Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.1 LAccepted-AOC SHIVAJI NAGAR GALI NO 1 DHANGU ROAD MODEL TOWN PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹32.6 L+₹5.3 L (19.3%)Rejected-Finance | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹34.4 L+₹7.1 L (26.0%)Rejected-Finance 252 22 NEAR SOCITY BUS STAND INDRA COLONY PATHANKOT 145001 | PATHANKOT | PUNJAB | 145001 | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹46.8 L+₹19.4 L (71.1%)Rejected-Finance 1ST FLOOR GURJEET MARKET DHANGU ROAD | L4 | Rejected-Finance Not Lowest |
Tender Value
₹41 L
EMD Value
₹82,000
Closing Date
12 Jan 2021, 6:00 pmClosed
GE (SOUTH) PATHANKOT
GE (SOUTH) PATHANKOT
REP MAINT OF LT OHLINE UG CABLE LTFEEDER PILLER BOXE LT CABLE CNNECTED WORK DGSET CAPCITOR PANEL CNNECTED SWITCHGEAR REP MAINTOFPERIMETER LIGHT STREET SEC POST TOP LNTRN GRDEN GATE INCL CNTROL PANEL ATDMTAL NANGAL KAN KNTERPUR AND MIR GE S PTK
2020_MES_401823_1
GES/PKT/T-56/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (SOUTH) PATHANKOT
All contractors enlisted with MES in Class D and above and category b i
8 documents required · 8 mandatory
₹500
GE (SOUTH) PATHANKOT
₹82,000
Yes
12 Mar 2021
8 Dec 2020
14 Jan 2021
8 Dec 2020
12 Jan 2021
23 Dec 2020
Amount
Excavation in trenches in any type of soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth and getting out all as required for laying of cables,Foundation filling of poles or stays.
All as per above item but exceeding depth 1.5 mtr and n exceeding 3 mtrs
Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point.
Returning filling, in including spreading ,leveling, watering and well ramming in layers not exc 25 cm each all as required.
M & L for good quality dry sand cushioning to under ground electric cable on layer of 8 cm thick before laying the cable and second layer of 15 cm thick after laying the cable all as specified in clause 19.75 of MES Schedule part-I (2009) Note : Sand shall be fined sand as specifed and punned thickness shall be measured and paid.
Supply and laying sub class 'B' bricks of old size (230x115x75 mm) or of size locally available , laid along alignment of cable as protection to cable in trenches complete all as specified and directed by Engineer-in-Charge
Laying only old bricks retrieved from item No.6 of any size/type laid along alignment of cable as protection to cable in trenches complete all as specified and directed by Engineer-in-Charge
Removing existing 1100 volts grade, XLPE/PVC, armoured, electric power cables (heavy duty) with aluminium conductor of sizes 6 Sqmm 4 core to 16 Sqmm 4 core from trench/ duct/ pipe carefully for identifying the defects and relaying the same after rectification of defects complete all as directed. Note: Earth work ( Excavation, Returning & refilling and removal), sand cushining , cable protection cover, GI protection pipe shall be measured and paid for seperately under respective item of Schedule
M&L for GI pipe light grade 40 mm dia for cable protection on road crossings /plinth protection with fixed to the pole wall etc. suitable fittings for cable protection .
M&L for GI pipe light grade 50 mm dia for cable protection on road crossings /plinth protection/ lamps post etc with fixed to the pole wall etc. suitable fittings for cable protection .
M&L for GI pipe light grade 80 mm dia for cable protection on road crossings /plinth protection/ lamps post etc with fixed to the pole wall etc. suitable fittings for cable protection .
M&L for GI pipe light grade 100 mm dia for cable protection on road crossings /plinth protection/ lamps post etc with fixed to the pole wall etc. suitable fittings for cable protection .
Cutting the tarmac / hard standings and excavating in trenches across the road for laying cable including making good the excavated portion by means of PCC 1:3:6, type C1 matching with the surroundings all as directed.
Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade 3.5 core PVC sheathed, armoured, electric power cables (heavy duty) with aluminium conductor of the following size including dismantling old one. Note: The rate quoted inclusive of termination at ends with suitable aluminium lugs wherever required.
16 Sqmm 2 core
16 Sqmm 4 core
25 Sqmm 4 core
3.5 core 35 Sqmm
3.5 core 50 Sqmm
3.5 core 70 Sqmm
3.5 core 95 Sqmm
3.5 core 120 Sqmm
3.5 core 150 Sqmm
M&L for heat shrinkable end termination joint for LT UG cable including jointing kits complete for making joints suitable for aluminium conductor cable of size 3.5/ 4 core 16 to 50 sq.mm.
All as per Item above herein before but for cable of size 3.5 core 70 to 120 sq.mm.
All as per Item above herein before but for cable of size 3.5 core 150 to 185 sq.mm
Supply & fixing in repairs of MCCBs of following current carrying capacity including necessary connecting terminals to bus bar, nut bolts etc complete all as directed .
320-400 Amps, 3P, Adjustable type,415V MCCB, 35KA rating
200-250 Amps, 3P,Adjustable type, 415 V MCCB, 25KA rating
160-200Amps, 3P,Adjustable type, 415 V MCCB, 25KA rating
125-160Amps, 3P,Adjustable type, 415 V MCCB, 25KA rating
32 to 80 Amps, 3P, 415 V MCCB, 16KA rating
4 Pole MCCB, 415 V, Adjustable type with breaking capacity 35 KA, 320-400 A rated
4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA, 200-250 A rated
4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA, 160-200 A rated
4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA, 125A to 160 A rated .
Dismentling old feeder pillar & Supply, installing, testing and commissioning of LT feeder pillar box factory made cubicle outdoor type, fabricated out of 3.00 mm thick CRCA sheet floor mounted with angle iron base frame made of 40 x 40 x 6mm , 50 cm height, floor mounted duly bolts and nuts grouted, dust and vermine proof, suitable for voltage 415 V 3 Phase 4 wire ,Square copper bus bar Chamber 400 Amp Capacity weather proof, with IP-54 protection, with separate hinge door for each compartment for incoming and outgoing MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC complete including painting with two coats of epoxy powder paint over a coat of primer complete including supply fixing and making provision of the following :- (a) MCCB 4 pole 415 volts 3 phase 250 Amp 25 KA -01 No (f) LED Indicator RYB -01 Set ( Set of three). Note: The panel shall be as per CPRI certificate. Note : PCC will be measured and paid separately.
Dismentling old feeder pillar & Supply, installing, testing and commissioning of LT feeder pillar box factory made cubicle outdoor type, fabricated out of 3.00 mm thick CRCA sheet floor mounted with angle iron base frame made of 40 x 40 x 6mm , 50 cm height, floor mounted duly bolts and nuts grouted, dust and vermine proof, suitable for voltage 415 V 3 Phase 4 wire ,Square copper bus bar Chamber 320 Amp Capacity weather proof, with IP-54 protection, with separate hinge door for each compartment for incoming and outgoing MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC complete including painting with two coats of epoxy powder paint over a coat of primer complete including supply fixing and making provision of the following :- (a) MCCB 4 pole 415 volts 3 phase 200 Amp 25 KA -01 No (f) LED Indicator RYB -01 Set ( Set of three). Note: The panel shall be as per CPRI certificate. Note : PCC will be measured and paid separately.
M & L for replacement of unsv/broken thermoplastic polycarbonate spring type locks suitable for panel locking (Mi DV 01 with Mi SR 4) complete.
S&F in replacement of existing UNSV Prestressed cement concrete poles of size 9 mtr long 102 mm x 172mm at top and 102mm x 279mm at bottom class-10 complete erected truly in vertical position and painting the poles with synthetic enamel paint upto 1.5 mtr from the coping above the ground level with alternate layer 30 cm with black and yellow paint complete all as specified and directed by Engr-in-Charge. Note : PCC in foundation, coping, Earth work ( Excavation, Returning & refilling and removal) will be measured and paid separately under relative items of Sch 'A'.
Dismantling old unserviceable poles and Supply and erection in vertical position Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws, type 410 SP-55 (11.00 metres long) all as specified duly factory painted with two coats of black bituminous paint internally through out and externaly for embeded portion and painting with one coat of red oxide primer, applying two coats of synthetic enamel aluminium paint on remaining exposed surfaces after errection complete, painting with synthetic enamel paint of colours black and yellow alternate strips of 30cm width upto 1.5 mtr from the top of coping complete including making suitable holes where required all as specified and directed .Note : PCC in foundation, coping, Earth work ( Excavation, Returning & refilling and removal) will be measured and paid separately under relative items of Sch 'A'.
Dismantling old unserviceable poles and Supply and erection in vertical position Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws, type 410 SP-31 (9.00 metres long) all as specified duly factory painted with two coats of black bituminous paint internally through out and externaly for embeded portion and painting with one coat of red oxide primer, applying two coats of synthetic enamel aluminium paint on remaining exposed surfaces after errection complete, painting with synthetic enamel paint of colours black and yellow alternate strips of 30cm width upto 1.5 mtr from the top of coping complete including making suitable holes where required all as specified and directed .Note : PCC in foundation, coping, Earth work ( Excavation, Returning & refilling and removal) will be measured and paid separately under relative items of Sch 'A'
M&L for PCC 1:4:8 type D2 with 40 mm graded aggregate as in foundation complete.
M&L for PCC 1:3:6 type C1 with 20 mm graded aggregate for coping of poles and stay including form work.
Restretching of ACSR conductor of any size of over head lines LT/HT on poles including binding with insulators, jointing jumpers etc including connections of incoming and out going cables complete all as specified and directed. Note: ACSR conductor Required for winding etc to be included in quoted rates.
Material, labour , testing & commissioning of straight through jointing kit, heat shrinkable type suitable for XLPE/ PVC cables of size 6 to 16 Sqmm 3.5/4 core with working voltage 1100 volts .
All as per srl item above but of size 3.5 core 16 to 50 sq.mm.
All as per srl item above but of size 3.5 core 70 to120 sq.mm.
All as per srl item above but of size 3.5 core 150 to185 sq.mm.
Cutting, trimming of hanging/ extended braches of trees upto a distance 3 meter from the overhead HT/LT line and making the line clear upto the entire length of the feeder including removal and disposal of the cut tree branches 50 meters away from the site complete all as specified and directed. Note : The Rates shall inclusive of T&P, hydraulic ladder, equipment such as motorised diesel operated hacksaw etc complete. One span comprises of 3 to 5 conductors of any distance between one pole to adjacent pole including trimming of all tree branches in vicinty & around poles /conductor & will be measured as one span. Necessary prior permission shall be obtained from concerned I/C JE E/M before carrying out the work. All safety measures & insurance to the staff undertaking the Job shall be the Contractor's responsibility.
Dismantling unserviceable cross arms including clamps, bolts, nuts, washers etc from pole.
Supply, fabricate and fix cross arms any size along with, brackets, clamps, bolts, nuts, washers, bracers etc including drilling holes, cold/hot complete and fixed to pole including one primer coat and one under and finishing coat of paint.
Dismantlin of ACSR conductor of any size, from insulator etc from the structure/over head line all as directed.
M&L replacement of ACSR conductor of any size as ordered by Engr-in-charge including tightening and bindingh with new binding wires to insulators all as directed.
Dismantling insulators any type, size
M&L pin type insulator vitreous, white, brown, or green insulator includig one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut 100 mm height, 65 mm dia for 1100 volts grade.
Material & labour for fixing in repairs Stay assembly complete with accessories such as MS stay plate of size 300mmx300mmx6mm thick, stay rod 20mm dia, stay bow, nuts, bolts and check nuts of GI including GI stay strand of size 7/4 mm all as shown in electrical plate No. 1 of SSR Part-I of 2009 or directed by Engr-in-charge. Note: Earth work ( Excavation, Returning & refilling and removal), PCC, stay clamp and loop type insulators will be measured and paid separately under relevant schedule items).
Supply, installing, testing and commissioning of LT feeder pillar box factory made cubicle indoor type, fabricated out of 2.00 mm thick CRCA sheet with angle iron base frame made of 40 x 40 x 6mm , 45 cm height, floor mounted duly bolts and nuts grouted, dust and vermine proof, suitable for voltage 415 V 3 Phase 4 wire weather proof, with IP-66 protection, with separate hinge door for each compartment for incoming and outgoing MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC complete including painting with two coats of epoxy powder paint over a coat of primer after under going a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate and with aluminium busbar (TPN), suitable double compression copper cable glands complete in all respect for Bay work station and including provn of the following:- Note: The panel shall be as per CPRI certificate. Note : PCC will be measured and paid separately.
i) Aluminium Bus bar 630 A- mounted on porcelain insulator - 01 Set ( Set of 4 Nos) with PVC sleeve insulation
ii) MCCB 4 pole 415 V 3 phase 400 Amp, 36 KA (Thermal magnetic release) Ics=100%Icu - 01 Nos (incoming)
ii) MCCB 3 pole 415 V 3 phase 250 Amp, 25 KA (Thermal magnetic release) Ics=100%Icu - 02 Nos (outgoing)
ii) MCCB 3 pole 415 V 3 phase 200 Amp, 25 KA (Thermal magnetic release) Ics=100%Icu - 01 Nos (outgoing)
ii) MCCB 3 pole 415 V 3 phase 160 Amp, 25 KA (Thermal magnetic release) Ics=100%Icu - 02 Nos (outgoing)
vii) Digital Amp meter of size 96x96mm rating 0-100 Amp with CT's & slection switch - 01 Nos
viii) RYB LED indicator- one set
S&F in repair Capacitor duty contactor with 1 No Aux contact 230V AC coil voltage suitable for minimum 10 KVAR capacitor.
S&F in repair Capacitor duty contactor with 1 No Aux contact 230V AC coil voltage suitable for minimum 25 KVAR capacitor.
S&F in repair Double metalised paper and polypropylene technology ( Mixed Dielectric) capacitor cylindrical/box type for power factor correction of 440 V, 50 HZ rated of capacity 3 to 15 KVAR.
S&F in repair Double metalised paper and polypropylene technology ( Mixed Dielectric) capacitor cylindrical/box type for power factor correction of 440 V, 50 HZ rated of capacity 20 to 25 KVAR.
M&L in replacement of existing unserviceable cantactor of current carring range 25 A to 40 Amp (AC-3 duty) at different places in APFC panels including required electrical connections with suitable size of single core pvc copper cable & testing all as directed .
M&L in replacement of existing unserviceable contactor current carring range 9 A to 18 Amp (AC-3 duty) at different places in APFC panels including required electrical connections with suitable size of single core pvc copper cable & testing all as directed .
M&L in replacement of existing unserviceable MCB 25-40 Amps TPN 415 volts at different places in LT Panels/APFC panels including required electrical connections & testing all as directed .
M&L in replacement of existing unserviceable MCB 32 - 63 Amps TPN 415 volts at different places in LT Panels/APFC panels including required electrical connections & testing all as directed .
S&F in repair APFC relay with inbuilt PF meter suitable for 5A CTR suitable for 8 Stage.
S&F in repair APFC relay with inbuilt PF meter suitable for 5A CTR suitable for 12 Stage.
Ditto, but capacity 30 KVAR with incoming MCCB of capacity 63 Amps 4 pole (6x5)
Ditto, but capacity 40 KVAR with incoming MCCB of capacity 80 Amps 4 pole (8x5)
Maintenance and servicing of DG set consisting of replacement of fuel filter, air filter and lub oil filter including replacement of eninge oil all as directed and testing on full connected load for the following capacity of DG Sets and any make as per OEM.Note: Engine oil will be measured and paid seperately.
DG Set 10 KVA to 20 KVA
DG Set 25 KVA to 50 KVA
DG Set 62.5 KVA to 75 KVA
M & L for replecement of existing unservicible Fan Belt and testing complete for the following capacity of DG Sets and any make as per OEM.
DG Set 10 KVA to 20 KVA
DG Set 25 KVA to 50 KVA
DG Set 62.5 KVA to 75 KVA
M & L for replecement of existing unservicible Hose Pipes with clamps and testing complete for the following capacity of DG Sets and any make: :-
DG Set 10 KVA to 20 KVA
DG Set 25 KVA to 50 KVA
DG Set 62.5 KVA to 75 KVA
Taking out the old unserviceable radiator from the DG set and taking it to work shop for overhauling & cleaning descaling with restore plus solution, removal of leakage, welding brazing & refixing it duly repaired etc complete all as directed for the following capacity of DG Sets and any make as per OEM.
DG Set 10 KVA to 20 KVA
DG Set 25 KVA to 50 KVA
DG Set 62.5 KVA to 75 KVA
M&L for repair and overhauling of unsv self starter 12 V of any capacity DG set including repair/replacement unsv/defective spares such as field coil, armature winding, carbon bushes, clutch bushes and pinion assy complete all as specified and directed.
M&L for repair and overhauling of unsv dynamo/alternator 12 V of any capacity DG set including repair/replacement unsv/defective spares such as field coil, armature winding, carbon bushes, clutch bushes and pinion assy complete all as specified and directed.
S&F in repair AVR with functions to adjust generator output voltage, prevent voltage hunting, set under frequency roll off knee point, set generator droop to 5% at full load, match AVR input to accessory output, set the over excitation cut off level, set intial frequency related voltage dip, over-voltage protection cut off level, maximum short circuit current with sensing input voltage range 170 - 250 V AC max, 50 -60 HZ frequency with output max upto 120 V DC, continuous current 2.7A & transient 6A for 10 sec including necessary control wiring complete from alternator to AVR complete testing & commissioning for DG sets of capacity 10.5 to 25 KVA.
All as per srl item above but for D set capacity 50 to 75 KVA
Taking out the old unserviceable battery from the DG Set and supply and fix new 12 V, 180 AH maintenance free battery make Amron/Exide including testing and commissioning complete all as specified and directed
Taking out the old unserviceable battery from the DG Set and supply and fix new 12 V, 100 AH maintenance free battery make Amron/Exide including testing and commissioning complete all as specified and directed
M & L for repair of Water pump of 10.5 to 25 KVA DG set including replacement of defective unsv spare part of any make and model and refix the same after repair complete all as specified and as directed
M & L for repair of Water pump of 50 to 75 KVA DG set including replacement of defective unsv spare part of any make and model and refix the same after repair complete all as specified and as directed
M&L for Calibration of Fuel pump including replacement of unsv/defective spares of 10.5 to 25 KVA KVA DG Set of any make and model complete all as directed.
M&L for Calibration of Fuel pump including replacement of unsv/defective spares of 50 to 75 KVA DG Set of any make and model complete all as directed.
M&L for overhauling and calliberation of fuel injector assembly including replacement of unsv/defective spares of 10.5 to 25 KVA DG Set of any make and model complete all as directed.
M&L for overhauling and calliberation of fuel injector assembly including replacement of unsv/defective spares of 50 to 75 KVA DG Set of any make and model complete all as directed.
Supply and fix in replacement battery leads set, PVC insulated multisranded, copper conductor of min size 35 sqmm 1 mtr long each duly fixed with brass clamps, copper lugs suitable for DG sets of different capacities.
M/L for replacement of coolant for radiator.
M/L for replecement of Lub Oil (Engine Oil) of grade 20W40 for Engine for DG set at various locations.
M & L for replacement of starter ring gear assembly for capacity 50 to 75 KVA DG set.
M/L for cleaning the fuel tank both internally and externally by removing all the dust / sediments etc including replacement of PVC pipe fuel level indicator, writing of tank capacity, date of cleaning and next due date for tank to be cleaned for following capacities of DG Set and any make as per OEM.
DG Set 10 KVA to 20 KVA
DG Set 25 KVA to 50 KVA
DG Set 62.5 KVA to 75 KVA
M & L for scrapping of old paint from DG set and preparation of old painted surfaces for re-painting. Repainting complete body of DG set with superior quality super enamelled paint of colour as per standard engineering practice for engine, alternator, base frame etc by sparying including writting SM/MES No, all as specified and directed.
DG Set 10 KVA to 20 KVA
DG Set 25 KVA to 50 KVA
DG Set 62.5 KVA to 75 KVA
Supplying and fixing in replacement of old u/s service cable size 4 sqmm, twin core multistranded 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service with galvanised steel wire complete all as spd and directed.
All as per above item but for service cable of size 6 sqmm,complete all as spd and directed.
All as per above item but for service cable of size 10 sqmm,complete all as spd and directed.
Taking down defective street light fitting of any size/ type/ capacity from height of pole/walls/high mast of any location exceeding 7.0 m height for repair work and re-fixing back after repair work including checking, inspecting, testing and commmissioning complete all as directed by Engr-in-Charge. Note:a) The M/L for Items like lamp, electronic drivers,surge protection devices etc shall be measured and paid separately under relevant items here in under this Schedule. b) Necessary tools like ladders & other T&P required etc shall be arranged by the Contractor. c) The rate quoted deemed to be inclusive for minor parts nut bolts, circle clips, clamps etc if any required at site.d) The M/L for repairs to LED panel is not included in the scope and shall be measured and paid separately.
supply and fix in repair Electronic digital Timer (Astronomical) suitable for street light timer DB panels .
Supply only the following spares suitable for LED street/Flood light fittings of
Electronic driver potted type IP-65, suitable for 90 to 120 W LED light fitting
Electronic driver potted type IP-65, suitable for 70 to 80 W LED light fitting
Electronic driver potted type IP-65, suitable for 30 to 60 W LED light fitting
Surge protection device of capacity 10 KV suitable for LED light fitting
Supply only the following spares suitable for street light fittings.
Lamp Holder suitable for 40 watt LED
LED Lamp 40 watt
Dismantling LED light fitting of capacity 90 to120 W ,strip opening the elctronic driver, LED panel complete, identifying defective LEDs , replacement of defective LEDs complete including soldering, replacement of pitted control wiring from LED panel to driver etc complete, including testing and commissioning complete. Note : The rate quoted is not inclusive of taking down and refixing of street light fittings and shall be measured and paid separately under relevant schedule items
Dismantling LED light fitting of capacity 70 to 80 W ,strip opening the elctronic driver, LED panel complete, identifying defective LEDs , replacement of defective LEDs complete including soldering, replacement of pitted control wiring from LED panel to driver etc complete, including testing and commissioning complete. Note : The rate quoted is not inclusive of taking down and refixing of street light fittings and shall be measured and paid separately under relevant schedule items
Dismantling LED light fitting of capacity 40 to 60 W ,strip opening the elctronic driver, LED panel complete, identifying defective LEDs , replacement of defective LEDs complete including soldering, replacement of pitted control wiring from LED panel to driver etc complete, including testing and commissioning complete. Note : The rate quoted is not inclusive of taking down and refixing of street light fittings and shall be measured and paid separately under relevant schedule items
Dismantling LED light fitting of capacity 25 to 36 W ,strip opening the elctronic driver, LED panel complete, identifying defective LEDs , replacement of defective LEDs complete including soldering, replacement of pitted control wiring from LED panel to driver etc complete, including testing and commissioning complete. Note : The rate quoted is not inclusive of taking down and refixing of street light fittings and shall be measured and paid separately under relevant schedule items
Taking down old unserviceable security light fittings from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 2500 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 25 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed . Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable security light fittings from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 3000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 30 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable security light fittings roadway lumanarie type from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 4500 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) Min 45 watt roadway lumanarie type with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. . Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable security light fittings roadway lumanarie type from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 6000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 60 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable security light fittings roadway lumanarie type from any height and Supply & fixing LED “inverter type bldg security light fittings with inbuilt battery backup for min 3 to 4 hrs, comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 4500 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) Min 45 watt roadway lumanarie type with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. . Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable security light fittings roadway lumanarie type from any height and Supply & fixing LED “inverter type bldg security light fittings with inbuilt battery backup for min 3 to 4 hrs, comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 6000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) Min 60 watt roadway lumanarie type with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. . Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable security light fittings roadway lumanarie type from any height and Supply & fixing LED “inverter type bldg security light fittings with inbuilt battery backup for min 3 to 4 hrs, comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 7200 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) Min 72 watt roadway lumanarie type with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. . Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable security light fittings roadway lumanarie type from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 7200 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 72 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 5000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 50 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 12000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 120 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed.
Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 15000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 150 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed.
Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 20000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 200 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed.
Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 6000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 60 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed.
Dismantling old un-serviceable flood light fittings from any position exceeding 7.5 m height, Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame LED type (with total lumen output not less than 10000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 100 watt, with ingress protection IP 65 and surge protection device of 10 KV capacity etc incl necessary, angle iron supports , clamps etc complete and testing on completion all as specified and as directed
Supply & fix replacement decorative path way light lighting LED decorative post top lantern for 360 degree 40 watts 230 volts, 50 HZ, maple shaped in sothing opal/ prismatic finish made up of polycarbonate,including all accessories prewired complete.Note :- (i) Minimum 2 years gaurntee period of LED fittings (ii) Driver shall be IP 66 degree of protection potted seal type. (iii) Power factor more than 0.9
Taking down old unserviceable street light fittings from any height and Supply & Supply & fixing LED street light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,with lumen output not less than 9000 lumens suitable wattage for efficiency not less than 100 lumens/Watt,min wattage 90 watt, with ingress protection IP 65 and SPD of capacity 10 KV etc complete and testing on completion all as specified and as directed. . Note: The GI pipe if rquired bracket will be measured and paid separately under relevant schedule items
S&F in repair PVC insulated 3 core 2.5 Sq mm stranded Aluminium conductor cable for connecting OH line/junction box to street light fitting testing and commissioning all as directed.
Supply and fixing timelite distribution boards (street light DBs) 40 A 3 pole with 230 V Astronomical time switch complete all as directed including dismantling old one .
Earthing complete with Galvanised Steel earthplate of size 60x60cmx6.3mm thick electrode and GI wire 4 sqmm dia as earth lead, buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below ground level, connected to earth wire 4 sqmm by means of nuts, bolts, check nuts and washers of GI all as shown in electrical plate No.3 of SSR Part-I, including testing on completion (Rates inclusive of neccessary excavation in any type of soil, earth work, PCC pit, CI cover, funnel with watering pipe, suitable size of light grade GI Protection pipe for earth strip in ground etc. all as required at site for complete earthing).
S&F loop-in/loop-out box of outer size size 250x210x115 mm made out of FRP(Hot moulded type) with weather proof canopy and locking screws along with with 5/6 Amps MCB - 01 No, 50 Amps rated 3 pole connector- 01 Nos, neutral link mounted and Din rail suitable size for mounting MCB/Connector etc complete in the box, duly fixed to to steel tubular/rail/PCC/RCC pole using 25 x 3mm FI clamp, including suitable gland and lugs for connecting cable complete all as directed including dismantling old one.
Material and Labour for Galvanised iron round bracket made out of 40mm dia GI tubing including making provision for fixing of 04/06 no flood light on 11 mtr steel tubular pole ad fixing and connecting up of LED lights (LED lights shall be measured seperately under respective items of sch ) complete all as specified and directed. Note: The inner diameter of ring shall not be less than 1.0 meter
M&L for bracket for street light fitting made out of 40 mm bore pipe light grade GI tube bent to shape required, not less than 1.20 meter long, fixed with and including MS flat iron clamps made out of 40x6 mm FI, bolts, nuts, washers etc complete including dismantling old defective.
M&L for bracket for street light fitting made out of 25 mm bore pipe light grade GI tube bent to shape required,not less than 1.20 meter long, fixed with and including MS flat iron clamps made out of 40x6 mm FI, bolts, nuts, washers etc complete including dismantling old defective.
M&L for preparation of old painted steel surfaces of 9 m long steel poles incl removing oily/greasy spots and applying one coat of aluminium paint complete including applying a coat of white wash on pole coping and lettering the pole details with white letters/ blackground etc complete all as directed
Repairs to High Mast/mid mast pole motor of Capacity 1.0 HP/0.75 KW 415 Volts 50 Hz 3 Phase 930 RPM and necessary rewinding with super enamelled copper wire all as per existing and servicing/greasing of reduction gear box complete all as specified and as directed by Engr-in-Charge.
Decarbonising of the control panel of High mast/Mid mast and including sevicing of parts such as contactors/timers including replacement of pitted lugs,thimbles, control wiring etc complete including painting with a coat of synthetic enamel paint
S & F in repair 3 pole power contactor with coil voltage 230 volt AC of current carring capacity 32 to 40 Amps complete including control wiring thimbles etc complete all as directed.
M&L for preparation of old painted surfaces of 9 m long PCC poles incl removing oily/greasy spots and applying one coat of synthetic enamel paint of black and yellow in alternate strips of 30 cm width upto 1.5 mtr height including applying a coat of white wash on pole coping and lettering the pole details with white letters/ blackground etc complete all as directed
M&L for replacement of traffic light & alternate flasher/blinker LED more than 250 CDL & No of LED more than 108/12V solar plate charging current >= 500 MA, LED color yellow/Red/Green with battery backup 12V/7.5 Ah 24 Hrs Atonomy, auto on/off function with high & low voltage cut off with dawn dusk function inbuilt and mounting on GI pole 80mm dia making necessary connection with suitable size of 4 sqmm cable.
Note for item No.1 to 169: The work involves of various areas of AGE E/M (S) Pathankot. The Contractor shall depute manpower on daily basis for attending and rectifying the jobs in time. If any breakdowns/complaints simultaneously occured in any areas shall be attended simultaneously by deputing additional manpower/T&P for rectification of defects.The rate quoted deemed to be included for the same. Recovery for non attending of any type rectification/complaint/breakdowns shall be at the rate of Rs 2500 per day irrespective nature of complaint/defect.
Schedule of credit - Rs. 126010.00
Note: In case the tenderer quotes different rates for similar item then lowest rate shall only be applicable for payment and contractor shall not have any claim on this account.
vivek and co
VIMAL TRADERS AND SUPPLIERS
Vijay Kumar Contractor and Engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .