Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.8 CrAccepted-AOC | ₹22.8 Cr | L1 | Accepted-AOC qualified |
| 2 | L2₹23.6 CrRejected-AOC | ₹23.6 Cr | L2 | Rejected-AOC qualified |
| 3 | L3₹23.9 CrRejected-AOC | ₹23.9 Cr | L3 | Rejected-AOC qualified |
| 4 | Rejected-Technical GROUND FLOOR BUILDING NO 1 MORE COMPLEX ROHA KOLAD ROAD DHATAV RAIGAD MAHARASHTRA 402116 | RAIGAD | MAHARASHTRA | 402116 | - | - | Rejected-Technical The technical support letter from OEM of HT breaker is not submitted as per NIT, Hence Disqualified |
| Sl No | Description | Qty | Unit | sagarsai Enterprises L1 | Damodhartech International Pvt. Ltd L2 | ACDC Saideep Buildcon Pvt Ltd L3 |
|---|---|---|---|---|---|---|
| 1.00Description | ||||||
| 2.00 | Item no.01 Hermetically Sealed transformer (SS-TR-HSL) 1.1 Supplying, installing, testing & commissioning 3 phase, 22/0.433 kV, 50 Hz., 315 kVA, Mineral oil immersed and naturally cooled outdoor type, Copper wound, without gas cushioning, hermetically Sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 45? by thermometer in oil and 50? by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with off load tap changer) off Load +5 to -10 in steps of 2.5%, having 7 number of tap positions with standard accessories complete with test certificate with losses below 1076 Watts at 50% load, 3255 Watts at 100% load as per IS:1180 (part 1) : 2014 with necessary permissions of Electrical Inspector, as per specification no SS- TR-HSL. | 3 | each | 8,26,160 ₹24,78,480 Lowest | 9,85,818 ₹29,57,454 | 9,98,822 ₹29,96,466 |
| 3.00 | 1.2 Supplying, installing, testing & commissioning 3 phase, 22/0.433 kV, 50 Hz., 630 kVA, Mineral oil immersed and naturally cooled outdoor type, Copper wound, without gas cushioning, hermetically Sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 45? by thermometer in oil and 50? by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with off load tap changer) off load +5 to -10 in steps of 2.5%,having 7 number of tap positions with standard accessories complete with test certificate with losses below 1953 Watts at 50% load, 5565 Watts at 100% load as per IS:1180 (part 1) : 2014 with necessary permissions of Electrical Inspector, as per specification no SS- TR-HSL. | 3 | each | 12,50,680 ₹37,52,040 Lowest | 18,91,230 ₹56,73,690 | 19,16,176 ₹57,48,528 |
| 4.00 | Item No.02 Accessories 2.1 Supplying and erecting 22 kV outdoor type gang operated air break, triple pole switch 200 A capacity with 3 post pin type insulator per phase, mounted in horizontal or vertical position with necessary channels on provided cross arm with adequate length of "C" class G.I. pipe for operating handle erected on extended square shaft. The operating handle provided with lock and key at suitable height from ground level with necessary clamp. | 8 | Per Set | 24,000 ₹1,92,000 | 19,420 ₹1,55,360 Lowest | 19,676 ₹1,57,408 |
| 5.00 | 2.2 Supplying and erecting, 22 kV outdoor type drop out fuse with insulator complete with fuse holders, fuse barrel with metal fitting, fuse element mounted on M.S. channel with working current of 15A capacity complete erected on provided cross arm. | 8 | Per Set | 14,800 ₹1,18,400 | 11,173 ₹89,384 Lowest | 11,321 ₹90,568 |
| 6.00 | 2.3 Supplying and erecting hard drawn copper solid wire no. 0 to 6 SWG complete erected for connections on H.T. sides. | 4 | kilogram | 1,100 ₹4,400 Lowest | 1,137 ₹4,548 | 1,152 ₹4,608 |
| 7.00 | 2.4 Supplying and erecting extra thick alkathene pipe 10 mm dia. erected to enclose bare conductor wires complete.. (use shall be restricted to H.T.) | 15 | Meter | 30 ₹450 Lowest | 64 ₹960 | 65 ₹975 |
| 8.00 | 2.5 Supplying and erecting fencing of section having size at least 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete with provided earthing as per specification no. SS-AS/FSG | 96 | each | 5,175 ₹4,96,800 Lowest | 7,137 ₹6,85,152 | 7,231 ₹6,94,176 |
| 9.00 | 2.6 Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2.45m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminium paint complete. | 24 | each | 2,010 ₹48,240 | 1,450 ₹34,800 Lowest | 1,469 ₹35,256 |
| 10.00 | 2.7 Supplying and erecting double leaf hinged door each 1500 mm in width x 2450 mm in height using B class GI pipe, hinges and angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation and painted complete as per specification no SS-AS/DLD | 96 | each | 11,800 ₹11,32,800 Lowest | 20,828 ₹19,99,488 | 21,103 ₹20,25,888 |
Tender Value
₹23.1 Cr
EMD Value
₹11.5 L
Closing Date
13 Mar 2026, 5:00 pmClosed
SE E and M Comm Mumbai
MIDC HQ office Udyog sarathi Andheri Mumbai 93
Additional Taloja Industrial area.....Providing Power Supply Infrastructure for Quarry and PAP Plots at Additional Taloja Industrial Area
2026_MIDC_1279119_1
MIDC/E and M/AMB/37812/72/2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
Taloja Mahape
Please refer Tender documents.
2 documents required · 2 mandatory
₹30,680
₹11.5 L
27 Jul 2026
18 Feb 2026
17 Mar 2026
18 Feb 2026
13 Mar 2026
27 Feb 2026
18 Feb 2026 - 23 Feb 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Description | - | - | - | - |
| 2 | Item no.01 Hermetically Sealed transformer (SS-TR-HSL) 1.1 Supplying, installing, testing & commissioning 3 phase, 22/0.433 kV, 50 Hz., 315 kVA, Mineral oil immersed and naturally cooled outdoor type, Copper wound, without gas cushioning, hermetically Sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 45? by thermometer in oil and 50? by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with off load tap changer) off Load +5 to -10 in steps of 2.5%, having 7 number of tap positions with standard accessories complete with test certificate with losses below 1076 Watts at 50% load, 3255 Watts at 100% load as per IS:1180 (part 1) : 2014 with necessary permissions of Electrical Inspector, as per specification no SS- TR-HSL. | 3 | each | - | - |
| 3 | 1.2 Supplying, installing, testing & commissioning 3 phase, 22/0.433 kV, 50 Hz., 630 kVA, Mineral oil immersed and naturally cooled outdoor type, Copper wound, without gas cushioning, hermetically Sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 45? by thermometer in oil and 50? by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with off load tap changer) off load +5 to -10 in steps of 2.5%,having 7 number of tap positions with standard accessories complete with test certificate with losses below 1953 Watts at 50% load, 5565 Watts at 100% load as per IS:1180 (part 1) : 2014 with necessary permissions of Electrical Inspector, as per specification no SS- TR-HSL. | 3 | each | - | - |
| 4 | Item No.02 Accessories 2.1 Supplying and erecting 22 kV outdoor type gang operated air break, triple pole switch 200 A capacity with 3 post pin type insulator per phase, mounted in horizontal or vertical position with necessary channels on provided cross arm with adequate length of "C" class G.I. pipe for operating handle erected on extended square shaft. The operating handle provided with lock and key at suitable height from ground level with necessary clamp. | 8 | Per Set | - | - |
| 5 | 2.2 Supplying and erecting, 22 kV outdoor type drop out fuse with insulator complete with fuse holders, fuse barrel with metal fitting, fuse element mounted on M.S. channel with working current of 15A capacity complete erected on provided cross arm. | 8 | Per Set | - | - |
| 6 | 2.3 Supplying and erecting hard drawn copper solid wire no. 0 to 6 SWG complete erected for connections on H.T. sides. | 4 | kilogram | - | - |
| 7 | 2.4 Supplying and erecting extra thick alkathene pipe 10 mm dia. erected to enclose bare conductor wires complete.. (use shall be restricted to H.T.) | 15 | Meter | - | - |
| 8 | 2.5 Supplying and erecting fencing of section having size at least 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete with provided earthing as per specification no. SS-AS/FSG | 96 | each | - | - |
| 9 | 2.6 Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2.45m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminium paint complete. | 24 | each | - | - |
| 10 | 2.7 Supplying and erecting double leaf hinged door each 1500 mm in width x 2450 mm in height using B class GI pipe, hinges and angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation and painted complete as per specification no SS-AS/DLD | 96 | each | - | - |
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.99 MB
TenderDocument.pdf
Tender Documents • 0.46 MB
ItemSpecification.pdf
Other Document • 0.07 MB
BOQ_2200578.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].