complete all as specified and directed.
Supplying, laying & testing cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade cable of size 3 core 95 sq mm complete all as specified and as directed. (from existing 4 pole structure to proposed 2 pole structure/Transformer)
Supply and fix Cable termination kit 11 KV (Earthed) grade cable for outdoor end termination joints cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor Cable of size 70 to 95 Sqmm complete all as specified and directed
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 240 Sqmm 3.5 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 185 Sqmm 3.5 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 120 Sqmm 3.5 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 95 Sqmm 3.5 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 35 Sqmm 3.5 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 25 Sqmm 4 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 16 Sqmm 4 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ,ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 10 Sqmm 4 core complete all as specified and directed.
Steel tubular swaged pole complete with MS base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31, 09 mtr long, ISI marked confirming to IS 2713 (Part I to III) of 1980 all as specified and shown on drawings including the followings:- (a) Excavation in post holes in any types of soil, returning, filling, well ramming and disposal of surplus soil to a distance not exceeding 50m from the starting points. (b) PCC (1:4:8) type D2 using 40mm graded stone aggregate as in base. (c) PCC (1:3:6) type C2 using 40mm graded stone aggregate as in foundation (d) PCC (1:2:4) type B-1 using 20mm graded stone aggregate as in coping of size 300x300x300 mm including necessary form work (e) Painting of poles externally with one coat of bituminous paint (upto planting depth) and above plinth block concrete collar with two coat of aluminum paint over one coat of red oxide primer including preparation of surface . (f) The portion above coping shall be painted in alternation bands of black and yellow colour (each band of 30 cm wide) by two coats of super enameled paint upto 1.5m height.
LED street light luminaires of capacity 60 watt comprising of pressure die-cast aluminium housing, road way luminaires with high power LED, enclosed with glass cover in frame, IP 66 protection including bracket made out of GI tubing 1.20 mtr long of 32/40 mm dia light grade bent to shape with suitable size MS clamps, nut, bolts and washers including one coat of anti corossive primer and two coats aluminium paints with 1.5 Sqmm 3 core sheathed multistranded copper cable from LED light to pole box complete as per direction of Engr-in-charge.
M & L for DK Thermoplastic cable junction boxes IP 65 with metric knockouts for cable entry, weather proof for outdoor installation and including glands and with 4 terminals for terminating one incoming and outgoing UG cable of size 10/16 sqmm 3.5/4 core and fixed to the PSC/Steel Poles by means of suitable size of clamps with nut and bolt complete all as specified and directed.
M & L for wall mounted panel made of 2 mm thick CRCA sheet consisting bus bar Chamber of suitable size complete 8 way with copper bus bar strip 63 Amp complete all as specified and directed.
Earthing complete with GI earth plate electrode 600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25 m deep below GL) with top edge of the plate not less than 1.5 m below the normal ground level connected with GI strip 32 x 6 mm thick by means of bolts, nuts, check nuts and washers of galvanised iron or steel including necessary excavation & earth work in any type of soil, removing surplus soil to a distance not exc 50 m, with and including PCC chamber in PCC (1:2:4), type B1 using (20 mm graded stone aggregate), mild steel frame made out of angle iron of size 40 mm x 40 mm x 3 mm thick duly paint with two coats of synthetic enamel paint over one coat of red oxide zinc chrome primer hinged with and including 6 mm thick CI cover with handle, watering arrangement with funnel internally secured with wire mesh with 20mm dia medium grade pipe for watering, 15 mm dia light grade GI pipe for lead protection in and including alternate layer of charcoal dust and common salt complete all as shown in electrical plate No. 3 connected to earthing test point all as specified and indicated including testing on completion as directed. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
Earthing complete with galvansided steel earth plate electrode 600 x 600 x 6.0mm thick directly burried in the ground (Earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.50M below the normal ground level, GI wire 4.0 mm dia from earth plate/ electrode to test point (upto max distance of 7.50M is included in unit rate) and connected to earth plate & earth test point by means of bolts, nuts, check nuts and washers of galvanised iron or steel, 15mm bore GI pipe light grade including necessary fittings for protection of earthing wire, watering pipe 20 mm bore GI medium grade, concrete chamber in PCC (1:4:8) type D-2 using 40 mm grade stone aggregate, coping shall be in PCC (1:3:6) type C-1 using 20 mm grade aggregate and internal surfaces of concrete chamber shall be renderd 12 mm thick plaster in cement mortor (1:4), funnel with wire mesh of 22 gauge (0.63 mm) 8 mesh per linear including 50mm thick cover of RCC (1:2:4) type B-1 using 20mm grade stone aggregate reinforced with 8mm MS deformed bar @ 75 mm C/C both ways, char coal dust and common salt all as shown in electrical plate No. 3 of SSR Part-I (2009) including all necessary excavation & earth work and removal of surplus soil to a distance n. exc 50M and connection from DB to earth electrode with same GI wire alongwith protection pipe and testing on completion complete all as specified and directed.
EXTERNAL WATER SUPPLY Supply and laying of 100 mm bore centrifugally cast (spun) ductile iron pressure pipes for water mains with socket & spigot ends conforming to IS 8329/2000 any length for classification of K7 suitable for rubber gasket joint (push on type) with cement mortar lining inside the pipe with outside zinc coating complete all including existing connection with required size of Tee or MS clamp with rubber bush as specified and directed. Note :Cutting of pipe, fittings for pipe, lead joints shall be measured and paid separately under respective items of BOQ.
M&L for construction of valve chamber 600 x 600 x 600 mm (internal dimensions), including excavation & earth work 100 mm thick PCC 1:4:8 Type D-2 using stone aggregate as in foundation, 230 mm thick fly ash brick work in cement mortar 1:4 , 15 mm thick rendering in cement mortor 1:4 on internal surface of valve pit and mild steel sheet cover 6 mm thick angle iron size 40 x 40 x 6 mm frame around of valve pit, sheet welded on four corners, locking arrangement with pad lock of size 50 mm brass, 6 leavers and duplicate key (Make Godrej) or equivalant specified make as approved including two coat synthetic enamel paint over one coat of red oxide primer on prepared steel surface complete all as specified shown on drawing and as directed.
Drilling hole in DI water main (in position) and making arrangement for tapping water connection for 40/25mm GI tubing with and including all necessary nut bolts, u clamps with socket, gasket etc required for fittings complete all as specified and directed.
Cutting the existing Cast Iron pipe of size 150 mm and insertion of tee of size 150 x 150 x 400 mm in position (comprising of two cuts) for taking connection for 150mm NB DI pipe & then filling the joints with lead etc to make them leak proof. Note : Cost of the tee lead joints & other T&P required for taking connection. Deemed to be included in the quoted rates. However, the connected length wk will be measured and paid separately.
MEDICAL GAS Supplying,laying, testing and commissioning 28 mm dia of 0.90 mm thickness Medical grade copper pipe solid drawn, half Hardened, phosphorus de-oxidized , nonarsenical, de-greased, tempered, seamless and conforming to EN : 13348 standards. Pipe should be delivered in plugged or capped at both ends conditions complete all as specified and directed. Make:-Maxflow, Rajco & Mandev .
Supplying,laying, testing and commissioning 22 mm dia of 0.90 mm thickness Medical grade copper pipe solid drawn, half Hardened, phosphorus de-oxidized , nonarsenical, de-greased, tempered, seamless and conforming to EN : 13348 standards. Pipe should be delivered in plugged or capped at both ends conditions complete all as specified and directed. Make:-Maxflow, Rajco & Mandev .
Supplying,laying, testing and commissioning 15 mm dia of 0.90 mm thickness Medical grade copper pipe solid drawn, half Hardened, phosphorus de-oxidized , nonarsenical, de-greased, tempered, seamless and conforming to EN : 13348 standards. Pipe should be delivered in plugged or capped at both ends conditions complete all as specified and directed. Make:-Maxflow, Rajco & Mandev .
Supplying,laying, testing and commissioning 12 mm dia of 0.70 mm thickness Medical grade copper pipe solid drawn, half Hardened, phosphorus de-oxidized , nonarsenical, de-greased, tempered, seamless and conforming to EN : 13348 standards. Pipe should be delivered in plugged or capped at both ends conditions complete all as specified and directed. Make:-Maxflow, Rajco & Mandev .
Supply, installation and Testing of Zone service units including necessary valves with connected acessories for all 04 Gas services complete all as specified and directed. Make:- MPS,KN Ent,SAS,MR Engg & AKTIV.
Supply ,Installation Testing and commissioning Medical Gas Alarm panel with analog pressure gauge incorporating all gases, with Test button, mute button shall give alarm when pressure below desired value and restore when pressure for gases up to the desired value complete all as specified and directed. Make:- MPS,KN Ent,SAS,MR Engg & AKTIV.
OXYGEN SUPPLY SYSTEM Supply, installation, testing and commisioning of semi automatic control panel complete all as specified and directed. Make:- MPS,KN Ent,SAS,MR Engg & AKTIV.
Supply, installation, testing and commisioning of 6+6 Cylinder Oxygen manifold system with tail pipe (excluding Cylinders) complete all as specified and directed. Make:- MPS,KN Ent,SAS,MR Engg & AKTIV.
Supply, installation, testing and commisioning of 6+6 size Oxygen Emergency cylinder supply system with tail pipe (excluding Cylinders) complete all as specified and directed.Make:- MPS,KN Ent,SAS,MR Engg & AKTIV.
Supply, installation, testing and commisioning of ward vaccum units with unbreakable collection jars and regulators .The unit shall have vaccume gauge to indicate the suction supplied to the suction unit with 600 ml jar bottle unbreakable polycarbonate and autoclave at 121 Degree centigrade complete all as specified and directed. Make:- MPS,KN Ent,SAS,MR Engg & AKTIV.
VACCUM PUMP FOR MEDICAL VACCUM SYSTEM Supply, installation, testing and commisioning of Medical vaccum system plant with alluminium venes fitted with gas ballast valve,inlet suction filter with paper cartridge.Suction pump should have 3 vanes.Pump shall with first charge of vaccume pump oil.Capacity of pump shall 10 HP /7.5 KW with twin comressor with related accessories and starter panel complete all as specified and directed. Make : IR ,Anesta lwata.
Supply, installation 500 litre MS Reservoir tank made with 6 mm thick MS plate complete all as per standard engineering practice , specified and directed.Make : IR ,Anesta lwata.
Supply, installation Anti bacterial tank with accessories complete all as specified and directed.Make : IR ,Anesta lwata.
Supply, installation, testing and commisioning of oxygen flow meter with humidifier bottle of range 0-15 LPM.The flow tube shall be of clear ,impact resistant polycarbonate .The humidifier bottle shall be unbreakable polycarbonate and autoclave at 121 Degree centigrade and complete with all meters suitable for putlets offered complete all as specified and directed. Make:- MPS,KN Ent,SAS,MR Engg & AKTIV.
COMPRESSED AIR SYSTEM Supply, installation, testing and commisioning compressed Air Plant. The compressed Air system should be of make-Ingersoll rand, model W5i A10 or equivalent specified or approved by GE . The stem should consist oil free scroll compressors 02 Nos as per latest edition of the ISO 8573-1:10 Zero level. It should include centrifugal fan, double inlet Efficient double inlet filter, Belt driving, 40 C max ambient, efficient copper tube fin heat exchanger, single phase AC fan of large air volume and low sound level, LCD display, serious fault protection and extension fault alarm, three control mode : local control, remonte control and communicated control standard RS-485 communication connector, Multiple units control ligic operation with CFM 18.7 and 5.5 KW TEFC motor and Max pressure 10 Bar with low sound. Make : IR ,Anesta lwata.
Supply, installation 500 litre MS Reservoir tank made with 6 mm thick MS plate complete all as per standard engineering practice , specified and directed.Make : IR ,Anesta lwata.
Supply, installation 3 stage ultra filter and drier complete all as specified and directed.Make : IR ,Anesta lwata.
NITROUS OXIDE SYSTEM Supply, installation, testing and commisioning of 2+2 Cylinder Nitrous oxide manifold system with tail pipe (excluding Cylinders) complete all as specified and directed.Make:- MPS,KN Ent,SAS,MR Engg & AKTIV.
Supply, installation, testing and commisioning of ward vaccum units with unbreakable collection jars and regulators .The unit shall have vaccume gauge to indicate the suction supplied to the suction unit shall have a bracket for wall mounting with 600 ml jar shall be made of unbreakable polycarbonate and are autoclavable at 121 Degree centigrade complete all as specified and directed. Make:- MPS,KN Ent,SAS,MR Engg & AKTIV.
BED HEAD PANELS Supply, installation and providing wiring and piping connections for bed head wall panels. The panel shall be fabricated out of high strengths extruded aluminium sections within build single rolling slider and powder coated to colour as approved by GE. The panel shall have facility to accommodate: Max 5 no of Gas outlets, 5/15 A multi pin switched socket outlet 04 Nos and holder for vaccume collection Jar.Make:- MPS,KN Ent,SAS,MR Engg & AKTIV.
ISOLATION VALVES Supply, installation and providing Isolation valves 12 mm (Brass) .Isolation valves shall be ball valve type,non-greased suitable to isolate pipe section complete with fittings complete all as specified and directed. Make:- Matrix,RN,RB, AKTIV & CONEX.
Supply, installation and providing Isolation valves 15 mm (Brass) .Isolation valves shall be ball valve type,non-greased suitable to isolate pipe section complete with fittings complete all as specified and directed. Make:- Matrix,RN,RB, AKTIV & CONEX.
Supply, installation and providing Isolation valves 22 mm (Brass) .Isolation valves shall be ball valve type,non-greased suitable to isolate pipe section complete with fittings complete all as specified and directed. Make:- Matrix,RN,RB, AKTIV & CONEX.
Supply, installation and providing Isolation valves 28 mm (Brass) .Isolation valves shall be ball valve type,non-greased suitable to isolate pipe section complete with fittings complete all as specified and directed. Make:- Matrix,RN,RB, AKTIV & CONEX.
DG SET Silent/containerzed diesel engine driven generating set complete to give an output of 250 KVA AC 415 Volts, 50 Cycles per second, 3 phase 4 wire supply with power factor 0.8, 1500 RPM diesel engine and alternator mounted on common base plate, anti vibration rubber mounting pad (AVM Pads "B" series) complete in all respect with and including accessories and components as specified below including sound proof integral accoustic enclosure for 250 KVA Gen Sets ECO friendly and as per Ministry of Environment, forests notification 17 May 2002 complete including, emergency stop button, illumination inside canopy, Temperature sensor for high temp safety, exhaust fan etc complete as per IS 4722, AMF type with relay panel for automatic starting on mains failure. (a) Diesel Driven Engine (Prime mover):- Multi cylinder, vertical/horizontal, 4 stroke cycle, suitable for 250 KVA alternator, water cooled conforming to BSS- 649 rated for continuous running diesel engine suitable to FF matching BHP at 1500 RPM as per latest ISS/BSS, capable of taking 10% over load for any one hour in any 12 hour running, complete with and including following accessories:-
i) Fuel filter ii) Governor ( Electronic) iii) Complete battery set with lead & lugs as recommended by manufacturer. iv) Lubricant oil cooler v) Lubricant oil pump. vi) Lubricant oil filter vii)Digital oil pressure gauge viii) Any other parts as prescribed by manufacturer for its good functional performance. ix) Battery charging alternator suitable for charging Batteries. x) Dry type air filter xi) MS channel fabricated frame rigidly welded suitable for receiving the diesel engine and alternator and anti vibration pads. xii) Coupling guard. xiii) Exhaust pipe fully extended to exhaust gases outside the acoustic enclosure including silencer and necessary insulation lagging all as per manufacturer's recommendations. xiv) Fuel tank of sheet steel and of capacity for 12 hours running on full load with inlet and outlet connection, filling cap, drain valve, air vent with caliberated scale on outer surface, floor mounted with suitable angle iron supports. xv) Digital type RPM meter with hour meter. xvi)Self starter of suitable size xvii) Turbo charger xviii) In line mono block
(xi) Auto change over complete with suitable size power contactor of size upto 400 Amps with tripping relay complete. (xii) Engine starting relay.xiii) Frequency stabilizer auto mechanism to maintain the supply.xiv) Battery charger suitable to charge the battery of 12 V/24 Volt DC with buck/ boost system - 01 No (e) Supply & install of Acoustic Enclosure suitable for 250 KVA DG set as underi) Fabricated out of CRCA sheet of suitable thickness as per manufacture design. Polyster based powder coated internaly and externaly with lockable type door handle. All nuts and handles shall be zinc coated. ii)The doors are gasketed with EPDM gaskets. iii) Sound proofing with high quality rock wool/ mineral wool confirming to IS 8183 of 50 mm thickness and density at 96 Kg/Cum covered with fiber glass cloth and perforated powder coated sheet specialy designed allenuators (Sound controller) at air entry and exit of the container noice level shall be not exceed 75 Decible at 1 meter distance as per CPCB/Government of India Norms. iv) Adequate ventilation to meet air requirement for combustion and heat removal with provn of a blower.v) Emergency stop push button outside the container.vi) Provn of light inside the canopy i.e. providing LED light fitting 1 x 20 Watt with wiring and control switch.(f) MOUNTING ARRANGEMENT- Prime mover and alternator shall be mounted on skid mounting type base frame fabricated from ISMC channel or in sheet metal providing common bed for engine and alternator directly coupled together the base frame has provision for grouting on foundation bolt as well as fixing on vibration mounts provision is made in base frame for tilting arrangement of DG set as recommended by manufacturer. The base frame shall have provision of lifting hook for convenient lifting of complete set ie along the canopy engine and alternator.
SPECIAL INTERNAL ELECTRIFICATION Supply and fix Shadow less light fitting complete with emergency power unit & battery back up for min 30 minutes (3 KVA), having dome of minimum 500 mm dia, fully counter balanced and fixed on suspension rod,portable type capable of having angular ,axial and radial. The unit to be suitable for minor OT and Capable for operation on 230 Volt single phase, 50 cycles mains supply having lux level > 70,000 complete all as specified and directed by Engr-in-Charge.Make:- SPARX-LED 06 of Hardik Medi- Tech or Technomed.
Supply & fix electronic dimmers, 450 Watt , 250 Volt flush type on the existing phenolic laminated sheet etc complete all as specified and directed by Engr-in-Charge.
NURSE AND PATIENT CALL SYSTEMS Supply & fix wireless Attendent calling system consisting of a microprocessor based Central display unit/control panel and Min 12 number of wireless calling unit depending upon the number of callers with audible and visual indications, necessary interfaces, regulated power supply and making necessary connection complete all as specified and directed by Engr-in-Charge.Cat WACS T12 FF NB 1 of textel or equivalent of DIGI-Tech .
Supply & fix wireless Attendent calling system consisting of a microprocessor based Central display unit/control panel and Min 32 number of wireless calling unit depending upon the number of callers with audible and visual indications, necessary interfaces, regulated power supply and making necessary connection complete all as specified and directed by Engr-in-Charge.Cat WACS T32 FF NB 1 of textel or equivalent of DIGI-Tech .
Supply and fix Automatic hand dryers suitable for 210-230 volts, 50HZ AC supply, wall mounted type with air delivering @ 90-270 cum per hour complete all as specified and directed.
Supply and fix Automatic hand soap dispensers having container capacity of not less than 750 ml, suitable for 210-230 volts, 50HZ AC supply ,wall mounted type with dispensing liquid soap 1 ml volume in one use complete all as specified and as directed.
GEYSER Supply & installation of Water heater storage type, electric driven (Single phase) having approx storage of capacity 25 litres with inlet and outlet heavy duty flexible pipe connection thermostate, copper tank, release valve, non return valve and indicator lights complete all as specified.
Hot water inlet /outlet heavy duty PVC pipe, end made of brass chromium plated with Union rubber washer suitable for 15 mm bore GI pipe for hot/cold water complete all as specified and directed.
Submain wiring with two single core 4 sqmm FRLS copper conductor, PVC insulated, multistranded, unsheathed cable ISI marked drawn in PVC conduit concealed in wall surface / ceiling for sub main connection including 4 sqmm FRLS PVC insulated multistranded unsheathed copper conductor used as earth wire to common earth and connection to earth dolly complete all as specified and directed. Note : Two single core 4 sqmm copper conductor, one run PVC conduit and one run of 4.00 Sqmm earth wire shall be considered and measured as one unit.
LIFT :- Supply and fix Lift electrically operated Microprocessor controlled complete with power driven automatic stainless steel (SS) sliding doors and having SS car enclosure of size 1600 x 2400 mm , suitable for Hospital stretcher, suitable to carry 26 passenger (1768 Kg) at a speed of 1 metre/sec to serve upto 2 floors (G+1 floors) including automatic rescue device having following specifications : - Basic elevator data Elevator Type Passenger cum stretcher Elevator Product Minispace / Imonospace No of Units - 01 Load & capacity 1768 kg or 26 persons Speed 1 m/s Stops & Openings 2 stops & 2 openings, Single entrance car Travel height 4.2 m to 4.35 m (Approx) Elevator Grouping Simplex Full collective control Well dimension 2800 mm width and 3185 mm depth (Approx) Head Room height 4400 mm (Approx) Pit Height 1600 mm (Approx) MAP Floor Position Ex machine room Car Dimensions 1600 mm wide x 2400 mm deep x 2600 mm high Door dimensions 1200 mm wide x 2400 mm internal height Door Type Two-panel centre opening Note:- Minor variation in dimensions can be done at site based on site requirement by approval of GE. Finishes Car design - Midrange Basic SL10
Basic elevator data Contd .... Car Panel Finish Midrange Basic SL10 Ceiling & Lighting – Square spot, LED Stainless Steel Square Spot Light LED Flooring – 3 mm Rubber flooring – Denver gray Coin Patterned Grey Car Skirting material: Stainless steel Hairline AISI441 Car door Finish SS Vandalproof Textured Floor number Floor Mark Interfloor distance 1-2 0,1 4200 mm (Approx) Landing door material Stainless steel AISI441 Car operating Panel – 2 full height stainless steel face plate silver brushed StSt segmented LCD display Square flush mounted with Braille KDS90 Landing Signalization – Stainless Steel 7 segment display Flush Mounted Silver brushed StSt Square,flush mounted with Braille KDS90. Features :- Standard Car Emenrgency Light Firemen Drive Curtain of Light 169 Beams Accurate Relevelling, Automatic closed door Additional Emergency Rescue Device with audio announcer Provision for local intercom Attendent service Doors Closed Square Spot Light LED Interface only
TELE COMMUNICATION Rigid non-metallic PVC conduit 25mm exclusive of boxes (junction/terminal) but inclusive of all tees, bends elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and directed.
Cast Iron/ pressed steel terminal boxes of size 75mm x 75 mm and 60 mm deep for mounting, switches, sockets, fan regulator, etc. with 3mm thick plastic laminated sheet cover complete all as specified and directed.
Telephone socket RJ 11 with Shutter 1 module complete all as specified and directed.
Tele com PVC insulated cable for indoor 0.4mm ATC complete all as specified and directed.
Supply, installation, testing of online UPS of 1 KVA capacity with output voltage 240 volts AC, ± 3% variation from no load, high line to low line frequency 50 Hz ± 0.5 Hz sine wave output from protected with internal electronic overload protection, 30 min battery backup including maintenance free (AGM), battery 12 Volt/1000 VAh including interconnection complete all as specified and as directed by Engr-in-Charge.
DEORA ELECTRIC WORKS
HI TECH COLONISERS PRIVATE LIMITED
M/s Highway Construction
VEE SONS BUILDERS PVT LTD
M/s NSA Engineering Corporation
M P KHAITAN
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .