Loading…
Loading…
Tender Value
₹7.6 Cr
EMD Value
₹15.2 L
Closing Date
9 Jun 2026, 3:30 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
90 days
Expenditure
Capital (Works)
Above/Below/Par
CONS
14 conditions · 2 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or V whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB(GCC) of tender document, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
The tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: •Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or •Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, or •One similar work each costing not less than the amount equal to 60% of advertised value of the tender.
Defination of Similar Work :- Any supply and installation work involving systems of at least 11 kV voltage level
24 conditions · 10 needing a document upload
The tenderer should submit the consent in a mandate form of Enclosure-1 for receipt of payment through NEFT
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Certificates which may be an attested Certificate from the client, Audited Balance Sheet duly certified by the Chartered Accountant etc regarding contractual payments received in the past
Tenderer shall indicate their GSTIN No. & PAN No. with proper document proof.
If the tenderer wish to submit Bank guarantee for bid security (EMD), the Tenderer shall download the Tender Document Annexure -VI A for bid security in the form of bank guarantee and upload the Annexure -VI A duly filling the necessary details. The original Bank Guarantee should be delivered in person to Office of the PCEE, II floor, Shell Administrative building, ICF, Chennai - 600 038 before closing date for submission of bids (i.e. excluding the last date of submission of bids)
Startups are not exempted from satisfying the Eligibility criteria for this tender.
The Tenderer shall have valid required level Electrical License. Attested copy of the Electrical License shall be submitted along with the offer.
The successful tenderer shall prepare and submit the Scheme for wiring along with layout of arrangement of Electrical switchgear drawings according to the site and obtain approval from the competent authority or their authorized representative prior to the commencement of work.
After completion of all wiring and installation, the successful tenderer shall submit 3 sets of General arrangement and Schematic drawings along with the electrical wiring documentation.
The rate quoted shall be net inclusive of all taxes (GST) and duties.
The Contractor has to engage only Police verified Pvt. labour /Pvt. Employee. If any new person (other than already verified) to be engaged by the contractor, he has to submit proof of Police verification application for issuing a "Temporary permission" like present permit system. However, Contractor has to arrange PV report within permissible period of one month.
The tenderer shall download the Tender Document Annexure -I and upload the Annexure -I duly filling the necessary details.
Electrical Power supply arrangements for Climatic test chamber.
2026245212220
2026245212220
Open
Works - General
6 Months
Chennai, Tamil Nadu
₹0
₹15.2 L
9 Jun 2026
16 May 2026
26 May 2026
57 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 7,61,70,831 | ||
| — | 2.00 | — | — | ||
| Design, Fabrication, supply of Outdoor type 5 way RMU Consist of 2 nos 11 kV, 630 A LBS motorized and 3 Nos of 11 kV, 630 A SF6 VCB Motorized, and Metering compartment with Bus PT Panel (With Bus PT, Aux PT & Battery Charger) and self-powered microprocessor based numerical over current and earth fault (IDMT + Inst) relay protection in the minimum 2mm thickness sheet steel enclosure as per the detailed ICF Specification. Suitable to SCADA Compatibility. | — | — | — | 33,73,208 | |
| — | 2.00 | — | — | ||
| Installation Testing & Commissioning of 5-way outdoor RMU as per ICF Specification. | — | — | — | 3,30,400 | |
| — | 3.00 | — | — | ||
| Supply of 2000KVA Dyn 11, 3-Phase Oil cooled transformer voltage level primary 11KV and secondary 433V copper wound corrugated tank, ON Load tap changer (OLTC) (+10% to - 10%) Voltage Variation in Steps of 2.5% Position) with AVR Control Panel (RTCC) IS:1180Level-II as per ICF Specification. | — | — | — | 1,37,35,200 | |
| — | 3.00 | — | — | ||
| Installation, Testing & Commissioning of 2000 KVA 11KV/433 V Transformer with OLTC and RTCC Panel as per ICF Specification. | — | — | — | 6,00,000 | |
| — | 15.00 | — | — | ||
| Supply, Installation, Testing and Commissioning of Earth station to Drg. ICF / EL / 1109 incl. of Supply of All reqd. materials as per enclosed ICF Specification. | — | — | — | 3,49,800 | |
| — | 1.00 | — | — | ||
| Design, Fabrication, Supply of Outdoor type LT Panel (415V) consist of Incomer as 3200A 4P 100KA EDO ACB 3 Nos and 5000A 4P EDO 100KA ACB 2 Nos as Bus coupler and outgoing as 3200A 4P EDO 100KA ACB-1No 1600A 4P EDO 100KA ACB-5 Nos, 630A TPN 100KA MCCB-3 Nos, 400A TPN 100KA MCCB-3 Nos, 250A TPN 100KA MCCB-3 Nos. ACB release similar to LK Make Omega MTX3.5 and MCCB Itrip-4/MTX 3.0 with Main bus bar as 7000A Electrolyte Copper having Short Circuit Withstand (Icw) 100kA for 1 Sec and other dropper as per OEM design as per IEC 61439, Part- 6, with required CT,PT, Indication lamps & push button and control wiring and MFM for Incomer feeders connected with RTU and ready for Scada communication as per ICF Specification. | — | — | — | 2,54,46,700 | |
| — | 1.00 | — | — | ||
| Installation Testing & Commissioning of Main LT Panel as per ICF Specification. | — | — | — | 2,50,000 | |
| — | 1.00 | — | — | ||
| Supply, erection, testing & commissioning of Mini RTU of 32 DI/ 16DO with OFC to ethernet convertor and suitable PSU (Power supply unit) as per ICF Specification. | — | — | — | 3,11,347 | |
| — | 500.00 | — | — | ||
| Supply of 11KV 3x300 Sq.mm HT Armored Aluminum Cable as per ICF Specification. | — | — | — | 11,19,500 | |
| — | 500.00 | — | — | ||
| Laying of HT cable up to 300 sq.mm duly excavating and re-filling the trench including with excavated earth as per ICF Specification. | — | — | — | 70,500 | |
| — | 20.00 | — | — | ||
| Supply, Installation, Testing & Commissioning of 11KV 3x300 Sq.mm End Termination as per ICF Specification. | — | — | — | 2,37,040 | |
| — | 700.00 | — | — | ||
| Supply of 1.1 KV Single core 400 Sq.mm Armored copper Cable as per ICF Specification. | — | — | — | 1,01,51,400 | |
| — | 150.00 | — | — | ||
| Supply of 300 Sq.mm. 3½ core, XLPE LT, Copper, Armored, UG Cable as per ICF Specification. | — | — | — | 54,33,900 | |
| — | 200.00 | — | — | ||
| Supply of 185 Sq.mm. 3½ core, XLPE LT, Copper, Armored, UG Cable as per ICF Specification. | — | — | — | 44,47,000 | |
| — | 1050.00 | — | — | ||
| Laying of LT cable up to 400 Sq.mm Armored copper Cable Duly Excavating and refilling the trench with excavated earth as per ICF specification. | — | — | — | 3,67,500 | |
| — | 96.00 | — | — | ||
| Supply Installation Testing & Commissioning of End Termination for Single core copper cable size up to 400 Sq.mm copper cable as per ICF Specification. | — | — | — | 43,200 | |
| — | 40.00 | — | — | ||
| Supply Installation Testing & Commissioning of End Termination for 3.5 core copper cable size up to 300 Sq.mm copper cable as per ICF Specification. | — | — | — | 64,000 | |
| — | 1000.00 | — | — | ||
| Supply of 1.1 KV 12x2.5 Sq.mm Armored Copper Control Cable as per ICF Specification. | — | — | — | 10,90,000 | |
| — | 1000.00 | — | — | ||
| Laying, termination, testing of 1.1 kV 12x2.5 Sq.mm Armored Copper Control Cable as per ICF specification. | — | — | — | 60,000 | |
| — | 25.00 | — | — | ||
| Supply Installation Testing & Commissioning of Earth Pit as per Drawing ICF/EL/1289 as per ICF Specification. | — | — | — | 2,00,000 | |
| — | 460.00 | — | — | ||
| Supply of 50 x 6 mm & 25 x 3 mm Copper strip for earthing as per enclosed ICF Specification. | — | — | — | 4,17,680 | |
| — | 120.00 | — | — | ||
| Laying of 50 x 6 mm copper strip for earthing of individual machines and pillars as per enclosed ICF Specification. | — | — | — | 5,040 | |
| — | 130.00 | — | — | ||
| Laying of 25 x 3 mm copper strip for earthing of individual machines and pillars as per enclosed ICF Specification. | — | — | — | 2,340 | |
| — | 150.00 | — | — | ||
| Provision of Concrete Pedestal with 1:1.5:3 ratio for foundations & RCC Cable Trenches as per ICF specification. | — | — | — | 27,00,000 | |
| — | 4.00 | — | — | ||
| Supply Fabrication and Installation of various sizes of Reinforcement steel rods for foundations and Cable Trenches as per ICF Specification. | — | — | — | 4,80,000 | |
| — | 4.00 | — | — | ||
| Supply, erection, testing & commissioning of 300KVAR APFCR PANEL WITH REACTOR as per ICF Specification. | — | — | — | 43,40,076 | |
| — | 400.00 | — | — | ||
| Provision of Fencing arrangement with MS angle/sheet & roof sheet (approx. size 40M(L) x 10M(W) as per ICF Specification. | — | — | — | 3,80,000 | |
| — | 1.00 | — | — | ||
| Supply and Provision of the following safety items as per CEIG rules to be kept in HT substation Following Items to be Supplied as per ICF Specification. 1.Shock treatment charts in three languages with wooden frame and glass top - 03 Nos 2.First aid box with first fill of medicine - 02 Nos 3.11 KV Hand gloves - 04 Sets 4.Rubber mat size 1200 mm X 1000 mm grade 15 mm thick 11 KV Grade to ISS-- 20 nos 5.Fire buckets round bottom 9 litres cap With fixing stand - 04 Nos 6.Respiratory mask - 02 Nos 7.Carbon Dioxide (CO2) fire extinguisher of 4.5 kg capacity type conforming to IS 2878 complete with stand - 08 Set 8.Portable stretcher - 01 No 9. HT and LT distribution drawing duly laminated with perplex sheet - 01 Set | — | — | — | 1,65,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
LISTOFWORKSONHAND.pdf
ATTACHMENT
LISTOFMachinery.pdf
ATTACHMENT
NEFTForm.pdf
ATTACHMENT
LISTOFCONTRACT.pdf
ATTACHMENT
LISTOFPERSONNEL_1.pdf
ATTACHMENT
TenderFormAnnexure-I.pdf
ATTACHMENT
IRGCC_April-2022.pdf
ATTACHMENT
IRGCCACSCombined_3.pdf
ATTACHMENT
annex6B.pdf
ATTACHMENT
928Tenderdocument.pdf
ATTACHMENT
EL-1451CableTag.pdf
ATTACHMENT
EL-1109Alt-AEarthStation.pdf Drawing
ATTACHMENT
EL-1289Earthpit.pdf
ATTACHMENT
AnnexureVIABidSecurity.pdf
ATTACHMENT
EL-1109Alt-AEarthStation.pdf
ATTACHMENT
928UpdatedTenderdocument.pdf
CORRIGENDUM
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .