Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.6 LAccepted-AOC SCHEME NO 07 BLOCK NO 22 FLAT NO 03 NEW GURDASPUR DISTT GURDASPUR PB 143521 | GURDASPUR | PUNJAB | 143521 | L1 | Accepted-AOC SINCE L1 BIDDER | |
| 2 | L2₹14.6 L+₹1.9 L (15.2%)Rejected-Finance | L2 | Rejected-Finance SINCE NOT L1 BIDDER | |
| 3 | L3₹15.0 L+₹2.3 L (18.4%)Rejected-Finance NEAR PARDEEP MEDICAL HALL DEEP NAGAR JALANDHAR CANTT JALANDHAR PUNJAB 144005 | JALANDHAR | PUNJAB | 144005 | L3 | Rejected-Finance SINCE NOT L1 BIDDER | |
| 4 | L4₹15.8 L+₹3.2 L (25.0%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L4 | Rejected-Finance SINCE NOT L1 BIDDER | |
| 5 | L5₹16.2 L+₹3.5 L (27.6%)Rejected-Finance 29 MODEL TOWN BEHIND GURUDWARA PATHANKOT | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L5 | Rejected-Finance SINCE NOT L1 BIDDER |
Tender Value
₹15.5 L
EMD Value
₹31,000
Closing Date
17 Nov 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE AMRITSAR CANTT
HQ CWE OLD AMRITSAR CANTT
SPL REPAIR / REPLACEMENT OF SF6 CIRCUIT BREAKER OF 66 KV CAPACITY AGAINST BER SF6 AT TIBRI MIL STN UNDER GE GURDASPUR
2022_MES_550322_1
CWE/ASR-35/2022-23
Open Tender
Civil Works
Item Rate
180 days
GE GURDASPUR
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE GURDASPUR
₹31,000
Yes
10 Dec 2022
6 Sept 2022
19 Nov 2022
6 Sept 2022
17 Nov 2022
5 Nov 2022
Amount
Taking down carefully SF6 breaker 66 KV capacity, incomer/outgoing feeder complete removing with connecting material complete and deposit to MES store for keeping in safe custody or re-use at site.
Supply and installation, testing and commissioning of Circuit Breaker SF6 outdoor type 66 KV nominal voltage 3 phase , 50 HZ as per IEC 62271-100 complete with all accssories and of the following technical specifications complete all as specified and direced by Engineer-in-charge. (a) Highest system voltage between phase 72.5 KV. (b) Rated Normal current : 1650 Amps (c) Rated power frequency withstand voltage :- 140 KV (d) Short breaking current 31.5 KA. (e) Short circuit making current 80 KA. (f) Rated duration of shortcircuit 3 second. (g) Minimum creepage distance to ground : 1813 mm . (h) Rated lightning impulse with stand voltage : 325 KVP. (j) Type of mechanism enclosed in housing, motor operatin spring. (k) Rated operating sequence : 0-0.3 Sec CO-3 Min CO. (l) Rated closing /Tripping voltage : 220 VDC. (m) Current of closing/triping coil : 6A max at 220 vdc. (n) Rated current for terminal connections:630 Amps all others specifications as per stand IE rules and as directed .
Note : (i) Testing and commissioning of SF6 circuit breaker including checking of compatibility with existing 8 MVA power transformer shall be done by the PSPCl department. The contractor will deposit the calibration/testing and commissioning charges whatsoever to PSPCL departmennt and make necessary arrangements for the testing and commissioning of new SF6 circuit breaker.The charges of PSPCL department transportation, checking charges, tools and plants etc as required are included in the quoted rate and nothing extra on this account shall be paid. (ii) If required the foundation for fixing of SF 6 shall be provided by the contrator as per manufaturer instructions without any exta cost.
Supply, installation, commissioning and testing of HT outdoor 66 kv protection current transformer of 72.5 KV, 31.5 KA sec , oil cooled, Hermetically sealed, Wound Primary Type, four core live tank Type current transformer of Ratio 150/1-1-1-1 Core 1 : Class -0.2, Burden : 30 VA (Metering) Core 2: Class - 5P 20, Burden 30 VA (protection) Core 3 : Class -PS (Differential) Complete Core 4: Class PS (ref) Complete in all respect to the entire satisfaction of Engineer-in-charge. Other specifications as per std IE rules and entire satisfaction of the Engineer- in-charge. Note : If required the foundation/ Structure for fixing of CT shall be provided by the contrator as per manufaturer instructions without any exta cost.B15
Supply installation, commissioning, and testing of 66 KV Class station heavy duty metal oxide gapless type outdoor lighting Arrester for use with effective ground natural system with insulating base including surge minitors for 66 kv with all accessories to meet the requirement as under :- (a) Nominal system voltage 66 kv (rms). (b) Highest system voltage 72.5 KV (rms) (c) MCOV 52 KV (d) Nominal Discharge current - 10 KAP (e) Line discharge - class 3 (f) High current discharge (g) Max residual voltage - 165 KVP at 01 KAp complete all as specified.
M& L for renewal of earthing complete with galvanised steel pipe electrode, 40 mm bore medium grade, 2.5 meteres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing lead by using aluminium strip 25x4 mm as earthing lead all as shown in plate No 2 the earthing test point all as specified and indicated including testing on completion and PCC chamber using PCC 1:3:6 type C2 &C1 cover funnel & wire mesh all as specified & directed by Engr-in-charge. Note :The whole earthing will be redone if the result found not satisfactorily and the decision of Engineer-in-charge will be final and binding, No extra cost will be paid to the contractor for rectification of the earthing.
Kaul Enterprises
GULSHAN SINGH GHAI AND SON
R D Bansal
kailu construction co
INDERJIT SINGH
M/S SATPAL & BROTHERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .