PROVIDING HVAC SYSTEM AT BUNKER FOR LINEAR ACCELERATOR MACHINE at Rashtra Sant Tukdoji Regional Cancer Hospital and Research Centre Nagpur
2019_CRSN_493158_2
E Tender Notice 01/2019
Open Tender
Electrical and Maintenance Works
365 days
Nagpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,000
via Payment Gateway
₹44,000
Nagpur
7 Jan 2020
11 Sept 2019
10 Oct 2019
11 Sept 2019
9 Oct 2019
11 Sept 2019
11 Sept 2019 - 20 Sept 2019
24 Sept 2019
Amount
Supply, installation, testing and commissioning of factory fabricated Double Skinned direct expansion (DX) coil Air handling unit Ceiling / floor mounted (Horizontal / Vertical to suit site) as per EUROVENT standard EN1886 fabricated out of extruded aluminium section with 0.6mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.6mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil made of Aluminium finned Copper tube with coil section, pre-filter section with non woven synthetic media of 10micron particle size with an efficiency of 90% (MERV 7), polished stainless steel drain pan made out of 18 G sheet duly insulated complete with motor, belt drive etc. without face and bypass dampers. The AHU panels shall be insulated with 23mm thick & 48 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specification. The face velocity across cooling coil shall be limited to 500 FPM maximum. All AHUs shall be connected with DOL type starter panel having cable termination, Volt and Ammeter with required rated MCB for tirpping, earthing connection with the body of the panel. The capacity of Air-handlers shall be as follows: AHU shall be compatible with BMS System
Supply of Equipments VRV AHUs
4800 CFM 12 TR with 50mm static pressure (Ceiling Suspended)
Description of Work / Item(s)
Amount
1. All Items shall be quoted in the given format. 2. Client reserves the right to take any item as client supplied 3. Client reserves the right to add or delete any item from the tender during or after the finalization of the tender. 4. Boq items shall be read with the technical specifications 5. In case of discrepancy in Boq and technical specifications the stringent shall be followed. 6. Control cable from outdoor unit to indoor unit (condenser to evaporator) with necessary insulating tape etc. 7. It is advice to visit the site before quoting the boq 8. MS Powder coated bracket with fasteners to be fixed on walls / slab with all necessary fixing accessories 9. The Items in the Boq may or may not be operated as per site conditions. 10. Any deviation with respect to boq shall be informed and mentioned while quoting OR during prebid meeting 11. Insulation shall be done properly with vapour barrier and to provide mechanical protection against abrasion. 12. Indoor unit shall be considered with required structural support to hang in ceiling or floor / loft with anchor fasteners, rubber gaskets, nuts, bolts, inlet outlet connections 13. Treated fresh air unit shall be considered with MERV 13 pre filter 14. Copper piping shall be considered with T and Y joints with insulation. 15. All AHUs except VRF ductable unit shall be DX type unless otherwise mentioned. 16. Any item missed in the tender for competing the installation, testing, commissioning of the complete HVAC system all also to be included.
Supply of Equipments
Non-Ductable Air -Conditioners
Hiwall Air -Conditioners
Outdoor Units
24 HP MODULE (12HPX2NOS)
Refrigerant Distribution Joints
Y- Joints
T- Joints
Centralized Control Systems
Installation and testing of Intelligent Controller Centralized Control Systems ,BACnet Compatible related accessories for field devices interface as per drawings
Cordless Remote Controller
For Hiwall
TOILET EXHAUST FAN
Supply, installation, testing & commissioning of Propeller type exhaust fans.
i) Mounting Frames
ii) Necessary wiring (approx. 2m)
iii) Gravity louvers
50 CFM Propeller Fan 150 MM DIA
Description of Work / Item(s)
Amount
Vacuumising, Gas Charging, Installation, testing & Commissioning of entire systems
Refrigerant Copper Piping Piping material shall Confirm to ASTM B280 Standards
Supply, installation, testing & commissioning of 16/18 G Hard refrigerant copper piping connected between evaporator unit & condenser units covered with 19 mm thk. Nitrile foam insulation
Electricals
Supply, installation, testing & commissioning of electrical control cabling between condenser and evaporator unit.
Supply, Installation, Commissioning and Testing of Supply wire between indoor unit to the socket (3core x 1.5 sqmm Cu wire) laid in conduits
Installation, Commissioning and Testing of necessary Three pin tops for VRV indoor units.
Installation Installation Commissioning and Testing of VRF Indoor(mentioned in item 4.1 onwards) and Outdoor units with inverter Compressors complete with epoxy painted MS stand, anti-vibration isolators inverter Compressors complete with epoxy painted MS stand, anti-vibration isolators
a) 24 HP MODULE
Non-Ductable/Ductable Air -Conditioners
Hiwall Air -Conditioners
WATER DISTRIBUTION SIDE DRAIN PIPING
Supply, installation, testing & Commissioning of following sizes 6 mm thick nitrile rubber foam insulated PVC drain pipes
a) 25mm dia
b) 32mm dia
c) 40mm dia
d) 50mm dia
Drain up Pump-kit for Hi-wall & Ductable Units
AIR DISTRIBUTION SIDE Ducting /Dampers/Grills Rectangular
Square Dcuting
Supply and installation of Aluminium, site fabricated rectangular ducts, supported by MFR Test Certificates, complete with RTV Sealant joints with necessary supports using thread roads (as directed) and anchor bolts, supply air collars, vanes, splitters dampers duly painting of the ducts and as per specification for Air Conditioned Areas. (For Linac Areas )
24 SWG Aluminium sheet
22 SWG Aluminium sheet
Grilles/Diffusers
Supply & fixing of grilles as per following requirements
Aluminium extruded powder coated stripline Rectangular grilles under the Round&Rectangular ducts for AC areas.
6" Linear Grille Down Throw & Side Throw 15 degree
GI Opposed Blade Volume control Line damper in ducts
20 G Frame / 22 G Blade Construction
Collar Dampers of opposed blade type made out of Aluminium alloy extrusion with anodised matt black finish for supply air and toilet grills.
Fire & Smoke Dampers
Supply & fixing of Combined Fire & Smoke Dampers as per following ratings:- UL555S & NFPA90A, 92A & 92B with actuators and fire sleeves shall be factory fitted & of the same material. as that for Dampers
Canvass Connection for A/C units
at outlet/ inlet of Unit (Considered as 1 set)
Supplying and fixing GSS Louvres with bird screen, adjustable damper.
THERMAL & ACOUSTIC INSULATION
Supplying and fixing physically cross linked, fire retardant insulation Thermobreak nitrile butadiene rubber self adhesive class A insulation Thermal Conductivity – 0.032 W/mK (@ 23º C meant temp, 50-70% R.H) having Permeance : 3.3 X 10^-4 g / M.N.s, Permeability : 8.19 X10-15 Kg/Pa.s.m (0.029 mg.m/N.h), Permeability Resistance Factor : μ> 15,000, Reinforced pure aluminium foil facing for ducting insulation
i) Insulation
ii) Vapour barrier
iii) Final finish as specified.
iv) PVC straps at 2.5m intervals
v) Painting of the bottom side of the duct with black or of approved colour.
25 mm For Supply & Return air Ducting
19 mm For Supply/Return air Ducting.
Duct acoustic insulation with acoustic lining of duct with open cell nitrile rubber with 0.8mm thick aluminium vapour barrier foil and conforming to specification given in the tender.
i) Insulation
ii) Finish with 0.45mm Al. perforated sheet on the inner surface.
19 mm thick
25 mm thick
Lifting & Shifting Works
Lifting & Shifting/placing of VRV Outdoors upto terrace floor as indicated in the drawings.
Outdoor Units
COOL KRAFT
M K Enterprises
COOL KRAFT
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid