Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.5 CrAccepted-AOC 13 29 3RD FLOOR EAST PATEL NAGAR NEW DELHI 110 008 | WEST | DELHI | 110008 | ₹1.5 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹1.6 Cr+₹6.0 L (3.94%)Rejected-Finance BASEMENT PLOT NO 17 4657 21 ANSARI ROAD CENTRAL DELHI NEW DELHI 110002 | CENTRAL DELHI | DELHI | 110002 | ₹1.6 Cr+₹6.0 L (3.94%) | L2 | Rejected-Finance other than L1 |
| 3 | L3₹1.6 Cr+₹8.9 L (5.85%)Rejected-Finance 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | ₹1.6 Cr+₹8.9 L (5.85%) | L3 | Rejected-Finance other than L1 |
| 4 | L4₹1.6 Cr+₹11.9 L (7.78%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | ₹1.6 Cr+₹11.9 L (7.78%) | L4 | Rejected-Finance other than L1 |
| 5 | L5₹1.7 Cr+₹20.8 L (13.6%)Rejected-Finance | ₹1.7 Cr+₹20.8 L (13.6%) | L5 | Rejected-Finance other than L1 |
Tender Value
Refer Docs
EMD Value
₹2.9 L
Closing Date
26 Oct 2020, 6:00 pmClosed
CWE NO 2
CWE NO 2 DELHI CANTT
ADDN / ALTN AND IMPROVEMENT OF COMMERCIAL POWER TRANSFORMER AND RMUs / VCBs AT BASE HOSPITAL UNDER GE (E/M) BASE HOSP, DELHI CANTT-10
2020_MES_345796_2
CWE/BH-05/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
DELHI CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
GE (E/M) BASE HOSPITAL
₹2.9 L
Yes
4 Dec 2020
19 Sept 2020
28 Oct 2020
19 Sept 2020
26 Oct 2020
14 Oct 2020
Amount
Supply and fixing of 11 KV , 630 Amps, outdoor type Compact switch gear Ring Main unit Extensible type " CCV+ M " having 02 Nos. Load Break Switches and 01 Nos Vacuum circuit breaker all Motor Operated modules ( Total number of modules 3 Pcs + 1 Metering modules) ,with IP class as IP54 for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foudnation work as recommended by manufactuer along with bottom cable entry and front cable termination complete all as specified and directed with following specification:- Note : (a) RMU shall be IAC AFLR 20kA/1s tested with gas release from top of the Switchgear to ensure utmost operator and pedestrian safety .Test report(from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU
(d) RMU shall be completely motorized with all SCADA contacts terminated on a designated Terminal Block for easy Take off by the SCADA team for integration.Same contacts shall be clearly mapped in the Engineering drawings for approval with designated TB nos. for easy identification and integration. (e) RMU tank shall be of 304 grade ,Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (f) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (g) Earth switch should be on line side and should have making capacity. (h) Contractor shall purchase RMU directly from OEM and necessary factory inspection shall be arranged before dispatch RMU from OEM premises. The testing officer shall be nominated by accepting officer after written confirmation received from contractor for RMU is ready for testing with all respect as per CA provision. All testing and inspection shall be carried out in OEM premises in presence of testing officer and contractor. The joint inspection report shall be submitted after completion of testing. All expenditure in this respect should be bore by contractor and inclusive in quoted rate. No other charges admissible to contractor in this respect after ward. Note :- The rates inclusive of making Platform as per OEM recommandatiion made with brickes and necessary PPC at Bottom and Top and plastering complete all as recommended by Engg-in-charge
(A) 630A motorised Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity-2 nos. Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38kV Impulse withstand voltage - 75KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Set of 03nos. Ring Core Metering CTs 150-300 - 02 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos
(B) 630A motorised VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity-1 nos. operated 630 A Vacuum circuit breaker having spring stored mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 21KA/ 3 sec Making Capacity - 52.5 kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38KV Impulse withstand voltage - 98KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Green(ON)/Red(OFF) push buttons to operate VCB. 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. (C) Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Right angle non-touch proof Termination boots - 1 Set (R,Y,B)
(D) Stored energy mech. for motor operation - 01 Nos Control voltage, motor operation 24 V DC - 01 Nos Self Powered OC+EF Protection Relay - 01 Nos Set of 03nos. Ring Core Protection CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, 10P10 - 01 Nos Set of 03nos. Ring Core Metering CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos Metering Module Type M SafePlus M is an air insulated metering module.
(E) Set of 03nos. single-phase potential transformers having ratio 11kV/rt3:110V/rt3, 25VA, Class 1.0 with HRC fuses for protection on primary side and MCBs for protection on secondary side.- 01 Nos Space Heater (230VAC)- 01 Nos Low Voltage Box inside the metering enclosure for mounting:- 01 Nos • Multifunction Meter for each feeder • CSPC make Under/Over Voltage Relay • 2x12VDC Battery+Charger scheme • R-Y-B Phase Indication Additional equipment delivered separately or mounted in respective panel. Set of Coupling busbars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle- 01 Nos
Supply and fixing of 11 KV , 630 Amps, outdoor type Compact switch gear Ring Main unit Extensible type " CCCCC+ M " having 05 Nos. Load Break Switches Motorised Operated ( Total number of modules 5 Pcs + 01 Pcs Metering module ) , with IP class as IP54 for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foudnation work as recommended by manufactuer along with bottom cable entry and front cable termination complete all as specified and directed with following specification:- Note : (a) RMU shall be IAC AFLR 20kA/1s tested with gas release from top of the Switchgear to ensure utmost operator and pedestrian safety .Test report(from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU
(d) RMU shall be completely motorized with all SCADA contacts terminated on a designated Terminal Block for easy Take off by the SCADA team for integration.Same contacts shall be clearly mapped in the Engineering drawings for approval with designated TB nos. for easy identification and integration. (e) RMU tank shall be of 304 grade ,Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (f) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (g) Earth switch should be on line side and should have making capacity. (h) Contractor shall purchase RMU directly from OEM and necessary factory inspection shall be arranged before dispatch RMU from OEM premises. The testing officer shall be nominated by accepting officer after written confirmation received from contractor for RMU is ready for testing with all respect as per CA provision. All testing and inspection shall be carried out in OEM premises in presence of testing officer and contractor. The joint inspection report shall be submitted after completion of testing. All expenditure in this respect should be bore by contractor and inclusive in quoted rate. No other charges admissible to contractor in this respect after ward. Note :- The rates inclusive of making Platform as per OEM recommandatiion made with brickes and necessary PPC at Bottom and Top and plastering complete all as specified and directed Engg-in-charge
(A) 630A Module Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity-5 nos. Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38kV Impulse withstand voltage - 75KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Set of 03nos. Ring Core Metering CTs of ration 40-80A - 01 Nos and 150-300 - 02 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos
(B) Metering Module Type M SafePlus M is an air insulated metering module. Set of 03nos. single-phase potential transformers having ratio 11kV/rt3:110V/rt3, 25VA, Class 1.0 with HRC fuses for protection on primary side and MCBs for protection on secondary side.- 01 Nos Space Heater (230VAC)- 01 Nos Low Voltage Box inside the metering enclosure for mounting:- 01 Nos • Multifunction Meter for each feeder • CSPC make Under/Over Voltage Relay • 2x12VDC Battery+Charger scheme • R-Y-B Phase Indication Additional equipment delivered separately or mounted in respective panel. Set of Coupling busbars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle- 01 Nos
Supply and fixing of 11 KV , 630 Amps, outdoor type Compact switch gear Ring Main unit Extensible type motorised " CCCCC+V+ M " having 05 Nos. Load Break Switches and 01 Nos Vacuum circuit breaker,Motor Operated ( Total number of modules 5 Pcs load break switch + 1 Pcs Vaccum circuit breaker + 1 Pcs metering unit ) , with IP class as IP54 for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foudnation work as recommended by manufactuer along with bottom cable entry and front cable termination complete all as specified and directed with following specification:- Note : (a) RMU shall be IAC AFLR 20kA/1s tested with gas release from top of the Switchgear to ensure utmost operator and pedestrian safety .Test report(from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU
(d) RMU shall be completely motorized with all SCADA contacts terminated on a designated Terminal Block for easy Take off by the SCADA team for integration.Same contacts shall be clearly mapped in the Engineering drawings for approval with designated TB nos. for easy identification and integration. (e) RMU tank shall be of 304 grade ,Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (f) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (g) Earth switch should be on line side and should have making capacity. (h) Contractor shall purchase RMU directly from OEM and necessary factory inspection shall be arranged before dispatch RMU from OEM premises. The testing officer shall be nominated by accepting officer after written confirmation received from contractor for RMU is ready for testing with all respect as per CA provision. All testing and inspection shall be carried out in OEM premises in presence of testing officer and contractor. The joint inspection report shall be submitted after completion of testing. All expenditure in this respect should be bore by contractor and inclusive in quoted rate. No other charges admissible to contractor in this respect after ward. Note :- The rates inclusive of making Platform as per OEM recommandatiion made with brickes and necessary PPC at Bottom and Top and plastering complete all as specified and directed by Engg-in-charge
(A) 630A motorised Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity-5 nos. Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38kV Impulse withstand voltage - 75KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Set of 03nos. Ring Core Metering CTs of ration 150-300 - 05 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos
(B) 630A motorised VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity-1 nos. 630 A Vacuum circuit breaker having spring stored mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 21KA/ 3 sec Making Capacity - 52.5 kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38KV Impulse withstand voltage - 98KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Green(ON)/Red(OFF) push buttons to operate VCB. 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. (C) Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Right angle non-touch proof Termination boots - 1 Set (R,Y,B)
(D) Stored energy mech. for motor operation - 01 Nos Control voltage, motor operation 24 V DC - 01 Nos Self Powered OC+EF Protection Relay - 01 Nos Set of 03nos. Ring Core Protection CTs of ration 40-80A - 01 Nos and 150-300 - 02 Nos as per feeder load, 2.5VA, 10P10 - 01 Nos Set of 03nos. Ring Core Metering CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos Metering Module Type M SafePlus M is an air insulated metering module.
(E) Set of 03nos. single-phase potential transformers having ratio 11kV/rt3:110V/rt3, 25VA, Class 1.0 with HRC fuses for protection on primary side and MCBs for protection on secondary side.- 01 Nos Space Heater (230VAC)- 01 Nos Low Voltage Box inside the metering enclosure for mounting:- 01 Nos • Multifunction Meter for each feeder • CSPC make Under/Over Voltage Relay • 2x12VDC Battery+Charger scheme • R-Y-B Phase Indication Additional equipment delivered separately or mounted in respective panel. Set of Coupling busbars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle- 01 Nos
Supply and fixing of 11 KV , 630 Amps, outdoor type Compact switch gear Ring Main unit Extensible type motorised " CCCCC+CV+M (nomenclature may change based on make) " having 06 Nos. Load Break Switches and 01 Nos Vacuum circuit breaker, ( Total number of modules 6 Pcs Load Break Switches and 01 Nos Vacuum circuit breaker and 01 No Metering module) , with IP class as IP54 for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foudnation work as recommended by manufactuer along with bottom cable entry and front cable termination complete all as specified and directed with following specification:- Note : (a) RMU shall be IAC AFLR 20kA/1s tested with gas release from top of the Switchgear to ensure utmost operator and pedestrian safety .Test report(from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU.
(c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU shall be completely motorized with all SCADA contacts terminated on a designated Terminal Block for easy Take off by the SCADA team for integration.Same contacts shall be clearly mapped in the Engineering drawings for approval with designated TB nos. for easy identification and integration. (e) RMU tank shall be of 304 grade ,Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (f) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (g) Earth switch should be on line side and should have making capacity. (h) Contractor shall purchase RMU directly from OEM and necessary factory inspection shall be arranged before dispatch RMU from OEM premises. The testing officer shall be nominated by accepting officer after written confirmation received from contractor for RMU is ready for testing with all respect as per CA provision. All testing and inspection shall be carried out in OEM premises in presence of testing officer and contractor. The joint inspection report shall be submitted after completion of testing. All expenditure in this respect should be bore by contractor and inclusive in quoted rate. No other charges admissible to contractor in this respect after ward. Note :- The rates inclusive of making Platform as per OEM recommandatiion made with brickes and necessary PPC at Bottom and Top and plastering complete all as specified and directed Engg-in-charge
(A) 630A motorised Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity-6 nos. Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38kV Impulse withstand voltage - 75KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Set of 03nos. Ring Core Metering CTs of ration 150-300 - 06 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos
(B) 630A motorised VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity-1 nos. 630 A Vacuum circuit breaker having spring stored mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 21KA/ 3 sec Making Capacity - 52.5 kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38KV Impulse withstand voltage - 98KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Green(ON)/Red(OFF) push buttons to operate VCB. 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. (C) Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Right angle non-touch proof Termination boots - 1 Set (R,Y,B)
(D) Stored energy mech. for motor operation - 01 Nos Control voltage, motor operation 24 V DC - 01 Nos Self Powered OC+EF Protection Relay - 01 Nos Set of 03nos. Ring Core Protection CTs of ration 40-80A - 01 Nos and 150-300 - 02 Nos as per feeder load, 2.5VA, 10P10 - 01 Nos Set of 03nos. Ring Core Metering CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos Metering Module Type M SafePlus M is an air insulated metering module.
(E) Set of 03nos. single-phase potential transformers having ratio 11kV/rt3:110V/rt3, 25VA, Class 1.0 with HRC fuses for protection on primary side and MCBs for protection on secondary side.- 01 Nos Space Heater (230VAC)- 01 Nos Low Voltage Box inside the metering enclosure for mounting:- 01 Nos • Multifunction Meter for each feeder • CSPC make Under/Over Voltage Relay • 2x12VDC Battery+Charger scheme • R-Y-B Phase Indication Additional equipment delivered separately or mounted in respective panel. Set of Coupling busbars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle- 01 Nos
Supply and fixing of 11 KV , 630 Amps, outdoor type Compact switch gear Ring Main unit Extensible type motorised " CCCV+ M " having 03 Nos. Load Break Switches and 01 Nos Vacuum circuit breakerand 01 No Metering moduel ( 03 Nos. Load Break Switches and 01 Nos Vacuum circuit breakerand 01 No Metering moduel ) , with IP class as IP54 for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foudnation work as recommended by manufactuer along with bottom cable entry and front cable termination complete all as specified and directed with following specification:- Note : (a) RMU shall be IAC AFLR 20kA/1s tested with gas release from top of the Switchgear to ensure utmost operator and pedestrian safety .Test report(from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU.
(c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU shall be completely motorized with all SCADA contacts terminated on a designated Terminal Block for easy Take off by the SCADA team for integration.Same contacts shall be clearly mapped in the Engineering drawings for approval with designated TB nos. for easy identification and integration. (e) RMU tank shall be of 304 grade ,Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (f) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (g) Earth switch should be on line side and should have making capacity. (h) Contractor shall purchase RMU directly from OEM and necessary factory inspection shall be arranged before dispatch RMU from OEM premises. The testing officer shall be nominated by accepting officer after written confirmation received from contractor for RMU is ready for testing with all respect as per CA provision. All testing and inspection shall be carried out in OEM premises in presence of testing officer and contractor. The joint inspection report shall be submitted after completion of testing. All expenditure in this respect should be bore by contractor and inclusive in quoted rate. No other charges admissible to contractor in this respect after ward. Note :- The rates inclusive of making Platform as per OEM recommandatiion made with brickes and necessary PPC at Bottom and Top and plastering complete all as specified and directed by Engg-in-charge.
(A) 630A motorised Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity-3 nos. Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38kV Impulse withstand voltage - 75KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Set of 03nos. Ring Core Metering CTs of ration 150-300 - 03 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos
(B) 630A motorised VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity-1 nos. 630 A Vacuum circuit breaker having spring stored mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 21KA/ 3 sec Making Capacity - 52.5 kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38KV Impulse withstand voltage - 98KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Green(ON)/Red(OFF) push buttons to operate VCB. 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. (C) Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Right angle non-touch proof Termination boots - 1 Set (R,Y,B)
(D) Stored energy mech. for motor operation - 01 Nos Control voltage, motor operation 24 V DC - 01 Nos Self Powered OC+EF Protection Relay - 01 Nos Set of 03nos. Ring Core Protection CTs of ration 40-80A - 01 Nos and 150-300 - 02 Nos as per feeder load, 2.5VA, 10P10 - 01 Nos Set of 03nos. Ring Core Metering CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos Metering Module Type M SafePlus M is an air insulated metering module.
(E) Set of 03nos. single-phase potential transformers having ratio 11kV/rt3:110V/rt3, 25VA, Class 1.0 with HRC fuses for protection on primary side and MCBs for protection on secondary side.- 01 Nos Space Heater (230VAC)- 01 Nos Low Voltage Box inside the metering enclosure for mounting:- 01 Nos • Multifunction Meter for each feeder • CSPC make Under/Over Voltage Relay • 2x12VDC Battery+Charger scheme • R-Y-B Phase Indication Additional equipment delivered separately or mounted in respective panel. Set of Coupling busbars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle- 01 Nos
Supply and fixing of 11 KV , 630 Amps, outdoor type Compact switch gear Ring Main unit Extensible type Motorised " CCCVV+ (nomenclature may change based on make) " having 03 Nos. Load Break Switches , 02 Nos Vacuum circuit breaker and 01 No Metering Module , ( Total number of modules 03 Nos. Load Break Switches , 02 Nos Vacuum circuit breaker and 01 No Metering Module) , with IP class as IP54 for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foudnation work as recommended by manufactuer along with bottom cable entry and front cable termination complete all as specified and directed with following specification:- Note : (a) RMU shall be IAC AFLR 20kA/1s tested with gas release from top of the Switchgear to ensure utmost operator and pedestrian safety .Test report(from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU.
(c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU shall be completely motorized with all SCADA contacts terminated on a designated Terminal Block for easy Take off by the SCADA team for integration.Same contacts shall be clearly mapped in the Engineering drawings for approval with designated TB nos. for easy identification and integration. (e) RMU tank shall be of 304 grade ,Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (f) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (g) Earth switch should be on line side and should have making capacity. (h) Contractor shall purchase RMU directly from OEM and necessary factory inspection shall be arranged before dispatch RMU from OEM premises. The testing officer shall be nominated by accepting officer after written confirmation received from contractor for RMU is ready for testing with all respect as per CA provision. All testing and inspection shall be carried out in OEM premises in presence of testing officer and contractor. The joint inspection report shall be submitted after completion of testing. All expenditure in this respect should be bore by contractor and inclusive in quoted rate. No other charges admissible to contractor in this respect after ward. Note :- The rates inclusive of making Platform as per OEM recommandatiion made with brickes and necessary PPC at Bottom and Top and plastering complete all as specified and directed by Engg-in-charge.
(A) 630A motorised Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity-3 nos. Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38kV Impulse withstand voltage - 75KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Set of 03nos. Ring Core Metering CTs of ration 150-300 - 03 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos
(B) 630A motorised VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity-2 nos. 630 A Vacuum circuit breaker having spring stored mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 21KA/ 3 sec Making Capacity - 52.5 kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38KV Impulse withstand voltage - 98KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Green(ON)/Red(OFF) push buttons to operate VCB. 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. (C) Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Right angle non-touch proof Termination boots - 1 Set (R,Y,B)
(D) Stored energy mech. for motor operation - 01 Nos Control voltage, motor operation 24 V DC - 01 Nos Self Powered OC+EF Protection Relay - 01 Nos Set of 03nos. Ring Core Protection CTs of ration 40-80A - 02 Nos and 150-300 - 02 Nos as per feeder load, 2.5VA, 10P10 - 01 Nos Set of 03nos. Ring Core Metering CTs of ration 40-80A - 02 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos Metering Module Type M SafePlus M is an air insulated metering module.
(E) Set of 03nos. single-phase potential transformers having ratio 11kV/rt3:110V/rt3, 25VA, Class 1.0 with HRC fuses for protection on primary side and MCBs for protection on secondary side.- 01 Nos Space Heater (230VAC)- 01 Nos Low Voltage Box inside the metering enclosure for mounting:- 01 Nos • Multifunction Meter for each feeder • CSPC make Under/Over Voltage Relay • 2x12VDC Battery+Charger scheme • R-Y-B Phase Indication Additional equipment delivered separately or mounted in respective panel. Set of Coupling busbars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle- 01 Nos
Supply, installation, testing and commissioning of outdoor type 200 kVA Compact Package Substation, “Non walk in type” fabricated by GI Steel shall house having modular construction of Galvanized Sheet Steel. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP 23 degree of protection for Transformer compartment. The enclosure exterior shall be powder coated. Enclosure should have slant roof suitable to avoid water. Each compartment will be provided with the door and pad locking arrangement. The Compartment illumination lamp with door operated switch shall be provided for each compartment, including PCC foundation at the hight of 3 m as recommended by manufacturerhave complete all as specified and directed with following equipments:- Note : (a) CSS shall be tested for IAC AB for 1 sec, considering utmost safety of Operator and pedestrian. (b) CSS ,RMU,LT Switchgear ,Vacuum Interrupter shall be of same make as CSS OEM to ensure life cycle optimization. (c) CSS shall be supplied by OEM only and not their authorized system integrators. (d) Contractor shall purchase CSS containing RMU directly from OEM necessary factory inspection shall be arranged before dispatch CSS from OEM premises. The testing officer shall be nominated by accepting officer after written confirmation received from contractor for CSS is ready for testing with all respect as per CA provision. All testing and inspection shall be submitted after completion of testing. All expenditure in this respect should be bore by contractor and inclusive in quoted rate. No other charges admissible to contractor in this respect afterward. Note :- The rates inclusive of making Platform as per OEM recommandatiion made with brickes and necessary PPC at Bottom and Top and plastering complete all as specified and directed by Engg-in-charge
(A) RMU 3 way type :- Indoor type Compact switch gear Ring Main unit built in type in CSS " CCV+ M " having 02 Nos. Load Break Switches and 01 Nos Vacuum circuit breaker all Motor Operated modules ( Total number of modules 3 Pcs + 1 Metering modules) ,with IP class as IP54 for outer door separately for CSS Enclosure , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X Note : (a) RMU shall be IAC AFL 20kA/1s tested to ensure utmost operator and pedestrian safety .Test report(from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU shall be completely motorized with all SCADA contacts terminated on a designated Terminal Block for easy Take off by the SCADA team for integration.Same contacts shall be clearly mapped in the Engineering drawings for approval with designated TB nos. for easy identification and integration. (e) RMU tank shall be of 304 grade ,Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (f) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (g) Earth switch should be on line side and should have making capacity.
(B) 630A motorised Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity-2 nos. Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38kV Impulse withstand voltage - 75KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Set of 03nos. Ring Core Metering CTs 150-300 - 02 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos
(C) 630A motorised VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity-1 nos. operated 630 A Vacuum circuit breaker having spring stored mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 21KA/ 3 sec Making Capacity - 52.5 kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38KV Impulse withstand voltage - 98KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Green(ON)/Red(OFF) push buttons to operate VCB. 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. (D) Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Right angle non-touch proof Termination boots - 1 Set (R,Y,B)
(E) Stored energy mech. for motor operation - 01 Nos Control voltage, motor operation 24 V DC - 01 Nos Self Powered OC+EF Protection Relay - 01 Nos Set of 03nos. Ring Core Protection CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, 10P10 - 01 Nos Set of 03nos. Ring Core Metering CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos Metering Module Type M SafePlus M is an air insulated metering module.
(F) Set of 03nos. single-phase potential transformers having ratio 11kV/rt3:110V/rt3, 25VA, Class 1.0 with HRC fuses for protection on primary side and MCBs for protection on secondary side.- 01 Nos Space Heater (230VAC)- 01 Nos Low Voltage Box inside the metering enclosure for mounting:- 01 Nos • Multifunction Meter for VCB feeders • CSPC make Under/Over Voltage Relay • 2x12VDC Battery+Charger scheme • R-Y-B Phase Indication Additional equipment delivered separately or mounted in respective panel. Set of Coupling busbars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle- 01 Nos
(G) TRANSFORMER 200KVA 11KV/433V DYn11 Oil filled hermatically sealed transformer without conservator type of design & Top normal porcelein Bushings for HT & LT with Off load tap switch of rating +2.5% to -5% @2.5%. Temp Rise in Oil/Winding shall be 35/40 deg cel respectively (Make:- Nucon/Danish/Kotsons/Schneider/Cahors) Losses shall be as per IS1180 level 2 Max Losses at 50% Loading: 780 Watts Max Losses at 100% Loading: 2300 Watts Impedance: %Z - 4.5% (IS Tol.) WTI & OTI with Alarm & Trip Contact
(H) LT PANEL 415V LT Indoor panel with Aluminium Busbars , Fabrication using 1.5/2 MM CRCA sheet steel , Ingress protection IP4X , complete with internal wiring consisting of following. MCCB 4 pole 320 Amps 36 KA (I/C)) with thermal magnetic release for over load and short circuit protection – 02Nos MCCB 4 pole 250 Amps 36 KA (I/C)) with thermal magnetic release for over load and short circuit protection – 02Nos MCCB 4 pole 63 Amps 36 KA (O/G) – 02Nos Multi function digital meter cornel 4350 Make L&T or equivalent in Conzerv Panel wiring with 2.5 sqmm PVC sheathed, PVC insulated FR/HR stranded copper conductor cable through MCB DP 10 A mounted on DIN rail. Interconnection & Earthing Interconnection Between HT switchgear & Transformer using 1Cx3x95Sq.mm XLPE Single core cable & Interconnection between Transformer & LT switchgear using Busbars. Internal earthing connections shall be done by GI strips. - 01 Set Note :- (i) The Quoted rate shall include construction of foundation/plinthin PCC 1:2:4 type B-2 all as per manufacturer's instruction and standard drawing. Height of foundation shall be 800mm out of which 500mm shall be above ground level (ii) This factor shall be considered by the tenderer and nothing extra shall be admissible on this account.
Supply, installation, testing and commissioning of outdoor type 315 kVA Compact Package Substation, “Non walk in type” fabricated by GI Steel shall house having modular construction of Galvanized Sheet Steel. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP 23 degree of protection for Transformer compartment. The enclosure exterior shall be powder coated. Enclosure should have slant roof suitable to avoid water. Each compartment will be provided with the door and pad locking arrangement. The Compartment illumination lamp with door operated switch shall be provided for each compartment, including PCC foundation at the hight of 3 m as recommended by manufacturerhave complete all as specified and directed with following equipment:- Note : (a) CSS shall be tested for IAC AB for 1 sec, considering utmost safety of Operator and pedestrian. (b) CSS ,RMU,LT Switchgear ,Vacuum Interrupter shall be of same make as CSS OEM to ensure life cycle optimization. (c) CSS shall be supplied by OEM only and not their authorized system integrators. (d) Contractor shall purchase CSS containing RMU directly from OEM necessary factory inspection shall be arranged before dispatch CSS from OEM premises. The testing officer shall be nominated by accepting officer after written confirmation received from contractor for CSS is ready for testing with all respect as per CA provision. All testing and inspection shall be submitted after completion of testing. All expenditure in this respect should be bore by contractor and inclusive in quoted rate. No other charges admissible to contractor in this respect afterward. Note :- The rates inclusive of making Platform as per OEM recommandatiion made with brickes and necessary PPC at Bottom and Top and plastering complete all as specified and directed by Engg-in-charge.
(A) RMU 3 way type :- Indoor type Compact switch gear Ring Main unit built in type in CSS " CCV+ M " having 02 Nos. Load Break Switches and 01 Nos Vacuum circuit breaker all Motor Operated modules ( Total number of modules 3 Pcs + 1 Metering modules) ,with IP class as IP54 for outer door separately for CSS Enclosure , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X Note : (a) RMU shall be IAC AFL 20kA/1s tested to ensure utmost operator and pedestrian safety .Test report(from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU shall be completely motorized with all SCADA contacts terminated on a designated Terminal Block for easy Take off by the SCADA team for integration.Same contacts shall be clearly mapped in the Engineering drawings for approval with designated TB nos. for easy identification and integration. (e) RMU tank shall be of 304 grade ,Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (f) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (g) Earth switch should be on line side and should have making capacity.
(B) 630A motorised Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity-2 nos. Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38kV Impulse withstand voltage - 75KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Set of 03nos. Ring Core Metering CTs 150-300 - 02 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos
(C) 630A motorised VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity-1 nos. operated 630 A Vacuum circuit breaker having spring stored mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 21KA/ 3 sec Making Capacity - 52.5 kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38KV Impulse withstand voltage - 98KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Green(ON)/Red(OFF) push buttons to operate VCB. 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. (D) Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Right angle non-touch proof Termination boots - 1 Set (R,Y,B)
(E) Stored energy mech. for motor operation - 01 Nos Control voltage, motor operation 24 V DC - 01 Nos Self Powered OC+EF Protection Relay - 01 Nos Set of 03nos. Ring Core Protection CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, 10P10 - 01 Nos Set of 03nos. Ring Core Metering CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos Metering Module Type M SafePlus M is an air insulated metering module.
(F) Set of 03nos. single-phase potential transformers having ratio 11kV/rt3:110V/rt3, 25VA, Class 1.0 with HRC fuses for protection on primary side and MCBs for protection on secondary side.- 01 Nos Space Heater (230VAC)- 01 Nos Low Voltage Box inside the metering enclosure for mounting:- 01 Nos • Multifunction Meter for each feeder • CSPC make Under/Over Voltage Relay • 2x12VDC Battery+Charger scheme • R-Y-B Phase Indication Additional equipment delivered separately or mounted in respective panel. Set of Coupling busbars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle- 01 Nos
(G) TRANSFORMER 315KVA, 11KV/433V DYn11 Copper wound Oil filled hermatically sealed transformer with corrugated wall without conservator type of design & Top Bushings for HT & LT with Off circuit tap links of rating +5% to -5% in steps of 2.5% by means of hand operated off load tap changing gear. Class - A, Temp Rise - Oil/Winding 40/45 Deg cel. Losses ( As per IS 1180 EEL 2 ) Max. Losses at 50% loading: 1025Watts, Max. Losses at 100% loading: 3100Watts and Impedance of 4.5% (subject to IS Tol.) (Make:- Nucon/Danish/Kotsons/Schneider/Cahors) WTI & OTI with Alarm & Trip Contact
(H) LT PANEL 415V LT Indoor panel with Aluminium Busbars , Fabrication using 1.5/2 MM CRCA sheet steel , Ingress protection IP4X , complete with internal wiring consisting of following. MCCB 4 pole 800 Amps 36 KA (I/C)) with thermal magnetic release for over load and short circuit protection – 01Nos MCCB 4 pole 400 Amps 36 KA (I/C)) with thermal magnetic release for over load and short circuit protection – 02 Nos MCCB 4 pole 200 Amps 36 KA (I/C)) with thermal magnetic release for over load and short circuit protection – 02Nos MCCB 4 pole 100 Amps 36 KA (I/C)) with thermal magnetic release for over load and short circuit protection – 02Nos MCCB 4 pole 63 Amps 36 KA (O/G) – 02Nos Multi function digital meter cornel 4350 Make L&T or equivalent in Conzerv Panel wiring with 2.5 sqmm PVC sheathed, PVC insulated FR/HR stranded copper conductor cable through MCB DP 10 A mounted on DIN rail. Interconnection & Earthing Interconnection Between HT switchgear & Transformer using 1Cx3x95Sq.mm XLPE Single core cable & Interconnection between Transformer & LT switchgear using Busbars. Internal earthing connections shall be done by GI strips. - 01 Set Note :- (i) The Quoted rate shall include construction of foundation/plinthin PCC 1:2:4 type B-2 all as per manufacturer's instruction and standard drawing. Height of foundation shall be 800mm out of which 500mm shall be above ground level (ii) This factor shall be considered by the tenderer and nothing extra shall be admissible on this account.
Supply , fix and install 1000 KVA, 11/0.433KV, AN, Oil Type Transformer with corrugated off circuit tap links of rating +5 to - 5% @2.5 %.by means of hand operated off load tap changing gear 1000 kVA capacity transformer copper worund step down outdoor type 11000/433 Volt(at no load) double wound oil immersed naturally cooled with external cooling tubes core type delta connected on primary side (HV) and star connected on secondary side(LV) in accordance with vector symbol Dy-II (vector group) with neutral brought on secoundary side (LV side) and having tapping changing at +/- 7.5% in step of +/- 2.5% to be changed and the maximum temperature rise should not exceed 45 degree centrigrade in oil and 55 degree centrigrade in HV/LV winding when measured by resistance method after continuous full oad run in ambient temp of 40 degree centrigrade and the transformer shall be comprised complete all as specified and directed with the following standard fittings:-
(i) Pressure Release Valve (ii) Thermometer pocket on tank cover (iii) Oil temprature indicator with 2 contacts alarm & trip (iv) Rating plate with terminal marking (v) Two earthing terminals on tank and cover to facilitate fixing of GI earth strip (vi) Oil level guage (vii) Oil drain filter valve (viii) Lifting lugs (ix) Oil filter hole with cap/plug including connection complete (x) Four plain solid cast steel detachable rollers (xi) First fill of transformer oil confirming to relevant IS and testing upto 60 KV di-electric strength Note:- (i) Transformer should be double copper wound (Level- 02) as per IS: 1180 (Part-I) 2014 with HT, LT cable box, OTI & PRV. (ii) The rates inclusive of making platform as per OEM recommendation made with bricks and necessary PPC at bottom and top and plastering complete all specified and directed by Engg-in-charge.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade 95 Sqmm 3 core (earth system) complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV grade cable for in door termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 95 sqmm complete all as specified and directed. Note :- The joniting material like long sleeve for RMU connection and other connected items will incluive in above rate
Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 95 sqmm complete all as specified and directed. Note :- The joniting material like long sleeve for RMU connection and other connected items will incluive in above rate
Supply and fix cable jointing kit for 11 KV grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 Sqmm to 95 sqmm, Indoor/Outdoor type complete all as specified and directed.
Material and labour for earthing complete with gavanised steel earth plate electrode 60 cm x 60 cm x 6.3 mm thick burried directly in ground ( earth pit not less than 2.25 Mtrs below gorund level) with top edge of the plate not less than 1.5mtr beolw normal ground level, connected to galvanised earth strip 32 x 6mm size upto a distance of 7.5 mtr long by means of bolts , check nuts and washers of galvnised iron or steel all as shown in electrical plate no 5 connected to earthing test point all as specified and indicated and testing complete including execvation earth work drilling holes for electrode PCC pit & cover , funnel , water pipe , lugs etc. complete all as specified and directed.
Earthing complete with galvanised GI earth plate eletrode 600x600x6mm thick,burried directly in ground (earth pit not less than 2.25mtrdeep below GL) with top edge of the plate n.less than 1.5mtr below normal.GL surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15cm all round the plate using 4mm dia GI wire as earth wire electrode welded and revetted to earth plate at one end connected to main DBs of Bldg at another end GI earth wire encased in and including 15mm dia GI light grade pipe through upper end of earth plate upto main DB of bldg with 20mm bore GI pipe light grade as water pipe from earth chamber to upper edge of earth plate MS funnel with wire mesh fixed on water pipe and Provn of PCC pit in PCC 1:2:4 type B-1 chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type BI duly reinforeced with MS bars 8mm dia @ 150C/c with both ways complete with lifting handle all as shown in electrical plate no 5 of SSR of part-I (1991) complete all as specified and directed by Engr-in-charge.
Supply , laying and testing cable XLPE insulated screende, PVC bedded galvanised steel strip or wire moured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt grade of size 3.5 Core , 120 Sqmm complete all as specified and directed.
Supply , laying and testing cable XLPE insulated screende, PVC bedded galvanised steel strip or wire moured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt grade of size 3.5 Core , 95 Sqmm complete all as specified and directed.
Supply , laying and testing cable XLPE insulated screende, PVC bedded galvanised steel strip or wire moured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt grade of size 3.5 Core , 70 Sqmm complete all as specified and directed.
Dismantling of existing transformer of 320 KVA from OT substation with removing LT and HT end terminations with necessary T & P and Manpower and transported to Polycline S/S upto 2.0 KM distance and fix ,install , testing and commissioning of the same including necessary lugging nuts , bolts and connected accessories connecting earthing strips with bolts etc all as specified and directed by Engg-in-charge Note :- The damage during transporting of transformer from OT substation to polyclince substation should be recover from contractor as per market rates. The rates inclusive of making Platform made with brickes and necessary PPC at Bottom and Top and plastering complete all as specified and directed by Engg-in-charge
Excavation in trenches not exc 1.5 m wide and n.exc 1.5 m in depth for foundation / fixing pole / laying cable and pipe line etc or for man hole etc not exc 10 sqm on plan and getting out in soft / loose soil complete all as specified and directed.
Returning filling in including spreading, levilling, watering and well ramming in layers, not exeecding 25 cm thick using excavated soil complete all as specified and directed.
Removing excavated Soil to a distence not exceeding 50 m and deposting where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
M&L for providing dry river sand as in sand cushioning to under ground electric cable including punning down of sand in layercomplete all as specified and directed by Engg-in-Charge. Note: for measurement purpose punned thicness of sand only will be considered.
Supply and Laying burn brick size 225 mm X 113 mm X 75 mm etc complete all as specified and directed.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed by Engg -in-charge
Material & labour for GI steel tubing light grade for protection of cable/ earth continuty conductor fixed to poles/ walls/ roof or laid in floors, road, crossing or ducts fixed with clamps , bolts nuts and wahser etc of pipes of size 80mm dia complete all as specified and directed.
VINAY ENTERPRISES
M P TYAGI ENGINEERS AND CONTRACTORS
R D Bansal
JAZZCON ENGINEERS PVT LTD
Vijay Electricals
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .