Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹65.5 LAccepted-AOC 4TH FLOOR VOLTAS HOUSE A BLOCK DR BABASAHEB AMBEDKAR ROAD CHINCHPOKLI MUMBAI MAHARASHTRA 400033 | MUMBAI | MAHARASHTRA | 400033 | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹65.5 L+₹5,403 (0.08%)Rejected-Finance | L2 | Rejected-Finance SECOND LOWEST | |
| 3 | L3₹65.6 L+₹17,783 (0.27%)Rejected-Finance 53 VAISHAILI ENCLAVE SECTOR 9 INDIRA NAGAR LUCKNOW | LUCKNOW | L3 | Rejected-Finance HIGHEST |
Tender Value
₹65.7 L
EMD Value
₹1.3 L
Closing Date
1 Jul 2024, 3:00 pmClosed
Director CSIR IITR Lucknow
Vishvigyan Bhawan 31 MG Marg CSIR IITR Lucknow 226001
Retrofit work in cooling tower chilled water and hot water pipe lines of HVAC system Central AC Plant installed for Animal House at CRK campus of CSIR IITR Lucknow
2024_CSIR_197783_1
IITR/EME-17(08)/2024
Open Tender
Electrical Works
Item Rate
90 days
CRK campus of CSIR IITR Sarojani Nagar Lucknow
As per NIT and Tender Document
2 documents required · 2 mandatory
₹0
₹1.3 L
18 Dec 2024
10 Jun 2024
2 Jul 2024
10 Jun 2024
1 Jul 2024
10 Jun 2024
Amount
Condenser Water Piping: Supplying, fixing, testing and commissioning of condenser water pipes of following size of MS 'C' class along with necessary clamps, vibration isolators and fitings such as bends, tees etc., but excluding valves, strainers, gauges etc. adequately supported on rigid suppots duly painted/buried in ground exacavation and refilling etc., as per specification and as per specification and as required complete in all respect.
150 mm dia
125 mm dia
Insulated Valves: Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled ater plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Butterfly Valve (Mannual) with CI body SS disc nitrile rubber sheal & O-ring PN 16 pressure rating for chilled water/ hot eater circulation as specified
150 mm dia
80 mm dia
40 mm dia
Dismantling C.I pipes including excavation and refilling trenches after taking out the pipes, manually/ by mechanical means breaking lead caulked joints, melting of lead and making into blocks including stacking of pipes & lead at site within 50 meter lead as per direction of Engineer-in-charge.Upto 150 mm diameter
SITC of FRP induced draft cross/ counter flow, 2 to 4 fan as required, direct / gear driven, site erected cooling tower of capacity as mentioned below based on the parameters given below and complete with PVC fill, Louver, Drift Eliminator, Wheather Proof IP 55 TEFC Motor (IE2), Propeller Fan, FRP Basin with additional sump in the condensor water pipe line, Hot dip galvanised steel ladder, stainless steel hardware, float valves, nut, bolt, washer etc complete as required. (a)Designed Wet Bulb Temperature -28.3 degree C (b)Water inlet/ Outlet Temperature - 36.38 degree C/ 32.22 degree C (c) Cooling Tower Basin Height - 300.0 mm (d) 200 TR Cooling Tower
Condenser Water Piping: Supplying, fixing, testing and commissioning of condenser water pipes of following size of MS 'C' class along with necessary clamps, vibration isolators and fitings such as bends, tees etc., but excluding valves, strainers, gauges etc. adequately supported on rigid suppots duly painted/buried in ground exacavation and refilling etc., as per specification and as per specification and as required complete in all respect.
40 mm dia
80 mm dia
Insulated Valves: Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled ater plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Butterfly Valve (Mannual) with CI body SS disc nitrile rubber sheal & O-ring PN 16 pressure rating for chilled water/ hot eater circulation as specified 25 mm dia
Chilled Water/ Hot Water distribution piping: Supplying, laying / fixing, testing and commissoining of "C" class mild steel chilled water/hot water piping with insulation and all necessary fittings like bend, tees, reducers, flanges, supports and duly insulated with suitable materials with all accessories.
80 mm dia
100 mm dia
125 mm dia
Pot Strainer and having MS body, bolted cover, flanged ends, basket of stainless steel screen with 1.5 mm perforations and a permanent magnet for condenser water application complete with flanges, nuts-bolts, gasket etc., complete as required.150 mm dia
Replacement of Microprocessor controller of chiller and reprograming, recommissioning and testing of existing voltas make chiller complete as required.
Supply and fixing of PVC expansion tank of capacity 10,000 ltrs for make up of cooling tower to maintain flow of water during plant running with new foundation and its required connection complete as required.
Modification of CC foundation block as per new cooling tower with required accessories to complete the foundation as required.
Supply and fixing of suitable size MS Structure for new cooling towers 200 TR capacity complete as required.
Dismantling and removal of existing cooling towers with pipe and valves, civil foundation and excavation and removing underground pipe for cooling tower line and shifting the dismantled item by using hydra including rental charges of T&P and labour.
Modification of existing panel of starter panel as per new cooling tower complete as required.
Supply, laying S/U of 4 Core x10 Sq.mm XLPE Alluminium Armoured power cable from HVAC electrical panel to Cooling tower with necessary gland and aIluminium lug complete as required.
Less buy back cost of the salvage value of dismantled condensor pipe line, hot water pipe line, chilled water pipe line, cooling tower, valves, pot strainer, nut bolts including taking them out from the site complete with required labour, tools.
AMIT ELECTRICALS
KRISHNA REFRIGERATION
AMIT ELECTRICALS
KRISHNA REFRIGERATION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .