Loading…
Loading…
Tender ID
Tender Value
Refer Docs
EMD Value
₹20 L
Closing Date
24 Feb 2026, 2:00 pmClosed
Executive Engineer ED-III
Office of Executive Engineer ED-III Bhagwati Nagar, Jammu
Creation of 29x100kva7x63kva distribution substns along HtLt HtLt networkforfor electrification of AIOS fencing in area of responsibility of rakh muthi station and pallanwala military station in the jurisdiction of ED III jpdcl jammu on turnkey basis
2026_PDD_302270_1
ED-III/Jammu/54 of 2025-26
Open Tender
Electrical Works
Item Rate
120 days
Jurisdiction of SD Jourian
Please refer Tender documents.
7 documents required · 7 mandatory
₹10,000
Executive Engineer ED-III
₹20 L
Office of Executive Engineer ED-III
6 Feb 2026
4 Feb 2026
25 Feb 2026
4 Feb 2026
24 Feb 2026
4 Feb 2026
9 Feb 2026
Supply, Installation & commissioning of 11/0.433 KV, 63 KVA, 50 HZ, Aluminium woundDistribution transformer of latest energy efficiency level -2 ,(New), IS1180 Part-I; 2014 as per latest upto date amendment with externally fitted MCCB with cable box and 4x4Mtrs.suitable cable of ratings(Aluminium wound upto 200KVA, copper wound for 250KVA or higher KVA ratings).
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Providing & Fixing of 70mm2 (2Ckt) cable, 1.1 KV Grade, PVC Insulated Stranded Conductor FRLS Type.
Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV with Fitting ,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing of Galvanized Nuts and Bolts
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing of Wedge Connectors/PG Clamps
Providing of GI Barbed wire for Anti Climbing
Painting of Poles Red Oxide
Sundry items like Aluminuim Lugs, Jumpers, Binding tape
Supply, Installation & commissioning of 11/0.433 KV, 100 KVA, 50 HZ, Aluminium woundDistribution transformer of latest energy efficiency level -2 ,(New), IS1180 Part-I; 2014 as per latest upto date amendment with externally fitted MCCB with cable box and 4x4Mtrs.suitable cable of ratings(Aluminium wound upto 200KVA, copper wound for 250KVA or higher KVA ratings).
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Providing & Fixing of 185 mm2 (2Ckt) cable, 1.1 KV Grade, PVC Insulated Stranded Conductor FRLS Type.
Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV with Fitting ,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing of Galvanized Nuts and Bolts
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing of Wedge Connectors/PG Clamps
Providing of GI Barbed wire for Anti Climbing
Painting of Poles Red Oxide
Sundry items like Aluminuim Lugs, Jumpers, Binding tape
Steel Tubular Pole 9.0 Mtr long (ST-410 SP-33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
GI V Cross Arm with Top bracket including clamp
30mm 2 ACSR Weasel
11kV Polymeric composite Pin Insulator 12kV,5kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm
Galvanised Nuts nad Bolts
Anti Climbing device with Clamps
Red Oxide
Cement Bottoming 1:2:4 mix as per REC Standards 0.4cum/Pole
Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid GS Stay Rod & 7/3.15 mm dia stranded wire complete
PCC Pole 9.0 Mtr long (WL 300 Kg) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
GI V Cross Arm with Top bracket including clamp
50mm 2 ACSR Rabbit
11kV Polymeric composite Pin Insulator 12kV,5kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm
Galvanised Nuts nad Bolts
Anti Climbing device with Clamps
Stone Pad 300 mmx300mmx75mm
Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid GS Stay Rod & 7/3.15 mm dia stranded wire complete
13 Mtr Long ST Poles (ST-410 SP-69) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
GI Channel X-arm inclduing clamp and braces
11kV Polymeric composite Pin Insulator 12kV,5kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm
Galvanized nuts & Bolts
Anti Climbing Device with Clamps
Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid GS Stay Rod & 7/3.15 mm dia stranded wire complete
PCC Pole 9.0 Mtr long (WL 300 Kg) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
GiI Channel X arm including clamps and braces.
50 mm² ACSR Conductor
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm
Danger Plates with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm 2.5 mtr long through GI Strip
PCC Pole 8.0 Mtr long (WL 200 Kg) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
GI U-Clamp (duly painted with twio coats of Red Oxide and Al. paint) for Shackle Insulator (Polymer/Porcelain) along with Nut & Bolt of sorts
16KN Polymer/ Porcelain Shackle Insulators
Danger Plates with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip
Aluminium Jointing sleeves
Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid GS Stay Rod & 7/3.15 mm dia GI stranded wire complete
11 KV VCB Panel Board (12 KV, 1250A, 25 KA, Outdoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter-5 Amps, DLMS Compliant with RS-485 port
ACSR Dog Conductor
Cable kit 185 sq mm Outdoor
Al thimble 185 sq mm
GI Angle 65x65x6
11KV Isolator Horizontal Mounting Type 600 Amps with earthing switch
Cement Bottoming
Galvanised Nuts & Bolts
11KV Horn Gap Fuse single Phase 200 Amp
Aluminium Paint
# of occurrences
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.95 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 3.07 MB
Tendernotice_2.pdf
PDF • 1.41 MB
GuaranteedTechnicalRequirements.pdf
Tender Documents • 11.04 MB
BOQ_980923.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .