| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.2 LAccepted-AOC | ₹24.2 L Quoted ₹25.1 L | L1 | Accepted-AOC The lowest tenderer |
| 2 | L2₹25.2 L+₹2,610 (0.10%)Rejected-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | ₹25.2 L+₹2,610 (0.10%) | L2 | Rejected-AOC Other than the lowest tenderer |
| 3 | L3₹28.5 L+₹3.4 L (13.5%)Rejected-AOC 546 14 JUTOGH CANTT SHIMLA HP 171008 | SHIMLA | HIMACHAL PRADESH | 171008 | ₹28.5 L+₹3.4 L (13.5%) | L3 | Rejected-AOC Other than the lowest tenderer |
| 4 | L4₹28.9 L+₹3.7 L (14.9%)Rejected-AOC | ₹28.9 L+₹3.7 L (14.9%) | L4 | Rejected-AOC Other than the lowest tenderer |
| 5 | L5₹31.7 L+₹6.6 L (26.1%)Rejected-AOC 186 GANDHI MARKET AMBALA CANTT 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | ₹31.7 L+₹6.6 L (26.1%) | L5 | Rejected-AOC Other than the lowest tenderer |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
30 Jul 2020, 6:00 pmClosed
GE JUTOGH
GE JUTOGH JUTOGH CANTT SHIMLA (HP) 171008
REPAIR / MAINT OF LT OVER HEAD LINE, UG CABLE, MCCBS,FEEDER PILLAR BOX AND OTHER MISC WORK OF EXTERNAL ELECTRIC AT JUTOGH, KUFRI, SANJAULI AND KELVIN GROVE UNDER GE JUTOGH
2020_MES_347616_2
GE/JUT-18/2020-21
Open Tender
Civil Works
Item Rate
270 days
JUTOGH
CLASS D CATEGORY b (i)
7 documents required · 7 mandatory
₹500
GE JUTOGH
₹70,000
Yes
28 Aug 2020
7 Jul 2020
1 Aug 2020
7 Jul 2020
30 Jul 2020
16 Jul 2020
Amount
Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr deep in loose/soft soil and getting out for underground cable/erection of poles, stays , trench etc complete all as specified and as directed.
All as per item No.01 above but exceeding 1.5 mtr deep and not exc 3.0mtr deep complete all as specified and as directed.
M&L for sand cushioning for cable with river washed sand and pinning to provide required cover as per SSR Part –I complete all as specified and directed. Note :-Punnd thickness of sand layed shall be measured and paid to contractor.
Supply and laying bricks common burnt clay sub class 'B' bricks old size for cable protection or laid dry on surface/foundation complete all as specified and as directed.
M&L for PCC 1:4:8 type D-2 using 40mm graded crushed stone aggregate, as in wall, reataining wall any thickness, size, shape, base of pole in pole pit and foundation etc. complete all as specified and as directed.
M&L for PCC 1:3:6 type C-1 using 20mm graded stone aggregate as mass filling and coping of pole and strut, stay around the pole etc including necessary form work complete all as specified and as directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers n.exc 25 cm thick layers complete all as specified and as directed.
Removal of excavated material to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above from starting point complete all as specified and as directed.
Dismantling and taking down old unserviceable pole any type after disconnecting all electrical connection incl clearance of site complete all as the direction of Engr-in-Charge.
Supply and errection in true vertical position steel tubular swaged pole type 410 SP-31, 09 mtr long complete with cast iron base plate and finial taper plug, bolts, nuts, washers and screws incl painting with synthetic enamelled aluminium paint two coats over one coat of red oxide primer after errection and providing black and white strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip complete and marking pole number on pole all as specified and as directed. Note: (i) Earth work and PCC shall be measured and paid separately. (ii) Description as per direction of Engr-in-Charge will be printed on each pole without any extra cost.
S&F stay assembly complete with all accessories, such as stay plate 230X230X6 mm3, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc. all as per electrical plate No 1 of SSR part I and as directed incl taking down old unserviceable stay assembly. Note: Excavation and PCC will be measured and paid separately.
M & L in replacement cross arms, bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primercoat, one under coat and one finishing coat of paint. incl dismantling and taking down old unsv complete all as specified and directed.
S&F in replacement shackle type porcelain vitreous white or brown insulator including Galvanised steel straps, washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm height, 90 mm dia, section of strap 30mmx3mm & dia of bolt 12 mm complete all as specified and as directed.
S&F in replacement pin type insulator porcelain vitreous white or brown 1100 volts grade 100 mm height and 65 mm dia with Galvanised mild steel spindle two GI washer and one GI nut complete all as specified and as directed.
S&F aluminium conductor steel reinforced (ACSR) including fixing, stretching on poles and proper noseling with binding wire with insulator, jumpring of any size as required at site incl dismantling and taking down old unserviceable conductor complete all as specified and as directed.
S&F in replacement for 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm GI suspension wire, one twin core cable flat or circular of size 10 sqmm 2 core complete all as directed by Engr-in Charge.
M&L for earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick surrounded by char coal and salt buried directly in ground vertically in pit of depth not less then 2.25 mtr below ground level with top edge of the earth plate at depth of not less then 1.5 mtr below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth plate electrode connected to GI earth lead strip of size 25X4.0 mm at two points by means of GI nuts bolts, check nuts and washers and connected to earthling test point drawn through 40 mm dia GI pipe for protection pipe incl PCC earth pit (1:3:6) type C-2 with CI frame and RCC cover all as shown in electrical Plate No 3 on SSR Part-I including testing and dismantling ,taking down old unser earthing all as directed by Engr-In-Charge. Note: (i) Rate of Earth work, Earthing electrode, all connections, nut-bolts, washers, complete labour, testing, Earth lead upto 7.5 mtr, char coal dust, common salt, porcelain insulator,PCC earth Pit, CI frame ,RCC cover, funnel with wire mesh are incl in quoted rate and watering pipe, earth lead protection pipe, test poit, and earth lead exceeding 7.5 mtr are measured and paid separately.
M&L for earthing complete with galvanized steel plate earth electrode 60cmx60cmx6mm thick surrounded by char coal and salt buried directly in ground vertically in pit of depth not less then 2.25 mtr below ground level with top edge of the earth plate at depth of not less then 1.5 mtr below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth plate electrode connected to galvanised earth lead wire of 4.0mm dia at two points by means of GI nuts bolts, check nuts and washers and connected to earthling test point drawn through GI pipe for protection of earth lead wire incl PCC earth pit (1:3:6) type C-2 with CI frame and RCC cover all as shown in electrical Plate No 3 on SSR Part-I including testing and dismantling ,taking down old unser earthing all as directed by Engr-In-Charge. Note: (i) Rate of Earth work, Earthing electrode, all connections, nut-bolts, washers, complete labour, testing, Earth lead upto 7.5 mtr, char coal dust, common salt, porcelain insulator, PCC earth Pit, CI frame ,RCC cover, funnel with wire mesh are incl in quoted rate and watering pipe, earth lead protection pipe, test poit, earth lead exceeding 7.5 mt are measured and paid separately.
S&Fin repair of Earth continuity GI wire of 4 mm dia or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required complete all as directed by Engr-in-Charge.
S&F in repair of Earth continuity strip or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or fixed on wall with porcelain insulator or any other indicated situation for loop earthing etc. as required 25x4 mm GI strip complete all as directed by Engr-in-Charge.
Supply , Fixing & laying GI tubing light grade 15 mm dia used as water pipe in earthing complete all as directed. Note: All required items and accessories, bend, joints, nut bolts, clamps etc are incl in quoted rates.
Supply, Fixing & laying GI tubing light grade 20 mm dia used as protection pipe for earth lead wire in earthing complete all as directed. Note: All required items and accessories, bend, joints, nut bolts, clamps etc are incl in quoted rates.
Supply , Fixing & laying GI tubing light grade 40 mm dia used as protection pipe for earth lead strip in earthing or alongwith pole / wall/ culvert / drainage etc for mechanical protection of cable complete all as directed. Note: All required items and accessories, bend, joints, nut bolts, clamps etc are incl in quoted rates.
Supply, Fixing & laying GI tubing light grade 80 mm dia for road crossing along with pole/culvert /drainage for mechanical protection of cable complete all as directed. Note: All items and accessories, bend, joints, nut bolts, clamps etc are incl in quoted rates.
Supply & fixing or laying in replacement HDPE (DWC) tubing 50mm dia of pressure rating 6Kgf/Cm2 fixing on poles, walls under floors, road crossing laying on surface etc as reqd at site complete all as specified and as directed. Note: The rate of all accessories such as bend, joints, nut bolts, clamps etc deemed to be incuded in quoted rates.
S&F danger notice board/plate of 1.6mm thick mild steel sheet, vitreous enamelled white with letters, figures and conventional skull and bone in signal red colour and fixed with MS clamps bolts approved size for LT 20x15cm complete all as specified and as directed.
M&L for Anti-climbing device, spikes type fabricated out of mild steel bars (round,square and flat) including nuts, bolts, washers and welding in two halves make to shape to suit the cross section of the pole complete, all as specified and as directed.
M&L for Anti climbing devices, comprising 2.24mm dia galvanised steel 2-strand barbed wire with 2.00mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped and properly secured or as ordered. Note: All items and accessories , bend, joints, nut bolts, clamps etc are measured and paid separately under relevent items.
Disconnecting & taking out defective underground cable any size and any type from trenches, pole, pipe, floor, wall etc complete all as specified and directed.
Supply and laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 35 sqmm 3.5 core laid in trenches/ on poles/ road crossing or passing through existing/new pipe under road crossing, clamping on wall etc. Note: (i) Earth work, sand, bricks, removing, returning filling Aluminium thimbles/lugs will be paid separately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii) All equipments , machinery or tools if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
All as per Item No.30 here in above but size of cable 3.5 core 50 Sqmm complete all as specified and as directed.
All as per Item No.30 here in above but size of cable 3.5 core 70Sqmm complete all as specified and as directed.
All as per Item No.30 here in above but size of cable 3.5 core 95Sqmm complete all as specified and as directed.
All as per Item No.30 here in above but size of cable 3.5 core 150Sqmm complete all as specified and as directed.
All as per Item No.30 here in above but size of cable 3.5 core 185Sqmm complete all as specified and as directed.
All as per Item No.30 here in above but size of cable 3.5 core 300Sqmm complete all as specified and as directed.
All as per Item No.30 here in above but size of cable one core 625/630Sqmm complete all as specified and as directed.
Demolition of cement concrete of any description and in any position not otherwise specifically provided for cement concrete (unreinforced) or road cutting complete all as specified and as directed.
M&L for PCC 1:2:4 type B-0 using 12.5.0 mm graded crushed stone aggregate as in filling demolished surface or as leveling course or in foundation or under tiles or in any required work and make surface as per existing complete all as specified and directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises complete all as specified and directed.
M&L for coloured non skid ceramic tiles 7 to 8mm thick (Square/rectangular) area of each tile exc 0.06 sqm but n. exc. 0.11 sqm, as in floors set and jointed in neat cement slurry and pointed in coloured cement over and including 15mm thick screed bed /bedding layer in CM (1:6) complete all as specified and directed.
M&L chequered cement concrete tile 20 cm x 20cm x 25mm thick, set, jointed and pointed in neat cement slurry with gray cement and pigment in floors fixed over and including 20mm thick screed bed/bedding layer in CM (1:6), complete all as specified and directed.
Demolition of brick work or stone/boulder masonry, built in lime mortar including all quoins,arches, pillars, etc but excluding ashlar facing, dressed stonework and precast concrete articles complete all as specified and directed.
M&L for brick work with using sub class 'B' bricks straight or curved on plan exc 6 m mean radius, built in CM 1:6 and pointed flush as the work proceeds or in trenches, complete all as specified and as directed.
M&L for 10 mm thick rendering in cement morter 1:6 on fair surfaces of brick work or concrete surfaces to be finished even and smooth without using extra cement complete all as specified and directed.
M & L for loose filling in substations, under poles, under transformers, near LT panel and other areas of hard core broken to gauge not exc 63 mm broken stone/boulders incl leveling and spreading lime stone powder under stones complete all as per direction of Engr-in-Charge.
Excavation in hard/dense soil as in post holes or similar holes each n.exc 0.50 cum, getting out, returning filling in and ramming earth or broken rubble mixed with earth around in layers n.exc 25 cm, watering and removing surplus soil complete all as specified and directed.
S&F for posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; fixing of flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, welding etc. and similar work or any other work conforming to Fe-290 Gde E-165 etc. wind ties for roof including securing bolt complete all as specified and directed. Note: PCC will be measured and paid separately.
Supply, Fixing, fabrication and erection for hard drawn steel wire fabric cut to lengths bent to shape required and welding to steel frame weight n. exc 4 Kg per sqm complete all as specified and directed.
M&L for framed work as in doors or gates of angle or other section with gusset plates, rails, braces etc complete, drilled for fixing of steel sheeting or other covering doors etc. to be prepared for hanging or sliding with and including either hook and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete Fe-290 (Gde E-165) complete all as specified and as directed.
M&L for preparation of new iron or steel surfaces of any description, over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and directed.
S&F in replacement guarding wire Cradles, hexagonal /rectangular, fabricated with galvanised steel wire 3.15 or 4mm dia under overhead ACSR conductor to provide protection against conductor broken complete all as per direction of Engr-in-Charge. Note: (i) Cost of cross arms , nut , bolts, clamps etc shall be measured and paid separately.
S&F ACB 4 pole , 415 V, Manual drawout type of rated current 1250 Apms , Icu =50 kA , Ics =100% Icu , rated short time withstand current for 1 sec Icw=50 kA @ 415 Volts, disconnection time 23-32 ms, horizontal/vertical type with to protect the electric circuit against the dangers such as overload , short circuit incl complete accessories and connection with setting of tripping parameters incl dismantling and taking out old unservicable ACB complete all as specified and directed.
M&L for GI Nut, washers and screwed bolts (Machine made) of different length and dia as per site requirement with hexa or square heads on one end and screwed the others or both ends, each screwed end to be fitted with washer and one hexagonal or square nut complete all as specified and directed.
S&F in replacement Electronic - Micro-processor based MCCB 400 Amps, 36 KA 4 pole 415 Volts AC, Ics=100% Icu as per IEC 60947-II , adjustable overload setting Ir=0.4-1.0xIn , Tr 3-30 Sec, adjustable short circuit setting Isd=1.5-10xIr, Ground fault setting Ig=0.2-1xIn with double break contacts with spreader and phase barrier complete all as directed by Engr-in-charge.
S&F in replacement MCCB 400 Amps, 36 KA 4 pole 415 Volts AC, Ics=100% Icu as per IEC 60947-II , adjustable overload setting , adjustable short circuit setting with double break contacts with spreader and phase barrier complete all as specified and directed.
S&F in replacement MCCB TPN 250 Amps , 415 Volts, 36 KA, 4 Pole, Ics=100% Icu , overload adjustable short circuit adjustable type incl connection complete all as specified and directed.
S&F in replacement MCCB TPN 160 Amps , 415 Volts, 25 KA, 4 POLE, Ics=100% Icu , overload adjustable short circuit fixed type incl connection complete all as specified and directed.
S&F in replacement MCCB TPN 100 Amps , 415 Volts, 16/18 KA, 4 Pole, Ics=100% Icu , overload adjustable short circuit fixed type incl connection complete all as specified and directed.
Repair and replacement of Non contact AC voltage detector 12 A , voltage range 90 -1000 volts, 50/60 Hz ,low battery indicator, Auto power off with LED flash light and buzzer, CAT VI 1000 V safety category suitable to detect electricity when it is in close in range of live wire incl batteries and complete accessories all specified and directed by Engr-in-Charge.
Repair and replacement of Digital Clamp meter for measuring current, voltage and other parameters , AC current range 600 A, AC voltage range 600 Volt, data hold , Auto range, low battery indicator, Auto power off and buzzer, CAT II 600 V safety category incl batteries and complete accessories all specified and directed by Engr-in-Charge.
Repair and replacement insulating electrical safety gloves suitable for LV 1100 Volts electric supply as per IE rule complete all as directed by Engr-in-Charge.
Disconnecting & taking out defective underground cable from trenches, pole, pipe, floor, wall etc and locate the fault manualy, rectify the defect and relaying the XLPE cable underground PVC insulated and overall sheathed aluminum conductor heavy duty 1100 volts including connecting and testing for any size complete as directed by Engineer-in-Charge. Note: The rate of excavation/earth work deemed to be included in quoted rates and joints and any other item required shall be measured & paid separately under relevent item of BOQ.
S&F indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-150 Sqmm complete all as specified and directed.
S&F indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-300 Sqmm complete all as specified and directed.
S&F indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 400 Sqmm complete all as specified and directed.
S&F indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 1 x 500-630 Sqmm complete all as directed by Engr-in charge.
S&F straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4 x 25-50 Sqmm complete all as specified and directed. Note: Earth work will be measured and paid separately.
S&F straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-150 Sqmm complete all as specified and directed. Note: Earth work will be measured and paid separately.
S&F straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-400 Sqmm complete all as specified and directed. Note: Earth work will be measured and paid separately.
S&F aluminium tubular/ferrules / terminals (thimbles) in 1100 volt LT XLPE cable upto size 50sqmm incl dismantling old unserviceable thimbles of any type complete all as specified and directed.
S&F tubular/ferrules / terminals (thimbles) in 1100 volt LT XLPE cable upto size 70-185sqmm incl dismantling old unserviceable thimbles of any type complete all as specified and directed.
M & L for tubular/ferrules / terminals (thimbles) in 1100 volt LT XLPE cable upto size 240-400sqmm incl dismantling old unserviceable thimbles of any type complete all as specified and directed.
S&F LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 4 line as per IS complete complete all as specified and directed.
M & L for Chemical spray (DC> 2-26) having container 415ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricates, displaces and seals out moisture release rusted mechanism cleanse etc complete all as specified and directed.
M & L for spraying chemical (Roundup) on area to remove unwanted vegitation/grass at various locations as directed by Engr-in-Charge. Note: (i) Labour and equipments to spray chemical on required area are incl in quoted rates. (ii) Spray will be repeated quarterly or as per direction of Engr in Charge.
Supply & fixing or laying in replacement HDPE (DWC) tubing 100 mm dia of pressure rating 6Kgf/Cm2 fixing on poles, walls under floors, laying on surface etc as reqd at site and as per direction of Engr-in-Charge. Note: All accessories such as bend, joints, nut bolts, clamps etc deemed to be included in quoted rates.
M&L for detecting of fault in LT under ground cable with fault locator equipment . Note :- (a) The fault which is detected through cable fault locater will only be paid under this item (b) Charges of cable fault locator and DG set including transportation charges deemed to be included in the quoted rate. (c ) Earth fault locator will be provided by the contractor for even single fault and no dealy on this account will be acceptable otherwise penality will levied Rs 1000/- per day. (d) Necessary testing of cable after making joint will be deemed to be including in the cost of relevent item. However necessary earth work cable cutting , joint making Joint will be paid under relevant item.
Repair and replacement of hydraulic crimping machine with crimping range from 10 sqmm to 400 sqmm with standard dies from 10 mm to 400 mm complete all as specified and directed.
Re-stretching existing/retrieved ACSR conductor on LT pole and binding conductor on insulator properly using new binding wire/jumper wire complete all as specified and directed. Note : (i) Each Run of line conductor shall be measured & paid for separately.
Supply and fixing Busbar chamber based on single door enclosure construction duly powder coated , IP 42 , DMC insulators , CRCA sheet of 1.2 mm, cable entry from bottom , 04 nos. AL busbar of capacity 400 Amps suitable for set of 04 aluminium busbar 200 amps or three phases and neutral, locking arrangement tral, chamber may be fixed on pole , wall, surface as per site requiremnet complete all as specified and directed. Note: Nut, bolts, clamps, PCC and other items will be measured and paid separately.
S&F in replacement of on load changeover switches 4 pole 160 Amps , 415 volts , fixed in sheet metal enclosure allows changeover from main supply to generator supply & vice versa complete all as specified and directed.
S&F in replacement of on load changeover switches 4 pole 160 Amps , 415 volts , open type fixed in existing panel allows changeover from main supply to generator supply & vice versa complete all as specified and directed.
Dismantling post or struts (wood, steel or RCC) any section, including taking out embedded portion and making good disturbed ground post embedded in concrete, brick work, masonry etc complete all as specified and directed.
Supply, installation, testing and commissioning outdoor type cubical LT panel board of size not less than 1.2 mtr x 1.0 mtr x 0.60 mtr outer shell made out of 3.15 and inner shell made out of 2.0 mm thick MS sheet and MS angle section 50 x 50 x 6mm on PCC 1:2:4 type B-1 platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front and back openable double door system (each door hinged with body at 4 places) lockable, openable by keys, having pad lock arrangement with both side, with pad lock of three keys 2 nos. olouvers and air vent, gasket ‘u’ type for natural flow of air, completed dust & vermin proof suitable for 3 phase 4 wire 415 volt 50 Hz factor fabricated ( Factory approved from CPRI) having modern fabrication followed by power coated painting having thickness not less than 100 microns TPN aluminum bus bar 600 Amps insulated with colour coded heat shrinkable and shall be mounted on suitable size ‘F’ class insulators, marking connection with aluminum strip conductor of and general construction to IS-8623 of 1993 comprising of the following:-
Electronic - Micro-processor based MCCB 400 Amps, 36 KA 4 pole 415 Volts AC, Ics=100% Icu as per IEC 60947-II , adjustable overload setting Ir=0.4-1.0xIn , Tr 3-30 Sec, adjustable short circuit setting Isd=1.5-10xIr, ground fault setting Ig=0.2-1xIn with double break contacts with spreader and phase barrier complete all as directed by Engg-in-charge (incoming)-01
MCCB 160 Amps, 25 KA 4 pole 415 Volts AC, FP, overload adjustable and fixed short circuit (IOutgoing), -04 Nos.
RYB indication LED type, 22.5mm dia, 230 volts protected with MCB SP 2 Amp showing 3 phase supply -03 Nos
Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves etc complete
Note (i) The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc. (ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694. (iii) Panel drawing shall be got approved before placing of order from Engr-in-Charge/GE. (iv) The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated.
Supply, installation, testing and commissioning indoor type cubical LT panel board suitable for fixing 01 nos ACB of capacity 1250 Amps draw out type as incomer and 06 nos. of MCCBs of capacity 400 Amps each as outgoing , size of panel not less than 1.6 m x 1.2 m x 0.8 m shell made out of 2.00 mm thick MS sheet and MS angle section 50 x 50 x 6mm on PCC 1:2:4 type B-1 platform 60cm above the ground level and 45cm below the ground level, factory fabricated , lockable, openable by keys, having pad lock arrangement with both side, with pad lock of three keys 2 nos. olouvers and air vent, gasket ‘u’ type for natural flow of air, completed dust & vermin proof suitable for 3 phase 4 wire 415 volt 50 Hz factory fabricated having modern fabrication followed by power coated painting having thickness not less than 100 microns TPN aluminum bus bar 1600 Amps insulated with colour coded heat shrinkable and shall be mounted on suitable size ‘F’ class insulators, marking connection with aluminum strip conductor of and general construction to IS-8623 of 1993 comprising of the following:-
RYB indication LED type, 22.5mm dia, 230 volts protected with MCB SP 2 Amp showing 3 phase supply -03 Nos
Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves etc complete
Note (i) The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc. (ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694. (iii) Panel drawing shall be got approved before placing of order from Engr-in-Charge/GE. (iv) The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. (v) MCCBs and ACBs will be measured and paid separately under relevent items.
M & L for Black colour PVC electrical insulation tape role of length 16m -20m and width 18 mm to 22 mm , single sided suitable for voltage upto 600 volts complete all as specified and directed by Engr-in-Charge.
S&F overvoltage relay 230 V AC, U>275 V AC, 3 Phase in 1 module suitable for 3 Ph+N incl complete connections with MCB 4 pole all as specified and directed. Make: Madel No. MZ 216 of Hager or equivalent in Schenider or Legrand.
S&F in replacement MCB TPN 415 Volts, 'C' series, breaking capacity 10 KA of rating 63 Amps suitable for fixing with overvoltage relay incl connection complete all as specified and directed. Note: Make of MCB TPN will be same as overvoltage relay.
R D Bansal
M/S kuldeep kumar khullar
M/S JAI MAA JAGDHAMBA CONSTRUCTION
M/S Sonu Traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .