Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹43.8 LAccepted-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | ₹43.8 L Quoted ₹44.7 L | L1 | Accepted-AOC Accepted |
| 2 | L2₹56.5 L+₹11.7 L (26.2%)Rejected-AOC SECTOR 10 PANCHKULA | PANCHKULA | PANCHKULA | HARYANA | ₹56.5 L+₹11.7 L (26.2%) | L2 | Rejected-AOC Rejected |
| 3 | L3₹56.7 L+₹12.0 L (26.8%)Rejected-AOC | ₹56.7 L+₹12.0 L (26.8%) | L3 | Rejected-AOC Rejected |
Tender Value
₹45.0 L
EMD Value
₹90,000
Closing Date
7 Jul 2023, 6:00 pmClosed
GE (U) CHANDIMANDIR
GE (U) CHANDIMANDIR PIN-134107
REPAIR TO LT PANEL FEEDER PILLAR BOXES AND OTHER ACCESSORIES AND CONNECTED DISTRIBUTION WORK AT VARIOUS SUB STATIONS AT CHANDIMANDIR
2023_MES_587164_2
GE(U)/CHM-46/2022-23
Open Tender
Miscellaneous Works
Works
240 days
GE (U) CHANDIMANDIR
As per tender documents
5 documents required · 5 mandatory
₹500
GE (U) CHANDIMANDIR
₹90,000
Yes
25 Aug 2023
16 Jun 2023
14 Jul 2023
16 Jun 2023
7 Jul 2023
23 Jun 2023
Amount
Excavation in trenches in any type of soil not exceeding 1.50 meter wide and not exceeding 1.5 meter in depth; for laying/taking out cables and foundations of poles etc and getting out complete, all as specified.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm thick each as in soft/loose soil, complete all as specified.
Removing of surplus soil / excavated material to a distance not exceeding 50 metre and depositing where directed complete all as specified.
Supply, laying, jointing, testing and commissioning Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 400 Sqmm 3.5core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, including taking out / down old existing cables, complete all as specified and as directed. Note: Excavation & earth work shall be measured and paid separately.
Supply, laying, jointing, testing and commissioning Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 300 Sqmm 3.5core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, including taking out / down old existing cables, complete all as specified and as directed. Note: Excavation & earth work shall be measured and paid separately.
Supply, laying, jointing, testing and commissioning Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 240 Sqmm 3.5core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, including taking out / down old existing cables, complete all as specified and as directed. Note: Excavation & earth work shall be measured and paid separately.
Supply, laying, jointing, testing and commissioning Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 185 Sqmm 3.5core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, including taking out / down old existing cables, complete all as specified and as directed. Note: Excavation & earth work shall be measured and paid separately.
Supply, laying, jointing, testing and commissioning Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 150 Sqmm 3.5core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, including taking out / down old existing cables, complete all as specified and as directed. Note: Excavation & earth work shall be measured and paid separately.
Supply, laying, jointing, testing and commissioning Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 120 Sqmm 3.5core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, including taking out / down old existing cables, complete all as specified and as directed. Note: Excavation & earth work shall be measured and paid separately.
Supply, laying, jointing, testing and commissioning Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 95 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, including taking out / down old existing cables, complete all as specified and as directed. Note: Excavation & earth work shall be measured and paid separately.
Supply, laying, jointing, testing and commissioning Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 70 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, including taking out / down old existing cables, complete all as specified and as directed. Note: Excavation & earth work shall be measured and paid separately.
Supply, jointing & testing straight through joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 1100 Volts grade, LT, underground XLPE insulated armoured aluminium conductor, 3.5/4 core 400 sqmm size cable, complete all as specified and directed.
Supply, jointing & testing, indoor/outdoor straight through joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 1100 Volts grade, LT, underground XLPE insulated armoured aluminium conductor, 3.5/4 core 240 to 300 sqmm size cable, complete all as specified and directed.
Supply, jointing & testing, indoor/outdoor straight through joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 1100 Volts grade, LT, underground XLPE insulated armoured aluminium conductor, 3.5/4 core 185 sqmm size cable, complete all as specified and directed.
Supply, jointing & testing, indoor/outdoor straight through joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 1100 Volts grade, LT, underground XLPE insulated armoured aluminium conductor, 3.5/4 core 95 to 120 sqmm size cable, complete all as specified and directed.
Supply, jointing & testing, indoor/outdoor straight through joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 1100 Volts grade, LT, underground XLPE insulated armoured aluminium conductor, 3.5/4 core 50 to 70 sqmm size cable, complete all as specified and directed.
Supply and laying 100mm outer dia double walled corrugated HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties, of approved colou, complete with fittings for cable protection, complete all as specified and as directed.
Supply and laying / fixing , GI pipe light grade 80mm bore for cable protection fixed to pole/wall or laid under floor/road/pavement,including MS clamps,nut,bolts etc, complete all as specified and directed.
Material and labour for cutting of Road/hardstanding not less than 30 cm in depth and 30 cm in width for passing the cable/pipe and making good the disturbed surface with PCC 1:2:4 type B-1 where road cutting is done to make the road surface fair and levellled, complete all as specified and directed
Taking down old unserviceable LT Panel/feeder pillar of any size/capacity including all accessories from the existing position after disconnecting all electric connections complete all as specified and directed
Supply, installation, testing and commissioning of out door type LT Panel, factory made, CPRI approved, opening from front & rear, double door type, dust and vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with approved shade over a coat of zinc chromate primer, 4 Nos heat shrink insulated aluminium bus bars of 1.5 times rating of incoming MCCB , including all connections with aluminium strip pillar board, provided with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connections with new lugs, glands to be provided at cable entries, including MS channel frame of ISMC 75 at base of panel and 04 Nos legs of not less than 75 cm long each below the base of panel made of angle iron 50 mmx 50 mm x 6 mm and grouted in PCC 1:2:4 type B1(using 20 mm graded stone aggregate) complete all as specified and directed and comprising of following accessories:- (A) INCOMING :- (a) ACB, 415 Volts, 50 HZ, four pole 1000 Amp, EDO Type, microprocessor based, breaking capacity 52 KA, IEC - 60947, EN - 60947 double insulation = 01 No (b) OUT GOING :- (a) ACB, 415 Volts, 50 HZ, four pole 630 Amp, EDO Type, microprocessor based breaking capacity 52 KA, IEC - 60947, EN - 60947 double insulation = 02 Nos (c) Phase indicator lamp complete with copper control wiring and suitable size of CT complete = 01 (Set of three). (d) Digital type multi meter LCD display complete for Volt meter and ammeter of size 96 x 96 mm complete all as specified and directed.
Supply, installation, testing and commissioning of out door type LT Panel, factory made, CPRI approved, opening from front & rear, double door type, dust and vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with approved shade over a coat of zinc chromate primer, 4 Nos heat shrink insulated aluminium bus bars of 1.5 times rating of incoming MCCB including all connections with aluminium strip pillar board provided with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connections with new lugs, glands to be provided at cable entries, including , MS channel frame of ISMC 75 at base of panel only and 04 Nos legs of not less than 75 cm long each below the base of panel made of angle iron 50mm x 5 0mm x 6 mm and grouted in PCC 1:2:4 type B1( using 20 mm graded stone aggregate), complete all as specified and directed and comprising of following accessories:- (A) INCOMING :- (a) ACB, 415 Volts, 50 Hz, four pole 1000 Amp, EDO Type, microprocessor based breaking capacity 52 KA, IEC - 60947, EN - 60947 double insulation = 01 No (B) OUT GOING :- (a) ACB, 415 Volts, 50 Hz, four pole 630 Amp, EDO Type, microprocessor based, breaking capacity 52 KA, IEC - 60947, EN - 60947 double insulation = 02 Nos (b) MCCB four pole 415 Volts ,50 Hz, 630 Amps adjustable thermal and adjustable magnetic protection release, breaking capacity 36 KA with Ics = 100% Icu=02 Nos . (Reserve) (c) Phase indicator lamp complete with copper control wiring and suiable size of CT complete = 01 (Set of three). (d) Digital type multi meter LCD display complete for Volt meter and ammeter of size 96 x 96 mm complete all as specified and directed.
Supply, installation testing and commissioning of out door type LT feeder piller box CPRI approved opening from front & rear double door type,dust and vermin proof, fabricated out of 3.15 mm CRCA sheet of size 0.75 x 0.50 x 0.50 m duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and MS channel frame of ISMC 75 at base of panel and 04 Nos legs of not less than 50 cm long each below the base of panel made of angle iron 50 mm x 50 mm x 6mm and grouted in PCC 1:2:4 type B1( using 20 mm graded stone aggregate) alongwith incoming MCCB four pole, 415 volts, 25 KA, 50 Hz, 200 amps - 01 No including 4 Nos heat shrink insulated 200 Amps rated aluminum bus bar suitable for 4 Nos outgoing 25 sqmm to 35 sqmm 3.5/4 core XLPE armoured cable, complete all as specified and directed
Taking down old unserviceable ACB any type and Supply, installation testing and commissioning new LT ACB of 1000 Amps four pole mannual draw out thermal magnetic release, 415 Volts, 50 Hz, suitable for existing location alongwith replacement of burnt aluminum bus bars with connected nut bolts and lugs with new aluminum bus bars /nut bolts/lugs complete all as specified and directed
Taking down old unserviceable ACB any type and Supply, installation testing and commissioning new LT ACB of 800 Amps four pole manual draw out thermal magnetic release, 415 Volts, 50 Hz suitable for existing location alongwith replacement of burnt aluminum bus basr with connected nut bolts and lugs with new aluminum bus bars /nut bolts/lugs, complete all as specified and directed
Taking down old unserviceable ACB any type and Supply, installation testing and commissioning new LT ACB of 630 Amps four pole manual draw out thermal magnetic release, 415 Volts, 50 Hz suitable for existing location alongwith replacement of burnt aluminum bus bars with connected nut bolts and lugs with new aluminum bus bars /nut bolts/lugs complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement MCCB 4 pole 630 Amps, 415 volts, 50 Hz, with breaking capacity 36 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 4 pole 400 Amps, 415 volts, 50 Hz, with breaking capacity 36 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 4 pole 320/350 Amps, 415 volts, 50 Hz, with breaking capacity 36 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 4 pole 250 Amps, 415 volts, 50 Hz, with breaking capacity 25 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 4 pole 200 Amps, 415 volts, 50 Hz, with breaking capacity 25 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 4 pole 160 Amps, 415 volts, 50 Hz, with breaking capacity 25 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 4 pole 125 Amps, 415 volts, 50 Hz, with breaking capacity 25 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 4 pole 100 Amps, 415 volts, 50 Hz, with breaking capacity 25 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 4 pole 63 Amps, 415 volts, 50 Hz, with breaking capacity 25 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 3 pole 630 Amps, 415 volts, 50 Hz, with breaking capacity 36 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 3 pole 400 Amps, 415 volts, 50 Hz, with breaking capacity 36 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 3 pole 250 Amps, 415 volts, 50 Hz, with breaking capacity 25 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 3 pole 200 Amps, 415 volts, 50 Hz, with breaking capacity 25 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 3 pole 160 Amps, 415 volts, 50 Hz, with breaking capacity 25 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 3 pole 125 Amps, 415 volts, 50 Hz, with breaking capacity 25 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 3 pole 100 Amps, 415 volts, 50 Hz, with breaking capacity 25 KA, complete all as specified and directed.
Supply and fixing in replacement MCCB 3 pole 63 Amps, 415 volts, 50 Hz, with breaking capacity 25 KA, complete all as specified and directed.
Material and labour for welding of broken hinges of LT panel doors including painting of LT out door/ indoor panel in front, top, rear and both sides above ground level with two coats of synthetic enamel paint as per existing colour after preparation of surface complete all as specified and directed
Supply and fixing in repairs electric panel doors fabricated from MS sheet as per existing size and shape and fixed with hinges by properly welding and checking for proper opening and closing complete all as specified and directed.
Supply and fixing in replacement multimeter flush mounitng type, digital type,0 -500 volts and 0-750 amp, 50 Hz, 96 x 96 mm complete all as specified and directed
Supply and fixing in replacement Godrej type lock for LT panel matching with the existing complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement aluminum bus bars of different size and capacity required as per site including PVC insulating materials and cutting, welding, making holes etc complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement APFC panel relay 8 steps, 415 volts, complete all as specified and directed. Make : L&T, Cat No- CS909020000 or equivalent in the makes mentioned in Appx 'B'
Supply and fixing in replacement APFC panel relay 12 steps, 415 volts, complete all as specified and directed. Make : L&T, Cat No - CS909030000 or equivalent in the makes mentioned in Appx 'B'
Suppy and fixing in replacement capacitor duty connector MOC 12.5, 440 volt, 3 Ph, 50 Hz, detatching type early make contacts, seprate termination for damping resistors, encapsulated damping resistor assembly, built in surge suppressor, low pick up VA consumption complete all as specified and directed . Make : L&T, Cat No - CS96321 or equivalent in the makes mentioned in Appx 'B'
Suppy and fixing in replacement capacitor duty connector MOC 25, 440 volt, 3 Ph, 50 Hz, detatching type early make contacts, seprate termination for damping resistors, encapsulated damping resistor assembly, built in surge suppressor, low pick up VA consumption complete all as specified and directed. Make : L&T, Cat No - CS96322 or equivalent in the makes mentioned in Appx 'B'
Supply and fix in replacement heavy duty capacitors, cylindrical series 12.5 KVAr rating, 440 volt ,complete all as specified and directed .
Supply and fix in replacement heavy duty capacitors, cylindrical series 25 KVAr rating, 440 volt ,complete all as specified and directed .
Supply and fixing in replacement MCB TP 40 Amps, 415 volts, 'D' curve/ series, complete all as specified and directed.
Supply and fixing in replacement MCB TP 32 Amps, 415 volts, 'D' curve/ series, complete all as specified and directed.
Supply and fixing in replacement MCB FP 63 Amps, 415 volts, 'C' curve/ series, complete all as specified and directed.
Supply and fixing in replacement change over switch ON LOAD type, 415 Volt 50 Hz, AC, 3 pole I-O-II Position door interlock feature, in Steel Sheet enclosures, capacity 600 Amps rated current, manually operated, conforming to IS:13947 of latest edition, with high thermal and dynamic strength to withstand short circuit current level of 80 KA rms complete all as specified and directed.
Taking down old/down u/s earthing with GI earth plate, GI strip earthing lead (where feasible and economical) with GI Strip, watering pipe and protection pipe and disposing of the material having scrap value and making good the spot all as specified and directed
Material and labour for providing earthing complete with galvanised steel earth electrode plate of size 600x 600 x6 mm thick buried directly in ground in a earth pit not lessthan 2.25 mtr deep below ground level with the top edge of the earth plate at a depth not less than 1.5 mtr below ground level , connected to and including galvanised iron strip of size 32 x6 mm earth strip by means of bolts & nuts ,check nuts and washers and connected to earth test point connected to earth point / transformer /panel / feeder pillor box all as specified and directed by Engr-in-charge including necessary earth work in any type of soil ,disposal of surplus soil not exceeding 50 m ( the rate also includes for cost of charcoal & salt in alternate layers of 15 cm thickness , providing suitable size of GI pipe ( medium grade) for watering ,funnel, wirmesh, PCC connected PCC chamber(1:3:6) type C1 , RCC pit cover , charcoal ,salt including provision of earth lead protected by 40 mm dia light grade GI pipe and 20 mm medium gradeGI pipe for watering complete all as specified and directed by Engr-in-charge.
Material and labour for 40mm bore tube "light grade" galvanized laid in trenches or fixed along poles with mild steel clamps or protection to GI earth strip/cable, fixed in repaircomplete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repair GI strip 32 x 6 mm for earthing complete all as specified and directed
Material and labour for drawing out of LT ACB 4 pole 415 volts of capacity 630/800/1000/1200 amps form the LT panel and servicing/ repairing the same for proper functioning, tightening the loose hardware parts and loose connections and lubricating all mechanism, clean all contacts with fine emery paper and CRC, replacement of burnt/defective parts, applying petroleum jelly on the contacts, refixing in the original position and checking for proper functioning, complete all as specified and directed Note - Defective parts will be measured and paid seprately under the rellevant items.
Supply only fixed contacts as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed
Supply only moving contacts as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed
Supply only spring charging and operating mechanism as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge.
Supply only shunt trip coil 240 volts as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge.
Supply only CT as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge.
M/s Friends Engineering Works
Vasudeva Trading Co.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .