Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹70 L
EMD Value
₹1.4 L
Closing Date
14 Jul 2020, 2:00 pmClosed
DGM Unit Electric JKPCC Ltd Srinagar
DGM Unit Electric JKPCC Ltd Srinagar
Internal Electrification of Administration Block of Government Medical College at Anantnag.
2020_PWDJK_99837_2
20/E/K of 2020-21 Dt. 06.07.2020
Open Tender
Electrical Works
Item Rate
90 days
ANANTNAG
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,000
Yes
FC JKPCC Ltd A/c
₹1.4 L
Yes
GM JKPCC LTD SRINAGAR
27 Jul 2020
7 Jul 2020
15 Jul 2020
7 Jul 2020
14 Jul 2020
7 Jul 2020
10 Jul 2020
Amount
POWER DISTRIBUTION BOARDS(415V AC, 3 phase, 4 wire, 50 Hz)
Supply,erection, testing & commissioning of PDB. This will be floor mounted, free standing, indoor duty, dust & vermin proof, front operated, having front hinged lockable doors, and will be complete with the main and auxiliaries bus bars, interconnection, earth terminals, earth bus and will be powder coated finished with 70 micron. The PDB panel shall use all for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panels will be made as per detailed specifications and drawings forming part of this document. The incoming and outgoing for PDB shall be as follows:
(Each MCCB will be variable current setting for over current and short circuit, front extended lockable handle, pad lockable in off position, indication light for ON, shrouding on incomer side, termination shall be suitable for aluminium bus bars.)
Bus bar shall be of Aluminium and continuous throughout the width of the panel and vertical cross section of bus bar shall be equal to the total ratings of feeders fed by the vertical bus bars subjected to minimum size being used as per fault level. Bus bar shall have minimum conductivity of 58%. All MCCB's shall have indication light for ON, shrouding on incomer side, phase barriers, rotary extended handle.
L&P PDB FOR ADMIN BLOCK ( LOCATION : ADMIN BLOCK G/F) (Ics=10KA) (Ics = Icu = 100%)
One set of TPN, Al. bus bar rated 250 Amps (after considering necessary deratings of 75%) for phases and neutral for half capacity of phases.
The outgoing feeders are as follows :
4 Nos. 125 Amps TPN feeder each having one number 125 Amps TP MCCB with isolable neutral and ON indication.
2 Nos. 100 Amps TPN feeder each having one number 100 Amps TP MCCB with isolable neutral and ON indication.
7 Nos. 63 Amps TPN feeder each having one number 63 Amps TP MCCB with isolable neutral and ON indication.
1 No. Type II SPD 4 Mode Din mounted for nominal current 50kA per pole (8/20 micro-second) with HRC Fuses as per specification to meet 440V TOV withstand for 2 hrs. Voltage protection (VP) level will be less than 1.5kV.
1 set of complete wiring
INTERNAL WIRING
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. (Excluding cost of conduit, as the conduit is already laid )
Group A
Group B
Group C
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. (Excluding cost of conduit, as the conduit is already laid )
Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
4 X 4 sq. mm + 2 X 4 sq. mm earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
4 X 10 sq. mm + 2 X 6 sq. mm earth wire
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 amps switch
2 way 5/6 amps switch
15/16 amp switch
3 pin 5/6 amp socket outlet
6 pin 15/16 amp socket outlet
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
1 or 2 Module (75 mmX75 mm)
3 Module (100mm X 75mm)
4 Module (125mm X 75mm)
6 Module (200mm X 75mm)
8 Module (125mm X 125mm)
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.
1 or 2 Module
3 Module
4 Module
6 Module
8 Module
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required.
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required.
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
Upto 450 mm sweep
Supplying of 1200mm dia ceiling fan.
Supplying of 300mm dia exhaust fan.
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group A
Group B
Group C
MCB & DB'S
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, inter connections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
8 way Double door
12 way Double door
Supplying and fixing following way prewired TP&N MCB distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FRLS PVC insulated copper conductor up to terminal blocks, tinned copper bus bar,neutral link, earth bar, din bar, detachable gland plate interconnections, powder painted including earthing etc. as required.(But without MCB/ RCCB/ Isolator)
8 way (4 + 24), Double door
12 way (4 + 36), Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
8 way (4 + 24), Double door
12 way (4 + 36), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Single pole and neutral
Double pole
Triple pole
Triple pole and neutral
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating,4pole, 415 volts, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
Supplying and fixing following rating,2pole, 240 volts, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
Supplying and fixing following rating,three pole, 415 volts, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
100 Amp, 16 KA,TPMCCB
125 Amp, 16 KA,TPMCCB
CABLE TRAYS
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
EARTHING
Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal / coke and salt as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Supplying and laying 6 SWG G.I. wire at 0.50 meter below ground level for conductor earth electrode, including connection / termination with GI thimble etc. as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 meter below ground as strip earth electrode, including connection / terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50 mm)
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 meter below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm)
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
LIGHTNING CONDUCTOR
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required.
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting / sweating and soldering etc. as required.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required. (For horizontal run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required. (For vertical run)
Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required. (For horizontal run)
Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required. (For vertical run)
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 Nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
Laying copper/ G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
MV CABLE LAYING
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Above 95 sq. mm and upto 185 sq. mm (clamped with 25 / 40x3mm MS flat clamp)
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on cable tray as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
MV CABLE JOINTING & END TERMINATION
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
3 X 10 sq. mm (22mm)
3½ X 35 sq. mm (32mm)
3½ X 50 sq. mm (35 mm)
3.5 X 70 sq. mm (38mm)
3.5 X 185 sq. mm (57mm)
4 X 10 sq. mm (25mm)
4 X 16 sq. mm (28mm)
4 X 25 sq. mm (28mm)
4 X 35 sq. mm (32mm)
4 X 2.5 sq. mm
CABLE SUPPLY
Supply of multi core, stranded / solid aluminum conductor, XLPE / PVC insulated armoured, PVC outter sheathed 1100V, grade cables of the following sizes. ( Cable shall be suitable for -15ºC to + 50ºC temprature condition )
3.5c * 70sqmm Al, XLPE, arm
3.5c * 50sqmm Al, XLPE, arm
3.5c * 35sqmm Al, XLPE, arm
4c * 25sqmm Al, XLPE, arm
4c x 16 sqmm copper,XLPE, arm
4c x 10 sqmm copper, XLPE, arm
4c x 6 sqmm copper,XLPE arm
4c x 4 sqmm copper,XLPE arm
4c x 2.5 sqmm copper,PVC arm
LIGHTING FIXTURES (Supplying & installation of following fixtures shall be complete in everyway.System output of each luminaire lm/watt shall be given by vendor alongwith the BoQ )
Supplying & installation of Integral LED 4 ft luminaire with CRCA housing and PC Glossy cover. The luminaire should have a color consistency SDCM < 5, CRI > 80 and CCT of 6500K. The luminaire shall be compliant with IP20 classification. Luminaire shall be designed to emit at least 4000 nominal lumens at a system efficacy of atleast 115 lumen/watt with a maximum system wattage of 34 Watts. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 50k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor >0.95 and THD <10% and suitable for an operationg voltage range of 140-270V AC.The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters.
Supplying & installation of LED 2x2 luminaire with CRCA housing suitable with fully diffused diffuser for general lighting in office areas. The luminaire should have a color consistency SDCM < 5, CRI > 80 and CCT of both 4000K / 6500K. The luminaire shall be compliant with IP20 and IK02 classification. Luminaire shall be designed to emit at least 3600 nominal lumens and an outstanding backlit solution efficacy of atleast 120 lumen/watt and maximum system wattage of 31 Watts. The lumanaire should have outstanding backlit solution efficacy.The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 50k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor >0.95 and THD <10% . he fixture should comply with the parameters as per IS10322. The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters.
Supplying & installation Recess LED 300 x 1200 mm fitting made of CRCA and PMMA diffuser. Fixture should have minimum efficacy at System level (Not Chip Level) >=120lumens/watt and a minimum system lumen output of 3000 lumens and maximum system wattage of 23W. Luminaire should have Life of 50000hrs@L70B50 Lumen maintenance, CCT up to 4000/6500K, CRI >80, PF >0.9, THD<10% and an operating Voltage Range of 140 - 270 Internal Surge Protection 2.5KV.The fixture should comply with the parameters as per IS10322. The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters
Supplying & installation LED indoor surface downlighter suitable for general lighting. Luminaire should have polycarbonate cover with diffused optics. The luminaire should have CRI > 80 and CCT of 3000K/4000K/6500K. The luminaire shall be compliant with IP20 classification.The fixture should have a minimum system efficacy of 110 lumen/Watt and a minimum system lumen output of 2000 lumens and maximum system wattage of 18 Watts. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 50k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor >0.95 , THD <10%. he fixture should comply with the parameters as per IS10322. The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters.
Supplying & installation of LED indoor recessed downlighter suitable for general lighting. Luminaire should have die cast heat sink with reflector of PC and high quality diffuser. The luminaire should have CRI > 80 and CCT of 3000K/4000K/6500K. The luminaire shall be compliant with IP20 classification.The fixture should have a minimum system efficacy of 110 lumen/Watt and a minimum system lumen output of 1500 lumens and maximum system wattage of 13.5 Watts. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 50k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor >0.95 , THD <10%. The fixture should comply with the parameters as per IS10322. The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters.
Supplying & installation of LED indoor Recess downlighter suitable for general lighting. Luminaire should have polycarbonate cover with diffused optics. The luminaire should have CRI > 80 and CCT of 3000K/4000K/6500K. The luminaire shall be compliant with IP20 classification.The fixture should have a minimum system efficacy of 95 lumen/Watt and a minimum system lumen output of 1000 lumens and maximum system wattage of 11 Watts. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 50k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor >0.95 , THD <10%. he fixture should comply with the parameters as per IS10322. The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Surface.
Supplying & installation of LED indoor surface downlighter suitable for general lighting. Luminaire should have polycarbonate cover with diffused optics. The luminaire should have CRI > 80 and CCT of 3000K/4000K/6500K. The luminaire shall be compliant with IP20 classification.The fixture should have a minimum system efficacy of 100 lumen/Watt and a minimum system lumen output of 1200 lumens and maximum system wattage of 12 Watts. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 50k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor >0.95 , THD <10%. he fixture should comply with the parameters as per IS10322. The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters.
Supplying & installation of Integral LED 2 ft luminaire with extruded almunium housing with PC cover. The luminaire should have a color consistency SDCM < 5, CRI > 80 and CCT of4000/ 6500K. The luminaire shall be compliant with IP20 classification. Luminaire shall be designed to emit at least 1200 nominal lumens at a system efficacy of atleast 100 lumen/watt with a maximum system wattage of 12 Watts. The luminaire shall be designed so as to ensure lumen depreciation of up to 25k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor >0.95 and THD <20% and suitable for an operationg voltage range of 140-270V AC.The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Telephone socket outlet
TV antenna socket outlet
Data socket outlet
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
1 or 2 Module (75 mmX75 mm)
4 Module (125 mmX75 mm)
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.
1 or 2 Module
4 Module
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.
1 run of cable
Supplying and laying following telephone cables.
5 pair 0.6mm arm cable
10 pair 0.6mm arm cable
20 pair 0.6mm arm cable
50 pair 0.6mm arm cable
100 pair 0.6mm arm cable
Supplying,fixing,testing & commissioning of following MDF box with module complete in all respect.
10 pair MDF box with module
20 pair MDF box with module
30 pair MDF box with module
50 pair MDF box with module
100 pair MDF box with module
M/s PAMPOSH ELECTRICALS
N S ENTERPRISES
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .