| 1 | L1₹2.9 LAccepted-AOC 852 EKTA VIHAR 1 C NEAR ANAND NAGAR 9 B PATIALA 147001 | PATIALA | PATIALA | PUNJAB | 147001 | L1 | Accepted-AOC BEING LOWEST | |
| 2 | L2₹34.6 L+₹4.6 L (15.5%)Rejected-Finance 44 NEAR DURGA MANDIR TRIPURI TOABA TRIPURI TOWN PATIALA 147004 PB | PATIALA | PUNJAB | 147004 | L2 | Rejected-Finance NOT BEING LOWEST | |
| 3 | L3₹37.4 L+₹7.4 L (24.7%)Rejected-Finance 32 FATEH ENCLAVE OFFICERS ENCLAVE PHASE II PATIALA 147001 PB | PATIALA | PATIALA | PUNJAB | 147001 | L3 | Rejected-Finance NOT BEING LOWEST | |
| 4 | L4₹39.2 L+₹9.3 L (31.0%)Rejected-Finance 300 PREM BASTI 10 SANGRUR SANGRUR PUNJAB 148001 | SANGRUR | PUNJAB | 148001 | L4 | Rejected-Finance NOT BEING LOWEST | |
| 5 | L5₹41.3 L+₹11.3 L (37.8%)Rejected-Finance H NO 597 SEONA ROAD RANJIT NAGAR PATIALA PB 147001 | PATIALA | PATIALA | PUNJAB | 147001 | L5 | Rejected-Finance NOT BEING LOWEST |
| Sl No | Description | Qty | Unit | Arneja Builders L1 | SWAMI ENGINEERS L3 | Jawandha Enterprises L5 | AGGARWAL & CO L4 | Mohinder Pal and Sons L2 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of cables including getting out in any kind of soil complete all as specified and directed. | 914.76 | Cum | 80 ₹73,180.8 Lowest | 80 ₹73,180.8 Lowest | 100 ₹91,476 | 90 ₹82,328.4 | 100 ₹91,476 |
| 2.00 | Returning filling in including spreading, levelling, and well ramming, in layers not exceeding 25 cm each layer of any kind of soil. | 606.58 | Cum | 50 ₹30,329 | 18 ₹10,918.44 Lowest | 25 ₹15,164.5 | 30 ₹18,197.4 | 20 ₹12,131.6 |
| 3.00 | Removing surplus excavated material from site not exceeding 50 mtrs from starting point and depositing where directed at level not exceeding 1.5 mtr above the starting point. | 308.18 | Cum | 40 ₹12,327.2 | 18 ₹5,547.24 Lowest | 25 ₹7,704.5 | 30 ₹9,245.4 | 20 ₹6,163.6 |
| 4.00 | Material and labour for sand cushioning for cables 8 cm below the cable and 15 cm above with dry river sand in trenches for cushioning of underground cable line including spreading, leveling, well ramming completed all as specified and directed. | 274.43 | CUM | 100 ₹27,443 Lowest | 450 ₹1,23,493.5 | 150 ₹41,164.5 | 330 ₹90,561.9 | 260 ₹71,351.8 |
| 5.00 | Supplying & laying factory made unreinforced Precast concrete cable covers class LV type 1, flat, Size 250x150x40mm laid in trenches as protection to cables complete all as directed by Engr-in-Charge | 22,500 | Each | 10 ₹2,25,000 | 13 ₹2,92,500 | 5 ₹1,12,500 Lowest | 12 ₹2,70,000 | 13 ₹2,92,500 |
| 6.00 | Material and labour for replacement of GI tubing light grade 40 mm bore for passing through cables under the floor ,along the wall or along the pole complete all as specified and directed. | 330 | RM | 150 ₹49,500 Lowest | 200 ₹66,000 | 250 ₹82,500 | 180 ₹59,400 | 225 ₹74,250 |
| 7.00 | Supply & lay in replacement of existing unserviceable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volt grade of cross sectional area 35 Sqmm 3.5 Core all as specified & directed by Engr-in-Charge.Note:- Cost of Al thimbles for connection of LT XLPE Cable with MCCB DB VTPN is included in the unit rate quoted by contractor. | 900 | RM | 170 ₹1,53,000 Lowest | 240 ₹2,16,000 | 195 ₹1,75,500 | 350 ₹3,15,000 | 180 ₹1,62,000 |
| 8.00 | Supply & lay in replacement of existing unserviceable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volt grade of cross sectional area 25 Sqmm 4 Core all as specified & directed by Engr-in-Charge.Note:- Cost of Al thimbles for connection of LT XLPE Cable with MCCB DB VTPN is included in the unit rate quoted by contractor. | 1,660 | RM | 150 ₹2,49,000 | 175 ₹2,90,500 | 150 ₹2,49,000 | 250 ₹4,15,000 | 140 ₹2,32,400 Lowest |
| 9.00 | Supply & lay in replacement of existing unserviceable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volt grade of cross sectional area 16 Sqmm 4 Core all as specified & directed by Engr-in-Charge. Note:- Cost of Al thimbles for connection of LT XLPE Cable with MCCB DB VTPN is included in the unit rate quoted by contractor. | 1,700 | RM | 120 ₹2,04,000 Lowest | 135 ₹2,29,500 | 120 ₹2,04,000 Lowest | 170 ₹2,89,000 | 125 ₹2,12,500 |
| 10.00 | Supply & lay in replacement of existing unserviceable XLPE insulated, armoured heavy dutyelectric cable with aluminium conductor, 1100 volt grade of cross sectional area 10 Sqmm 2 Core all as specified & directed by Engr-in-Charge. | 580 | RM | 90 ₹52,200 | 100 ₹58,000 | 75 ₹43,500 Lowest | 140 ₹81,200 | 90 ₹52,200 |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
14 Aug 2025, 6:00 pmClosed
MAJ MOHAMMED AQIL AZEEM
GE NORTH PATIALA MILITARY ENGINEER SERVICES SANGRUR ROAD PATIALA CANTT
REPAIRS AND MAINTENANCE OF SUB MAIN WIRING, DISTR BOARD MCBS AND SERVICE CONNECTION SECT A AND C UNDER GE(N) PATIALA
2025_MES_720791_1
GE (N)/TOKEN-21/2025-2026
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
PATIALA
AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
GE N PATIALA
₹90,000
Yes
19 Sept 2025
17 Jul 2025
16 Aug 2025
17 Jul 2025
14 Aug 2025
31 Jul 2025
Amount
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of cables including getting out in any kind of soil complete all as specified and directed.
Returning filling in including spreading, levelling, and well ramming, in layers not exceeding 25 cm each layer of any kind of soil.
Removing surplus excavated material from site not exceeding 50 mtrs from starting point and depositing where directed at level not exceeding 1.5 mtr above the starting point.
Material and labour for sand cushioning for cables 8 cm below the cable and 15 cm above with dry river sand in trenches for cushioning of underground cable line including spreading, leveling, well ramming completed all as specified and directed.
Supplying & laying factory made unreinforced Precast concrete cable covers class LV type 1, flat, Size 250x150x40mm laid in trenches as protection to cables complete all as directed by Engr-in-Charge
Material and labour for replacement of GI tubing light grade 40 mm bore for passing through cables under the floor ,along the wall or along the pole complete all as specified and directed.
Supply & lay in replacement of existing unserviceable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volt grade of cross sectional area 35 Sqmm 3.5 Core all as specified & directed by Engr-in-Charge.Note:- Cost of Al thimbles for connection of LT XLPE Cable with MCCB DB VTPN is included in the unit rate quoted by contractor.
Supply & lay in replacement of existing unserviceable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volt grade of cross sectional area 25 Sqmm 4 Core all as specified & directed by Engr-in-Charge.Note:- Cost of Al thimbles for connection of LT XLPE Cable with MCCB DB VTPN is included in the unit rate quoted by contractor.
Supply & lay in replacement of existing unserviceable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volt grade of cross sectional area 16 Sqmm 4 Core all as specified & directed by Engr-in-Charge. Note:- Cost of Al thimbles for connection of LT XLPE Cable with MCCB DB VTPN is included in the unit rate quoted by contractor.
Supply & lay in replacement of existing unserviceable XLPE insulated, armoured heavy dutyelectric cable with aluminium conductor, 1100 volt grade of cross sectional area 10 Sqmm 2 Core all as specified & directed by Engr-in-Charge.
M & L for Sub main wiring with two single core 6.0 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through PVC concealed conduit 25 mm dia including 6.0 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2 Runs of 6.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 6.00 Sqmm Copper conductor Earth wire shall be measured as one unit) Note 2 : Rate quoted for this items shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of 25 mm dia with tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc. 10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring. (iv) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB.
Supply and fix in replacement of MCB SP up to 6-32 Amp all as specified and directed.
Supply and fix in replacement of MCB SPN 6-32 Amp complete all as specified and directed.
Supply & fix in replacement of existing unserviceable Sheet metal enclosure with new DB’s suitable for MCBs of single pole and neutral 8 way double door type with 200 amp rated bus bar. Note: i) Connnections of the MCB'S shall be done with appropriate size of brass/Cooper thimble. ii) The DB shall be fiush fixed and making good the disturbed surface shall be part of job at no extra cost.
Supply & fix in replacement of existing unserviceable Sheet metal enclosure with new DB’s suitable for MCBs of single pole and neutral 4 way double door type with 200 amp rated bus bar. Note: i) Connnections of the MCB'S shall be done with appropriate size of brass/Cooper thimble. ii) The DB shall be fiush fixed and making good the disturbed surface shall be part of job at no extra cost.
Supply and fix epoxy power coated MCCB distribution box double door VTPN 4 way vertical type AC 415 V with IP 43 protection for MCBs alongwith provision of MCCB as incomer with commen bus-bar at incoming end of outgoing MCBs grouted/ flush to wall, complete all as specified by Engineer-in-charge. (Note :- MCCB will be measured and paid under seperate item) (i) Cost of Eye/bottle thimbles used for connection MCBs in DBs shall deemed to be included in unit rate quoted for this items, (ii) Electric wiring should be done in proper colour coding i.e. Red for phase, Black for neutral and Green for Earth. (iii) connection of theMCCBs/ MCBs with cable shall be made through appropriate size pin /bottle type thimble -properly crimped. all the vacant holes of the DB shall be provided with blank plates of appropriate size complete all as specified and directed by Engr-in-charge.
S & F MCCB, 4 Pole, 100 A, 25 KA for fixing in DB including proper thimble connection, thermal and magnetic release protection complete all as specified and directed by Engineer-in-charge.
S & F MCCB, 4 Pole, 63 A, 16 KA for fixing in DB including proper thimble connection, thermal and magnetic release protection complete all as specified and directed by Engineer-in-charge.
S & F in replacement of Sheet metal enclosure DB TPN 4 ways double door 415 volts with 200 Amps standard bus bar of suitable size and common neutral link flush mounting type, drilling holes for incoming and out going cables complete with IP-43 protection complete all as specified and directed by Engr-in-charge
S & F in replacement of MCB, TRIPLE pole & neutral (TPN) 10 KA 240 volts 63 Amp capacity fixing in DB’s complete all as specified and directed. (Note: MCB should be B or C curve as directed by engineer in charge)
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6mm tthick buried directly in ground(earth plate not less than 2.25 mtr deep below the normal ground level ) with top edge of plate not less than 1.5 mtr below the normal ground level connected to galvanized earth wire 4mm dia by means of nuts bolts,washers,check nuts of iron or steel including test point PCC pits and RCC cover in PCC 1:2:4 (type B-1) including iron angle frme 40*40*6mm. and medium grade GI watering pipe 20mm dia with funnel and wire mesh and 15 mm bore GI pipe light grade proection pipe including excavation and charcoal ,common salt surrounded with 15cm all around the plate all as specified and shown in EP-3 of SSR Part-I
Cutting of hardstanding floor/wall for laying of cable including matching with suface by using cement concrete all as specified and directed. Note:- Necessary concrete work to be measured and paid separately.
M&L for Boring of holes under road, pavement, hard standing by trench-less technology using ultrasound technique and necessary machine suitable to pass through 40 to 80 mm bore GI tubing and cable etc complete all as specified and directed. Note: GI pipe shall be measured and paid seperately under relevant item.
Supply and fixing in replacement single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps, complete all as specified and as directed by Engineer-in-charge.
Supply and fix DB box MCB protected socket PVC plastic base having MCB of suitable rating 20 amp C series complete all as specified and directed by engr-in-charge.
M & L for Sub main wiring with two single core 4.0 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through PVC concealed conduit of suitable dia including 4.0 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2 Runs of 4.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 4.0 Sqmm Copper conductor Earth wire shall be measured as one unit) Note 2 : Rate quoted for this items shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of 25 mm dia with tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc. 10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring. (iv) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB.
M & L for Sub main wiring with two single core 2.5 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through PVC concealed conduit of suitable dia including 2.5 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2 Runs of 2.50 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 2.5 Sqmm Copper conductor Earth wire shall be measured as one unit) Note 2 : Rate quoted for this items shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of 25 mm dia with tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc. 10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring. (iv) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB.
Supply & fix Sheet metal enclosure suitable for fixing DB and Electric meter, factory made of size 60 x 60 x 18 cm made out of 1.6 mm thick MS sheet with double door, sutiable locking arrangements, powder coated, cutting chasing in wall and fixing and making good as per existing surface complete including removing old one, complete all as specified and directed by Engr-in-charge.
M&L Painting to existing Enclosures for DB and Electric meter of any type complete with two coat of weather proof synthetic enamel spray paint over a coat of red oxide primer complete all as directed by Engr-in-Charge.
S & F PVC enclosure size suitable for single phase electric meter having security Seal Wire Make: SINTEX SPGSMB3527 (single phase) or equivalent including electric connection, cutting chasing wall and making good the disturbed surface complete all as specified and directed by Engr-in-charge.
Taking down existing LT panel board (Meter Box) located at Map block and supply and fixing sheet metal enclosure board made of 1.6 mm thick metal sheet and painting 2 coats with synthic enamel paint over a coat of red oxide primer including Aluminium bus bar of suitable rating and fixed with wall for fixing MCCB 4P 125 amp and electric meters complete with wiring, fitting and accessories, locking arrangements with handle (adequate size and adequate depth for the following equipments, internal wiring and termination of external cable, lugs and glands and conduits as required) comprising of following. (a) Incoming 125 Amp 4 pole MCCB 25 KA-01 Nos.(Main incomer) (b) Aluminium Bus bar rated 200 Amp capacity. (c) 10Amp DP/SPN MCB-01 No (Outgoing for stair case and garrage) (d) 63 Amp DP/SPN MCB-06 Nos (Outgoing for Qtr meters) (e) Taking down and Refixing of electric meter energy meters single phase 240Volt 40Amps 50HZ -06 Nos.
M & L for Sub main wiring with 04 (Four) single core 10.0 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through pvc concealed conduit of suitable dia including 10.0 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note1:- 4 Runs of 10.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 10.00 Sqmm Copper conductor Earth wire shall be measured as one unit) Note2 : Rate quoted for this item shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of suitable size dia with tees, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in and making good to facing where required pointing in cement mortar 1:3 to match the existing surfaces and cutting not exc. 10 cm girth. (iii) Taking down/out existing unserviceable sub main wiring. (iv) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB.
M & L for Sub main wiring with 04 (Four) single core 16.0 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through pvc concealed conduit of suitable dia including 10.0 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note1:- 4 Runs of 16.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 10.00 Sqmm Copper conductor Earth wire shall be measured as one unit) Note2 : Rate quoted for this item shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of suitable size dia with tees, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in and making good to facing where required pointing in cement mortar 1:3 to match the existing surfaces and cutting not exc. 10 cm girth. (iii) Taking down/out existing unserviceable sub main wiring. (iv) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB.
S&F batten LED 22 w inveter LED tube light complete fitting 230 volt energy saving, 04 hrs battery backup, CRI ≥80 more than, driver efficiency ≥ 85%, operating voltage 230 volt, 50hz operating temp (-10°C to 50°C) complete accessories internally pre wired and including connecting up with flexible copper conductor cable with suitable size complete all as specified and directed by Engineer-in-charge. .
S & F LED lamp invertor technology 9 watt with 4 hour power back up with efficiency more than 100 lumen per watt, Lithium ion battery including removing of unserviceable lamp complete all as specified and directed by Engr-in-charge.
M&L for cutting chases for concealed conduit wiring, pinning in making good to facings where required and pointig in cement mortar1:3 to ends or edges of landings, and making good, cutting not exc 10 cm girth.all as specified and directed by engg- in charge
M&L for PVC conduit 20 mm medium garde (ISI marked) inreplacement of old damaged PVC conduit for protection of sunmain wiring fixed to walls or in chasing, wall crossing with all necessary fittings and fixed with clamps and fixtures etc complete all as specified and directed.
M & L for Sub main wiring with two single core 10.0 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through PVC concealed conduit 25 mm dia including 10.0 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2 Runs of 10.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 10.00 Sqmm Copper conductor Earth wire shall be measured as one unit) Note 2 : Rate quoted for this items shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of 25 mm dia with tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc. 10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring. (iv) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB.
S&F MCB DB double door 240 volts with 200 Amps standard bus bar of suitable size and common neutral link all enclosed in standard sheet flush mounting type, drilling holes for incoming and out going cables complete suitable for 12 ways with IP43 protection complete all as specified and directed. (Note: MCB should be B or C curve as directed by engineer in charge)
Taking down carefully existing points wiring on surface conduit/concealed conduit including conduit from surface and expect conduit in concealed wiring for light/fan/socket/power/bell from wall & roof along with fitting and fixtures such as switches, sockets, ceiling roses, batten holders, unserviceable light fittings, pieces of wires, gutties, conduit, wooden boards etc removing materials to store for keeping in safe custody of contractor for which the credit has been considered under schedule of credit and making good the disturbed portion of all floor, ceiling etc all as specified and directed.
Point wiring with 1.5 sqmm PVC insulated and unsheathed FRLSH single core multi-stranded copper conductor for one light/fan/bell in new PVC conduit to be terminated in pressed steel terminal boxes with top cover plate including 1.5 sqmm PVC insulated and unsheathed FRLSH single core multi-stranded copper earth continuity conductor controlled by one switch and/or one regulator complete including repairing the surfaces in CM 1:3 and finishing the surface as per existing treatment all as specified and directed by Engineer in-charge Note-I-(Switches and regulators shall be measured and paid for separately). Note-II- ( Wiring shall be done as per colour code in IS for phase, neutral and earth). Note-III- (The cost of modular cover plate and metal flush boxes is deemed to be included in the unit rate quoted for this item). Note -IV - cost of Eye/bottle thimbles used for connection in switches/sockets & MCBs in DBs is deemed to be included in the unit rate quoted for this item. Note:- V- Rate of cutting chasing included in the unit rate quoted for this item
All as per Sl item No 42.00 above herein before but one socket out let 5 pins 5 Amp on the same board with other switches complete all as specified and directed.
All as per Sl item No 42.00 above herein before but for one socket out let 5 pins 5 Amp on independent board complete all as specified and directed.
All as per item No.42.00 herein before but 2.5 Sqmm PVC insulated and unsheathed FRLSH single core multistranded copper conductor incl 2.5 Sqmm PVC insulated and unsheathed FRLSH single core muilti-stranded copper earth wire for switch socket combination 3 pin 15 amps on independent board.
M & L for Point wiring with 1.5 sqmm PVC insulated and unsheathed FRLSH single core multi-stranded copper conductor for one light/fan in existing conduit to be terminated in pressed steel terminal boxes with top cover plate including 1.5 sqmm PVC insulated and unsheathed FRLSH single core multi-stranded copper earth continuity conductor connected to cmmon earth dolly controlled by one switch and/or one regulator complete including repairing the surfaces in CM 1:3 and finishing the surface as per existing treatment all as specified and directed by Engineer iin-charge Note-I-(Switches and regulators shall be measured and paid for separately). Note-II- ( Wiring shall be done as per colour code in IS for phase, neutral and earth). Note-III- (The cost of modular cover plate and metal flush boxes is deemed to be included in the unit rate quoted for this item). Note -IV - cost of Eye/bottle thimbles used for connection in switches/sockets & MCBs in DBs is deemed to be included in the unit rate quoted for this item.
All as per Sl item No 46.00 above herein before but one socket out let 5 pins 5 Amp on the same board with other switches complete all as specified and directed.
All as per Sl item No 46.00 above herein before but for one socket out let 5 pins 5 Amp on independent board complete all as specified and directed.
All as per item No 46.00 herein before but 2.5 Sqmm PVC insulated and unsheathed FRLSH single core multistranded copper conductor incl 2.5 Sqmm PVC insulated and unsheathed FRLSH single core muilti-stranded copper earth wire for switch socket combination 3 pin 15 amps on independent board.
Supply and fix in replacement of Modular switch 1 way, 6 Amps, 1 module complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement of Modular switch 1 way, 16 Amps, 1 module complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement of Modular Bell switch 1 way, 6 Amps, 1 module complete all as specified.and directed by Engr-in-charge.
S & F Bell ding dong electronic complete all as specified and directed by Engineer-in-charge.
Supply and fix in replacement of Modular socket 5 pin 6 Amps, 2 module complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement of Modular socket 5 pin 6/16 Amps, combination type 2 module complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement of Fan regulator modular type 2 module complete all as specified and directed by Engr-in-charge.
Lamp holder including LED bulb 9 W including flexible wire 0.5 Sqmm copper cable all as specified & directed by Engr-in-charge.
Ceiling rose surface bakelite surface 65 x 50mm 3 terminals all as specified & directed by Engr-in-charge.
M & L for Sub main wiring with two single core 1.5 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through PVC concealed conduit of suitable dia including 1.5 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2 Runs of 1.50 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 1.5 Sqmm Copper conductor Earth wire shall be measured as one unit) Note 2 : Rate quoted for this items shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of 25 mm dia with tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc. 10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring. (iv) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB.
M&L for replacement of old damaged PVC Meter Box of suitable size for three phase LT meter. door with 1 Nos of transparent glass of suitable for visibility of meter fixed on door with suitable arrangemnets. meter box shall be fixed in wall and necessary chiseling and meke good of wall to be included in quoted cost. NOTE:-To fix the meter box required disconnecting and refixing of connections to be included in quoted rate.
Mohinder Pal and Sons (BID ID -3382673)
SWAMI ENGINEERS (BID ID -3388848)
AGGARWAL & CO (BID ID -3386180)
Jawandha Enterprises (BID ID -3394176)
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .