Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.9 LAccepted-AOC RZF 498 MG MARG RAJ NAGAR II PALAM DELHI CANTT 110077 | NEW DELHI | DELHI | 110077 | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹26.0 L+₹4,881 (0.19%)Rejected-Finance D 662 WZ 1598 R 1 NANGAL RAYA NEW DELHI 110046 | NEW DELHI | NEW DELHI | DELHI | 110046 | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹26.0 L+₹6,460 (0.25%)Rejected-Finance C 9 53 SECTOR 8 ROHINI NEW DELHI 110085 | NEW DELHI | NEW DELHI | DELHI | 110085 | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹26.9 L+₹92,180 (3.55%)Rejected-Finance A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | L4 | Rejected-Finance Other than lowest | |
| 5 | L5₹26.9 L+₹93,085 (3.58%)Rejected-Finance RZ 18 260 WEST SAGARPUR NEAR MCD SCHOOL NEW DELHI 110046 | NEW DELHI | NEW DELHI | DELHI | 110046 | L5 | Rejected-Finance Other than lowest |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
20 Dec 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE UTILITY PLANT AND MACHINERY DELHI CANTT-10
GE UTILITY PLANT AND MACHINERY KIRBY PLACE DELHI CANTT-10
PREVENTIVE AND COMPREHENSIVE MAINTENANCE OF MAIN AND STANDBY POWER SYSTEM, PRECISION COOLING, FIRE SUSPPRESSION SYSTEM AND ALLIED ACCESSORIES FOR PROJECT VYOMA AT 1 WEC UNDER GE(U) PM DELHI CANTT-10.
2021_MES_491262_1
GE(U)/PM/D-51/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
DELHI CANTT
MES contractor enlisted under class D category b(i)/c(i) having deposited standing security of Rs 100000 with department. Contractor not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category.
6 documents required · 6 mandatory
₹500
GE UTILITY PLANT AND MACHINERY DELHI CANTT-10
₹60,000
Yes
29 Dec 2021
29 Nov 2021
22 Dec 2021
29 Nov 2021
20 Dec 2021
13 Dec 2021
60 days
Amount
SECTION-I
Periodical, preventive and comprehensive maintenance to Integrated Data Centre Solution/IT Racks (02 Nos) suitable for 35 KW IT load distributed in 4 Racks which provide active approx 165 U space for IT devices of OEM VERTIV and consisting of the following :- (i) Precision Air Conditioning (04 Nos) :- Direct Expansion microprocessor based precision AC units (Para metric cooling CFM) of min 35 KW sensible capacity precision AC unit with air cooled condenser, digita scroll compressor in each unit with suitable refrigerant circuits, evaporator coil with hydrophilic coating, direct driven electronic thermostatic expansion valve suitable for environment friendly R410A refrigerant, electric heater locking disconnect switch, adjustable modular baffle system, heater, clocked filter, 2 Nos rack sensors, Infrared humidifiers and vibration isolator. The unit refrigerant circuit has factory installed solenoid valve and service valves. Motor is suitable for 415V + 10%, 50 cycles, 3 phase AC supply with EC fan and external static pressure 20 Pa. Smart row capacity modulated cooling, which is self contained precision cooling unit designed for cooling racks. Note :- The rates quoted by the contractor shall deemed to include the cost of refrigerant gas (R-410A) including testing/rectification of leakage for satisfactory working.
(ii) Fire Detection and Suppression system :- Fire detection, fire suppression, smoke detection, NOVEC 1230 gas for fire suppression. The accessories are compression of:- Seamless cylinger with pressure guage & low pressure switch fillable with NOVEC 1230 gas - 02 Nos. Electrical solenoid 24V DC stackable – 2 Nos. Manual & pneumatic actuator – 2 Nos. Discharge Hose – 2 Nos. 360-180 deg ceiling type discharge nozzle – 6 Nos. Cylinder strap – 2 Nos. 2 zone fire alarm panel with single zone gas release panel – 2 Nos. Release switch – 2 Nos. Abort switch – 2 Nos. MS Seamless pipes as per ASTMA with necessary fittings – 2 Lot. Smoke detectors photoelectric type 24V DC – 12 Nos. Warning plates – 2 Nos. Hooter cum strobe – 2 Nos. (iii) Remote display unit (RDU). (iv) Power distribution unit (PDU). (v) Camera surveillance and recording system. (vi) Event alerts system. (vii) Biometric Access Control system. (vii) Rodent repellent system. (viii) Temperature monitoring system. (ix) Humidity monitoring system. (x) Water leak detection system.
Microprocessor/DSP controlled modular UPS of capacity 150 KVA (30 KVA Modules X 5 Numbers ) UPS Rack to be Scalable upto minimum 300 KVA and comprising IGBT based rectifier inverter to achieve input THDI<3% and input power factor >.99 at 100 % loading. The UPS frame having the space to scale 100% of the rated output and option to be paralleled with another frame if required in future. True online double conversion (VFI as per IEC 62040-3) UPS using PMW IGBT technology, 3 Phase input and 3 Phase 400 V output UPS system of OEM VERTIV complete all as specified and directed by Engineer-in-Charge and each comprising of the following:- (i) Fully rated, unity power factor designed user replacecable Rectifier, charger & inverter unit integrated in each power module, 5 Nos of 30 KVA power module to be integrated to achieve 150 KVA connected load. (ii) Module should be redundent & Controller should also be redundent. (iii) 100% rated static bypass module at the bypass line. The static bypass module should be rated equivalent to the total power ratings of the power modules. (iv) Web-enabled monitoring and management through SNMP protocol for multi-OS environments. (v) UPS efficiency upto 95% at full load. (vi) High performance battery module comprising of lead acid sealed maintenance free batteries of capacity 12 Volts, 200 AH - 40 Nos, for providing 15 minutes backup to 150 KVA connected float. (vii) Health monitoring of battery back up.
Periodical, preventive and comprehensive maintenance to VRV/VRF (Variable Refrigerant Volume/ Variable Refrigerant Flow) Air Conditioners of modular system type, with number of indoor connected to centrally located outdoor units as per (OEM DAIKIN) instructions. (a) Outdoor Units :- VRV/VRF outdoor units with multiple compressors complete with inverter based type Rotary/Scroll compressors, R 410A refrigerant, cooling & heating mode both options, special pre-coated fin type heat exchanger, low noise direct driven propeller condenser fans in each module with top discharge every module having minimum 02 Nos. fans, GI coated condenser stand, microprocessor panel with sequential staring of condensing unit, coils, expansion valves, filters in refrigerant circuits, single phase preventor, all vibration isolators, safeties, operation range of dry Bulb Temperature -5 of 49 Deg C (i.e. in cooling mode) and -20 to 15.5 Wet Bulb Temperature Deg C (I.E. in heating mode) with Minimum capacity control of 8% of ODU capacity. Each system had the provision to combine maximum 3 Nos. single outdoor unit, Every single outdoor unit had multiple compressors Minimum 2 and maximum 3 Nos. in single module of system. Level Difference of piping is 50 Mtr if DODU is above or below from IDU in both cases. Make- Daikin. (a) 18 HP Outdoor unit VRV/VRF System. (b) 14 HP Outdoor unit VRV/VRF System.
(c) Indoor Units :- Ceiling Mounted Cassette type Indoor Units with inbuilt drain pump & decorative panels and having dimensions 900x900 mm complete all as specified and directed be Engineer-in-Charge for the following capacities :- (i) 2 TR round flow type cassette unit with remote controls - 02 Nos. (ii) 2.65 TR round flow type cassette unit with remote controls - 01 Nos. (iii) 3.3 TR round flow type cassette unit with remote controls - 02 Nos. (iv) 4.0 TR round flow type cassette unit with remote controls - 02 Nos. (v) 2.0 TR 2 Way Ceiling mounted Ductable type unit - 04 Nos. Note :- The rates quoted by the contractor shall deemed to include the cost of refrigerant gas (R-410A) including testing/rectification of leakage for satisfactory working.
Periodical, preventive and comphrensive maintenance to Microprocessor based 2 wire fault tolerant loop, 1 loop (each loop accessing minimum 99 detectors and 99 modules) fire alarm/detection control panel. The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is trigged. The panel shall have rectifier, loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output complete in all respects. The panel shall have a built in power supply and battery charger along with maintenance free 24 AH, 2x12 volt SMF lead acid batteries capable of running for a minimum of 8 hours with battery charger complete as required and as per specification alongwith the following accessories :- Make of Control panel - Honeywell/GST/GE/Siemens. (a) Photo electric addressable smoke detector with standard base - 24 Nos. Make - Honeywell/GST/GE/Siemens. (b) Photo electric addressable heat detector with standad base - 01 Nos. Make - Honeywell/GST/GE/Siemens. (c) Photo electric addressable multi detector with standard base - 03 Nos. Make - Honeywell. (d) Fault isolator base - 03 Nos. Make - Honeywell. (e) Addressable manual push button to initiate audio alarm with a breakable glass cover/resettable, intelligent addressable type - 03 Nos. Make - Honeywell. (f) Fire Alarm Hooter, conventional, (sound output of minimum 90 dB upto a distance of 10 feet) with strobe light of minimum 75 cd intensity with power supply arrangement - 02 Nos. Make - GST.
NOTE FOR ITEM NOS. 2 to 5:- (a) The comprehensive maintanance of equipment under this contract shall be done through respective OEM i.e. VERTIV and DAIKIN. The contractor will have to submit MoU on stamp paper of Rs. 100/- duly notarized as per performa (on serial page No. 121 to 123) within fifteen days from date of Accptance of tender. If the delay from OEM side to submit the MoU, the contractor to be submit evidence to the Accepting Officer and permission to be obtained from Accepting Officer for delay in submission of MoU. (b) The contractor should submit the monthly test report of Equipment conducted by the OEM with in first week of every month to the Engr-in-Charge, failing which recovery of Rs. 2000/- per Equipment per month shall be deducted from contractors dues.
SECTION-II
Supply & fixing MCCB 3 Pole of capacity 250 Amps, 50 Hz, 415V with rupturing capacity of 35 kA with spreader terminals including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.)
Supply & fixing MCCB 3 Pole of capacity 100 Amps, 50 Hz, 415V with rupturing capacity of 16 kA with spreader terminals including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.)
Supply & fixing MCCB 3 Pole of capacity 63 Amps, 50 Hz, 415V with rupturing capacity of 10 kA with spreader terminals including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.)
Supply & fixing integral LED street light fitting 45 watts comprising pressure die cast housing with powder coated aluminium housing working as a heat shrink and toughened glass suitable fixing with GI pipe bracket and pre-wired including necessary electric connection from ceiling rose to light fitting including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- Crompton Greaves Cat Part No. LSTS-45-CDL-1 equivalent model or cat No of make in Havells/Philips/ Bajaj.) (Note:- GImedium garde bracket along with clamp, nut & bolts shall be included in quoted rates.)
Supply & fixing PVC insulated Weather proof flat twin core cable copper conductor cable of size 2.5 sqmm for connection of street light fittings including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- RR KABEL./ FINOLEX/ POLYCAB/ KEI INDUSTRIES LTD./ HAVELLS.)
Material and labour for maintenance of feeder pillar/LT panel indoor/outdoor type including removing the carbonized/melted sparked thimbles, cleaning the carbonized bus bar making cable ends fresh and supply and crimping new thimbles/lugs and fixing the cable on bus bar/MCCB/Main switch/MCB including providing new nut bolts and washer if required greasing the doors of feeder pillar/LT panel outdoor/indoor type complete all as specified & directed by Engr-in-Charge.
M&L in repair pipe earthing (PIP) comprising of GI 50mm bore pipe, wall thickness of pipe 4.85 mm (Medium grade), 3.00 Metre length, terminal size 40x6mm & internal strip 25x4mm with one bag of BFC (50 Kg) as per IS 3043-1987, tubing filled with jelly earthing compound, duly inserted in soil, boring of 100mm bore filled with back filled compound including fibre chamber cover 1x1 feet, openable type, including testing of earthing complete all as specified and as directed. Note: On testing after completion, if the earth resistance 1.00 Ohms is not obtain, earthing shall be rejuvenated at no extra cost till the desired earth resistance is obtained.
M&L for comprehensive maintenance of Servo Voltage Stabilizer/ Servo Voltage Regulator, 150 KVA, comprising of following jobs complete all as specified and as directed:- (a) Free maintenance and repair of Normal accessories (Spare Parts), Servo Voltage Stabilizer/ Servo Voltage Regulator. (b) Dismantling and removing of defective voltage stabilizer, removing to workshop for repair, opening up and taking out coil, core and core assembly for estimation of repair and damaged parts cleaning/washing of tanks and removing the dust from all parts including cores, tanks, cooling tubes, removal of damaged parts making connection and assembling complete in all respects after repair of coils IC's, Regulators, Condensors, Triac, Transistors etc. respective cards nuts and bolts, refilling of transformer oil, installation and testing on full load. (c) Preventive maintenance of all systems on quarterly basis and upkeep of Report. (d) Attending all complaints within 24 working hours. Note:- (i) Replacement of defective spares for making the Voltage Stabilizer units in satisfactory working condition will be measured & paid separately under relevant items as 'Supply only'. These shall be identical to those specified by the original manufacturer. (ii) Labour charges for taking out old spares & refixing of new spares shall deemed to be included in unit quoted rate.} (iii) The rates quoted by the contractor shall deemed to be inclusive of T&P and minor sundries items etc as required. (iv) The job shall also includes shifting through crane with necessary accessories, transportation from site to work shop and vice- versa.
Supply only of Electronic card for 150KVA.
Supply only of Electronic sensing transformer set 12V/16V for 150KVA.
Supply only of 12pin PCB connectors for 150KVA.
Supply only of servo motor of 10 kg torque for 150KVA.
Supply only of RC network of 10 KG torque for 150KVA.
Supply only of cut off circuit PCB Low/ High for 150KVA.
Supply only of voltage slector arm of Acute transformer for 150KVA.
Supply only of Gear of 120 teeth for 150KVA.
Supply only of Voltmeter 0-400 volts digital type complete (Suitable size and shape). (Make:- AE/MECO/ L & T (RISHABH)/AMTL/SECURE/ C & S ELECTRIC/ DUCATI/ RAAS CONCORD)
Supply only of Ammeter with CT (Digital type) complete (Suitable size and shape). (Make:- AE/MECO/ L & T (RISHABH)/AMTL/SECURE/ C & S ELECTRIC/ DUCATI/ RAAS CONCORD)
Supply only of Neon Indicators (Make:- AE/ L & T (RISHABH)/SECURE/ C & S ELECTRIC) Note for item No 16 to 27:- Materials of item Nos 16 to 27 to be incorporated in item No 15 here-in-before. Make of item No. 16 to 24 shall be suitable for existing make of Servo Voltage Stabilizer/ Servo Voltage Regulator as mentioned in item No.15.
M & L for repair and rewinding 100 Amp Variac dimmer including taking out old winding complete all as specified and as directed.
M & L for repair and rewinding buck/boost loading transformer capacity 200 Amp (each phase) including taking out old winding complete all as specified and as directed.
S & F in repairs of control wiring of Servo Voltage Stabilizer/ Servo Voltage Regulator, 150 KVA complete all as specified and as directed.
S&F in replacement Power wiring and copper thimble of Servo Voltage Stabilizer/ Servo Voltage Regulator, 150 KVA complete all as specified and as directed.
"Dehydration / filtration of voltage stablizer oil of voltage stabilizer of capacity 150 KVA by disconnecting plants electrically for recirculation existing volatge stablizer oil with trolley mounted filtration plant till dielectric strength is up to 45 KV to 50 KV. Note- Quoted rates shall be deem to include for following :- (i) Oil shall be tested after filtration and test result will be recorded before & after filtration of oil. (ii) Contractor should make his own arrangement for oil filtration plant including transportation complete. (iii) Transformer oil for topping up will be measured and paid in relevant item as required."
Supply & topping up of oil for volatge stablizer up to required level for voltage stabilizers of dielectric strength 50 KV & above all as per IS specification.
Supply, laying & fixing XLPE insulated, armoured heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, cross-sectional area 50 sqmm 3.5 core laid on wall/ duct or floor with necessary clamps, cable lugs, glands, accessories GI strips etc. including taking down old unserviceable one complete all as specified & directed by Engr-in-Charge. (Make:-FINOLEX/ R R KABEL/ KALINGA/ PLAZA / POLYCAB/ HAVELLS)
Taking down carefully existing surface/concealed unserviceable copper/Aluminium point wiring (light, fan socket or power) complete with fittings such as switches, ceiling rose, lamp holder, regulators, sockets, F/Tube/Sketch light fittings, wooden terminal box, plastic laminated sheet cover, from Teak Wood batten including Teak Wood batten or PVC conduits complete all as specified & as directed.
M & L for point wiring using 1.50 sqmm size FRLS, PVC insulated, unsheathed 1100 volts grade single core multi-stranded copper conductor cable in proper colour coding drawn into and including non metallic rigid PVC conduit medium grade (not less than 20 mm dia) for wall and 25mm PVC medium grading grade casing and caping in the ceiling wherever required with and including its all necessary fittings and accessories fixed concealed, sunk cast iron or 1.2 mm thick pressed steel terminal box for mounting fittings and covered with 3 mm thick white bakelite / laminated hard glossy surface sheet top cover fixed with brass screws and cup washers including one continuous run of PVC insulated (green colour) 1.50 sqmm size FRLS stranded copper conductor cable as in earth wire and connecting all metal parts to common earth dolly for one light / Fan / exhaust fan / Bell point controlled by one, one way switch complete all as specified & directed by Engr-in-Charge. (Make of cable:- NICCO / FINOLEX / RR KABEL/ HAVELL'S/ POLYCAB / KEI INDUSTRIES LTD Make of Conduit:- FINOLEX / PAYAL/KALINGA/ PRESTO PLAST)
-ditto- all as per item No. 36 above but for one 5 pin 5/6 Ampere socket outlet point controlled by one, one way switch on the same board complete all as specified and directed by Engr-in-Charge.
-ditto- all as per item No. 36 above but for one 5 pin 5/6 Ampere socket outlet point controlled by one, one way switch on independant board complete all as specified and directed by Engr-in-Charge.
M & L for point wiring for one 15/16 Ampere socket outlet independent point using 2.50 sqmm FRLS size (Nominal cross sectional area), PVC insulated, unsheathed 1100 volts grade single core multi-stranded copper conductor cable in proper colour coding drawn into and including non metallic rigid PVC conduit medium grade concealed (not less than 25 mm dia) for wall and 25mm PVC medium grading grade casing and caping in the ceiling wherever required with and including its all necessary fittings and accessories fixed concealed, sunk cast iron or 1.2 mm thick pressed steel terminal box for mounting fittings and covered with 3 mm thick white bakelite / laminated hard glossy surface sheet top cover fixed with brass screws and cup washers including one continuous run of PVC insulated (green colour) 2.50 sqmm FRLS size stranded copper conductor cable as in earth wire and connecting all metal parts to common earth dolly complete all as specified and directed. (Make of cable:- NICCO / FINOLEX / RR KABEL/ HAVELL'S/ POLYCAB / KEI INDUSTRIES LTD Make of Conduit:- FINOLEX / PAYAL/KALINGA/ PRESTO PLAST)
-ditto- all as per item No. 39 above but for 4.00 sqmm multi stranded copper cable for AC point wiring with 4.00sqmm earth conductor for one 5 pin 15/16 Ampere socket outlet point controlled by one, one way switch on independant board complete all as specified and directed by Engr-in-Charge.
S & F modular switch one module, 5/6 Amp, one way, 230 volts AC complete all as specified and as directed by Engr-in-Charge. (Make : Anchor / Cona / Crabtree / Legrand)
S & F modular switch one module, 15/16 Amp, one way, 230 volts AC complete all as specified and as directed by Engr-in-Charge. (Make : Anchor / Cona / Crabtree / Legrand)
Supply and fixing of modular socket outlet (two module) 5/6 amps, 2 in 1, 2 & 3 pin combined, 230 volts AC complete all as specified and as directed by Engr-in-Charge. (Make : Anchor / Cona / Crabtree / Legrand)
Supply and fixing of modular socket out let (two module), 2 in 1, 3 Pin suitable for 5/6 Amp and 3 Pin suitable 15/16 Amp combined, 230 volts AC complete all as specified and as directed by Engr-in-Charge. (Make : Anchor / Cona/ Crabtree / Legrand)
Taking down unserviceable sub main wiring of any type and any size including wooden batten, PVC conduit or casing caping complete all as specified and as directed.
Material and labour for sub main wiring with two runs of single core 4.0 Sqmm (nominal area) PVC insulated copper conductor FRLS (conforming to IS-694), stranded, unsheathed 1100 volts grade in PVC Conduit (heavy grade) of 25mm dia or more dia with all fittings and accessories surface type including one run 4.0 Sqmm single core unsheathed stranded copper conductor cable FRLS (conforming to IS-694) as earth wire complete all as specified and as directed by Engr-in-Charge. (Make of cable:- NICCO / FINOLEX / RR KABEL/ HAVELL'S/ POLYCAB / KEI INDUSTRIES LTD Make of Conduit:- FINOLEX / PAYAL/KALINGA/ PRESTO PLAST) Note : (a) Two runs of 4.00 sqmm copper cable and one run of 4.00 sqmm copper cable (earth wire) alongwith PVC conduit measured as one unit length. (b) Extra length of cable required for connetion to DBs shall deemed to be included in the unit quoted rate and shall not be measured separately. (c) Earth wire shall run inside the conduit. (d) Suitable colour code of wire shall be maintained for phase / neutral / earth).
S & F in repairs MCB SP, 6 to 32 Amp, 10 KA, 'C' curve type complete all as specified and as directed. (Make:- Legrand/ L&T/ ABB/ Siemens/ Schneider)
S & F in repairs MCB SPN, 40 Amp, 10 KA, 'C' curve type complete all as specified and as directed. (Make:- Legrand/ L&T/ ABB/ Siemens/ Schneider)
S & F in repairs MCB TPN, 63 Amp, 10 KA, 'C' curve type with overload and short circuit protection incl making necessary DB connection complete all as specified and as directed. (Make:- Legrand/ L&T/ ABB/ Siemens/ Schneider)
Supply and fix in replacement Energy efficient recessed mounted Ultra modern Slim design 36 Watt 2X2 recess LED Panel, 5700k to 6500k luminaire, Total system Lumen of 36W LED should be 3600 or above in Cool day Light(5700K to 6500K), Power factor>0.95, CRI (Ra) >80, System Lumen Efficacy>100 Lm/w, THD(%) < 10,Electronic driver Powered by independent isolated, SELV output electronic driver, with Average life of 50000 Burning hours including taking down old unserviceable one complete all as specified and directed by Engineer-in-Charge. Make : Havells Model No. ENDURASLIMPROPLUS2XPLR36WLED840MOD + LEDDRIVER36V36WS or Wipro Cat No. CRCO10R038HP57GL1 or Philips Cat No. RC380BLED36S6500G4L60W60PSUODOC or equivalent model of Bajaj / Crompton Greaves.
SHIVA ENTERPRISES
AMIT ASSOCIATES
M/s Adhikari construction co.
P S TRADERS
HIND CONSTRUCTIONS
M/s Dhapola Elevator and Engineering
Tushar engineers
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .