CWE(AF) Bareilly
HQ CWE(AF) Bareilly-243002
REPAIR AND MAINTENANCE OF TRANSFORMER, HT CABLES, VCBs AND OTHER CONNECTED WORKS AT AF STATION MEMAURA
2023_MES_583473_1
81347/E8
Open Tender
Civil Works
Item Rate
180 days
AGE(i)AF MEMAURA
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
AGE(I) AF MEMAURA
₹19,800
Yes
13 May 2023
28 Feb 2023
3 Apr 2023
28 Feb 2023
1 Apr 2023
14 Mar 2023
1 Mar 2023 - 9 Mar 2023
Amount
Replacement of HT 11 KV outdoor type triple pole switch air break , gang operated mounted on insulator (09 nos) and steel frame, with operating mechanism worked from ground level for current rating upto 400 amps for working 11000 volts with heavy duty gun metal or brush metal parts both top and bottom contracts with one copper ribon, brass/copper terminal clamps having six nuts & bolts for one connection point complete with locking arrengment and taking down of unserviceable and taking as credit complete all as specified and directed. (Make : PACTAILLEDATLAS/RaychemRPG).
Supply & fixing in replacement DO fuse assembly, triple pole mounted on porcelain HT insulator 6 Nos and MS galvanised steel frame rating upto 200 Amp, 11000 Volt, post insulator type on channel (two insulator for one phase) complete with expulsion type fiberglass fuse carrier barral type and including DO fuse and electrical connections compleate all as specified and directed by Engineer-in-Charge. (Make : PACTAILLED/JAIPURIA/ RAYCHEM RPG).
Supply, laying & testing HT cable XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured electric power cables (heavy duty) with aluminum conductor, 11000 volts, Earthed grade cross sectional area of size 95 SQMM 3 core complete all as specified and directed. Note:- Earth work shall be meaursed and paid separately
Supply, laying & testing HT cable XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured electric power cables (heavy duty) with aluminum conductor, 11000 volts, Earthed grade cross sectional area of size 240 SQMM 3 core complete all as directed. Note:- Earth work shall be meaursed and paid separately
Supply, laying & testing HT cable XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured electric power cables (heavy duty) with aluminum conductor, 11000 volts, Earthed grade cross sectional area of size 120 SQMM 3 core complete all as specified and directed. Note:- Earth work shall be meaursed and paid separately
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 Sqmm complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm including taking down old joint complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm including taking down old joint complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 Sqmm including taking down old joint complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 Sqmm to 300 Sqmm including taking down old joint complete all as specified and directed.
Earthing complete with galvanised steel earth plate electrode 600 x 600 x 6mm thick, burried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below normal ground level, connected ot galvanised iron strip of size 25x 4mm earth lead by means of bolt, nuts, washers of galvanised iron or steel, earth strip protected by and including GI pipe 40mm dia bore (light grade) and connected to main test point as directed including concrete pit in PCC (1:3:6) type C-1, precast RCC (1:1½:3) type A-1 cover slab of size 54 x54 x 5 cm reinforced with 8mm dia TMT bars @ 150 mm C/C both ways with one handle for lifting, made out of 8mm dia TMT bar embedded in precast cover slab, funnel, wire mesh, 20mm bore GI pipe (medium grade) for watering, charcoal and salt in alternate layers, including necessary excavation and earth work in any type of soil complete all as shown on electrical plate No 3 of SSR Part-I and testing complete all as specified and as directed.
Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr depth for laying cable and getting out soft/loose soil complete all as specified and directed by Engr-in-charge.
Removing excavated material to a distance n. exc 16 mtr and depositing where as directed as a level n.exc 1.5 mtr above the starting point complete all as specified and directed by Engr-in-charge.
Returning filling including spreading, levelling, watering and well ramming in layers n.exc 25 cm complete all as specified and directed by Engr -in-charge.
Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1 with flat, size 300mm x 180mm x 40mm all as specified.
M&l sand cushioning 8cm below the cable and 15cm above the cable for cable protection in trenches complete all as specified and directed by Engr-in-charge.
Supplying and fixing Galvanised mild steel pipe /tubing, light grade 100 mm dia complete with all fittings, laid in trenches / under roads, drain, paths, including fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers complete all as specified and directed. Note :- Excavation & Earth work , shall be measured and paid separately Make: - QST/ TATA / JINDAL
S & F HT 1KV insulatiopn electrical rubber mat 2mm thickness as per IS: 15652:2006 Class A complete, all as specified.
M&L for Painting of transformer excd 175 KVA but not exc 500 KVA after preparation of existing surface of transformer , remove oil stains, dust etc and applying two coat of hammertone by spray paint incl writing SM No/MES No complete all as specified and directed.
M&L for Painting of transformer of capacity 2000 KVA 33/11 kV after preparation of existing surface of transformer , remove oil stains, dust etc and applying two coat of hammertone by spray paint incl writing SM No/MES No complete all as specified and directed.
M&L for Painting of transformer of capacity 500 KVA after preparation of existing surface of transformer , remove oil stains, dust etc and applying two coat of hammertone by spray paint incl writing SM No/MES No complete all as specified and directed.
Dehydration /Filteration of Transformer Oil at site by means of centrifuging machine in order to improve dielectric strength of oil as per IS- 355, Breakdown voltage should not be less than 50 KV complete all as specified and directed.
Servicing of HT (11KV ) switchgear panel , detection of defective components, replacement of worn out parts and servicing/ cleaning of mechanical components, through authorized representative service centre of VCB manufacturer channel partner /OEM or UPPCL approved vendor for VCB repairing agency , Testing for smooth operation manual/ remote after caliberation of relay and resetting & generation of testing report by the primary injection set For 11KV VCB for OC/EF ,parameter of relay setting ,including writing of MES No. complete , all as specified and directed by Engr-in-Charge. Note: Worn out minor parts shall be deemed to be included in unit rate.
Servicing of HT (33 KV ) panel / VCB , detection of defective components, replacement of worn out parts and servicing/ cleaning of mechanical components, through authorized representative service centre of VCB manufacturer channel partner /OEM or UPPCL approved vendor for VCB repairing agency , Testing for smooth operation manual/ remote after caliberation of relay and resetting & generation of testing report by the primary injection set For 33 KV VCB for OC/EF ,parameter of relay setting ,,including writing of MES No. complete , all as specified and directed by Engr-in-Charge. Note: Worn out minor parts shall be deemed to be included in unit rate.
Supply and fixing in repairs spring charging motor suitable for fixing with 33 KV outdoor VCB panels complete all as specified and directed.
Suppy and filling silica gel of good quality in existing silica gel breather of transformer complete all as specified and directed.
Detection of pin point fault in HT cable (burried in ground/under road/path up to depth of 1.5 m) by cable fault locating machine comprising impulse generator,acoustic fault locator and reflectometer (laptop based) complete all as specified and as directed by Engr-in-Charge. Notes- (i) Cable fault locating machine to be arranged at site with in 12 hrs after intimation (ii) Earth work will be measured seperatly. (iii) Cost of transpotation in unit rate is deemed to be included.
M&L Transformer oil having di-electric strength of 60 KV as per IS complete for top up/ replacement all as specified and as directed by Engr-in-Charge. (Oil should be supplied in sealed barrel of Power/Transol brand) Note: oil shall be filled in the transformers/stabilizers to be repaired or installed at site at different locations.
Silica gel breather of capacity 11 KV Transformer 500 KVA complete all as specified and as directed.
Boring holes horizontally under road without damaging the sufrace of road (minimum 1.0 Metre below the road surface with the help of GI tubing not exc 80 mm bore(dia) for passing UG cable, complete all as specified and as directed. (Note:- GI Pipe laid will be measure and paid separately under appropriate item)
M&L for two pole structure preparing old painted surfaces by scrapping and removing old paints , rust etc from steel tubular poles ( above the planting depth and PCC coping 11 metre length pole) and Mild steel cross arm, cable protection pipe , bracket etc and applying one coat of synthetic enamel paint Air force blue paint and remaining portion of pole and cross arms, cable protection pipe , bracklets etc treated with one coats of Aluminium paint including writing pole No. with white paint black ground complete all as specified and as directed by Engr-in-Charge.
M&L for three pole structure preparing old painted surfaces by scrapping and removing old paints , rust etc from steel tubular poles ( above the planting depth and PCC coping 11 metre length pole) and Mild steel cross arm, cable protection pipe , bracket etc and applying one coat of synthetic enamel paint Air force blue paint and remaining portion of pole and cross arms, cable protection pipe , bracklets etc treated with one coats of Aluminium paint including writing pole No. with white paint black ground complete all as specified and as directed by Engr-in-Charge.
M&L for Four pole structure preparing old painted surfaces by scrapping and removing old paints , rust etc from steel tubular poles ( above the planting depth and PCC coping 11 metre length pole) and Mild steel cross arm, cable protection pipe , bracket etc and applying one coat of synthetic enamel paint Air force blue paint and remaining portion of pole and cross arms, cable protection pipe , bracklets etc treated with one coats of Aluminium paint including writing pole No. with white paint black ground complete all as specified and as directed by Engr-in-Charge.
Taking out old single gravel, gauge n. exc 63 mm from marshal yard of main receiving station Air force station Memaura and setting a side for reuse including dressing, levelling of surface and removing of excess soil complete all as directed.
Labour only for re- deposited, spread and leveled in layers n.exc 15 cm thick of single gravel in marshal yard against item No-36 as above.
Material & Labour for single gravel of gauge n.exc 63mm, deposited, spread and leveled in layers n.exc 15 cm thick watered and rammed to a true surface in marshal yard of main receiving station complete all as specifed and as directed.
M&L Rendering cement plaster, 15 mm thick on fair faces of brick/concrete surfaces of wall in cement mortar 1:4 finished even and smooth w/o using extra cement complete all as specified.
Demolition of brickwork/stone boulders, masonary built in cement mortar including all quoins, arches,pillars,etc. but excl ashlar facings, dressed stone works & precast concrete surfaces.
Brick work with subclass 'B' bricks, old size bricks, straight or curved on plan exceeding 6 metre mean radius built in cement mortar 1:4 complete all as specified and as directed by Engineer-in-charge
M/S WALIA TRADESRS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .