Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
Closing Date
6 Oct 2021, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EXECUTIVE ENGINEER STD 2ND RAJBAGH
OFFICE OF THE EXECUTIVE ENGINEER STD 2ND RAJBAGH
Augmentation of Receiving Station Charisharief I from 12.6MVA to 16.6MVA
2021_PDD_142102_1
eNIT No STD-II / 71 of 2021-22 Dated 29-09-2021
Open Tender
Electrical Works
Turn-key
21 days
BUDGAM
Please refer Tender documents.
4 documents required · 4 mandatory
₹1,000
EXECUTIVE ENGINEER STD 2ND RAJBAGH
Exempted
29 Oct 2021
1 Oct 2021
8 Oct 2021
1 Oct 2021
6 Oct 2021
1 Oct 2021
180 days
Amount
Installation, Testing and Commissioning, of 33/11kV, 4MVA Power Transformer I/C Dismantling, carriage, loading, unloading etc (Material to be provided by the department
Supply, Installation, Testing and commissioning of 11kV VCB Panel with breaker complete Set of reputed make 2 O/C (overcurrent) and 1 E/F (earth fault) relay (IEC61850) , Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port complete (12 kV, 1250A, 25 kA, Outgoing) complete with copper buses and other allied accessories Note:- Outgoing 11KV Panel VCB panel should be having 11KV CT of Ratio 600-300/5-5-5A
Supply, Installation, Testing & Commissioning of 33kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type)
Supply, Installation, Testing & Commissioning of 33kV Isolator without Earthing Blade (36kV,1250A, Outdoor, 3 poles, 25 kA)
Supply, Installation, Testing & Commissioning of 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO, Polymer) gap less
Supply, Installation, Testing & Commissioning of 33 kV Voltage Transformer (33 kV/110 V, 1Φ, Multi-Core, Outdoor), (1No. per Φ)
Supply and Erection of 9 Mtr. Long ST Pole(ST-410 SP33) with base plate and top cap including excavation of pit and back filling by boulders as per REC construction Standard
Supply, Installation, Testing & Commissioning of 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m
Supply, Installation, Testing & Commissioning of 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
P/F of pad clamps of sorts as per site requirements of standard make
P/F of 33kV Drop Out Set of standard make
P/F of GI Pipe structure of nonimal bore 200, 5.9 mm thick as per REC standards
Providing and fixing of GI Channel (100x50x50x6mm) /Angle (50x50x6mm) complete with nuts bolts and washers as per site requirement
Providing and fixing of Earthing Risers as per REC standards
Providing and fixing of Galvanised Nuts & Bolts
Providing and fixing of Earthing of 9 Mtr. Long ST Pole /Pipe Structures etc Complete by GI Rod 20mm 2.5 mtr long through GI strip as per REC standard
Providing and painting of ST poles with one coat of Red oxide and two coats of aluminium paint to give even shade of reputed brand
Supply,Laying,Testing, and commissioning of 11KV 300sqmm Xlpe Power Cable, THREE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED CABLES as per IS IS 7098 Part-2
Supply,Laying,Testing, and commissioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS
Supply,Laying,Testing, and commissioning of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS.
Supply,Laying,Testing, and commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS.
Proviidng,Laying,stringing ,tensioning and binding of 0.2 ACSR Conductor (Panther) as per REC construction standards
P/F of T- Clamps of sorts of standard make
Providing and fixing of Indoor Heat Shrinkable Cable Termination Kits
Providing and fixing of outdoor Heat Shrinkable Cable Termination Kits
Supply installation testing and commisioning of a). Battery Bank 30 V,100 AH , of 15 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant. b). 30V,100 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply .
Providing and laying of Cement bottoming of 9 mtr long ST Poles in mix 1:2:4 0.5cum/pole ( as per REC construction standard) using 20mm crush stone aggregate including shuttering ,form work etc
M/S IRFAN AHMAD DAR
GH. MOHI-UD-DIN DAR
stage.html
html • 0.03 MB
tech_bid_open.pdf
PDF • 0.12 MB
tech_eval.pdf
PDF • 0.12 MB
fin_bid_open.pdf
PDF • 0.12 MB
boq_comp_chart.xlsx
xlsx • 0.01 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .