Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
27 Jul 2026, 6:00 pm
GE (AWC) Mhow
GE (AWC) Mhow
REPAIR/ MAINTENANCE OF STREET LIGHT, HIGH MAST LIGHT, UG CABLES, OH LINES, JUNCTION BOXES, NATURE SWITCHES AND CONNECTED ITEMS AT AWC AND CAMP AREA, SARNA ENCLAVE, VINDHYA VIHAR, DEMO SQN, GOSWAMI ENCLAVE, AMN DUMPS, ACE, EME WKSP, 11 JAK LI, SUPPLY
2026_MES_776490_1
8972/AWC/MHOW/ OF 2026-27
Open Tender
Electrical and Maintenance Works
180 days
GE (AWC) Mhow
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (AWC) Mhow
₹60,000
4 Jul 2026
4 Jul 2026
29 Jul 2026
4 Jul 2026
27 Jul 2026
20 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Repair/Renewal/maintenance of street light feeder (over head conductors) after arranging elect shut down of street light feeders from sub station to remove oxidise part at the point of connection to street light from LT over head line and reconnect the same to LT over head line after removing the oxidise part all as specified and directed by Engr-in-charge .
Note:- (i) The electrician employed for the purpose will be highly skilled along with one mate and should have all necessary tools and safety devices. | 200 | Each job | - | - |
| 2 | Attending complaint & Checking of street light feeder (under ground cables) from Junction box to fittings using elect tools, equipments and safety devices after arranging elect shut down of street light feeders from sub station to remove elect faults like tightning of loose jumpers, trimming of tree branches on a particular span, re-tightning of binding wires on insulators, re-tightning of cable lugs etc all as required at site and as directed.
Note:- (i) The electrician employed for the purpose will be highly skilled along with one mate and should have all necessary tools and safety devices.
(ii) Materials like cables used for rectification of faults like will be measured and paid seperately. | 700 | Each job | - | - |
| 3 | M&L for Repair of Unsv street/security lights, flood lights , post top lanterns or any other external lights by taking down to ground, testing all the components/parts, wiring etc, identifying and replacing the defective components like choke (ballast), electronic driver (in case of LED Lights), ignitor, capacitor, lamp, lamp holder, connector, connection wires/ cable, MCB etc including refixing the fitting to its original position (if taken down), including repair/maint of street light control timer & junction box all as directed by Engr-in-charge for the complete contract period from the date of commencement of work. | 173 | Each | - | - |
| 4 | Description all as per ser item no. 3.00 & 3.01 above but for light fittings from Mini- mast Lights poles of 11 to 13 m long. | 5 | Each Job | - | - |
| 5 | Taking down high mast fitting from high mast structure through motorised system of 16/20mtr high and checking all fittings including cleaning & lubricating of steel rope and repair the light fittings to make functional by replacing accessories like choke, ignitor, lamp holder etc as required.
Note:- Accessories like choke, ignitor, lamp, capacitor, holder, connecting cable will be measured and paid for seperately under respective item of this BOQ. | 16 | Each Job | - | - |
| 6 | Supply and fixing in replacement for LED flood light 120 watt 230 V AC outdoor type with high pressure die-cast aluminium housing and toughened glass in frant with unique flood optics to ensure uniform distribution with system efficacy more than 120 lm/watt, thermal management in multiple optics and equipped with IP66, IK10 protection with impact and corrosion resistant complete with driver and lamp all as specified. | 15 | Each | - | - |
| 7 | Supply and fixing in replacement for LED flood light 150 watt 230 V AC outdoor type with high pressure die-cast aluminium housing and toughened glass in front with unique flood optics to ensure uniform distribution with system efficacy more than 120 lm/watt, thermal management in multiple optics and equipped with IP66, IK10 protection with impact and corrosion resistant complete with driver and lamp all as specified & directed. | 15 | Each | - | - |
| 8 | Supply and fixing in replacement for LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with PC cover in front and lens for batwing light disttribution with system efficacy more than 140 lm/watt with IP 66, IK10 protection complete all as specified & directed. | 60 | Each | - | - |
| 9 | Supply and fixing in replacement for LED street light fitting 120 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with PC cover in front and lens for batwing light disttribution with system efficacy more than 140 lm/watt with IP 66, IK10 protection complete all as specified & directed. | 60 | Each | - | - |
| 10 | Supply and fixing in replacement for post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete. | 10 | Each | - | - |