Amount
Providing Primary light point wiring using 2 x 2.5 sq mm stranded copperFRLS PVC insulated wires for phase and neutral and 1.5 sq mm green for earth laid in 25 mm Dia. PVC MMS conduit Conduits shall be cleated to the surface/walls with saddles and spacers as per engg practice. Rate to include Switches, wires. complete and civil works and making good but excluding conduits and modular boxes. For point wiring in areas with false ceiling, the point shall be terminated above the false ceiling next to the lighting fixture.(SB Controlled Primary light Points) Make of Material: PVC Conduit:- Anchor,Ravindra, Polycab, Paraflex. Modular Switches:- Crabtree (Athena), Legrand (Myrus) L&T (Englaze),Panasonic (vision), MK (elements). Wires:- Havells,Anchor, Standard,Polycab,HPL,KEI,Paraflex
Looping above light point ( say secondary light point using 3 x 1.5mm2 stranded copper/FRLS PVC insulated wires laid in 25 mm Dia. PVC MMS condu it Conduits shall be cleated to the surface/walls with saddles and spacers as per engg practice. Rate to include Switches, wires. complete and civil works and making good but excluding conduits and modular boxes. . For point wiring in areas with false ceiling, the point shall be terminated above the false ceiling next to the lighting fixture.(SB Controlled Secondary light Points) Make of Material: PVC Conduit:- Anchor,Ravindra, Polycab, Paraflex. Modular Switches:- Crabtree (Athena), Legrand (Myrus) L&T (Englaze),Panasonic (vision), MK (elements). Wires:- Havells, Anchor, Standard, Polycab,HPL,KEI,Paraflex
Providing Primary light point wiring using 2 x 2.5mm2 stranded copper/FRLS PVC insulated wires for phase and neutral and 1.5 sq mm green for earth laid in 25 mm Dia. PVC MMS conduit Conduits shall be cleated to the surface/walls with saddles and spacers as per engg practice. Rate to include Switches, wires. complete and civil works and making good but excluding conduits and modular boxes. For point wiring in areas with false ceiling, the point shall be terminated above the false ceiling next to the lighting fixture.(DB Controlled Primary light Points) Make of Material: PVC Conduit:- Anchor,Ravindra, Polycab, Paraflex. Modular Switches:- Crabtree (Athena), Legrand (Myrus) L&T (Englaze),Panasonic (vision), MK (elements). Wires:- Havells, Anchor, Standard, Polycab,HPL,KEI,Paraflex
Looping above light point ( say secondary light point using 3 x 1.5mm2 stranded copper/FRLS PVC insulated wires laid in 25 mm Dia. PVC MMS conduit Conduits shall be cleated to the surface/walls with saddles and spacers as per engg practice. Rate to include Switches, wires. complete and civil works and making good but excluding conduits and modular boxes. For point wiring in areas with false ceiling, the point shall be terminated above the false ceiling next to the lighting fixture.(DB Controlled Secondary light Points)
Wiring for Light /Power Plug with 2 x 4 sq.mm FRLS PVC Insulated Copper Conductor single core cable in surface/Recessed medium class PVC Conduit along with 1 No. 4 sq.mm FRLS PVC Insulated copper conductor single core cable for loop earthing as required. Make of Material: PVC Conduit:- Anchor, Ravindra, Polycab, Paraflex. Modular Switches:- Crabtree (Athena), Legrand (Myrus) L&T (Englaze),Panasonic (vision), MK (elements). Wires:- Havells, Anchor, Standard, Polycab, HPL, KEI, Paraflex
Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in surface/Recessed medium class PVC conduit as required. Make of Material: PVC Conduit:- Anchor, Ravindra, Polycab, Paraflex. Modular Switches:- Crabtree (Athena), Legrand (Myrus) L&T (Englaze),Panasonic (vision), MK (elements). Wires:- Havells, Anchor, Standard, Polycab, HPL, KEI, Paraflex
2 X 2.5 SQ.MM + 1 X 2.5 SQ.MM EARTH WIRE
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
Supplying and Fixing following modular switch/socket on the existing modular plate and switch box including connections but excluding modular plate etc. as required
5/6 amps switch
3 Pin 5/6 amp socket outlet
Supply and fixing modular blanking plate on the existing modular plate
Supply and fixing two module stepped type electronic fan regulator on the existing modular plate as required
Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess,including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch,connection,painting etc. as required.
Supplying and fixing following way,Prewired TP&N PPI Distribution Board of Sheet Steel for 415 Volts on surface/ Recess complete with Ready to use DBs - Provided with 100A insulated phase bus-bars,neutral bar/s with shroud/s, earth bar/s , sticking saddles , cement spill protector ,color-coded interconnecting wire set , cable ties , blanking plates and circuit identification labels.The D.B should be IK-09 Compliant.(The Cost of D.B is without MCB's)
4 way (8 Module Incomer),(2+2+2 incomer dp rcbo), (4+4+4 sp MCB's o/g's)
6 way (8 Module Incomer),(2+2+2 incomer dp rcbo), (4+4+4 sp MCB's o/g's)
Supplying and Fixing following Rating ,Four Pole ,415 Volts ,MCB 10 KA in the existing MCB DB complete with connections,testing and commissioning as required
Supply and Fixing of Double Pole RCBO with 100 ma Sensitivity of the following ratings. Make of Material: Crabtree (XPRO), Legrand (DX), ABB (S200), Schneider (Acti-9).
Supply and fixing of 6-32 Amp 240 volts C-series single pole MCB in the existing DB's.Make of Material: Crabtree (XPRO), Legrand (DX), ABB (S200), Schneider (Acti-9).
Supply and Fixing Single Pole Blanking Plate in the Existing MCB DB complete as Required
Supplying and Laying of B-Class 100 mm Dia Size G.I Pipe under the Road/Floor not less than 1 mtr below the Ground Level including cutting the Road/Floor and making Good the same as required. Make:- Jindal/Suraprakash
Supplying,Installation and Testing of 75 mm Cu. Pipe Filled with Crystalline conductive Mixture with Copper Strip of Size 40 mm x 6 mm of Length 2 mtr with Ecofriendly Backfill Compound 50 Kg.(2 Nos for Panel and 2 Nos for UPS for Fire Alarm Syatem)Makes:- Genus/Ashlok/G-MAXX--Earth pit chamber (300mm x 300mm) with CI cover for the above.Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value.
Providing and Fixing 25 mm x 5 mm Copper Strip in 40 mm dia. G.I Pipe FRL Earth Electrode including connection with Brass nut ,bolt,spring,washer,excavation and refilling etc. as required.
SITC of 1400 mm ceiling fan,Capacitor type suitable for low voltage operation including wiring the down rods of standard length (Upto 30 cm)with 1.5 sq.mm FR PVC insulated,copper conductor,single core cable including providing and fixing phenolic laminated sheet cover on the Fan Box etc as Required. Make-Panasonic,Usha, Havells, Orient,Eon,Halonix.
SITC of pre-wired Surface Mounted LED Ceiling Light Fitting including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required Make-Havells,Panasonic,Halonix, Philips,Eon,Jaquar.
SITC of pre-wired Recess Mounted LED Down Lighter Light Fitting including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required Make-Havells,Panasonic,Halonix, Philips,Eon,Jaquar.
SITC of pre-wired Surface Mounted LED Ceiling Downlighter Light Fitting including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required Make-Havells,Panasonic,Halonix, Philips,Eon,Jaquar.
SITC of pre-wired Surface Mounted LED Ceiling Down lighter Light Fitting including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required Make-Havells,Panasonic,Halonix, Philips,Eon, Jaquar.
Supply of AC 230/250 Volts, 50 Hz 300 mm exhaust fan with louveres of including connection etc. complete as required. Make-Panasonic,Usha, Havells, Orient,Eon,Halonix.
Supplying,Installation,Testing and Commissioning of Cubical Type LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars,Interlocking etc. as required as per the Following Description.(Main L.T Panel)
MCCB 160 Amps 4 P with Breaking Capacity 25 KA(Icu=Ics=100%)(2 Nos)
Power Contactor 4 P 200 Amps(2 Nos)
Indicating Lamps RYB (2 Nos)
Voltmeter-0-500 Volts(2 Nos)
Ammeter(0-200 A)(2 Nos)
Current Transformer 200/5 A 10 VA Burden, Class-1(2 Nos)
Aluminium Busbar 200 Amps FP E-91 E Grade Electrolytic Aluminium
OUTGOINGS
MCCB 63 Amps TP+N with Breaking Capacity 25 KA(Icu=Ics=100%) with T.M release(5 Nos)
MCCB 40 Amps TP+N with Breaking Capacity 25 KA(Icu=Ics=100%) with T.M release(3 Nos)
Indicating Lamps ON OFF TRIP(8 Nos)
Load Bearing Members to be made out of 2.0 mm CRCA Sheet.
Supplying,Installation,Testing and Commissioning of Cubical Type LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars,Interlocking etc. as required as per the Following Description.(UPS/Emergency Panel)
INCOMER
MCB 63 Amps 4 P with Breaking Capacity 10ka(1 Nos)
Indicating Lamps RYB (1 Nos)
Voltmeter-0-500 Volts(1 Nos)
Ammeter(0-100 A)(1 Nos)
Current Transformer 100/5 A 10 VA Burden, Class-1(1 Nos)
Aluminium Busbar 100 Amps FP E-91 E Grade Electrolytic Aluminium
OUTGOINGS
MCB 63 Amps TP+N 10 Ka(3 Nos)
MCB 40 Amps TP+N 10 Ka(3 Nos)
Indicating Lamps ON OFF TRIP(6 Nos)
Load Bearing Members to be made out of 2.0 mm CRCA Sheet.
Supplying,Installation,Testing and Commissioning of 10 KVA UPS with 3 Phase input and 3 Phase Output with 30 min. Back up as per the satisfaction of the Engineer incharge APC,Sukam, Exide, Microtek
Supplying and Laying of 160mm/136mm 1 No. DWC High Density Poly ethylene Pipe having Corrugation on Outer wall and Plain surface inner wall Conforming to IS: 14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cable Directly in Ground at a Depth of 50 CM including excavation and Refelling the Trench Etc.as Required .
Supplying and Laying of 3.5C 95 sqmm PVC/XLPE insulated and PVC Sheathed /XLPE Power Cable of 1.1 KV Grade of Following Sizes in the existing RCC/Hume/DWC/Stone ware/Metal Pipe as Required.
Supply and Making end Termination with Brass Compression Gland and Aluminium Lugs for the 3.5C 95sqmm of PVC insulated and PVC Sheathed/XLPE Aluminium Conductor Cable of 1.1 KV Grade as Required
Providing, fixing supplying, termination & certification of Telephone,Internet networking at Library Block . The item mentioned shall include the cost for laying Cat 6 UTP wire of in existing conduits for the wiring & it shall be such that each point has a dedicated single CAT 6 wire from the wall outlet to the patch panel.The rates quoted shall include the cost of termination of CAT6 cable in the wall sockets & patch panel including the cost of certification by network engineer using a penta-scanner , ferrulling of every point on both sides the contractor will have to provide the network certification in writing. Nothing extra shall be paid for on account of termination, crimping, certification etc. complete in all respects as desired by Engineer Incharge. The following items will be got exectued as under:-
Supplying,Installation,Testing and Commissioning of I/O Modules Complete with Box,RJ-45 Socket,Front Plate as per the Satisfaction of the Engineer Incharge. (SCHNEIDER/ LEGRAND)(FOR TELEPHONE AND INTERNET)
Supplying and Fixing of 25mm PVC Conduit along with Accessories in surface/recess including painting in case of surface conduit,cutting the wall and making good the same in case of recessed conduit as required.
Supplying and Drawing of UTP4 pair CAT-6 LAN cable in the existing surface/Recessed Steel/PVC Conduit as required .
Supply and fixing of 100KVA AVR
Provision for installation of Heavy Duty RO Water purifier with storage tank (As per LMR)-3M
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .