Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹31,100
Closing Date
19 Jun 2026, 9:30 pmClosed
Engineering Wing of Health and Family Welfare Department
M N Jagadish
Providing MGPLS facility to Raja OPD at K.R.Hospital, MMC & RI, Mysuru.
EWHFWD/2025-26/BD/WORK_INDENT2011
EWHFWD/2025-26/BD/WORK_INDENT2011
Open
Buildings
Two Tender Document System(Two Cover)
EWHFWD Executive Engineer Office Mysore
4 documents required · 4 mandatory
List of existing commitments and ongoing work
List of works for which tenders already submitted
Banker Details
KPWD class-IV & above Registration Certificate
GST Certificate
Clause ITT 3.2 a)To qualify for award of this contract, each tenderer in its name should have in the last five years i.e. (2021-22 to 2025-26) a)achieved in at least two financial year a minimum financial turnover (in all classes of civil engineering construction works only) of Rs.12.41 Lakhs Note : a) For Clause 3.2 (a) the certificate duly certified by the charted accountant is to be submitted.
Clause ITT 3.2(b)To qualify for award of this contract, each Tenderer in his/its name should have in the last five years i.e.(2021-22 to 2025-26) The tenderer should have been Satisfactorily completed at least one Similar nature of work of value not less than Rs. 6.20 Lakhs as prime contractor. Note : The Work done certificate should be issued by the Officer not less than the rank of Executive Engineer of State or Central Government/ Semi Government/Government undertaking/ autonomous bodies of Government will be considered for the clause 3.2 (b).
Clause 3.6 -Tenderers who meet the above specified minimum qualifying criteria, will only be qualified, if their available tender capacity is more than the total tender value. The available tender capacity will be calculated for prime contractor are as under Assessed available tender capacity AxNx2.5-B Where A maximum value of civil engineering works executed in any one year during the last five years 2021-22 to 2025-26 updated to 2026-27 price level taking into account the completed as well as works in progress. N Number of years prescribed for completion of the works for which tenders are invited. B Value, at 2026-27 price level of existing commitments and ongoing works to be completed during the next 3 months
₹500
₹31,100
10 Jun 2026
10 Jun 2026
20 Jun 2026
15 Jun 2026
Providing MGPLS facility to Raja OPD at K.R.Hospital, MMC & RI, Mysuru. (MGPLS Works)
All copper pipes should be Solid drawn, seamless, deoxidized, non arsenical, half hard, tempered
and degreased materials conforming to BS:EN:13348:2001+A1:2005.
Pipes sizes should be us...
All copper pipes should be Solid drawn, seamless, deoxidized, non arsenical, half hard, tempered
and degreased materials conforming to BS:EN:13348:2001+A1:2005.
Pipes sizes should be us...
All copper pipes should be Solid drawn, seamless, deoxidized, non arsenical, half hard, tempered
and degreased materials conforming to BS:EN:13348:2001+A1:2005.
Pipes sizes should be us...
All copper pipes should be Solid drawn, seamless, deoxidized, non arsenical, half hard, tempered
and degreased materials conforming to BS:EN:13348:2001+A1:2005.
Pipes sizes should be us...
Should have terminated properly Double locking DIN type valves which have a parking facility
which also avoids interchanging of outlets and keys(Gas specific probes)
Oxygen Outlets - dro...
Should have terminated properly Double locking DIN type valves which have a parking facility
which also avoids interchanging of outlets and keys(Gas specific probes)
Vacuum Outlets-drops...
ACCESSORIES ALONG WITH CALIBRATION CERTIFICATES. Oxygen Flow meter with Humidifier Bottle:
Flow meter should be Backpressure Compensated.
Flow meter should be accurate gas flow measurement and control...
Single piece wall mounted suction collection & regulation unit. With jar capacity
of 600ml each shall be provided at each of the bed side. Jars are should be made of
autoclavable materials. The units ...
ISOLATION VALVES: Should be 90deg turn, ball valves of brass body, duly chrome plated on the outer periphery, SS
ball with high quality Teflon seated, connected to pipeline with brass ferrule for easy...
ISOLATION VALVES:
Should be 90deg turn, ball valves of brass body, duly chrome plated on the outer periphery, SS
ball with high quality Teflon seated, connected to pipeline with brass ferrule for easy...
ISOLATION VALVES:
Should be 90deg turn, ball valves of brass body, duly chrome plated on the outer periphery, SS
ball with high quality Teflon seated, connected to pipeline with brass ferrule for easy...
Zonal Value box three Gas services
An Zonal area valve box should have bellow spec.
Wall mounted M.S. box with powder coated & lockable,
front glass mounting easily visible & using imported brass body...
Digital Area Alarm for Three Gas Systems.
Micro processor controlled Area Gas alarm panel five Lines, Should audio-visual alarms for each
gas used on the floor and come fitted with test and mute butto...
Providing MGPLS facility to Raja OPD at K.R.Hospital, MMC & RI, Mysuru. (Electrical Works)
Point wiring using Copper wire without switch. Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wi...
Point wiring using Copper wire without switch. Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wi...
Point wiring using Copper wire without switch. Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wi...
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 3...
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 8...
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing m...
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing m...
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. 6Amps one way Switch
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. 6Amps 3way socket
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. 32Amps DP switch
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. 6/16Amps universal socket
Supplying and fixing of PVC casing and capping on the wall
or ceiling using necessary materials like bends, junction box,
elbows, screws at an interval of 300mm …. etc. as required. 20mm
Supplying and fixing of PVC casing and capping on the wall
or ceiling using necessary materials like bends, junction box,
elbows, screws at an interval of 300mm …. etc. as required. 25mm
Supplying heavy gauge PVC Conduit Pipe . dia . mm thick
with suitable size bends, metal junction boxes adhesive paste etc., by
groove cutting in the wall and fixing by bracing U or J hooks and
Supplying heavy gauge PVC Conduit Pipe . dia . mm thick
with suitable size bends, metal junction boxes adhesive paste etc., by
groove cutting in the wall and fixing by bracing U or J hooks and
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS...
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS...
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS...
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS...
Supplying and fixing regular MCB distribution boards on wall/ wood board I flush mounting using required clamps,i bolts, nuts etc., with provision for fixing suitable type capacity MCB's s...
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short ci...
Supplying, fixing and wiring Residual current circuit breaker (RCCB)
240/450V upto 300mA sensitivity on existing wood/ panel board. 16A-25A 2 pole
Supplying, fixing, wiring, earth electrode for grounding conduits, I.C. cutouts and other equipment's on the meter board using 40 mm dia2.90 mm thick GI pipe 2.5m long buried in a pit . The pit should...
Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. 25x3mm GI strip
Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. 50 x 6 mm GI strip
Supplying of ......feet - PVC Batten with integrated LED tube .....W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI greater than 80. Power Input: 220-240V...
Supplying & fixing of retrofit type - LED bulb.......W with OPAL acrylic diffuser comprising of LED source with CCT 6500 degree K, CRIgreater than 70%. efficacy greater than80 lumen per watt, lifegrea...
Supplying & fixing of retrofit type - LED bulb.......W with OPAL acrylic diffuser comprising of LED source with CCT 6500 degree K, CRIgreater than 70%. efficacy greater than80 lumen per watt, lifegrea...
Supplying capacitor type ceiling fan complete with down rod
blades, shackle, canopies etc., for operation on 230 volts, 50 cycles. Single phase AC supply conforming to ISS-374-1979 and with double bal...
Supplying & Fixing of 70-150 Watts lamp holder 2 Pin
Fixing all types and all capacities of fluorescent / false ceiling / spot light / CFL / LED fittings indoor on the wall / ceiling / rafters / girders using 23/0.0076” twin twisted PVC insulated wire...
Fixing a ceiling / wall mounting fan of all capacities and all types, with necessary clamps and 'S' hook made out of 15mm dia MS rod, with 5 amps. ceiling rose of approved quality with necessary lengt...
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
kw-1-2011 - O.doc
Tender Document • 1.09 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .