Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance UDHAMPUR | Admitted-Finance |
| 4 | Admitted-Finance 271 CIVIL LINE GURUGRAM GURUGRAM GURGAON HARYANA 122001 | GURUGRAM | HARYANA | 122001 | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹69,000
Closing Date
3 Jun 2023, 4:00 pmClosed
Executive Engineer Electric Division UdhampurJPDCL
Executive Engineer Electric Division UdhampurJPDCL
Creation of 250 KVA and 63 KVA Sub station alongwith erection of 11 KV Line on 9 mtr. ST poles, 30mm sq. ACSR weasel Conductor at WSS Samole under JJM
2023_PDD_212040_1
ED/Udh/07 of 2023-24 dt. 13-05-2023
Open Tender
Electrical Works
Turn-key
120 days
In District Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Electric Division UdhampurJPDCL
₹69,000
25 Jul 2023
13 May 2023
6 Jun 2023
13 May 2023
3 Jun 2023
13 May 2023
13 May 2023 - 17 May 2023
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm² ACSR Conductor at WSS Samole (Stage Zero).
9 mtr. Long ST Pole (ST-410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30mm² ACSR conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for creation of 63 KVA Sub stn. at WSS Samole Stage Zero.
11/0.433 KV, 3-phase distribution Transformer 63 KVA with Bimetallic Terminal Connectors Energy Level-2 Aluminium Wound, & with LV Cable box having detachable Aluminium Gland plate
Gapless surge Arestor, 9 kv, 10 KA , LA with polymer housing stn. Type
11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
11 KV Horn gap fuse set 3 phase 200 A
120mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type
9 mtr. Long pole (ST-410 SP33)
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
GI Channel /Angle/flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mm for connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover
11 KV Poloymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm
LT distribution box for 63 KVA DTR with MCCB for incomer and SFU's for outgoing circuits
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
Danger Plates with Clamps
GI Barbed wire for Anticlimbing
3-Phase 4 Wire LT Prodigy Meter with Box.
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Painting of ST poles 9 mtr. Long with 1 coat of Red oxide & 2 coat of Aluminum paint.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 3 Phase 4 Wire LT line on 8 mtr. ST poles at WSS Samole (Stage Zero).
8 mtr. Long ST poles (ST-410 SP15)
GI M Clamps for shackle insulator
100mm² ACSR Dog Conductor
Shackle insulator
Galvinized Nuts and Bolts.
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20mm 2.5 mtr. Long through GI Strip
Painting of 8 mtr. Long ST poles with two coat of Aluminium paint
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm² ACSR Conductor at WSS Samole (Stage-Ist).
9 mtr. Long ST Pole (ST-410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30mm² ACSR conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 9 mtr ST poles with 1 coat of Red oxide Paint.
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for creation of 250 KVA Substation at WSS Samole Stage-Ist.
11/0.433 KV, 3-phase distribution Transformer 250 KVA with Bimetallic Terminal Connectors Energy Level-2 Copper Wound, & with LV Cable box having detachable Aluminium Gland plate
Gapless surge Arestor, 9 kv, 10 KA , LA with polymer housing stn. Type
11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
11 KV Horn gap fuse set 3 phase 200 A
300mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type
9 mtr. Long ST pole (ST-410 SP33)
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
GI Channel /Angle/flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mm for connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover
11 KV Poloymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm
LT distribution box for 250 KVA DTR with MCCB for incomer and SFU's for outgoing circuits
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
Danger Plates with Clamps
GI Barbed wire for Anticlimbing
3-phase HT Trivector meter with CT PT Unit
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Painting of ST poles 9 mtr. long with 1 coat of Red oxide & 2 coat of Al. paint
M/S VAISHNO TRADERS
VEENA CONSTRUCTION CO.
M R ENGINEERS & TRADERS
power control system
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .