Rate Contract for SITC of different types of relays in TPNODL Area
TPNODL-OT-2200000025-22-23
TPNODL/OT/2200000025/22-23
Open Tender
sitc
Tender Notice
Odisha
TP Northern Odisha Distribution Limited (TPNODL)
Yes
Online / as specified in tender document
30 Jun 2022
27 Mar 2023
13 May 2022
Tender No TPNODL/OT/2200000025/22-23 Dtd.29.04.22
Project Name Rate Contract for SITC of different types of relays in TPNODL Area
Sr. No. Detailed Reference to TPnODL Technical Document. Please specify Document No / Clause No / Page No Description as per Bid Document Remarks - Query / Clarification TPNODL Clarification
1 STANDARD TECHNICAL SPECIFICATION OF DIFFERENTIAL RELAY / Pdf page no 26 of 157 STANDARAD TECHNICAL SPECIFICATION OF DIFFERENTIAL RELAY FOR TRANSFORMER WITH POWER PACK We assume separate power pack is not required along with the relay. Please confirm, POWER PACK REQUIRED
2 5 /GENERAL TECHNICAL REQUIREMENTS: Aux. supply /pdf sheet no.30 of 157 If the auxiliary supply drifts, 2 alarms may be triggered: 1. High set point alarm, adjustable from 105 % to 150 % of rated supply (maximum 275 V). 2. Low set point alarm, adjustable from 60 % to 95 % of rated supply (minimum 20 V). Proposed IED doesn't support Aux D.C. supply monitoring feature. Please Accept the same. Accept
3 Tripping curve For Phase over current and Earth Fault / /pdf sheet no.31 of 157 SIT, LTI, VIT, EIT, UIT (1) DT, RI DT, IEC: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT, IEEE: MI (D), VI (E), EI (F) Proposed relay have following characteristics, DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-EI, ANSI-MI, ANSI-VI. Please consider the same IEC-NI CURVE 3.0 SEC
4 Network and machine diagnostics/pdf sheet no.32 of 157 Harmonic distortion (THD), current and voltage Ithd,Uthd. THD is Power quality requirement which needs CT input from Metering core as per general recommendation, however relays works from Protection core .Please consider the same. OK
5 Setting of Negative sequence / unbalance/pdf sheet no.32 of 157 Definite time setting - 0.1 to 5 Ib/10% to 500% For NPS protection setting range for DT stage is 10% to 400%. Please accept the same. Accept
6 Setting of Thermal overload/pdf sheet no.33 of 157 Time constant Heating T1: 1 to 600 min Cooling T2: 5 to 600 min Alarm and tripping set points 0 to 300 % of rated thermal capacity Maximum equipment temperature 60 to 200 °C (140 °F to 392 °F) Proposed relay supports thermal overload protection function (49) as per IEC characteristics. Application note & setting guideline is attached herewith. Please accept the same. Accept
7 Setting of Differential Protection (T-87) / pdf sheet no.33 of 157 Restraint on energization Current threshold - 1 to 10 % Time Delay - 0 to 300 s Choice of restraint - conventional & Self-adapting Proposed relay have dual slope bias restrained characterisitcs. Setting & parameter detailsare attached herewith.Please accept the same. OK
8 Setting of Over fluxing(V/Hz): pdf sheet no. 33 of 157 Set Point 1.03 to 2 pu Definite time Setting -0.0 to 20000 s IDMT Setting - 0.0 to 1250 s Proposed relay have following characteristics Definite time Setting 0.0 to 14400 s IDMT Setting - User defined characteristics with 6 point setting. Please accept the same. OK
9 Setting of Under voltage (L-L or L-N) : pdf sheet no.33 of 157 Set point 5 to 100 % of Unp Time Delay - 0.05 to 300 s U/V setting range is 5 -200V. Please consider the same. OK
10 Configuration Method: pdf sheet no. pdf sheet no.33 of 157 Relay shall be configurable from HMI as well as software through Laptop. IEC 61850 related configuration (i.e. RCB, Data set, Goose related configuration) are possible through laptop & relay software only. Please accept the same. accept
11 LCD Display: pdf sheet no. 35 of 157 Relay shall have minimum 4 line LCD backlit display As per Point no 5. GENERAL TECHNICAL REQUIREMENTS: / Display/ Page no 30 of 157, Advanced UMI with graphical LCD screen is required. Please confirm the same. OK with 4 line advaced umi graphical display
12 Communication protocol/pdf sheet no.37 of 157 Details of Numerical relay communication ports are as follows. Front: Ethernet port Proposed relay comes with front USB Type port. Please accept the same. ok
13 Rear: IEC 61850 (for integration of relays with SCADA and accessing DR from remote through Tata Power automation WAN) No of rear port not confirmed. We propose 2 nos of PRP compliant ethernet port (RJ45 or F.O.) RJ45 TWO PORT WITH CONSOLE PORT
14 Special Requirement/pdf sheet no.37 of 157 One complete set of Relay configuration tool (Laptop, communication cable, Moxa, Manual) to be supplied for every 5 no’s lot of Relays, and pre-configured relay software along with all device configuration software to be pre- installed. We understand that this tender requirement is only for supply of Numerical Relays. Any additional equipments like Laptops, Moxa converters are not in scope of this tender. Please confirm. LAPTOP, COMMUNICATION CABLE, MANUAL, SOFTWARE TO BE SUPPLIED WITH 5 SET OF RELAY .
15 Special Requirement/pdf sheet no.37 of 157 Individual relays must have embedded power pack (with battery) of 17 AH. Relays don't have any embedded power packs. POWER PACK REQUIRED ADDITIONAL WITH RELAY
16 8. RECOMMENDED IED’s MAKE/MODELS://pdf sheet no.46 of 157 We will propose a relay model which will be most suitable as per the TPNODL technical specification. Please accept the same. Please propose suitable MLFB as per the TPNODL technical specification
17 Operating Characteristics selectable: /pdf sheet no.53 of 157 1. IDMT IEC – 3 Sec. 2. IDMT - 1.3 sec. 3. IEC Very Inverse 4. IEC Normal Inverse 5. IEC Extremely Inverse 6. IEC Definite time 7. IEC User defined inverse 8. IEC Long time inverse Proposed relay have following characteristics, DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-EI, ANSI-MI, ANSI-VI. Please consider the same OK
18 Time multiplier setting for O/C & E/F for IDMT:/pdf sheet no.53 of 157 0.02 to 1.0 in steps of 0.01 Minimum setting for TMS is 0.025. Please accept the same. Minimum setting for TMS is 0.025. Please accept the same.
19 Push buttons: /pdf sheet no.65 of 157 Functional keys should be available for separate trip command. Proposed relay have dedicated keys for CB Trip & Close command. Please accept the same. OK
20 Communication protocol/pdf sheet no.66 of 157 Details of Numerical relay communication ports are as follows. Front: Ethernet port Proposed relay comes with front USB Type port. Please accept the same. OK
21 Rear: IEC 61850 (for integration of relays with SCADA and accessing DR from remote through Tata Power automation WAN) No of rear port not confirmed. We propose 2 nos of PRP compliant ethernet port (RJ45 or F.O.) RJ45 TWO PORT WITH CONSOLE PORT
22 Special Requirement/pdf sheet no.67 of 157 One complete set of Relay configuration tool (Laptop, communication cable, Moxa, Manual) to be supplied for every 30 no’s lot of Relays, and pre-configured relay software along with all device configuration software to be pre- installed. We understand that this tender requirement is only for supply of Numerical Relays. Any additional equipments like Laptops, Moxa converters are not in scope of this tender. Please confirm. LAPTOP, COMMUNICATION CABLE, MANUAL, SOFTWARE TO BE SUPPLIED WITH 5 SET OF RELAY .
23 Special Requirement/pdf sheet no.67 of 157 Individual relays must have embedded power pack (with battery) of 17 AH. Relays don't have any embedded power packs. POWER PACK REQUIRED ADDITIONAL WITH RELAY
24 18. RECOMMENDED IED’s MAKE/MODEL:/pdf sheet no.67 of 157 We will propose a relay model which will be most suitable as per the TPNODL technical specification. Please accept the same. Please propose suitable MLFB as per the TPNODL technical specification
25 7.0.4 & 7.0.6 Delivery Schedule Delivery period for supply of material shall be approx. 3 months from manufacturing clearance given by TPNODL. BA shall submit the GTP/ drawing within 15 days from date of issuance of RC. We request for delivery period to be 20 weeks from manufacturing clearance and GTP/Drawing submission from 3 weeks from RC/LOA. 3 months from manufacturing clearance given by TPNODL.
26 7.0.1 RC Duration After finalization of tender, Rate Contract shall be issued on successful bidder with a validity period of 24 Months. Considering today's voltaile market situation we request RC duration to be capped at 12 months. Any extension if required can be mutually discussed later. Please confirm.
Tender No TPNODL/OT/2200000025/22-23 Dtd.29.04.22
Project Name Rate Contract for SITC of different types of relays in TPNODL Area
Sr. No. Detailed Reference to TPnODL Technical Document. Please specify Document No / Clause No / Page No Description as per Bid Document Remarks - Query / Clarification TPNODL Clarification
1 STANDARD TECHNICAL SPECIFICATION OF DIFFERENTIAL RELAY / Pdf page no 26 of 157 STANDARAD TECHNICAL SPECIFICATION OF DIFFERENTIAL RELAY FOR TRANSFORMER WITH POWER PACK We assume separate power pack is not required along with the relay. Please confirm, POWER PACK REQUIRED
2 5 /GENERAL TECHNICAL REQUIREMENTS: Aux. supply /pdf sheet no.30 of 157 If the auxiliary supply drifts, 2 alarms may be triggered: 1. High set point alarm, adjustable from 105 % to 150 % of rated supply (maximum 275 V). 2. Low set point alarm, adjustable from 60 % to 95 % of rated supply (minimum 20 V). Proposed IED doesn't support Aux D.C. supply monitoring feature. Please Accept the same. Accept
3 Tripping curve For Phase over current and Earth Fault / /pdf sheet no.31 of 157 SIT, LTI, VIT, EIT, UIT (1) DT, RI DT, IEC: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT, IEEE: MI (D), VI (E), EI (F) Proposed relay have following characteristics, DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-EI, ANSI-MI, ANSI-VI. Please consider the same IEC-NI CURVE 3.0 SEC
4 Network and machine diagnostics/pdf sheet no.32 of 157 Harmonic distortion (THD), current and voltage Ithd,Uthd. THD is Power quality requirement which needs CT input from Metering core as per general recommendation, however relays works from Protection core .Please consider the same. OK
5 Setting of Negative sequence / unbalance/pdf sheet no.32 of 157 Definite time setting - 0.1 to 5 Ib/10% to 500% For NPS protection setting range for DT stage is 10% to 400%. Please accept the same. Accept
6 Setting of Thermal overload/pdf sheet no.33 of 157 Time constant Heating T1: 1 to 600 min Cooling T2: 5 to 600 min Alarm and tripping set points 0 to 300 % of rated thermal capacity Maximum equipment temperature 60 to 200 °C (140 °F to 392 °F) Proposed relay supports thermal overload protection function (49) as per IEC characteristics. Application note & setting guideline is attached herewith. Please accept the same. Accept
7 Setting of Differential Protection (T-87) / pdf sheet no.33 of 157 Restraint on energization Current threshold - 1 to 10 % Time Delay - 0 to 300 s Choice of restraint - conventional & Self-adapting Proposed relay have dual slope bias restrained characterisitcs. Setting & parameter detailsare attached herewith.Please accept the same. OK
8 Setting of Over fluxing(V/Hz): pdf sheet no. 33 of 157 Set Point 1.03 to 2 pu Definite time Setting -0.0 to 20000 s IDMT Setting - 0.0 to 1250 s Proposed relay have following characteristics Definite time Setting 0.0 to 14400 s IDMT Setting - User defined characteristics with 6 point setting. Please accept the same. OK
9 Setting of Under voltage (L-L or L-N) : pdf sheet no.33 of 157 Set point 5 to 100 % of Unp Time Delay - 0.05 to 300 s U/V setting range is 5 -200V. Please consider the same. OK
10 Configuration Method: pdf sheet no. pdf sheet no.33 of 157 Relay shall be configurable from HMI as well as software through Laptop. IEC 61850 related configuration (i.e. RCB, Data set, Goose related configuration) are possible through laptop & relay software only. Please accept the same. accept
11 LCD Display: pdf sheet no. 35 of 157 Relay shall have minimum 4 line LCD backlit display As per Point no 5. GENERAL TECHNICAL REQUIREMENTS: / Display/ Page no 30 of 157, Advanced UMI with graphical LCD screen is required. Please confirm the same. OK with 4 line advaced umi graphical display
12 Communication protocol/pdf sheet no.37 of 157 Details of Numerical relay communication ports are as follows. Front: Ethernet port Proposed relay comes with front USB Type port. Please accept the same. ok
13 Rear: IEC 61850 (for integration of relays with SCADA and accessing DR from remote through Tata Power automation WAN) No of rear port not confirmed. We propose 2 nos of PRP compliant ethernet port (RJ45 or F.O.) RJ45 TWO PORT WITH CONSOLE PORT
14 Special Requirement/pdf sheet no.37 of 157 One complete set of Relay configuration tool (Laptop, communication cable, Moxa, Manual) to be supplied for every 5 no’s lot of Relays, and pre-configured relay software along with all device configuration software to be pre- installed. We understand that this tender requirement is only for supply of Numerical Relays. Any additional equipments like Laptops, Moxa converters are not in scope of this tender. Please confirm. LAPTOP, COMMUNICATION CABLE, MANUAL, SOFTWARE TO BE SUPPLIED WITH 5 SET OF RELAY .
15 Special Requirement/pdf sheet no.37 of 157 Individual relays must have embedded power pack (with battery) of 17 AH. Relays don't have any embedded power packs. POWER PACK REQUIRED ADDITIONAL WITH RELAY
16 8. RECOMMENDED IED’s MAKE/MODELS://pdf sheet no.46 of 157 We will propose a relay model which will be most suitable as per the TPNODL technical specification. Please accept the same. Please propose suitable MLFB as per the TPNODL technical specification
17 Operating Characteristics selectable: /pdf sheet no.53 of 157 1. IDMT IEC – 3 Sec. 2. IDMT - 1.3 sec. 3. IEC Very Inverse 4. IEC Normal Inverse 5. IEC Extremely Inverse 6. IEC Definite time 7. IEC User defined inverse 8. IEC Long time inverse Proposed relay have following characteristics, DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-EI, ANSI-MI, ANSI-VI. Please consider the same OK
18 Time multiplier setting for O/C & E/F for IDMT:/pdf sheet no.53 of 157 0.02 to 1.0 in steps of 0.01 Minimum setting for TMS is 0.025. Please accept the same. Minimum setting for TMS is 0.025. Please accept the same.
19 Push buttons: /pdf sheet no.65 of 157 Functional keys should be available for separate trip command. Proposed relay have dedicated keys for CB Trip & Close command. Please accept the same. OK
20 Communication protocol/pdf sheet no.66 of 157 Details of Numerical relay communication ports are as follows. Front: Ethernet port Proposed relay comes with front USB Type port. Please accept the same. OK
21 Rear: IEC 61850 (for integration of relays with SCADA and accessing DR from remote through Tata Power automation WAN) No of rear port not confirmed. We propose 2 nos of PRP compliant ethernet port (RJ45 or F.O.) RJ45 TWO PORT WITH CONSOLE PORT
22 Special Requirement/pdf sheet no.67 of 157 One complete set of Relay configuration tool (Laptop, communication cable, Moxa, Manual) to be supplied for every 30 no’s lot of Relays, and pre-configured relay software along with all device configuration software to be pre- installed. We understand that this tender requirement is only for supply of Numerical Relays. Any additional equipments like Laptops, Moxa converters are not in scope of this tender. Please confirm. LAPTOP, COMMUNICATION CABLE, MANUAL, SOFTWARE TO BE SUPPLIED WITH 5 SET OF RELAY .
23 Special Requirement/pdf sheet no.67 of 157 Individual relays must have embedded power pack (with battery) of 17 AH. Relays don't have any embedded power packs. POWER PACK REQUIRED ADDITIONAL WITH RELAY
24 18. RECOMMENDED IED’s MAKE/MODEL:/pdf sheet no.67 of 157 We will propose a relay model which will be most suitable as per the TPNODL technical specification. Please accept the same. Please propose suitable MLFB as per the TPNODL technical specification
25 7.0.4 & 7.0.6 Delivery Schedule Delivery period for supply of material shall be approx. 3 months from manufacturing clearance given by TPNODL. BA shall submit the GTP/ drawing within 15 days from date of issuance of RC. We request for delivery period to be 20 weeks from manufacturing clearance and GTP/Drawing submission from 3 weeks from RC/LOA. 3 months from manufacturing clearance given by TPNODL.
26 7.0.1 RC Duration After finalization of tender, Rate Contract shall be issued on successful bidder with a validity period of 24 Months. Considering today's voltaile market situation we request RC duration to be capped at 12 months. Any extension if required can be mutually discussed later. Please confirm.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
listing-row.html
html • 0.00 MB
d5d10ee1cefa42b29308a58cd0196110.xlsx
xlsx • 0.01 MB
168bfb7ce03f4407a57772635d85ad78.xlsx
xlsx • 0.01 MB
a9726cc80b4e4afbabba9808b63ac3b9.pdf
pdf • 0.24 MB
CORb99ee753c2644358afaf4e07b7535b62.pdf
pdf • 0.88 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .