| 1 | L1₹25.8 LAccepted-AOC NEW HOSPITAL ROAD UDHAMPUR UDHAMPUR UDHAMPUR UDHAMPUR JAMMU KASHMIR 182101 | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L1 | Accepted-AOC L1 | |
| 2 | L2₹30.3 L+₹3.9 L (14.9%)Rejected-Finance WARD NO 1 HOUSE NO 04 SUBASH NAGAR UDHAMPUR 182101 J K | UDHAMPUR | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L2 | Rejected-Finance BEING L2 | |
| 3 | L3₹32.5 L+₹6.1 L (23.2%)Rejected-Finance MILITARY HOSPITAL ROAD UDHAMPUR 182101 J K | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L3 | Rejected-Finance BEING L3 | |
| 4 | L4₹33.6 L+₹7.2 L (27.4%)Rejected-Finance | L4 | Rejected-Finance BEING L4 | |
| 5 | L5₹34.1 L+₹7.7 L (29.1%)Rejected-Finance 15A 9 CHOWBHAGA ROAD KOLKATA KOLKATA 700039 | KOLKATA | WEST BENGAL | 700039 | L5 | Rejected-Finance BEING L5 |
Tender Value
Refer Docs
EMD Value
₹65,000
Closing Date
20 Dec 2022, 6:00 pmClosed
GE AF UDHAMPUR
GE AF UDHAMPUR
MAINT OF AFLS, TAXITRACK LIGHT, OBSTRUCTION LIGHT, HELIPAD LIGHT ALONGWITH CERTAIN MISC FITTING/FIXTURE AT 39 WING AT AF STN UDHAMPUR
2022_MES_565844_1
GE/AFU-58/2022-23
Open Tender
Civil Works
Item Rate
270 days
GE AF Udhampur
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
Yes
GE AF UDHAMPUR
₹65,000
Yes
13 Feb 2023
29 Nov 2022
22 Dec 2022
29 Nov 2022
20 Dec 2022
14 Dec 2022
29 Nov 2022 - 6 Dec 2022
Amount
Supply and Laying Cable XLPE insulated screened PVC bedded galvanized steel strips or wire armoured, cables (heavy duty) ISI marked with stranded aluminium conductor, 1100 volts grade and connecting and testing in trenches, under floors/ roads or on walls complete including taking down old complete all as specified and directed of following sizes :- (Note 1.: Earth work, excavation shall be measured & paid separately under respective item of Schedule and wherever cable laying on walls and uses of thimbles, GI clamps or PVC clamps according to the cable sizes etc rates shall deemed to be included in the quoted rates). make- Havells/Gloster/Polycab
Cable size 10 sqmm 4 core
(b) Cable 50 sqmm 3.5 core complete
Cable 70 sqmm 3.5 core complete
Cable 120 sqmm 3.5 core complete
Cable 150 sqmm 3.5 core complete
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for laying of cable and foundation of poles, stays and getting out in any type of soil, all as specified.
Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick each layer in any type of soil complete all as specified and as directed by Engineer-in-Charge.
Removing surplus excavated material to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5m above the starting point complete, all as specified and as directed by Engineer-in-Charge.
M & L for Sand cushioning to underground cable, provided with a layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable all as specified and directed. by Engineer-in-Charge. Note: Punned thickness of sand shall be measured.
Common burnt sub class ‘B’ brick laid flat in trenches over and across the length of cable with length of brick perpendicular to the direction of cable adjacent/abutting each other complete all as specified and directed for cable protection.
Repair and replacement of GI tube light grade of bore 50 mm with all fittings and fixed complete to walls and ceiling or laid in floor for cable crossing including cutting of bitumen roads/PCC and making good after laying of cable up to building height complete including taking down all as specified and directed by Engr in charge
Repair and replacement of GI tube light grade of bore 80 mm with all fittings and fixed complete to walls and ceiling or laid in floor for cable crossing including cutting of bitumen roads/PCC and making good after laying of cable up to building height complete including taking down all as specified and directed by Engr in charge
M&L complete for drilling hole through machine under hard standing /road in different location as per site requirement (between 03 mtr to 40mtr maximum) for laying of pipe for protection of cable etc by means of bookle and without disturbing the top surface and making good the disturbed surface if any complete all as specified
M&L for disconneting and taking down U/S High Mast light fitting from the steel tower and repair the same (of any type, capacity & make) by replacement of spare parts & making the fitting functional and refixing after repairs all as specified and directed by Engineer-in-Charge. Note : Spare parts/accessories required to be replace shall be measured and paid seperately as "Supply only" under the relevent items.
M&L for cleaning and greasing,lubrication of High Mast light lowering device and making it smooth to operate as specified and directed by Engr-in-charge. Note :- 1. Greasing to GI wire and electric motor shall deemed to be included in the quoted rate. 2. Rate shall deemed to be included for the use of hydra for repairing the high mast light.
M&L for repair of gear box of High Mast light lowering device and making it smooth to operate as specified and directed by Engr-in-charge.
Supply and fix 250 watt LED flood light, outdoor type with IP 66 protection, PF>= 0.90, lumen efficacy >= 100 lumen/watts, 5700 K, light luminaire engergy saving, environmental friendly long life with high power led as light source suitable for highlighting architectural feature or area lighting also suitable to rough services over the high mast tower of appx height upto 15 to 20 Mtr incl taking down old one etc from the tower complete as specified and directed Make- Wipro cat part No LF20-342-060-57-XX or equivalent HPL/Havells/CG etc as approved by GE. Note :- (a) Rate shall deemed to be included for taking down old unsv and fixing of flood light above the High Mast Tower at the height of 15 to 20 Mtr including proper alingment of Bracket of tower in symmetrical manne including minor repair etc.
S & F street light bracket made out of 40/50 mm dia GI heavy grade tubing not less than 1.5 Mtr long bend to shape including pole clamps made out of 50 x 6 FI and nut bolts and washers all as specified and directed including taking down old.
Supply and fix 1.5 Sqmm 2 core cable, PVC insulated and PVC round sheathed, copper conductor (flexible) industrial cable, 1100 volt, confirming to IS :694 including replacement of old unsv cable complete all as specified and directed by Engr-in-Charge.
M & L in replacement of LED Driver with surge protector suitable for 60 to 90 watt LED fitting with universal voltage 90-300 volts alternating current ,short circuit,over temperature and over load protection complete all as specified and directed by Engr-in-charge.Make C&S/ Wipro /Philips/syska/havells/Bajaj or equivalent as approved by GE. Note:-Driver & surge protector shall be of same make or suitable for LED fitting as available at site..
Replacement old/burnt LED light driver suitable for LED Flood light fitting of capacity upto 50/60/120/200 watt with existing make or equivalent out of makes specified in list of make complete all as specified and directed by Engr-in-Charge
M&L for preparation of old painted surface of pole of less than 6 mtr by removing all dirt, dust etc and apply paint with good finishing complete all as specified and directed.
M&L for preparation of old painted surface of electric steel pole by removing all dirt, dust etc and apply one coat of aluminium paint on complete steel surface including cross arm and writing of identification No , etc complete all as specified and directed
Supply and fixing of DWC HDPE tubing 50 mm bore for open/underground laying cable, cut to size and making the tubing for cable protection including cutting of road etc/cutting of PCC and making the good surface complete all as specified and directed by Engr-in-Charge.
Supply and fixing of DWC HDPE tubing 80 mm bore for open/underground laying cable, cut to size and making the tubing for cable protection including cutting of road etc/cutting of PCC and making the good surface complete all as specified and directed by Engr-in-Charge. Note for item no 20 & 21 :- (a) The using of GI Clamp in the wall/drainage rate are deemed to be included in the quoted rate. (b) The insulation of DWC pipe should be of high that does not deteriorate with UV rays/ heavy sun rays/winter season etc. (c) Drawing existing cable through DWC pipe or use of pipe and entry and exit of cable shall be deemed to be included in the quoted rates.
M&L cement concrete (1:3:6), type C-2 using 40 mm graded stone aggregate in foundations, filling and mass concrete complete for making coping of street/security pole of size 60x60x30 cm along with GI Pipe of 40mm light grade for entry/exit of cable all as specified and directed by Engr-In-charge. Note: The rate of pipe is seperately quoted in the schedule
M&L for bricks works with sub class B bricks straight or curved on plan exc 6m means radius built in cement mortar 1: 6 etc complete as specified and directed by Engr-in-Charge.
M&L for retro reflective signs with a corrosion resistance 03 mm thick aluminium composite panel face to be fully concord with high intensity prismatic sheeting type IV as per IRC-67:2012 retro reflective sheeting with MS angle frame of size 40 x 40 x 6 mm, along with HIP grade type IV sheeting, metallic border, aerows, name of plant/installation/destination name, Stainless steel nuts, bolts and washers and rivets including ploting/pasting/anti-corrosive paint - 02 coat over two coat of red oxide paint etc all as specified and directed by Engr-in-Charge. Note :-(a) Frame work excluding the ACP sign board shall be measured and paid separately. (b) letter writting shall deemed to be including in the quoted rate.
Supply and fixing of Mild steel frame work such as angles of size not less than 25x25x4 mm for supporting of aluminium composite panel including drilling and countersunk for screw, bending and welding angles, as necessary all as specified and directed by Engr-in-Charge.
Supply and fixing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 4 Sqmm x 2 Core complete all as specified and directed by Engr-in-Charge. Note :- (1) Cable laying on the wall/cement piller and uses of thimbles, PVC Clamp/Iron Clamp etc rates shall deemed to be included in the quoted rates.
Supply & fix sheet metal enclosure MCB distribution board. Single pole & neutral 240 volts 2 way with IP-43 IK-09 protection single door complete with appropriate size in wall including chases wall for fixing DB and making good distributed wall surfaces to match with existing specification . Make : HPL or equivalent as approved by Garrision Engineer.
Supply and fixing MCB single pole & neutral 240, 'C' curve SPN 32 amps,with rupturing capacity 10 KA and current carrying capacity in the MCB DB complete with connection testing and commissioning as specified and directed by Engr-in-Charge. Make : HPL or equivalent as approved by Garrision Engineer.
Supply and fixing LED flood light 70 watt 230 V in the retroreflective sign boards, AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp. Make :- HPL/Wipro/Havells or equivalent as approved by Garrison Engineer.
M&L for submain wiring with two single core 2.5 sqmm (2x 2.5 sqmm) PVC FR insulated unsheahted flexible copper conductor and one single core 2.5 sqmm PVC FR insulated unsheahted flexible copper conductor green colour as earth lead in and including concealed PVC conduit light grade cutting chases to wall for laying conduit and making good the disturbed wall surfaces to match with existing specification all as srequired at site or directed by engineer in charge Note :Earth wire is connected to Existing Earthing . Make : Finolex/Plaza/Havells
M&L for insulated tape of size 25 mm width , 20 Meter long and 1 mm thick complete all as per directed by engineer in charge
M&L for spraying the chemical (Roundup) in sub station in the ration 1: 3 for buring the grass every three month as specified and directed by Engr-in-charge.
M&L for Weather proof outdoor bus bar chamber wall mounted, made out of MS sheet comprising of Copper strips each of 200 Amps, 4 way,appx 60cm long duly insulated mounted on insulators including complete with all accessories and connections with copper thimbles, nuts, bolts & washers including cable glands at entry and outlet points including taking out old unserviceable bus bar chamber complete all as specified and directed by Engr-in-charge. Make :-Havells cat part No IHBC025004 or equivalent as approved by GE.
M&L for Weather proof outdoor bus bar chamber wall mounted, made out of MS sheet comprising of Copper strips each of 200 Amps, 8 way,appx 60 cm long duly insulated mounted on insulators including complete with all accessories and connections with copper thimbles, nuts, bolts & washers including cable glands at entry and outlet points including taking out old unserviceable bus bar chamber complete all as specified and directed by Engr-in-charge. Make :-Havells cat part No IHBC025008 or equivalent as approved by GE.
Disconnecting and taking down old unserviceable of bus bar chamber and Weather proof outdoor bus bar chamber, made out of 3.15 mm thick MS sheet comprising 4 Nos Copper strips each of 300 Amps, 60cm long duly insulated mounted on insulators incl MCCB 250 Amp 02 Numbers (one incoming and one outgoing) complete with 4 No’s mounting legs made out of 50mm x 50mm x 6mm angle iron grouted in PCC block of size 30cm x 30cm x 90cm (30cm depth below ground level and 60cm above ground level) in cement concrete 1:3:6, type C-2 (using 40mm grade crushed stone aggregate), and connections with size of aluminium thimbles, nuts, bolts & washers including cable glands at entry and outlet points including excavation and earth work, returning filling and removal of surplus soils, including taking out old unserviceable bus bar chamber complete all as specified and directed by Engr-in-charge.
Supply & installation and testing & Commissining CPRI approved outdoor cubical type IP 54,LT feeder piller box suiable for 415V, 3 phase 50 Hz , AC supply system, dust,weather & vermin proof, made of 3.15 mm thick MS sheet for outer shell and 2 mm thick for inner shell having TPN copper busbars of rating 600 Amp Cap of length not less than 60 cm and suitable size of strip for 3 phase and neutral with colour code heat shrinkable sleeve and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, inter connection of incoming and outging cable etc and Bottom base channel of MS section not less then 50 mm x 50 mm x 5 mm thick grouted in PCC block of size 30 cm x30 x 90 cm (30 cm depth below ground level and 60 cm above ground level) in cement 1:3:6, type C-2 (using 40 mm grade crushed stone aggregate and connection of cables with suitable size of thimble, nuts, bolts & washers including cable glands at entry and outlet points including execavation and earth work, returing filling and removal of surplus soil, double door both side opening single door system lockable/openable by key from both sides having flush pattern fancy locks with louvers as per site requirement with the following :- (a) CT's ration 600/05, CL 1.0 Tape wound - 01 set (Set of three) (b) Digital Voltmeter & Ammeter - 02 Nos (b) Phase indicator lamp RYB LED type - 1 Set (Set of three) Incoming: (a) MCCB 400 Amp 415V, 50 Hz, FP, 36 ka, Ics= 100% Icu, fixed type complete all as specified and directed by Engr-in-Charge. Note :- Panel shall be installed at least 60 cm above ground
Supply & installation and testing & Commissining CPRI approved outdoor cubical type IP 54,LT feeder piller box suiable for 415V, 3 phase 50 Hz , AC supply system, dust,weather & vermin proof, made of 3.15 mm thick MS sheet for outer shell and 2 mm thick for inner shell having TPN copper busbars of rating 400 Amp Cap of length not less than 60 cm and suitable size of strip for 3 phase and neutral with colour code heat shrinkable sleeve and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, inter connection of incoming and outging cable etc and Bottom base channel of MS section not less then 50 mm x 50 mm x 5 mm thick grouted in PCC block of size 30 cm x30 x 90 cm (30 cm depth below ground level and 60 cm above ground level) in cement 1:3:6, type C-2 (using 40 mm grade crushed stone aggregate and connection of cables with suitable size of thimble, nuts, bolts & washers including cable glands at entry and outlet points including execavation and earth work, returing filling and removal of surplus soil, double door both side opening single door system lockable/openable by key from both sides having flush pattern fancy locks with louvers as per site requirement with the following :- (a) CT's ration 400/05, CL 1.0 Tape wound - 01 set (Set of three) (b) Digital Voltmeter & Ammeter - 02 Nos (b) Phase indicator lamp RYB LED type - 1 Set (Set of three) Incoming: (a) MCCB 250 Amp 415V, 50 Hz, FP, 36 ka, Ics= 100% Icu, fixed type complete all as specified and directed by Engr-in-Charge. Note :- Panel shall be installed at least 60 cm above ground
Supply, installing, testing and commissioning of LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. Shall be dust and vermin proof, protection class (IP-54) and made of 3.15 mm thick CRCA SHEET & suitable frame work/ support made out of MS section of size 50 x 50 x 6 mm, front opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete and PCC (1:3:6) type C-2 foundation of size including connections of all out going/in coming existing cables of any size by drawing /digging out cable inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size of copper lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board and taking out of old skelton type panel with control switches complete all as specified and as directed by Engr-in-Charge. including the following items incorporated same panel and removed old unserviceable panel.The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 300 Amp insulated copper strip of length not less than 60 cm and suitable size of strip for 03 phase and neutral, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Volt Meter, 96X96mm, flush type rated 0-500V, with Volt meter push button type- 01 Set. (ii) Digital Amp Meter, 96X96mm, flush type rated 0-300A, with Amp meter push button type- 01 Set. (iii) C.T's 300/5 A CL 1.0 Tape Wound- 01 Set. (Set of three) (iv) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider or equivalent as approved. INCOMING SUPPLY :- (i) MCCB 160 Amps 36 KA , ICS 100% of ICU, 0.8 ln to 1 ln, 4 Pole with Thermal Magnetic trip, adjustable type overoad setting, 415 volts , frequency 50Hz,=01 No OUTGOING SUPPLY :- (i) MCCB 100 Amps 16 KA , 4 Pole fied type, 415 volts , 50Hz,=02 No., (ii) MCCB 40 Amps 16 KA , 4 pole, fixed type, 415 volts , 50Hz,=01 No. Make of MCCB:-L&T/ Siemens / Legrand or equivalent as approved. Note for Item No 35 to 38 :- The panel manufacturer should have following Govt. Approved Certificates: 1. Panel shall be installed at least 45 cm above ground 2. All civil/electrical work & material is deemed to be included in the quoted rates 3. Drawing of panel shall be got approved from GE.
M&L for replacement of Earthing with Galvanised Earth Plate Electrode 600x600x6 mm thick burried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre connected to GI strip 32 x 6 mm size and earthing lead protected with 50 mm bore GI pipe, light grade, filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to GI strip by means of GI nuts, bolts and washers strip connected to earth plate including necessary excavation and earth work in any type of soil so as to achieve earth resistance including excavation of polypit chamber with polyplastic pit cover (cost of polypit chamber with polyplastic pit cover shall be deemed to be included in the rate quoted) complete all as specified and as directed by Engineer-in-Charge including dismantling of existing unserviceable earthing.all as shown in Electrical Plate No. 3 of MES Schedule Part-I complete all as per specified and as directed by Engr-in-Charge.
M&L for replacement of Galvanised Iron Strip 32x6mm with Saddles and fixing Screws for Roof/Earth Conductors and Down Conductors, complete all as specified and as directed.
Material and labour for MCCB 4 Pole, 415 V, fixed type,thermal magnatic load ICS100% of ICU, 0.8 ln to 1ln, 63 Amps with breaking capacity 16 KA complete all as specified and directed by engineer in charge. Make :- Standard/Havells/Schneider/ABB or equivalent as approved by GE.
Material and labour for MCCB 4 Pole, 415 V, fixed type,thermal magnatic load ICS100% of ICU, 0.8 ln to 1ln, 100 Amps with breaking capacity 36 KA complete all as specified and directed by engineer in charge . Make :-Standard/Havells/Legrand or equivalent as approved by GE.
Material and labour for MCCB 4 Pole, 415 V, adjustable type, adjustable type,thermal magnatic load ICS100% of ICU, 0.8 ln to 1ln, 160 Amps with breaking capacity 36 KA complete all as specified and directed. Standard/Havells/Legrand or equivalent as approved by GE.
Material and labour for MCCB 4 Pole, 415 V, adjustable type,thermal magnatic load ICS100% of ICU, 0.8 ln to 1ln, 250 Amps with breaking capacity 36 KA complete all as specified and directed. Make :- Standard/Havells/Schneider/ABB or equivalent as approved by GE.
Material and labour for MCCB 4 Pole, 415 V, adjustable type, adjustable type,thermal magnatic load ICS100% of ICU, 0.8 ln to 1ln, 400 Amps with breaking capacity 36 KA complete all as specified and directed. Standard/Havells/Schneider/ABB or equivalent as approved by GE.
Supply and fix heat shrinkable End termination kits and accessories of following capacities and type:-
Outdoor/indoor 70 to 150 Sqmm 3.5/4 core cable jointing kit for 1.1 KV grade cable
Outdoor/indoor 185 Sqmm 3.5/4 core cable jointing kit for 1.1 KV grade cable
Outdoor/indoor 16 to 25 Sqmm 3.5/4 core cable jointing kit for 1.1 KV grade cable
Outdoor/indoor 35 to 50 Sqmm 3.5/4 core cable jointing kit for 1.1 KV grade cable
Supply and fix heat shrinkable straight through joint kit and accessories of following capacities and type:-
Straight through joint kit indoor/outdoor al conductor cable of size 70 to 150 Sqmm and 3.5/4 core
Straight through joint kit indoor/outdoor al conductor cable of size 185 Sqmm and 3.5/4 core
Straight through joint kit indoor/outdoor al conductor cable of size 10 to 16 Sqmm and 3.5/4 core
Straight through joint kit indoor/outdoor al conductor cable of size 25 to 50 Sqmm and 3.5/4 core
Supply and fix Powder coated Pin Type Panel lock in round shape (Male & Female socket) diameter appx 22 mm for female socket complete all as specified and as directed by Engr-in-charge
Taking out old steel tubler poles 9 mtr by breaking PCC foundation, and all related work and making the site well finished and Shifting of Pole to another location within 39 Wing area (i.e.Tech Area/Upper camp etc) complete all as specified and as directed by Engr-in-charge.
M&L for Fixing steel tubular pole single arm type 9 M retrieved from item No 42 hereinbefore including excavation in trenches in soft/ loose soil n exc1.5 M wide and net exc 1.8 M in depth and triming the sides , boring bottom surfaces to required level, providing PCC (1:3:6) type D-2 using 40mm stone agregate in foundation, 1.5 mtr GI pipe medium grade of 40mm dia for cable protection and PCC 1:2:4 type B-1 coping of pole including neccessory frame work complete all as specified and as directed by Engr-in-charge.
Supply only non -metallic PVC clamps required for cables laying above the wall/drainage/PCC area of size 20 sqmm etc.complete all as specified & as directed by Engr-in-Charge.
Supply only non -metallic PVC clamps required for cables laying above the wall/drainage/pcc area of size 40 sqmm etc.complete all as specified & as directed by Engr-in-Charge.
Taking down old unserviceable flexible pipe and M&L for flexible pipe of size 25 mm complete all as per specified and directed by Engr-in-Charge.
Taking down old unserviceable flexible pipe and M&L for flexible pipe of size 50 mm complete all as per specified and directed by Engr-in-Charge.
Taking down old unserviceableflexible pipe and M&L for flexible pipe of size 80 mm complete all as per specified and directed by Engr-in-Charge
Supply and fixing of suitable size of nut, bolts/ washers of brass/GI for replacing defective nut, bolts etccomplete all as specified and as directed by Engr-in-Charge Make : TVS or equivalent as approved by GE.
Heavy duty porcelain/poly carbonate insulators of size 32 x 32 mm to be fixed on wall/roof/pipe for laying of copper strip as roof/down conductor on building of height between upto 25 metres including nuts & bolts of brass of appropriate size all as specified and as directed by Engr-in-Charge
Repair and Replacement of MCB TPN 63 Amps, 240 Volts, having breaking capacity 10 kA, 'C' curveminiature circuit breaker (MCB) including taking down existing old unservicable including accessories therein & disposing from site complete all as specified and as directed.
Repair and Replacement of MCCB 3 Pole, 415 V, adjustable type thurmal magnitic ICS100%, 100 Amps with breaking capacity 36 KA as per existing MCB suitable of size with connected assosieries etc. Conplete all as specified and as directed by Engr-in-Charge.
Supply and fixing of MCB SPN 6 to 32 Amps, 240 Volts, having breaking capacity 10 kA, 'C' curveminiature circuit breaker (MCB) curveminiature circuit breaker (MCB) in the existing street light junction box including all accessories therein complete all as specified and as directed by Engr-in-Charge.
Supply and fixing of Change Over 200 Amps, Off load changeover switch 415 V, as per existing change over suitable of size with connected assosieries complete all as specified and as directed by Engr-in-Charge.
Supply and fixing of Change Over 100 Amps, Off load changeover switch 415 V, as per existing change over suitable of size with connected assosieries complete all as specified and as directed by Engr-in-Charge
Supply and fix 3 pole Mini power contactor type MNX 32 of AC1 rating of 55 amps of capacity suitable alongwith left and right auxiliary contact (1NO +1NC) for upto 20 KVA DG set ,AC 415 Volts, 50 Hz for AMF panel including testing or as per existing make/type/rating/model for AMF panel boards etc and taking down old unserviceable complete all as specified and directed by Engr-in-Charge.
S&F in replacement of Locking box made out of MS Sheet 16 Swg of Size 300x200x100mm comprising of aluminium Bus Bar 63 Amp Duly insulated mounted on porcelen fixed in locking box with nut bolts and washers including one number MCB 6 Amp 10 KA 240 Volts for protection of street lights complete all as specified and as directed by Engr-in-charge.
Supply only electronic control timer type ET-100 of suitable capacity or existing make,model and capcity etc as required at site incl taking down old one etc complete as specified and directed
Supply and fix 3/4 pole power contactor MCE 22 (2NO and 2NC), 250 amps of capacity suitable for upto 160 KVA to 200 KVA DG set ,AC 415 Volts, 50 Hz for AMF panel including testing or as per existing make/type/rating/model for AMF panel boards etc and taking down old unserviceable complete all as specified and directed by Engr-in-Charge.
Supply & fix 3/4 pole power contactor MCX 32 (2NO and 2NC), 200 Amps of capacity suitable for upto 62.5 KVA to 100 KVA DG set ,AC 415 Volts, 50 Hz for AMF panel including testing or as per existing make/type/rating/model for AMF panel boards etcand taking down old unserviceable complete all as specified and directed by Engr-in-Charge.
Supply & fix 3/4 pole power contactor MCE 15 R, 160 Amps of capacity suitable for upto 10 KVA to 40 KVA DG set ,AC 415 Volts, 50 Hz for AMF panel including testing or as per existing make/type/rating/model for AMF panel boards etc and taking down old unserviceable complete all as specified and directed by Engr-in-Charge.
S & F in repair Procom DGC-6D controller for electronic control panel for DG set of 10 KVA to 100 kvaor existing make/type/rating/model for AMF panel boards etc and taking down old unserviceable complete all as specified and directed by Engr-in-Charge.
Disconnecting and Taking down old unserviceable annunciator and M&L for electronic digital annunciator as per existing make,model & capaicty etc complete as specified and directed by Engr-in-Charge
Disconnecting and Taking down old unserviceable push button and M&L for Push button as per existing make,model & capaicty etc complete as specified and directed by Engr-in-Charge
Disconnecting and Taking down old unserviceable ammeter and M&L for digital/analog ammeter as per existing make,model & capcity etc complete as specified and directed by Engr-in-Charge.
Disconnecting and Taking down old unserviceable voltmeter and M&L for digital/analog voltmeter as per existing make,model & capcity etc complete as specified and directed by Engr-in-Charge.
Disconnecting and Taking down old unserviceable VAF/AVF meter and M&L for VAF/AAVF meter as per existing make, model & capcity etc complete as specified and directed by Engr-in-Charge
Disconnecting and Taking down old unserviceable relay and M & L for under voltage relay as per existing make,model & capcity etc complete as specified and directed by Engr-in-Charge
Disconnecting and Taking down old unserviceable of HRC fuse and supply and fixing of HRC fuse of capacity 315 Amps ,415 V,20.2 W as per IS :13703(part-II),IEC :60269-2 complete as specified and directed by Engr-in-Charge.Make : L&T /Havells
Disconnecting and Taking down old unserviceable of CT and M&L for indoor tape insulated ring type low type CT of ratio 100/5, 200/5 or 300/5 A ,or as per existing make or model complete all as specified and directed by Engr-in-Charge.
Disconnecting and Taking down old unserviceable of battery charger and M&L for battery charger 12 volts ,10 AH,input 220 Volts AC complete as specified and directed by Engr-in-Charge.
Supply and fixing crocodile clip for battery terminal of required size all as specified and directed by Engr-in-Charge.
S&F auxilliary contacts for change over switch of capacity 250 amps to 315 Amps or as per existing make/model incl taking down old one etc complete as specified and directed by Engr-in-Charge
S&F operating handle of change over switch of capacity 125 Amp to 200 Amp or as per existing size/make/model incl taking down old one etc complete as specified and directed by Engr-in-Charge.
S & F in repair PVC heavy duty pipe of size 10 mm dia for Diesel tank indicator with suitable clamps including taking down old unserviceable complete all as specified and directed by Engr-in-Charge
S&F PVC pipe of size 25 mm dia heavy duty for fol distibution including taking down old unserviceable complete all as specified and directed by Engr-in-Charge
M&L for cleaning and day to day maintenance of Lt Distribution panels installed at sub staion by using cotton waste -10 kg, yellow cloth 1x1 meter size-05 nos, Air cleaner blower and two broom stick -04 for cleaning DG Set installation all as directed by Engr-in-Charge.
M&L for cutting the existing cable from loop near the panel and making end termination with aluminium lugs of suitable size without jointing kit with cable glands suitable for LT U/G cable of following sizes:
120 x 3.5 to 185 x 3.5 sqmm .
50 x 3.5 to 95 x 3.5 sqmm .
M & L for 3.15 mm CRCA MS Sheet with 02 (two) coat Machine spray paint over one coat red oxide primer/paint alongwith fixing arrangement through nut, bolts or welding etc suitable for panel base plate or panel canopy all as specified and directed by Engineer-in-Charge. Note :- Rate include for making the hole in the gland according to the size of cable and re-connecting the cable in the existing panel etc.
M & L for brazing work with copper brazing alloy rod with help of oxygen and LPG cylinder using required copper strip of size 20mm x 3mm upto 30 mm length along with cleaning work of strip with descaling solution/emery paper which are laid as roof/down conductor on any height of building complete all as specified and directed by Engr-in-Charge.
M & L for brazing work with copper brazing alloy rod with help of oxygen and LPG cylinder using required copper strip of size 25 mm x 3mm upto 30 mm length along with cleaning work of strip with descaling solution/emery paper which are laid as roof/down conductor on any height of building complete all as specified and directed by Engr-in-Charge.
M & L for brazing work with copper brazing alloy rod with help of oxygen and LPG cylinder using required copper strip of size 32mm x 6mm upto 30 mm length along with cleaning work of strip with descaling solution/emery paper which are laid as roof/down conductor on any height of building complete all as specified and directed by Engr-in-Charge.
Laying only LT UG cable 10 sqmm x 4 core to 185 sqmm x 3.5 core cable shall be provided under Sch 'B'/underground the existing cable etc making all electrical connections as directed by Engr-in-Charge. Note :- 1. Execavation shall be got done alongwith other items of cable required for laying of cable and shall be paid in respective items for laying existing overground cables. 2. Laying of existing cable shall be done through department labour/employee
DAVINDER SINGH
RANBIR ENTERPRISES
PAWAN KUMAR GOVT. CONTRACTORS
M/S M P Construction Co
K S BUILDERS
KARAN TRADERS
MOHAN LAL AND SONS
shivom builders
Kanwal Enterprises
ANIKET TRADERS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .