Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1st₹1.4 CrAccepted-AOC | ₹1.4 Cr | 1st | Accepted-AOC Being Lowest |
| 2 | 2nd₹1.6 Cr+₹21.4 L (15.7%)Rejected-Finance PLOT NO 470 PACE CITY II SECTOR 37 GURGAON HARYANA 122001 | GURUGRAM | HARYANA | 122001 | ₹1.6 Cr+₹21.4 L (15.7%) | 2nd | Rejected-Finance Being Not Lowest |
| 3 | 3rd₹1.7 Cr+₹37.0 L (27.2%)Rejected-Finance | ₹1.7 Cr+₹37.0 L (27.2%) | 3rd | Rejected-Finance Being Not Lowest |
| 4 | 4th₹1.9 Cr+₹49.1 L (36.1%)Rejected-Finance SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | ₹1.9 Cr+₹49.1 L (36.1%) | 4th | Rejected-Finance Being Not Lowest |
Tender Value
Refer Docs
EMD Value
₹1.9 L
Closing Date
20 Apr 2022, 6:00 pmClosed
CE RND Delhi
CE RND Probyn Road Delhi-110054
SPL REPAIR FOR REPLACEMENT OF BER AC PLANT(2x60TR) INSTALLED FOR THYROID BUILDING AT INMAS DELHI UNDER GE (I) RND DELHI
2021_MES_462723_5
CE R and D / DLI-07/2021-2022
Open Tender
Civil Works
Item Rate
458 days
Delhi
Please refer tender documents
8 documents required · 8 mandatory
₹1,000
GE RND Delhi
₹1.9 L
Yes
11 May 2022
29 Mar 2022
25 Apr 2022
29 Mar 2022
20 Apr 2022
6 Apr 2022
Amount
Sechedule 'A' Section-I PART A EQUIPMENT CHILLERS Supply ,installation, testing and commissioning of Scroll Water Chilling Machine each specified capacities hereunder, suitable for operation on refrigerant Non CFC environment friendly refrigerator each comprising of the following complete as per specification and as required. The scope of work shall also include necessary lifting, shifting and positioning of chiller at location as shown on drawing comprises the followings Scroll Water Chilling Machine each having a capacity of 181440 K.CAL/ Hour (60 TR) at chilled water inlet/ outlet temperature of 54 Deg. F (12.22 Deg.C) / 44 Deg. F (6.67 Deg.C) with chilled water circulation rate of 144 GPM (nominal) and condenser water inlet/ outlet temperature of 90 Deg. F (32.22 Deg. C)/ 100 Deg.F (37.77 Deg. C) with circulation rate 180 GPM (Actual) (1W+1S) Refrigerant - R - 134a/407C/CFC free R-410 a gas. Evaporator Fouling Factor: 0.0005 (British Units) Condenser Fouling Factor: 0.001 (British Units) Min. COP = 4.7 Min. IPLV = 5.8 Max 1 KW/TR=0.70 Maximum Pressure Drop in evaporator- 8 mt Maximum Pressure Drop in condenser- 8 mt Each Chilling Machine shall also comprise the following (a) Micro processor controller scroll type chiller compressor semi hermetic sealed complete single/multi circuit with automatic capacity control, safety switches, speed increasing gears, forced feed lubrication system etc. as per specifications = 01 Nos (b) Suitable capacity in built refrigerant cooled drip proof squirrel cage induction motor with class 'F' Insulation suitable for operation on 415+10% volts, 50Hz, A.C. Supply = 01 Nos (b-1) Online scale preventer including necessary items=01 Nos Note :- For other requirment of this item refer note 31 alongwith other notes as given on srl page No 13 to 17 of CA.
CHILLED WATER PUMPS Supply and installed 144 GPM at 35 m head(1W+1S) chilled water pump of factory designed, built, tested Back pull out long coupled End Suction Pump with electric motor for re-circulation of water for the central air conditioning system, the pumps shall be rigid coupled protected by OSHA complaint coupling guard, with CI casing, Bronze impeller, high strength steel shaft. The pump motor shall be suitable for 415± 10% volts, 50 cycles, 3 phase AC power supply of IE3 efficiency class. Pumps shall have outside type mechanical seal and CI casing, Bronze Impeller & SS Shaft. The internal components of pumps including mechanical seal shall be suitable to sustain a temperature of 122 degree Fahrenheit minimum efficiency of pump shall be as per manufacturers. The pump shall be designed for PN-16 pressure ratings, complete all as specified & comprises the followings. (a) Suitable HP, TEFC squirrel cage induction motor IE-3 with class 'F' insulations 1450 rpm synchronous speed, operating on 415 + 10% volts, 3 phase, 50 Hz A.C. supply = 1 No. (b) Expanded polystyrene (T.F. Quality) insulation of not less than 75mm thick duly cladded with aluminium sheets of 24 G thickness and properly clamped to pump in two semicircular section as per specifications = 01 Lot. (c) Mounting mild steel frame work duly power coated paint with anti vibration pads = 01 Lot. (d) Sound level of pump shall not be more than 85 dBA at 1.5m distance.' 2A.
All as per srl item No 2 above but 40 GPM at 35 m head(1W+1S) Hot water pumps with operating temparature from 75°C to 85 °C.
CONDENSER PUMP Supply and installed 180 GPM at 20 m head(1W+1S) of factory designed, built, tested back pull out long coupled End Suction Pump with electric motor for re-circulation of water for the central air conditioning system. The pumps shall be rigid coupled protected by OSHA complaint coupling guard, with CI casing, Bronze impeller, high strength steel shaft. The pump motor shall be suitable for 415± 10% volts, 50 cycles, 3 phase AC power supply of IE3 efficiency class. Pumps shall have outside type mechanical seal and CI casing, Bronze Impeller & SS Shaft. The internal components of pumps including mechanical seal shall be suitable to sustain a temperature of 122 degree Fahrenheit minimum efficiency of pump shall be as per manufacturers instructions. The pump shall be designed for PN-16 pressure ratings complete all as specified & comprises the followings. (a) 1 No. Suitable HP, TEFC squirrel cage induction motor IE-3 with class 'F' insulations 1450 rpm synchronous speed, operating on 415 + 10% volts, 3 phase, 50 Hz A.C. supply (b) Lot - Mounting mild steel frame work duly powder coated paint with anti vibration pads. (c) Sound level of pump shall not be more than 85 dBA at 1.5m distance.
COOLING TOWERS: Supplying, installing, testing and commissioning of FRP Induced draft counter flow type cooling towers CTI approved of capacity 75 TR(1W+1S). The Cooling Tower shall be complete with FRP Casing, FRP Basin, Unpressurised Gravity Flow – Header and branch arm water distribution system. 0.2 mm thick PVC Film Fills, High Efficiency Drift Eliminators and direct driven Axial Flow Propeller type aerofoil design fans with adjustable pitch type blades and Totally Enclosed Air Over (TEAO) and High Efficiency (IE3, 'F' insulation) grade IP-65 rating motor, capable of working under moist air steam with weatherproof construction and FRP / GSS canopy etc; fitting, GI wire mesh at air inlet area, HDG supports, Hot Dip Galvanized Steel ladder, overflow, automatic make-up water, equalizing & quick fill arrangements and connection provision etc; No sprinkler system, no belt drive or gear box are acceptable comprises the followings. Ambient temperature Summer- 110 ⁰F DB, 75 ⁰F WB Monsoon- 95 ⁰F DB, 83 ⁰F WB WB approach 7 ⁰F Inlet temperature of Condenser- 90 ⁰F Outlet temperature of Condenser- 100 ⁰F
HOT WATER GENERATOR: M&L for providing and installing electrically operated Hot Water Generator of capacity 60 KW, 40 GPM tank shall vertical type of minium storage 40 Ltr, made of 6mm thick MS plate and having 1mm thick stainless steel lining with heaters arranged in banks and controlled by electronic controller having facility to set required temperature and thermostats so that following flow rate hot water at 70° C and with nominal variations could be supplied including 75mm thick fibre glass/ mineral wool/ insulation finished with 1.25mm thick G.I. sheet clading including necessary electrical panel board made out of CRC sheet 1.6 mm thick, having suitable incoming & outgoing switch gears for boiler and pump automatic controls including inlet and outlet connections for water, foundation for boiler as per manufacturers specifications complete all as specified & directed.
OPEN EXPENSION TANK: Supplying, installing ,testing & commissioning of expansion tank of size 1.0x1.0x1.0m made of out MS sheet of 3 mm thick duly painted two coats of synthetic enamel paint over one coat red oxide zinc chrome primer with inlet/ outlet valve Float valve, full way gate valve of 32mm dia & drain valve of 40 mm dia duly insulated and plastered complete all as specified & directed.
All as per srl item No 7 above but Horizontal Floor Mounted AHU-1: 2800 CFM at 50 mm static pressure. (5.39 T.R.) & Fresh Air 400 cfm
All as per srl item No 7 above but Horizontal Floor Mounted AHU-1: 5600 CFM at 50 mm static pressure. (9.27 T.R.) & Fresh Air 500 cfm
All as per srl item No 7 above but Horizontal Floor Mounted AHU-1: 4000 CFM at 50 mm static pressure. (7.26 T.R.) & Fresh Air 400 cfm
All as per srl item No 7 above but Horizontal Floor Mounted AHU-1: 6000 CFM at 50 mm static pressure. (11.16 T.R.) & Fresh Air 500 cfm
All as per srl item No 7. above but Horizontal Floor Mounted AHU-1: 4600 CFM at 50 mm static pressure. (8.89 T.R.) & Fresh Air 400 cfm
PART C PIPING (CHILLED WATER PIPING) Supplying, laying/ fixing, testing and commissioning of 100 mm dia M.S. pipes including welding & required accessories/fittings (50 mm insulation) nominal sizes of chilled water piping plumbing inside the building (with necessary M.S. clamps & angle iron support, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated PUF moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessian and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing felt strip(as per IS:1322 as amended up to date ) at joints repairing of damage to building etc. complete all as specified & directed.
All as per srl item No 8 here-in-before but 80 mm dia MS pipes (50 mm insulation)
All as per srl item No 8 here-in-before but 50 mm dia MS pipes (50 mm insulation)
All as per srl item No 8 here-in-before but 40 mm dia MS pipes (50 mm insulation)
All as per srl item No 8 here-in-before but 32 mm dia MS pipes (50 mm insulation)
All as per srl item No 8 here-in-before but 25 mm dia MS pipes (50 mm insulation)
DRAIN PIPING Supply,installation,testing and commissioning of "B" class GI drain 40 mm bore dia piping complete with fitting etc & 25 mm thick PUF insulation with sealing tapes & 28 G Aluminium cladding complete as per drawings, specifications and directed.
INSULATED VALVES Supplying, fixing, testing and commissioning of 100 mm dia valves in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported specified for BUTTERFLY VALVE (MANUAL) 100 mm dia with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified complete all as specified & directed.
All as per srl item No 10 here-in-before but 50 mm dia
All as per srl item No 10 here-in-before but 40 mm dia
All as per srl item No 10 here-in-before but 32 mm dia ball valve
All as per srl item No 10 here-in-before but 25 mm dia ball valve
Supplying, fixing, testing and commissioning valves in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported specified and suitable for BUTTERFLY VALVE (Motorized ) 100 mm dia with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation complete as specified and directed
All as per srl item No 11 here-in-before but 50 mm dia
Supplying, fixing, testing and commissioning valves in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported specified and suitable for BALANCING VALVE 100 mm dia WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation complete all as specified & directed.
All as per srl item No 12 here-in-before but 50 mm dia
All as per srl item No 12 here-in-before but 40 mm dia
All as per srl item No 12 here-in-before but 32 mm dia
All as per srl item No 12 here-in-before but 25 mm dia
Supplying, fixing, testing and commissioning valves in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported specified and suitable for NON - RETURN VALVE 100 mm dia with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified.
All as per srl item No 13 here-in-before but 50 mm dia
Supplying, fixing, testing and commissioning strainers in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported specified and suitable for Y - STRAINER 100 mm dia of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation complete all as specified & directed.
All as per srl item No 14 here-in-before but 50 mm dia
All as per srl item No 14 here-in-before but 40 mm dia
All as per srl item No 14 here-in-before but 32 mm dia
All as per srl item No 14 here-in-before but 25 mm dia
All as per srl item No 15 here-in-before but 50 mm dia
Supplying, fixing, testing and commissioning strainer, expension joints in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported specified and suitable for Bellows type rubber expansion joints for Chilled water piping 100 mm dia located at Pump inlet & exit, AHU inlet & exit and at chiller inlet & exit. Complete with double bellows, tie rods, MS flanges, necessary hardware and gaskets etc., with insulation complete all as specified & directed.
All as per srl item No 16 here-in-before but 50 mm dia
All as per srl item No 16 here-in-before but 40 mm dia
All as per srl item No 16 here-in-before but 32 mm dia
All as per srl item No 16 here-in-before but 25 mm dia
Supplying, fixing, testing and commissioning valves in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported specified and suitable for 3-way modulating control valve 50 mm dia in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20 mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 10 Bar minimum.
All as per srl item No 17 above but 40 mm dia
All as per srl item No 17 above but 32 mm dia
All as per srl item No 17 above but 25 mm dia
M&L for providing and fixing in position the industrial type pressure gauges with SS-304 valves uly insulated to the same specification on connected piping complete as required and directed.
M&L for providing & fixing in position the mercury in glass industrial type thermometers complete all as specified & directed.
Supply,installation,testing and commissioning of proportional type cooling and heating thermostats for the various Air Handling Units complete with required control wiring/installation kit etc. as per drawings specified & directed.
CONDENSER PIPE Supplying, fixing, testing and commissioning of condenser water pipes 100 mm bore diaof following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends, tees etc.but excluding valves, strainers, gauges etc. adequately supported on steel rigid supports duly painted/ buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:-The Pipes size 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
All as per srl item No 21 here-in-before but 50 mm dia.
VALVES WITHOUT INSULATION Supplying, fixing, testing and commissioning of BUTTERFLY VALVE (MANUAL) 100 mm dia with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified. for condenser water complete all as specified & directed.
All as per srl item No 22 here-in-before but 50 mm dia.
Supplying, fixing, testing and commissioning of BUTTERFLY VALVE (Motorized ) 100 mm dia with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified for condenser water circulation complete all as specified & directed.
Supplying, fixing, testing and commissioning of BALANCING VALVE 100 mm dia WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified for condenser water circulation complete all as specified & directed.
Supplying, fixing, testing and commissioning of NON - RETURN VALVE 100 mm dia with dual plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating as specified for condenser water circulation as per specifications.
Supplying, fixing, testing and commissioning of Y - STRAINER 100 mm dia of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified for condenser water circulation as per specifications for condenser water circulation complete all as specified & directed.
Supplying, fixing, testing and commissioning of Bellows type rubber expansion joints for condenser water piping 100 mm dia located at Pump inlet & exit and at condenser inlet & exit. Complete with double bellows, tie rods, MS flanges, necessary hardware and gaskets etc., with insulation of following sizes for condenser water circulation complete all as specified & directed.
Supplying, fixing, testing and commissioning of Self Cleaning Pot Stainer Cum Sediment Separator for 100 mm dia fabricated out of MS IS 226 with SS 304 filter element at outlet of Cooling Tower for condenser water circulation complete all as specified & directed.
Supply, installation, testing and commissioning of 10mmdia. Automatic air vent in brass construction complete with nipples, union etc. as required at all high points in the pipe lines. The valve shall be such as to have non-return valve as integral part of the vent complete all as specified & directed.
Supply, Installation, Testing, & Commissioning of 25mm diameter Plug valves in dirt legs complete with nipples etc. complete all as specified & directed.
Providing and fixing in position of approved make differential pressure switch of brass body complete with copper control wiring at condenser and chiller outlet of each machine complete all as specified & directed.
PART D AIR DISTRIBUTION SYSTEM (SHEET METAL DUCT) Supply,essembly and erection of GI sheet 24 Gauge with TDF flange rectangular/square duct/plenum made out of 'L'shaped hollow profile ,duly factory boxed including all accessories such as Corner ,Cleat,Carriage bolt,Gasket and appropriate sealant on longitudinal joints etc complete all as per drawing specified & directed.
All as per srl item No 33 above but of size 22 Guage
All as per srl item No 33 above but of size 20 Guage
All as per srl item No 33 above but of size 18 Guage
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, complete all as specified & directed.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete all as specified & directed.
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core complete all as specified & directed.
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core complete all as specified & directed.
Supplying, installing and testing of fresh air GI intake louvers with VCD, bird screen and carbon filter complete all as specified & directed.
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of appropriate sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
All as per srl item No 40 above but Actuator
Supply and fixing acoustic lining of supply air duct and plenum with 15 mm thick Open Cell engineered Nitrile Rubber foam of density 140-180 kg/cu.m with in built Microban and tested as per ISO 354:2003, ISO 11654:1997 and ASTM C 423 etc. complete all as specified & directed.
M&L for providing and fixing of acoustic lining on wall and ceiling of AHU rooms with 25mm thick Rigid Board of Glass wool one side aluminium faced and other side black glass cloth lamination, density 70 to 80 kg/cu.m complete all as specified & directed.
M & L for 40mm thick duct insulation with resin bonded fibre glass wool roll of density 24 Kg /Cum and 40mm thickness with factory laminated aluminium vapour barrier , thickness of insulation complete all as specified and including the following:- (a) M & L for cleaning the duct surface( to be insulated ) by scrapping carefully with wire brush etc. to make the surface completely free of mill scale ,durt,dust, grease and other foreign materials, taking special care so that all duct joints are sealed against any leakage. (b) M & L for applying rubber based adhesive CPRX compound. (c) M & L for sealing of all longitudinal joints and circular overlaps with and including aluminium foil tape 50 mm wide, to make the insulation leakproof. (d) M & L for securing the insulation with and including mechanically fastened nylon / steel straps of size 12mm / 50mm at maximum intervals of 1.2 mtr.
Supply & fixing, testing and commissioning of Lockable isolator box in powder coated MS enclosure suitable for wall mounting and floor mounting with provisions of incoming and outgoing cables. The protection class of the Isolator Box shall be IP-55 & the rating should be 40 amp, 4 pole complete all specified & directed.
CABLE: Supply laying commissioning and testing of XLPE insulated, unarmoured heavy duty electric cable with stranded copper conductor, 1100 volts grade, cross-sectional area 4 Core x 6 Sqmm (copper) for hot water pumps, Cooling Towers and AHUs fixed on walls or laid in ducts/trenches/flooring complete all as specified & directed.
All as per srl item 47 above but 4 Core x 10 Sqmm (copper) for Chilled water & Condensor water pumps
All as per srl item 47 above but armoured 3.5 Core x 120 Sqmm (copper) for chiller & hot water generator
All as per srl item 47 above but 6 Core x 1.5 Sq.mm (copper)
Material and Labour for earthing complete as shown in electical plate No 3 with GI earth plate electrode 600mmx600mmx6mm thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not lesss than 1.5 meter below the ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below and above 15 cm of earth plate. GI plate connected with galvanised iron strip of 32x6mm by means of GI nuts, bolts and washers. Strip laid in 40mm dia light grade GI pipe as protection from top of the plate up to test point (cost of protection pipe and earth strip up to 7.5 meters from earth electrode will be included in the unit rates quoted by the contractor) with following requirments:- (a) GI strip of size 32mm x 6mm. (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit. (GI Funnel should properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitable for watering of earth pits) (c) PCC earth pit 30x30x30cm internal dimension constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 including RCC 1 :2:4 type B0 reinforced with 8mm dia deformed bars @100 mm c/c bothways pit cover 25mm thick with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover. (d) Angle iron frame made of 40x40x4 mm for 30x30 cm PCC pit for holding the pit cover. (e ) Apply two coat of synthetic enamel paint over one coat of red oxide zinc chrome primer on exposed steel surfaces and two coat of hot tar on embedded portion of steel surfaces.
M&L for Earth continuity conductor or main earthing lead 32x6mm galvanised iron strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. including necesssary excavation and earth work if any required at site in soft/loose soil and remove of surplus soil out side defence land complete all as specified & directed.
All as per srl item No 49 above but 8 SWG Wire
CABLE TRAY: Supply, fabricating and installing of perforated cable trays of size 50 x 300 x 50 and made out of MS steel 2 mm thick including horizontal and vertical bends, reducers, tees, cross members and other accessories as required, and duly suspended from the ceiling with M.S. suspenders, including powder coated painting on all steel surfaces complete all as specified & directed.
All as per srl item No 51 above but 50 x 150 x 50 mm thick made out of 2 mm thick mild steel sheet.
Supply,laying and testing cable XLPE insulated screened PVC beded galvanised steel strip or wire armoured electric power cables heavy duty 1100 volts graded with multi stranded aluminium conductor conforming to IS-7098, cross-sectional area 185 sq mm 3.5 core fixed in duct/wall including angle iron support 50x50x6 mm and clamping with 25x3 mm flat iron duly painted with two coats of synthetic enamel paint over one coat primer on steel surfaces including all connected accessories all as specified and directed.
M&L for Cutting of existing 100 mm dia pipe and inserted tee for connection of 40 mm dia pipe alongwith all tools and connected items accessories complete all as specified and directed by Engr-in-charge.
Supply and fixing of 40 mm bore dia medium grade GI pipe alongwith necessary fitting/accessories fixed on wall with flat iron clamp 25x3 mm thick duly painted two coats of synthetic enamel paint over one coat primer on steel surfaces complete all as specified and directed.
Supply and fixing of gun metal gate valve heavy duty with iron wheel head, conforming to IS-778 & 1984, class I, screwed both ends as per IS-554, parelled for iron pipe of size 40mm bore comlete all as specified & directed .
B/R (PORTION) Section-II Dismantling wall panelling and ceiling boards (fibre pulp, insulation etc) or insulation boards/slabs/blankets any thickness including cover fillets complete all as specified and directed.
S&F Anodised aluminium snap grid having size 605mmx605mm of frame work, the aluminium section as per manufacturers recommendation for false ceiling and hangers 6mm dia GI (upto 1200mm length) adjusting level fixed to roof slabs by means of ceiling cleats made out of GI flat 40 x 3mm size 60mm long and expansion hold fasteners 12.5mm dia, 40mm long complete all as specified and directed.
M&L for 8mm thick exposed metal frame ceiling with calcium silicate board of siliceous and calcareous material reinforced with cellulose fibre for fixing in 605 mm x 605mm grid (Frame work for ceiling shall be measured and paid separately) complete all as specified and directed.
Taking down cement plaster on brick wall R.C.C. ceiling etc. including racking out joints, hacking for key and scrubbing down with water etc and including removal of rubbish out side defence land complete all as specified and directed.
M&L for rendering 15 mm thick on brick work in cement mortar 1:4 and finished even and smooth without using extra cement complete all as specified and directed.
M & L for rendering 5mm thick on ceiling in cement mortar 1:3 finished even and smooth without using extra cement complete all as specified and directed.
M&L for preparation of new plastered surface and applying two coats of oil bound distemper over a coat of chalk whiting(preparotory to distempering) on walls complete all as specified and directed.
M&L for applying three coat of white wash on new plastered ceiling surfaces and including preperation of surfaces, complete all as specified and directed.
Dismantling wrought iron or mild steel work (old steel rolling shutters including all fixtures/fittings or other steel work of any description not otherwise provided for complete all as specified and directed.
S&F factory made steel rolling shutters having thickness of laths of 1.0mm thick, gear operated type with bevel gear box and crank handle, as specified including top cover, anchoring rod, hasp and staple and one shop coat of primer; errected in position as indicated, complete all as specified and directed.
S&F ball bearing suitable for rolling shutters complete all as specified and directed.
S&F safety lever locks mild steel with 4 levers for rolling shutters complete all as specified and directed.
M&L for applying two coats of synthetic enamel paint over factory made rolling shutters steel or iron surfaces exc 10 cm width or girth not otherwise described, complete all as specified and directed.
Taking down chowkhats or frames with shutters (without taking of shutters from the frame area exc 1.50 sqm but n.exc 4 sqm including making holes as required for receiving and including PCC 1:3:6 type C-1(using 20mm graded crushed stone aggregates and to match with the existing surfaces complete all as specified and directed. Note:-Rate also includs necessary cutting doors for taking out hold fasts from the existing concrete/brick work and making good the disturbed surface with match the site complete all as specified and directed.
M&L for 2nd class hardwood plain, solid, straight, chowkats and frames, wrought, framed rebated on the solid, rounded or chamfered, put together with glue pinned at joints, supplied and fixed complete all as specified and directed. Note:- Unit rate also includs necessary provision for treatment of wooden chowkhats with cholophriphos/ Lindane[EC-20]
M&L for 35mm thick 2nd class hard wood (rail & style) factory made plain framed panelled shutters (two panels) with lock rail and panel of 9mm BWP commercial ply or 12mm veneered particle board with commercial veneering on both faces.The size of rail and stile as per IS:1003 (Part1),kiln seasoned and chemically pressure treated, complete all as specified and directed.
S&F 100 mm size butt hinges medium weight cold rolled mild steel fixed/ welded to frame complete all as directed complete all as specified and directed.
S&F 150 mm long,aluminium,anodised, barrel tower bolts having dia of bolt/shoot not less than 10 mm of extruded section complete all as specified and directed..
S&F 250mm long aluminium alloy, anodised, sliding door bolt (dia of bolt shoot not less than 16 mm) with hasp, staple (bolt type) and fixing clips of sheet,cast or extruded sections and fixing bolts and sliding bolts of extruded sections or cast aluminium alloy complete all as specified and directed.
S&F 150mm size aluminium handles,cast type,anodised complete all as specified and directed.
Demolition of stone slabs of any description or thickness laid, bedded and pointed in any mortar in floors, aprons etc and including removal of rubbish outside defence land complete all as specified and directed.
M&L for 18 to 20 mm thick machine cut Kota stone slabs of size (520mmx520mm to 550mmx550mm), set and jointed in neat cement slurry and pointed in cement slurry mixed with pigment to match shade/colour of stone slab including rubbing and polishing complete, as in floors, laid over and including 20mm thick screed bed in cement mortar 1:6, complete all as specified and as directed.
S&F mild steel bands,straps, hold fasts etc and similar articles conformong to Fe 290, Gde-E-165 complete all as specified & directed.
M&L for applying two coat of synthetic enamel paint over one coat pink primer after preparation of new or previously untreated wooden surface of any discription, not otherwise described, over 10 cm width or girth complete all as specified & directed
All as per srl item No 79 above but size 520 mm to 550 mm x 100 mm to 150 mm in skirting over and including 10 mm thick cement rendering in cm 1:3
Manning & operation of AC plant Sechedule 'A' Section-III Operation of Central type AC plant 2X60 TR installed at Thyroid lab of INMAS Delhi installed during defect liability period for 02 shifts of (08 hours per Shifts) (06.00 hrs to 14.00, 14.01 hrs to 22.00 hrs) all days of week including Sunday and Holidays for deployment of one operator per shift (ITI/ diploma holder having adequate experience in the respective trade) for two years from satisfactory completion of Phase-I test complete all as specified and directed. Note:- (a) Water and Electric for operation of plant shall be provided free of cost by the department (b) All consumable items such as refrigrant gas, compressor oil, and grease including descaling with chemical, servicing of Plant, AHU, Ducts, Filters, condensing pipes & coil, Cooling towers, Fire dumpers, Heaters etc required for operation of plant shall be provided by contractor at his own cost as per the manufacturer`s instructions and direction of GE during period of manning and operations, cost of the same shall be deemed included in the unit rates quoted by the contractor. (c) Please ensure that all tradesmen engaged in subject work covered in EPF scheme. Proper documets shall be maintained in this regard and submitted alongwith each payment. (d) The expeses incurred due to insured and EPF scheme for the staff deployed by the contractor for manning and operation shall also be deemed included in the quoted rates of BOQ. Nothing extra shall be admissible on this account. (e) In case contractor fails to employ the duty persoonel in any of the shift he shall be liable to bear the recovery @ Rs 1500/- per shift and no payment shall be made for that shift also.
Operation of Central type AC plant 2X60 TR installed at Thyroid lab of INMAS Delhi after defect liability period for 02 shifts of (08 hours per Shifts) (06.00 hrs to 14.00, 14.01 hrs to 22.00 hrs) all days of week including Sunday and Holidays for deployment of one operator per shift (ITI/ diploma holder having adequate experience in the respective trade) for one years after defect liability period complete all as specified and directed. Note:- (a) Water and Electric for operation of plant shall be provided free of cost by the department (b) All consumable items such as refrigrant gas, compressor oil, and grease including descaling with chemical, servicing of Plant, AHU, Ducts, Filters, condensing pipes & coil, Cooling towers, Fire dumpers, Heaters etc required for operation of plant shall be provided by contractor at his own cost as per the manufacturer`s instructions and direction of GE during period of manning and operations, cost of the same shall be deemed included in the unit rates quoted by the contractor. (c) Please ensure that all tradesmen engaged in subject work covered in EPF scheme. Proper documets shall be maintained in this regard and submitted alongwith each payment. (d) The expeses incurred due to insured and EPF scheme for the staff deployed by the contractor for manning and operation shall also be deemed included in the quoted rates of BOQ. Nothing extra shall be admissible on this account. (e) In case contractor fails to employ the duty persoonel in any of the shift he shall be liable to bear the recovery @ Rs 1500/- per shift and no payment shall be made for that shift. (f) Contractor rate will be deemed to include 12 months wages for labour & comprfehensive maintenance after defect liability period
ANEMO PRIME PRIVATE LIMITED
HVAC Engineering Co
Shree Ayyappa Engineering
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .