| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.3 LAccepted-AOC 10 SUBASH COLONY DEF LAB ROAD RATANADA JODHPUR 342006 RAJ | JODHPUR | JODHPUR | RAJASTHAN | 342006 | L1 | Accepted-AOC Lowest and reasonable bidder | |
| 2 | L2₹23.8 L+₹1.5 L (6.70%)Rejected-Finance | L2 | Rejected-Finance Not lowest | |
| 3 | L3₹24.1 L+₹1.7 L (7.75%)Rejected-Finance TEHSIL SARKAGHAT P O RAKHOH VILL GADHANI SARKAGHAT MANDI HP 175024 | MANDI | HIMACHAL PRADESH | 175024 | L3 | Rejected-Finance Not lowest | |
| 4 | L4₹25.5 L+₹3.2 L (14.3%)Rejected-Finance FLAT NO 201 GF KAMAL VIHAR CGHS LTD PLOT NO 5 SECTOR 7 DWARKA NEW DELHI 110075 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110075 | L4 | Rejected-Finance Not lowest | |
| 5 | L5₹25.9 L+₹3.6 L (16.0%)Rejected-Finance | L5 | Rejected-Finance Not lowest |
Tender Value
₹23.6 L
EMD Value
₹47,100
Closing Date
11 May 2024, 6:00 pmClosed
CWE (AF) AMBALA
HQ CWE (AF) Ambala Cantt-133001
RECTIFICATION OF DEFECTS IN AC PLANT FOR ATC BLDG AT AFS SARSAWA UNDER GE (AF) SARSAWA
2023_MES_615471_6
CWE/AF AMB/SAR-28/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
SARSAWA
For MES enlisted contractor Class E Category C (i) and for un-enlisted contractor refer NIT
7 documents required · 7 mandatory
₹500
GE (AF) SARSAWA
₹47,100
Yes
27 May 2024
16 Apr 2024
13 May 2024
16 Apr 2024
11 May 2024
29 Apr 2024
16 Apr 2024 - 20 Apr 2024
Amount
M&L for rectification of defects in AC plant water cooled scroll chiller No. 01 for the items mentioned here-in-below complete all as specified & directed. Make & Model No of existing Chiller unit, 52 TR: Model No XWC4S-052AR2, Serial No. BSL00025 of 'Blue Star'
M&L for leakage detection in the refrigeration line of CKT No. 01 and plugging the same, nitrogen pressure testing, vacummizing, testing & commissioning complete all as specified & directed.
Dismantling of defective compressor and fixing only of new compressor of CKT No. 2, 3 & 4 including detection of leakage, its plugging, nitrogen pressure testing, vacummizing, commissioning and testing complete all as specified & directed. Note: Supply of compressor shall be measured & paid seperately.
M&L for charging of refrigerant gas R-407C complete all as specified & directed. Make: Floron, Mefron, MPCL, Dupont
M&L in replacement of liquid line drier filter complete all as specified & directed. Make: Danfoss, Honeywell, Rapid Cool, Dwyer
M&L for descaling of condenser 04 Nos. including tube by tube chemical (as recommended by OEM) circulation rodding, flange gasket replacement complete all as specified & directed. Note: Descaling of all 04 Nos. condensers shall be considered as "Each Job".
M&L in replacement of power contactor 45 Amp, 415volt, 3 pole including NO/NC point complete all as specified & directed Make : Schneider, Siemens, ABB
M&L in replacement of crancage heater suitable for scroll compressor model No. SZ185S4RC make : Danfoss complete all as specified & directed.
Supply only Scroll compressor Model No. SZ185S4RC suitable for water cooled chiller unit, Make : Danfoss complete all as specified & directed. Note: Item to be procured from OEM or his authorized dealer/distributor
M&L for rectification of defects in AC plant water cooled scroll chiller No. 02 for the items mentioned here-in-below complete all as specified & directed. Make & Model No of existing Chiller unit, 52 TR: Model No XWC4S-052AR2, Serial No. BSL00024 of 'Blue Star'
Dismantling of defective compressor and fixing only of new compressor of CKT No. 1, 2, 3 & 4, including detection of leakage, its plugging, nitrogen pressure testing, vacummizing, testing and commissioning complete all as specified & directed. Note: Supply of compressor shall be measured & paid seperately.
M&L for charging of refrigerant gas R-407C complete all as specified & directed. Make: Floron, Mefron, MPCL, Dupont
M&L in replacement of liquid line drier filter complete all as specified & directed. Make: Danfoss, Honeywell, Rapid Cool, Dwyer
M&L for descaling of condenser 04 Nos. including tube by tube chemical (as recommended by OEM) circulation rodding, flange gasket replacement complete all as specified & directed. Note: Descaling of all 04 Nos. condensers shall be considered as "Each Job".
M&L in replacement of power contactor 45 Amp, 415volt, 4 pole including NO/NC point complete all as specified & directed Make : Schneider, Siemens, ABB
Supply only Scroll compressor Model No. SZ185S4RC suitable for water cooled chiller unit, Make : Danfoss complete all as specified & directed. Note: Item to be procured from OEM or his authorized dealer/distributor
M&L for rectification of defects in AC plant water cooled scroll chiller No. 03 for the item mentioned here-in-below complete all as specified & directed. Make & Model No of existing Chiller unit, 52 TR: Model No XWC4S-052AR2, Serial No. BSL00023 of 'Blue Star'
Dismantling of defective compressor and fixing only of new compressor of CKT No. 01, 02 and 04, including detection of leakage, its plugging, nitrogen pressure testing, vacummizing, testing and commissioning complete all as specified & directed. Note: Supply of compressor shall be measured & paid seperately.
M&L for charging of refrigerant gas R-407C complete all as specified & directed. Make: Floron, Mefron, MPCL, Dupont
M&L in replacement of liquid line drier filter complete all as specified & directed. Make: Danfoss, Honeywell, Rapid Cool, Dwyer
M&L for descaling of condenser 04Nos. including tube by tube chemical (as recommended by OEM) circulation rodding, flange gasket replacement complete all as specified & directed. Note: Descaling of all 04 Nos. condensers shall be considered as "Each Job".
Supply only Scroll compressor Model No. SZ185S4RC suitable for water cooled chiller unit, Make : Danfoss complete all as specified & directed. Note: Item to be procured from OEM or his authorized dealer/distributor
M&L in replacement MCCB 200 Amp, 4 pole, 415 volt, 25KA complete all as specified & directed. Make: Schneider, Siemens, ABB
M&L for carrying out Summer (in the month of May/June) seasonal testing of 72 Hrs duration of complete AC plant water cooled of capacity 2 x 52 TR + 1 x 52 TR comprising of 04 Nos. floor mounted AHUs (01 No. on each floor) and 05 Nos. ceiling suspended AHUs in ATC tower by recording inside weather parameters of each room, outside parameters, electric reading from panel, plotting graph for RH/Temp, calculation of COP including providing all instruments i.e. Energy meter, Cyclometer, Anemometer etc. all as directed by the testing officer complete all as specified & directed.
M&L for carrying out Mansoon ( in the month of Aug/Sep) seasonal testing of 72 Hrs duration of complete AC plant water cooled of capacity 2 x 52 TR + 1 x 52 TR comprising of 04 Nos. floor mounted AHUs (01 No. on each floor) and 05 Nos. ceiling suspended AHUs in ATC tower by recording inside weather parameters of each room, outside parameters, electric reading from panel, plotting graph for RH/Temp, calculation of COP including providing all instruments i.e. Energy meter, Cyclometer, Anemometer etc. all as directed by the testing officer complete all as specified & directed. Note for BOQ item No. 5.00 & 6.00: The seasonal testing shall be carried out in the presence of representative of HQ CE (AF) WAC Palam. The contractor shall request to Accepting officer through GE for each seasonal testing well in advance.
For Credit Schedule, refer tender documents. The amount of credit schedule shall be deducted from total quoted amount of BOQ to arrive contract sum.
shivrefrigeration
VATANUCOOL ENGINEERS
SHRI RAMSONS PROJECTS CORPORATION
Radhe Krishn Engineering
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .