Assistant Engineer, AHESD
West Bengal Legislative Assembly South Annex Building Gr Floor Kolkata 700 001
Repairing, renovation of old damage Electrical installation and wiring at different places of Assembly House Compound under Assembly House Electrical Sub. Division, PWDte.
2025_WBPWD_833472_1
eNIQ No. - 01 /WBPWD/AE/AHESD of 2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
7 days
Assembly House Elect Sub Divn
Please refer Tender documents.
6 documents required · 6 mandatory
₹5,900
21 May 2025
4 Apr 2025
25 Apr 2025
5 Apr 2025
22 Apr 2025
8 Apr 2025
Amount
PWD Sche. Item: D-1/1(b): Supplying and fixing Sheet steel Main Switches on angle iron frame on wall (Make- Havells) 60/63 A 415V TPN with fuse on L&N
PWD Sche. Item: D-3/4(a): Supplying and fixing 415V, TPN SFU with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. (Make- L&T) 63A Angle iron frame
PWD Sche. Item: D-9/13: Supplying and fixing double-door SPN MCB Distribution Board with IP- 42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make- Legrand and Seimens)
2+4 way - Enclosure (607710) - (Make- Legrand)
2+8 way - Enclosure (607711) - (Make- Legrand)
PWD Sche. Item: D-10/14: Supplying and fixing double-door Horizontal TPN MCB Distribution board with IP- 42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make- Legrand and Seimens) 4 way - Enclosure (607715) - (Make- Legrand)
PWD Sche. Item: D-5/6: Supplying and fixing 240/415 V MCB isolator on din rall of existing DBs and necessary connection. (Make- Legrand / Seimens)
40A DP (Make- Legrand)
100A FP (Make- Legrand)
PWD Sche. Item: D-6/7 : Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection. (Make- Legrand & Seimens) 6-32A SP (Make- Legrand)
PWD Sche. Item: D-7/9 : Supplying and fixing 240/415 V change over (MCB module) of on din rail of existing Dbs/enclosure and necessary connections. 40A FP (Lagrand)
PWD Sche. Item: E-14/1(a): Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required
2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC
2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC
PWD Sche. Item: E-15/5: Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [only PVC Rigid Conduit on ceiling and remaining portion concealed]
Average run 6 mtr
Average run 10 mtr
Average run 12 mtr
PWD Sche. Item: E-15/4: Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box and mending good the damages to original finish
On Board
Average run 7.5 mtr
PWD Sche. Item: E-6/17(b): Supply & Fixing 240 V, 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board incl. S & F 100x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required
PWD Sche. Item: E-7/26: Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch, indicator & 20A switch type SP MCB (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required
PWD Sche. Item: E-17/5(a): Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc.
PWD Sche. Item: E-17/5(b): Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections. Make- norisys,L&T,Crabtree,Northwest
PWD Sche. Item: E-19/17: Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (C-Curve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supplying & delivery og Industrial Battens TLED lamps luminaire with 1 No. 20W LED tube (Make: Philips, TMC 501 P 1XT-LED 22W 93241)
Supplying & delivery of Industrial Battens TLED lamps luminaire with 2 Nos. 20W LED tube (Make: Philips, TMC 501 P 2XT-LED 22W 93241)
PWD Sche. Item: C-2/17: Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with suitable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
PWD Sche. Item: C-2/16: Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
Supplying of 1200 mm sweep AC Ceiling Fan (Make: Orient Electric Apex-FX))
PWD Sche. Item: C-3/21(a): Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.
PWD Sche. Item: C-3/21(b): Extra for supplying additional wire for down rod & painting the rod exceeding 30 cm by 2x1.5 sqmm flexible copper wire.
Supply, delivery and installation of MS Powder Coated, light weight 100mm/4 inch Circular Inline Duct Exhaust Fan of Capacity 290 CMH at 290Pa Static Pressure operating at 230V, 50Hz AC. The casing ensures reliable operation of the fan in case of its outside installation. The motor is equipped with ball bearings for longer service life of the fan. Safe operation and low noise, each turbine is dynamically, balanced. The impeller with backward curve blade is powered by the single phase motor with external rotor and overheating protection. (Make : Astberg Model No. AEE 100G or equivalent) incl. wall cutting of suitable size to install the fan.
Supplying & delivery of 12 inch Havells Ventil Air DPS Exhaust Fan
PWD Sche. Item: C-3/28: Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter: 30 cm (12")
Supplying & delivery of Crompton Strom2 450mm 3 blade wall Bracket Fan.
PWD Sche. Item: C-4/29: Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length
Supplying & delivery of Crompton Strom2 450mm 3 blade Pedestal Fan.
Supplying and delivery of 1.1kV grade Aluminium Armoured Power Cable. (Make: Havells)
2 core x 6 sq. mm..
2 core x 10 sq. mm..
PWD Sche. Item: D-14/34(a): Supply & fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size incl. Al painting of MS support. (i): With out angle iron support
100x50x1.25mm (18SWG)
150x50x1.25mm (18SWG)
PWD Sche. Item: F-1/2(a): Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting
PWD Sche. Item: F-1/3(a): Laying only Cable upto 50 sqmm through existing RCC/Hume/GI Pipe/Open masonary trench for single, 2,3,3.5 & 4 core
PWD Sche. Item: F-3/4(a): Laying of one cable upto 150 sqmm through existing covered masonry trnch incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand
PWD Sche. Item: F-6/11: Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required
50 mm dia
80 mm dia
PWD Sche. Item: F-4/7: Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :
2 core x 6 sqmm
2 core x 10 sqmm
PWD Sche. Item: F-5/8(b): Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials :
2 core 6 sqmm cable
2 core 10 sqmm cable
PWD Sche. Item: G-1/1: Excavation of soil for installation of Earth Electrode and filling & ramming. PWD Sche. Item: G-1/1(a): For Soft Soil
PWD Sche. Item: G-1/2: Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: PWD Sche. Item: G-1/2(a): By TATA-Medium GI pipe
Supply, delivery & installation of 40 watt LED Well Glass Pendent Light Fitting incl S&F of 50 mm dia pipe clamp for fixing of light fitting. (Make: Crompton, Model No. LWV11-40-CDL)
Supply, delivery & installation of 100 watt Day Cool White Multi LED Flood Light Fixture (Make: Philips/Crompton)
Cost of dismantling charges of old damage wiring, DB's and Main Switch etc.
S B R ELECTRICAL ENTERPRISE (BID ID -6323776)
ALPHA ELECTRICALS (BID ID -6322911)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .