Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹3,200
Closing Date
21 Mar 2023, 11:00 amClosed
Superintending Engineer
15/12 A, Thornhill Road, Civil line, Prayagraj
Construction of 11 KV O/g, O/h line and Installatoin of Second point 11/0.4 kv 400 KVA S/S on Plinth/ D/P along with loading and unloading work under the Different Extende Area of EUDD BM and MH, Pyg. under Summer Plan of B.P. Year 2023-24
2023_PVVNV_783662_1
44/EUDC-II/PYG/SE/2022-23
Open Tender
Electrical Works
Lump-sum
90 days
Prayagraj
As per Tender Specification
2 documents required · 2 mandatory
₹236
Yes
S.E. EUDC-II, Prayagraj.
₹3,200
Yes
25 Mar 2023
11 Mar 2023
21 Mar 2023
11 Mar 2023
21 Mar 2023
11 Mar 2023
Amount
Erection & commissioning of T/F 250 KVA on D/P along with HT/LT connections with mounting of All accessories like 11 kv fuse set, TPMO, top channel,L.A. etc, Complete in all respect on existing D/P, (All required material will be arranged by the contractor as per Resspo and Electrical Safety rule)
Earthing of transformer body and neutral separately by lowering of GI pipe of size 1.50” dia 40’ deep/chemical pipe earthing, connecting with GI Strip of size 50x6 mm with clamp.(All material will be arranged by the contractor as per Resspo and Electrical Safety rule)
Erection, grouting, plinthing & earthing of sub station type 11m long STP double pole with mounting of accessories like 11 kv fuse set, TPMO, top channel, grouting in ratio 1:4:8, cement, stone grit & coarse sand, plinthing of support of size 0.4x0.45x0.3 Mtr.with cement sand& bricks blast in ratio 1:4:8 and 12 mm thick plastring around the plingth in ration 1:2:4 with 12 mm thickness curing of plingth should be done properly (Grouting & plinthing material will be arranged by the contractor)
Erection/Fixing of Tailless unit 500/300 amp in L.T. cubical Box or on D/P, with the help of channel, clamp & nut bolt including fixing of Helney type fuse 500 AMP,Helney type fuse 300 AMP,copper strip,cotact,cable holding clamp etc. (All material will be arranged by the contractor including L.T.Cubical box as per Resspo and Electrical Safety rule)
Hanging/Laying of L.T. cable of size 3 ½ x240 sq.mm. for connection. The cable will come from L.T.Cubical box to L.T. Section Pole. Crimping the both ends . (All required material will be arranged by the contractor as per Resspo and Electrical Safety rule)
Fixing & grouting of stay rod with cement, sand and bricks ballast in ratio 1:4:8 and fasteniong the stay wire with pole and stay rod nozzling.(Grouting material will be arranged by the contractor)
Errection&Commissioning of 11 KV,3X70 sq.mm XLPE Cable with hanging arrangement (with the help of stay wire). all required Local materials arranged by the contractor as per Resspo and Electrical Safety rule.
Fixing and providing of Heat Shrink cable type end Terminations suitable for 11 KV, 3x185/120sq mm XLPE cable and 11 KV 3X185/120/70sq mm ISI mark jointing kit will be arrange by the contractor as per Resspo and Electrical safety rules.
a)Outdoor/indoor jointing kit
Erection, grouting, plinthing & earthing of single support pole 8.5 mtr long PCC for LT line/ABC, including fixing of necessary clamps grouting in ratio 1:4:8, cement, stone grit & coarse sand, plinthing of support of size 0.4x0.45x0.3 Mtr.with cement sand& bricks blast in ratio 1:4:8 and 12 mm thick plastring around the plingth in ratio 1:2:4 with 12 mm thickness curing of plingth should be done properly (Grouting & plinthing material will be arranged by the contractor)
Errection&Commissioning of (3x120+1x195+1x16)/ (3x95+1x70+1x16) sq.mm ABC.with 1 no. weasel conductor for neutral ,Distribution box, necessary clamps, I-Hook, dead end clamp, suspension clamp,pierising connecter 1x35 sq.mm. & 1x16 sq.mm. PVC cable as per RESSPO norms will be arranged by the contractor .
Urmila Associates
J.L. Enterprises
M/s A.E. Enterprises
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .