Loading…
Loading…
Tender Value
₹23.8 L
EMD Value
₹2.4 L
Closing Date
26 Aug 2026, 12:00 pm2d left
SE
44th E/M Circle PWD Varanasi
Lalbahadur Shastri Chikitsalay Ramnagar me 13 Passanger Bed Lift Lagane ka karya
2026_CEEMP_1178408_1
1403/NIVIDA SUCHANA(VARANASI)-44/2026-27 DT. 12.08.2026
Open Tender
Electrical Works
Percentage
150 days
VARANASI
Please refer Tender documents.
3 documents required · 3 mandatory
₹854
EE E/M DIVISION PWD VARANASI
₹2.4 L
Varanasi
20 Aug 2026
20 Aug 2026
26 Aug 2026
20 Aug 2026
26 Aug 2026
20 Aug 2026
21 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | SITC of Lift and related electrical work ---
Supply and Erection of 680Kg 13person ,2stop (G+1), Lift Speet 1 MPS ,travel height 3.75m , machine room less, head room -4500mm, pit depth1500mm, shaft dimensions WxD-2000mmx2500mm , car dimension WXDXH-1050mmx2100mmx2200mm, car door size WxH 900mm x2000mm ,, , Drive-V3F Regenerative (Close loop ) , Powe r supply -400/415V (3 phase AC ), operation - Full collective operation , Car group one car (Simplex) , Automatic Rescue operation , Make sindlar3000 plus / or equivalent (Technical detail as per attached annexure) | 1 | nos | 13,91,647.62 | ₹13,91,647.62 |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C DSR No.1.10.3 | 2 | Nos | 1,247 | ₹2,494 |
| 3 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess,including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. DSR 1.31 | 2 | Nos | 398 | ₹796 |
| 4 | Supply and fixing 3 pin 5A celling rose on the existing Junction box including connection as required DSR 1.33 | 2 | Nos | 76 | ₹152 |
| 5 | Supply and fixing of 4way VTPN with additional metalic door suitable for For MCCB incomer (Analysis Rate) | 1 | Nos | 9,542.6 | ₹9,542.6 |
| 6 | 100 A,30KA,FPMCCB (Make - Havells/ Anchor/ Legrand) DSR 2.2.13 | 1 | Nos | 5,948 | ₹5,948 |
| 7 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole(Make - Havells/ Anchor/ Legrand) DSR 2.10.1 | 6 | Nos | 208 | ₹1,248 |
| 8 | Supply of Fresh air fan 300 mm (GeM) | 1 | Nos | 3,305 | ₹3,305 |
| 9 | Supply and fixing of water tight oblong 10 watt LED bulk head luminaries having die casting housing with driver set confirming to IP65 and above protection 1K 08 , high purity transmisivity UV stabilized non yellowish diffuser / for uniform light ditribution , detachable driver set , openand short circuit protection . 1200 system lumens,>120Lm/W, PF>0.95, THD<10%, CRI>80, sheet thickness min 0.8mm, tube with aluminium heat sink, >300V over voltage protection, 4KV internal Surge Protection with 5 year warrantee in complete in all espect . DSR 23.11 | 2 | Nos | 1,700 | ₹3,400 |
| 10 | Installation of Ex fan ( Fresh air fan ) in the existing opening including making good the damage connection ,testing ,commissioning etc as required DSR 1.50.1 | 1 | Nos | 406 | ₹406 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
Tendernotice_2.pdf
PDF • 0.27 MB
Tendernotice_3.pdf
PDF • 2.78 MB
BOQ_2214488.xls
BOQ • 0.29 MB
ANNEXESER.pdf
Additional Documents • 0.12 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].