| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.2 LAccepted-AOC R O WARD NO 08 H NO 108 DHAR ROAD UDHAMPUR TEHSIL DISTT UDHAMPUR 182101 | UDHAMPUR | UDHAMPUR | JAMMU KASHMIR | 182101 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹22.1 L+₹4.2 L (23.7%)Rejected-Finance | L2 | Rejected-Finance Not being lowest | |
| 3 | Rejected-Technical | - | Rejected-Technical Not enlisted in b(iii) cat required as per NIT | |
| 4 | Rejected-Technical | - | Rejected-Technical Not enlisted in b(iii) cat required as per NIT |
Tender Value
₹22 L
EMD Value
₹44,000
Closing Date
12 Jul 2023, 6:00 pmClosed
Col Sachin Sharma CWE
Military Engineer Services, Commander Works Engineer, Udhampur, PO - Garhi, Udhampur-182121
REPAIRS/ MAINT TO EXISTING 4 POLE/ 2 POLE STRUCTURES OF 33 KV SUBSTATION (SHRI KALIMATA SUBSTATION) AND 11 KV HT SYSTEM OF ASCON MAND UNDER GE (UTILITIES) UDHAMPUR
2023_MES_602989_1
CWE/U(U)-42/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
UDHAMPUR
AS PER NIT
7 documents required · 7 mandatory
₹500
GE (UTILITIES) UDHAMPUR
₹44,000
Yes
28 Aug 2023
13 Jun 2023
19 Jul 2023
13 Jun 2023
12 Jul 2023
30 Jun 2023
14 Jun 2023 - 24 Jun 2023
Amount
Taking down proper shut dowm from sub station and Scrapping the two pole structure with Emery Paper after that Painting of 11 kv HT pole 11mtr (set of pole structure including the MS Channel/ angle iron) with one coat of Red oxide and after that two coat of Aluminim paint . white washing of foundation and Marking on pole with Glow sign/ Paint sticker showing the Pole no and source of supply complete all as specified and directed.
Taking down the Power Shut down from Source. Material and Labour for 33 KV yard painting with one coat of synthetic enamel paint as required and writing the designation of equipments in english albhabets/ letters as specified & as directed by Engr-in-charge and mainly the following:- (i) Transformer 33/11 KV of capacity 6.3 MVA-02 No (ii) Structure - 02 No (iii) Duct cover - 60 Mtrs OLTC boxes- 01 No, (iV) Complete yard fencing paint Mast conductor-
Taking down proper shut dowm from sub station and Scrapping the two pole structure with Emery Paper after that Painting of 33kv HT pole 13 mtr (set of two pole structure including the MS Channel/ angle iron) with one coat of Red oxide and after that two coat of Aluminim paint . white washing of foundation and Marking on pole with Glow sign/ Paint sticker showing the Pole no and source of supply complete all as specified and directed.
Taking down the unserviceable/ damaged Rubber mats from the substation. Supply lay and utilisation of Rubber matting as per ISI mark 1 mtr x 2 mtr x 30 mm for HT breaker at substation complete all as specified and directed.
Taking down the old corroded / damaged HT Poles from the substation. Supply and fix steel tubular pole(12 Mtr) complete with cast iron base plate, finial taper plug, bolts , nuts & screws as specified type 410 SP-64 all as specified & directed Note : a) Necessary exacavation ,foundation and coping is inclusive of rate quoted by contractor.
Taking down the 33 KV circuit breaker from the system decarbonising the complete circuit system with CTC (carbon Tetra chloride) .Checking the complete moving/fixed contracts for any loose & retighney. The bus chamber should be inspected for loose joints. (a) Panel side: 33 KV panel side the circuit sprouts /Bus sprouts has to be checked. Proper closing of sprouts to be checked. Any mechanical imblancefound to be rectified. Proper DC system has to be checked for functioning indication system & tripping & closing system has to be prop checked and mentioned. (b) Breaker side: The trowlley to be checked for mechanical fitment inside the chamber,Proper checking of tripping/closing system application of greasing to complete mechanison. Minor repair related to mechanism to be rectified . Arc chutes. SF-6 punty test to be done on intemptons to maintain diclectric properly of are quenching in breakers. Following routes test are to be Performed on breaker a) SF-6 gas leakage test. b) Tightness test. c) Design/Visuel test. d) Mechanical operaton test. e)Measurement of resistance of main circuit(or) contract resistant test. f) Dielectric test on auxiailay circut & control circut. g) Power frequency over voltage with starter test.
Servicing, repairing and overhauling of 33 KV isolator including cleaning of complete moving and fixed contracts oiling/ greasing operating mechanismtightening connections and replacement of unserviceable parts including reassembling the isolator after complete repair, routine and periodical testing complete all as specified and directed.
Fixed contact assembly of 33 KV air break switch isolator rotating type complete all as specified and directed.
Moving contact assembly of 33 KV air break switch isolator rotating type complete all as specified and directed.
Repair/replacement of HT out door type Gang operated POLYMER based rotating type, triplepole,mechanically operated Air Break Switch 33 KV Volts rating, 400 Amp capacity, horizontal mounting, double break, mounted on insulation and steel frame, GI operating rod of suitable length to be worked from ground level. including taking down complete as specified and as directed.
Repair/replacement of HT out door type Gang operated rotating type, triplepole,mechanically operated Air Break Switch Volts rating, 33KV 400 Amp capacity, horizontal mounting, double break, mounted on insulation and steel frame, GI operating rod of suitable length to be worked from ground level. including taking down old complete as specified and as directed.
Supplying and fixing in repair/replacement of HT out door type Gang operated rotating type, triplepole,mechanically operated Air Break Switch 11 Kilo Volts rating, 400 Amp capacity, horizontal mounting, double break, mounted on insulation and steel frame, GI operating rod of suitable length to be worked from ground level including taking down old complete as specified and as directed.
Draining out the transformer oil from radiators after closing the inlet valve from main body of 6.3 MVA power transformer including filling transformer oil of good quality having not less than 55 KV dielectric strength, having low viscosity all as specified and directed. Make: Savita/Power oil as per IS 335 of 1983 all as specified and testing of Transformer after filling new oil complete upto 10 Hrs minimum to the entire satisfaciton of GE, complete all as specified & directed.
Dehydration & filtration of transformer oil in existing transformers installed at site with portable plant to improve the dielectric strength 70 KV including testing of dielectric strength after dehydration & filteration at site. Note:- a) Pre-heated oil shall be topped up as required at site before the process; extra oil will be measured and paid seperately under respective item. b) Qualified technician for filters of transformer shall be deputed. c) Transporaton of filhates machine from 132 KV sub station to 33 KV S/S is demmed to be including of rate quoted.
Silica gel breathers assembly filled complete suitable for transformer cap 6.3 MVA (As per Sample) complete all as specified and directed.
Chequered plates/GI sheet/ cross arms of MS fabricated complete with all accessories viz nut, bolts, washer etc. Including taking down old complete all as specified and directed.
Pin insulator, porcelain viterous brown including 01 galvanized Mild Steel spindle, two galvanised iron washers and one galvansised iron nut suitable for HT 33000 Volts, fixed in repairs, complete all as specified and directed.
XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable (Heavy Duty) with aluminium conductor 33000 volts grade cross sectional area 240 sq mm, 3 core including taking down of U/S Cable complete all as specified and directed. Note :-Retrived LT cable scrap ( Lumpsum ) shall be deposited to AGE E/M storeyard with own arrangement by the contractor.
XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable (Heavy Duty) with aluminium conductor 33000 volts grade cross sectional area 185 sq mm, 3 core including taking down of U/S Cable complete all as specified and directed. Note :-Retrived LT cable scrap ( Lumpsum ) shall be deposited to AGE E/M storeyard with own arrangement by the contractor.
Cable jointing kit for 33 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm to 240 sqmm complete, all as specified and directed.
Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 150 sqmm to 185 sqmm complete, all as specified and directed.
Separator sheet sheet for 33 KV Breaker complete with material and accessories complete, all as specified and directed.
Space heat 36 watt for 33 KV breaker complete with material and accessories complete, all as specified and directed.
Bus bar suitable Sleeves for 33 KV breaker complete with material and accessories complete, all as specified and directed.
Lightning Arresters, for non linear resistance type for 33 KV normal discharge count 5 Amps and high current impulse withstand 65 Kilo Amps conforming to IS-3070 Part-I for OH line including bracket, clamps, nuts and washers. Including Taking down complete all as specified and directed.
Numerical relay system from HT Breakers (33kv or 11 kv) . calibration shall be done by primary injector kit . Necessary plug setting and injector shall be done ( wind) load. Test report for te said calibration.
Cutting/ trimming of tree branches not exc 10cm girth touching/approaching the HT overhead lines upto 3 metre width on each side with hacksaw/axe to clear the HT line including disposal of trimmed branches 100 Metre away inside the cantonment area & clearing site complete all as specified and directed.
Taking down the unserviceable Battery bank from the substation . Supply install test and commissiong of Battery bank VRLA Type Sealed maintenance free operating on 110V DC + 110 V AC with (02 Volts-56Nos. Battries) Battery Stand & Inter-Connections (Make of Battery - EXIDE/AMARAJA)
Taking down the unserviceable Battery Charger from the VCB Panel Supply and fix 110V DC Battery Charger with following specification a) Trickle, Boost Facility system inbuilt. b) Protection system with MCB control 100Amps. c) 230V AC input charger. d) Air cooled rectifier e) Servo control charger.
Supply and spreading stone aggregates of size 20mm evenly at outdoor 33/11 KV sub stations after removing uprooting of tiny trees, bushes, beeds, grass, elephant grass, removing poly bags, brick bats, stone pebbles and other debris etc complete all as specified and directed.
ACSR conductor of required size for Over head lines on poles including streching, tightining of poles insulator with winding wire of suitable size with insulator/streching of ACSR conductor all as specified and directed.
PROACH ASSOCIATES BUILDERS & ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .