Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹73.5 LAccepted-AOC 67 RAMPURA GANDHI NAGAR JAMMU 180 004 J K | JAMMU | JAMMU | JAMMU AND KASHMIR | 180004 | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹88.4 L+₹14.9 L (20.3%)Rejected-Finance | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹1.2 Cr+₹43.6 L (59.3%)Rejected-Finance 5037 5038 URBAN ESTATE PH 1 PATIALA 147001 PUNJAB | PATIALA | PATIALA | PUNJAB | 147001 | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹1.2 Cr+₹44.4 L (60.5%)Rejected-Finance | L4 | Rejected-Finance Other than lowest | |
| 5 | L5₹1.4 Cr+₹71.4 L (97.2%)Rejected-Finance 135 CHAKRANA TIWARI CHAKA NAINI PRAYAGRAJ 211008 UTTAR PRADESH | PRAYAGRAJ | UTTAR PRADESH | 211008 | L5 | Rejected-Finance Other than lowest |
Tender Value
₹87.3 L
EMD Value
₹1.6 L
Closing Date
26 Jun 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE(I) 873 EWS
Garrison Engineer (Indep) 873 Engineer Works Section PIN 913 873 C/O 56 APO
AUGMENTATION AND IMPROVEMENT OF EXISTING E/S INFRA INCLUDING PROVN OF LED LIGHTS WITH CONNECTED WORKS AT BHALRA MIL STN UNDER GE (I) 873 EWS
2023_MES_597070_1
NIT-24 of 2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
290 days
Bhderewah
Please refer NIT and Tender Documents
7 documents required · 7 mandatory
₹1,000
GE(I) 873 EWS
₹1.6 L
Yes
21 Jul 2023
20 May 2023
28 Jun 2023
20 May 2023
26 Jun 2023
12 Jun 2023
Amount
Supply, install, testing & commissioning of 33/11 KV 1600 KVA OUTDOOR, 50 Hz ON load tap changer, 3 phase, mineral oil type transformer : (Make :- ITE / ABB / BHEL / BHARAT BIJLEE / ALTOM / SCHNEIDER) i) Standard: IS : 2026 with all latest amendments. ii) Losses and Temp. Rise shall be as per latest IS 2026. iii) Outdoor type (in and including material & labour for fencing works for transformers, gravel in the yard as per recommendations of original manufacturers drawings). iv) Vector group : Dyn11. v) Rating : 1600 KVA. vi) Cooling System: ONAN. vii) Winding: Copper. viii) Magnetic Core: Prime grade of M4 or better. ix) High voltage : 33KV - 50 Z. x) Low voltage: 11KV-50HZ. xi) System highest voltage : 36kV at the HV side. xii) Insulation Level - H.V. Power Frequency (KV rms): 70 kV, H.V. Impulse withstand voltage (KV peak): 170 kVp, tapping: +5% to -15% ON load tap changer in steps of 1.25%, Temperature rise of Oil / Winding over design ambient temperature of 50 deg C: 50/55 deg. C. xiii) HT Termination - Bare Bushing
The core material shall be purchased directly from manufacturer (Posco / Nippon / Novex / AK steels) or from their accredited marketing organisation. (ii) Only ISI marked core should be procured as per the requirement of BIS product manual guidelines (Annexure F of BIS order) & vide order no. S.O. 4637(E). (iii) The core and core assembly should be dried through a heating and drying oven. (iv) Manufacturer shall test transformer from NABL accredited lab to ascertain the authenticity of test results and Purchaser may test the transformer from CPRI / ERDA officials with their testing equipments. Note for Item Nos 1.00 of BOQ: (a) The quoted rate is inclusive for factory testing prior to dispatch for the schedule items in the manufactures premises, the Accepting officer shall detail a officer after confirmation received from Manufactures and contractor that the material are ready for dispatch and all necessary tests to be carried out as per manufactures procedures / recommendationbs in the presence of Accepting officer representatative in the manufactures factory premises.
(b) The quoted rate is inclusive for pre commissioning of VCBs and transformers on the site by the Senior Electrical inspector (c) The Bidder is responsible to submit Acryclic sheet 3 mm thick with vinyl print display boards duly framed and written specifications of VCBs and Transformers alongwith flow chart/schemenatic diagram duly marked all switchgears/Transformers in triplicate as per standard engineering methodology along with legend etc complete all as directed. (d) All VCBs incomers and outgoing feeders shall be provided with power pack with capacity to trip the breaket at least twice. (e) The bidder is responsible for provision of necessary socket point wirings near the switch gears/transformers for control wiring purpose for monitoring VCBs/Trs safety parameters round the clock strictly as directed.
S&F of HT 33 KV out door type isolator air break switch suitable for horizontal mounting fixed type complete with 9 polymer insulators and with earth switch upto 400 Amps coplete all as specified and directed.
S&F of Lightning arrestor expulsion type, Transmossion class consisting of multiple spark gaps in series with one or more non-linear resistor to limit voltage surge on AC power circuit to interrupt power flow current suitable for outdoor installation and exposed direct to sun with ambient temperature between (-) 10° C to (+) 50° C suitable for surge discharge capacity 65 KA, 33000 Volts grade conforming to IS-4350 complete with all fittings complete all as specified and directed.
M&L for earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick buried directly to ground vertically to a depth not less than 2.25 Mtr below the ground level with top edge of earth plate not less than 1.65 Mtr below normal ground level connected to GI strip 32 x 6 mm size and earthing lead protected with 50 mm bore GI pipe, light grade, filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to GI strip by means of GI nuts, bolts and washers strip connected to earth plate including chamber PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate in concrete pit pre-cast RCC 40 mm thick reinforced with 6 mm dia round at 75 mm C/C both way with 12 mm dia mild steel plain bar lifting handle 2 Nos funnel with wire mesh 20 mm dia GI pipe light grade watering pipe and frame work complete all as shown in electrical plate No. 3 of SSR Part-I 2009 including testing on completion complete all as specified and directed.
M&L for earthing complete with copper plate electrode 600 mm x 600 mm x 3mm burried directly in ground vertically in pit of depth not less than 2.25 mtr deep below GL with the top edge of the plate at a depth not less than 1.5 mtr from below normal GL, surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to copper earth strip of not less than 25 x 5 mm by means of nuts, bolts, washers, check nuts, earth wire protected by GI pipe 40mm light grade connected to transformers and VCBs etc, all as shown in electrical plate No. 3 of SSR-2009 Part-I in and including necessary excavation and earth work in any type of soil, 20mm bore medium grade GI pipe for watering funnel wire mesh, PCC chamber in PCC (1:3:6) type C1, manhole cover with RCC (1:2:4) type B1, reinforced with 6mm dia MS round bars @ 15cm c/c both ways for cover and MS frame etc, including test point and testing on completion, results should be less than 2 ohms complete all as specified and directed.
M&L for chemical earthing complete with copper plate electrode 900 mm x 600 mm x 5mm burried directly in ground vertically in pit of depth not less than 2.25 mtr deep below GL with the top edge of the plate at a depth not less than 1.5 mtr from below normal GL, surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to copper earth strip of not less than 32x6 mm by means of nuts, bolts, washers, check nuts, earth wire protected by GI pipe 40mm light grade connected to transformers and VCBs etc, all as shown in electrical plate No. 3 of SSR-2009 Part-I in and including necessary excavation and earth work in any type of soil, 20mm bore medium grade GI pipe for watering funnel wire mesh, PCC chamber in PCC (1:3:6) type C1, manhole cover with RCC (1:2:4) type B1, reinforced with 6mm dia MS round bars @ 15cm c/c both ways for cover and MS frame etc, including test point and testing on completion, results should be less than 2 ohms complete all as specified and directed.
S&F of 33 KV single phase out door oil cooled PT of ratio 11 KV/rt3/ 110V /rt3/ 110V /rt3,Class 0.5-3, Burden 50 VA – 50 VA all as specified and directed.
S&F of 33 KV, single phase, out door oil cooled CT of ratio 400/55 Amp, class 1.0 / 5P10, burden 15 VA all as specified and directed.
S&F of Steel Tubular swaged poles type 410 SP-55 (11.0 mtr long) conforming to IS : 2713 Part-I to III 1980, complete with 6 mm thick mild steel base plate, finial taper plug, MS bolts, nuts, screws including painting upto 1.5metre above PCC coping in black and white strips 05 Nos of 30cms each starting from the bottom of the pole and two coats epoxy based paint aluminium grade finish to the remaining external surface over one coat of primer complete all as specified and directed.
S&F of Steel Tubular swaged poles type 410 SP-31 (9.0 mtr long) conforming to IS : 2713 Part-I to III 1980, complete with 6 mm thick mild steel base plate, finial taper plug, MS bolts, nuts, screws including painting upto 1.5metre above PCC coping in black and white strips 05 Nos of 30cms each starting from the bottom of the pole and two coats epoxy based paint aluminium grade finish to the remaining external surface over one coat of primer complete including taking down old unserviceable Pole all as specified and directed.
M&L for stay Assembly using stay rod of 20mm dia complete accessories as shown in Electrical Plate No 1 of SSR 2009 Part-I such as loop type insulator, porcelain, vitreous white/ brown or green, large size with overall dimensions 90 x 140mm clearance of hole 16mm, stay wire of size 7/4mm etc., including taking down old, complete all as specified and directed. Note: Excavation and concrete shall be measured and paid separately.
M&L for cross arm bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, drilling holes for bolts, in any shape or size as indicated or directed and also inclusive of two coats of aluminium paint over one coat of red oxide primer including dismantling / taking down old unserviceable structural steel all as specified and directed.
S&F of street Light fitting 60 Watts LED made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having top opening separate driver compartment with IP65 protection and impact resistance of IK07 with 10KV built-in surge protection device complete all as specified and as directed. Make : Havells/ Wipro / Philips / Crompton /HPL/ SYSKA
S&F of street Light fitting 120 Watts LED made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having top opening separate driver compartment with IP65 protection and impact resistance of IK07 with 10KV built-in surge protection device complete all as specified and as directed. Make : Havells/ Wipro / Philips / Crompton /HPL/ SYSKA
Design, Supply, Erection, Testing and Commissioning of 11 KV, 630A, 25kA for 3 sec, SF6 insulated, Motorized, Indoor, extensible RMU along with air insulated bus connected unit for auxiliary supply & metering, type tested in line with latest IEC standards. The RMU shall be suitable for operations at a height up to 1000 meters above sea level and at 40 degree ambient temperature without any derating. The switchgear and busbar shall all be contained in a stainless steel enclosure filled with SF6 at 0.3 bar (300 hPa) relative pressure. The RMU tank shall provide full insulation, making the switchgear insensitive to the environment with degrees of protection of IP67 . The switchgear operating mechanism shall have an IP2X protection and cable chamber shall have IP3X. Accidental overpressure due to an internal arc is limited by the opening of the safety valve, at the bottom of the metal enclosure, away from the operator. Plug in type of extensibility must be provided and coupling busbar should not be exposed to air to avoid oxidation of busbars.
Extension of cubicle should only require 450mm to handle and the gap between the coupled RMU’s must be within 10mm. 11kV 4Way Ring Main Units: Each of the above Ring Main Unit shall comprise of the followings: (A) 1Nos. Load Break Switch (LBS) each comprising of the following: (i) 1 no. 11 KV, 630A, 25kA Motorized Load break switch with built in line side manual earth switch. (ii) 1 no. Position indicator through clear front mimic in lin with IEC 62271-103 (iii) 1 no. Live cable indicator with indications (Voltage Presence Indicator) at the front and three inlets provision to check the synchronization of phases. (iv)All operations shall be from front of the RMU, including access to cable bushings .Bushings along the sides or the rear of the RMU are not acceptable. (v)1 no. Cable Boots suitable for cable size up to 1R*3C*300 sq.mm. cable (vi)1 no. Fault passage indicator (FPI) with in-built Overcurrent, Short Circuit and earth fault indication (in (N-1) LBS). The FPI should be self-powered and should have internal lithium battery for external indication and setting of FPI in the absence of current. Note:LBS shall have 3 positions, open or disconnected, closed and earthed, and will be constructed in such a way that interlocking prevents unauthorized operations. Manual opening and closing will be driven by a fast-acting /snap action mechanism, independent of operator action. LBS and earth switch shall have a min of 1000 (M1) mechanical operations , 100 electrical operations at rated current and 5 nos operations ar rated SC current.
(B) 3 no. Vacuum circuit breaker (VCB) each comprising of the following: (i) 1 no. 11 KV, 400A, 25kA Motorized VCB with spring assisted mechanism and series trip coil; with built in manual line side three position disconnector cum earth switch. (ii) 1 no. Position indicator through clear front mimic in lin with IEC 62271-103 (iii) 1 no. Self powered / auxiliary powered relay with O/C , S/C , E/F protection. Relay should have a front USB port for laptop interface, LCD display, 10 event records, 5 fault records, min 2 setting group and keypad for setting parameters for the relay. (iv)3 nos. CT of ratio 85/1 A, Class 5P10, 2.5VA for protection & Class 0.5, 2.5VA (v)1 no. Digital MFM Class 0.5 along with RS485 Port (vi)1 no. Live cable indicator with indications (Voltage Presence Indicator) at the front and three inlets provision to check the synchronization of phases. (vii)1 set Cable box with termination bushing suitable for upto 1 RUN 3Cx300 Sq mm, XLPE cable (viii)1 set Cable Boots suitable for cable size up to 1Rx3Cx300 sq.mm. cable Note: The circuit breakers shall have 2 positions: open or disconnected and closed. A separate and independent 3 position earthing switch and disconnector shall be fitted to open and earth the cables in such way that interlocks prevent all unauthorized operations.An operating mechanism can be used to manually close the circuit breaker and charge the mechanism in a single movement. An independent mechanism shall be fitted for the 3 positions earthing switch and disconnector Circuit breaker shall be fitted with a local system for manual tripping by an integrated push button. There will be no automatic reclosing. Circit breaker shall have a min of 2000 mechanical and electrical operations and 50 nos SC operations.Disconnector and earthswitch shall have a min of 1000 (M1) mechanical operations , 100 electrical operations at rated current and 5 nos operations ar rated SC current.
(C) Air Insulated Bus Connected Unit comprising the following:- (i) 1 no. Air Insulated enclosure with necessary bus connection (ii) 3 nos. 11KV/rt3/110V/rt3; 50VA class 0.5. Single phase bus PT for metering (iii) 1 no. 11KV/230V AC, 1KVA control transformer (iv) 1 no. Battery and battery charger, 12Ah, (I/P-230V AC, O/P - 24V DC) (v) Connection with adjacent modules will be direct through busbar , via bushing. VT’s and CT’s from the manufacturer and according to IEC61869-3 and IEC 61869-2 respectively shall be accepted. Notes: (i) VI, Relay, FPI, VPI should be of same make as that of RMU (OEM) (ii) An operator situated in front, lateral and rear (A-FLR 25kA – 1sec, downwards exhaust, for tank as well as cable compartment) of the RMU switchboard during an internal fault will not be exposed to the effects of arcing. Internal Arc Type Test Report for IAC AFLR 25 kA for 1 sec for both tank & cable box should have been for minimum 3 way / 3 Function RMU. (iii) Ring Main Units shall be manufactured by OEM Or Licensed partner of OEM (iv) All operations shall be from front of the RMU, including access to cable bushings , Bushings along the sides or the rear of the RMU are not acceptable. (v) VCB consist of trafu card for OTI/WTI/ Buchholz for alarm trip (vi) Dead short circuit operation of Vaccum interrupter should not be less then 50
Supply, installation, testing & commissioning of HT 33 KV, 3 phase, 50 cycles, totally enclosed metal clad SF6 Switchgear (Outdoor Breaker switch) having Rupturing capacity upto 250 MVA, overload and earth fault protection, ammeter, voltmeter and of rating upto 400 Amp complete all as specified and directed.
Supply, laying XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts 3 core, Earthed, grade cross sectional area of size 120 sqmm complete all as specified and directed.
S&F of aluminium conductor, steel reinforced HT overhead line of 11KV on 11 mtr steel pole with continous GI earth wire including earthing of poles cross arm insulator etc and ACSR conductor of size of 3 of 6/1/3.5 dog type, all as specified and directed.
S&F of cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of of size 120 sqmm all as specified and directed.
S&F Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of of size 120 sqmm all as specified and directed.
M&L for disc type polymer insulator along with suitable clamp assembly for fixing tension with tension clamp for conductor of working pressure 33000 volts, complete all as specified & directed.
M&L for pin type Polymer insulator mild steel spindle, two galvanised iron washers and one galvanised iron nut,150 mm height, 150 mm dia for 33000 volts grade complete all as specified and directed
S&L of tubing, medium grade, galvanised, 80 mm dia for cable protection with all fittings and fixed complete to walls and ceiling or laid in floors/road crossing all as specified and directed.
M&L for PCC 1:2:4 type B-2 (using 40mm graded crushed stone aggregate) in coping and mass concrete for poles including formwork cement concrete complete all as specified and directed
M&L for PCC 1:3:6 type C-2(using 40mm graded crushed stone aggregate) in foundation of Transformer below ground level etc, basement and mass concrete for pole including formwork cement concrete complete all as specified and directed.
M&L for PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) as in foundation of poles/structure frame etc, including formwork cement concrete complete all as specified and directed.
M&L for concrete graded stone aggregate using 20 mm grade using for laying to cover the area of MRS, Transformer all as specified and directed.
Supply, Install Testing & Commissioning of self supporting totally enclosed double door at front, LT feeder piller compartmentalised design, dust and varmin proof of size 1000 mm (Height) x 1000 mm (Length) x 450 mm (Width) suitable for 440 Volt 3 phase 4 wire system made out of 3.14mm thick CRCA sheet and built upon regid frame work having front and rear hinged doors with neoprence rubber gasket including danger plate, earthing strip point and, ventilation louvers at the rear side, bottom detachable gland plate complete with suitable size of Zinc/Cromium plated and nuts, bolts ;and washers etc. The pannel shall be synthetic enamelled painted and the control circuit diagram shall be with colour code solid conductor copper 1.5 sqmm cable for easy identification including incomming / outgoing cable holes at the bottom, complete after taking down the old unserviceable one. The Panel shall be emmbeded with 75 x 6 mm MS Angle Iron frame and to be grouted with PCC foundation (1:2:4 ) type B2 upto a height of 50 cm from normal ground level complete all as specified and directed by Engr in charge and comprising of the following:-
(a) Aluminium bus bar 800 amps - 04 Nos, supported with suitable size of heavy duty porcelin stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. (b) MCCB of 4 pole, fixed thermal setting of 400 amps with breaking capacity of 36 KA - 01 No (c) MCCB of 4 pole, fixed thermal setting of 200 amps with breaking capacity of 25 KA, - 02 Nos (d) MCCB of 4 pole, fixed thermal setting of capacity 63 amps with breaking capacity of 25 KA, - 01 No
Supply, install, testing and commissioning of cubical housing cabinet type LTpanel of size 2000 mm x 1000 mm x 450 mm outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openable from both front and rear side made out of 3.14 mm thick CRCA (Cold Rolled Cold Annealed) MS Sheet, Powder coated, CPRI approved and built upon 50 x 50 x 6 mm size angle iron frame work, having front and rear hinged doors, lifting lugs (2 Nos), earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts, spring and washers, complete after taking down the old unserviceable one. The cabinet and all members should be chemically treated with MSR solution for anticorrosive treatment. Necessary foundation work as required at site and comprisingfollowing:- BUS BAR (a) Electrolytic grade high conductivity TP&N solid copper bus bars, rated 800 amps supported at required intervals sleeved with heat shrinkable PVC sleevings. The bars shall be colour coded at required intervals for identification - 04 Nos
INDICATING DEVICES (a) LED Indicating lamps for Main Supply indicating R', Y' B' - 01 Set of 3 (b) Digital Voltmeter - 01 No (c)Current Transformer having Ratio 400/5, 15 VA - 01 Set of 3 (d) Digital Ammeter - 01 No CONTROLS (a) MCCB of 4 pole, fixed thermal setting of 400 amps with breaking capacity of 36 KA - 01 No (Incomer) (b) MCCB of 4 pole, fixed thermal setting of 200 amps with breaking capacity of 25 KA - 02 Nos (c)MCCB of 4 pole, fixed thermal setting of capacity 160 amps with breaking capacity of 25 KA - 02 Nos (d) MCCB of 4 pole, fixed thermal setting of capacity 100 amps with breaking capacity of 25 KA - 01 No
Excavation in trenches not exceeding 1.5 mtr wide and exceeding 1.5 mtr but n.exc 3.0 mtr in depth and getting out in any type of soil for taking up or laying of cable, foundation of poles, stay etc complete all as specified & directed. Note : Due care shall be taken while deciding cable route for excavation. However any damage to Signal, BSNL, MES cable water/sewage pipe or any other service while excavation will be made good by the contractor and cost of the same for jointing material & labour is deemed to be included in the cost of excavation.
Returning , filling in including spreading, levelling watering and well ramming in layers not exceeding 25cm thick, all as specified.
Removing surplus spoil to a distance not exceeding 50m and deposited where directed at a level not exceeding 1.50m from the starting point, all as specified.
Supplying and laying reinforced precast concrete cable cover, class EHV, type 1 with peak, size size 300 mm x 180mm x 40mm in trenches flat complete all as specified and directed.
M&L for sand cushioning to underground cables using new dry river sand laid in trenches 8cm thick below the cable and 15cm thick above the cable after laying and stretching the cable complete, punned to 18cm, complete all as specified and directed Note : Punned thickness of 18cms shall be measured for payment.
Supply and fixing of alumnium disc clamp suitable for fixing ACSR dog conductor with insulator, lightening arrestor and isolator etc complete all as specified and directed.
Supply and fixing of copper 'D' clamp suitable for fixing ACSR dog conductor with Transformer HT bush complete all as specified and directed.
Supply and fixing of pad clamp suitable for fixing ACSR dog conductor with etc complete all as specified and directed.
M&L for aluminium strip 25x3.15 mm with saddles and fixing screws etc for roof conductors and down conductors above ground all as specified and directed.
Supply, laying XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 33000 volts 3core, Earthed, grade cross sectional area of size 240 sqmm complete all as specified and directed.
S&F Cable jointing kit for 33 KV (Earthed) grade cable for outdor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of of size 240 sqmm all as specified and directed.
RAVI KUMAR
Sant Construction Co.
PROACH ASSOCIATES BUILDERS & ENGINEERS
vijay builders
Bidder Name
Sant Construction Co.
vijay builders
RAVI KUMAR
Electromechanics Engineers & Contractors
PROACH ASSOCIATES BUILDERS & ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .