Ex. Engineer (elect.)/CNZ
C-Block, Defence Colony, New Delhi-110024
Improvement and development of E.I of Old OPD block at Chest Clinic/TB Hospital Nehru Nagar in ward no 57-S under central zone.
2021_SDMC_79976_1
EE(Elect.)/CNZ/2021-22/06-02
Open Tender
Electrical Works
Item Rate
30 days
C-Block, Defence Colony, New Delhi
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Yes
Commissioner SDMC
Exempted
25 Jun 2021
18 Jun 2021
25 Jun 2021
18 Jun 2021
24 Jun 2021
18 Jun 2021
30 days
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. Group C
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 5/6 &15/16A modular switch, connections etc. as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 8 module (125mm x125 mm)
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 12 module (200mm x150 mm)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required 3 pin 5/6 A socket outlet
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 A switch
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way double door
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way double door
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 100 Amps
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required Single pole
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole.
Supplying and fixing following rating ,double pole,240 volt,isolator in the existing MCB DB complete with connections,testing and commissioning etc. as required 63 amps
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required 200 A, 25kA, TPMCCB
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required 100 A, 16kA, TPMCCB
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 Amps
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 6 sq. mm + 1 X 6 sq. mm earth wire
Earthing with GI earth pipe 4.5 metre long ,40 mm dia including accessories,and providing massonary encloser with cover plate having locking arrangement and watering pipe etc.with charcoal /cock and salt as required.
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required
Providing and fixing 6 SWG dia GI wire on surface or in recess for loop earthing along with surface/recessed conduit/submain wiring/cable as required.
Installation of exhaust fan in the existing opening ,including making good the damage, connection, testing ,commissioning etc.as required Up to 450 mm sweep
Laying and fixing of one number PVC insulated and PVC sheathed I XLPE power cable of 1.1 kV grade of following size on wall surface as required. Up to 35 sqmm
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size in the existingRCC /HUME/METAL pipe as required. Up to 35 sqmm
Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 4 X 35 sq. mm
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supply of XLPE insulated,PVC sheathed Al.conductor Armoured Cable Conforming to IS 7098/1988 of following Sizes. 4 X 35 Sqmm
Providing and laying i/c HDPE pipe of 40 mm outer dia With PN rating 4 by hand molling/manual method conforming to IS 4984
S/L of following size DWC HDPE Pipe ISI marked along with all accessories like socket ,bend ,couplers etc.conforming to IS 14930 ,part II complete with fitting and cutting ,jointing etc .direct in ground (75 cm below ground level )including excavation and refilling the trench but excluding sand cushioning and protective covering etc, complete as required (a)63mm dia (OD-63mm ID -51mm nominal ).
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Up to 35 sqmm
Supply of 2x6 Sqmm size of XLPE insulated and PVC sheathed Al. Conductor Armored cable confirming to 7098 as reqd.
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Supply of 12'' ( 300 mm )sweep 1400 RPM exhaust fan heavy duty complete with shutter,blade etc as required.
S.I.T.C of LED Tube type Luminaire 20W rating complete with Extruded Aluminium Batten prewired with high efficient LED with the following: (a) Total System wattage 20 watt +/- 5% (b) Luminous Efficacy Lumens/watt >=95 (c) power factor >= 0.95
SITC of 150W LED Flood light luminiare fitted with lens ,made of pressure die cast aluminium housing & toughened glass cover complete with following specification as required.(b) Total system wattage=150 watt+/-5%.(d) Luminiaire effiency >=100Lm/w.(e) power factor >=0.95.(f) Protection class -IP-66
P & F of Hot Press Sheet Moulded Compound (SMC),fire retardant (Temp. resistanceup to 200 deg.C),IP-55 weatherproof pole box of inner dimension 200 mmx160 mmx98 mm complete with suitable arrangement for fixing of 2 nos.of 6 to 32 amp single pole MCB & 63 Amp. Double pole isolator (MCB/Isolator excluded) with neutral link duly shorting on DIN channelwith 2 nos.of MS clamps with SS back plate of suitable size with danger monogram property printed on the cover etc. as required.
Supply, installation, testing and commissioning of cubical panel board 4 Pole Double door Steel Sheet (Thickness min. 1.6 mm), Incomer Rating upto 400A, 4 way Outgoing Rating Options 63-250A, Degree of minimum Protection IP 31 with Bus Bar(Copper) Size 25x5x2 mm with Multifunction Digital Metering and interconnection suitable for switch gears i/c fasteners, masonary work and making foundation etc as required.
Grover Electricals
M/s HI TECH ELECTRICALS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .