| Sl No | Description | Qty | Unit | PERFECT IMAGE SOLUTIONS L3 | BANERJEE ENTERPRISE L2 | Computer Gallery L1 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm control panel ( VDS / UL / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events
in its memory (EPROM). The panel should have extra loop card slot for future expansion. Two Loop Panel. | 1 | No | 2,31,000 ₹2,31,000 | 2,00,000 ₹2,00,000 | 1,99,000 ₹1,99,000 Lowest |
| 2.00 | Supply, Installation,Testing & Commisioning of Micropresssor
controlled Addressable Multisensor detector ( VDS / UL / LPCB /
FM approved ) with inbuilt optical smoke sensors and heat detector
sensor with inbuilt short circuit fault isolator as per NFPA (Note :
Detectors without built-in fault isolator is also acceptable with one
independent short circuit fault isolator after every four (04) detector is
to be provided without extra cost) the detectors should have built in
response indicator with LED indicator. The detector should have 360
degree optical view with single / multiple LED that blinks on
actuation of detector. Reverse polarity or faulty zone wiring shall not
damage the detectors. Degree of protection as per OEM Standard. | 20 | each | 2,170 ₹43,400 Lowest | 2,268 ₹45,360 | 2,200 ₹44,000 |
| 3.00 | Supply, Installation, Testing & Commissioning of Addressable Loop
Powered /panel powered Hooter (sound output of minimum 90 db )
cum strobe (strength of light 10 cd) complete with inbuilt short circuit
fault isolator as per NFPA (Note :Hooter without built-in fault isolator
is also acceptable with one independent short circuit fault isolator is
to be provided without extra cost). ( VDS / UL / LPCB / FM approved
) approved. Degree of protection as per OEM Standard. | 2 | each | 5,120 ₹10,240 | 7,000 ₹14,000 | 5,000 ₹10,000 Lowest |
| 4.00 | Supply, Installation,Testing & Commisioning of Addressable Manual
Call Point ( VDS / UL / LPCB / FM approved ) with in built short
circuit fault isolator as per NFPA (Note : MCP without built-in fault
isolator is also acceptable with one independent short circuit fault
isolator is to be provided without extra cost). Degree of protection as
per OEM Standard. | 2 | each | 6,000 ₹12,000 | 4,500 ₹9,000 Lowest | 4,500 ₹9,000 Lowest |
| 5.00 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab ) through 19 mm dia PVC 'FR' type Rigid Conduit pipe with necessary arrangement as per G.S. (Make : Precision MMS) on the surface of the wall. | 160 | Mtr | 90 ₹14,400 Lowest | 110 ₹17,600 | 90 ₹14,400 Lowest |
Tender Value
Refer Docs
EMD Value
₹5,540
Closing Date
31 Jul 2026, 1:00 pmClosed
Executive Engineer Purba Medinipur Electrical D
AE,Contai Electrical Sub Division, PWD, Divisional Accounts Officer, PMED, PWD
Repair and renovation works for Shifting and Establishment of Blood Centre of Contai SDH, Nandigram HD --- SITC of Fire Alarm System.(2nd Call)
2026_WBPWD_5017107_1
WBPWD/EE/PMED/NIQ-74/26-27(2nd Call)
Open Tender
ELECTRICAL WORKS ORG
Item Rate
7 days
Contai
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,540
Office of the Executive Engineer Purba Medinipu
25 Aug 2026
21 Jul 2026
3 Aug 2026
21 Jul 2026
31 Jul 2026
25 Jul 2026
24 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm control panel ( VDS / UL / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events
in its memory (EPROM). The panel should have extra loop card slot for future expansion. Two Loop Panel. | 1 | No | - | - |
| 2 | Supply, Installation,Testing & Commisioning of Micropresssor
controlled Addressable Multisensor detector ( VDS / UL / LPCB /
FM approved ) with inbuilt optical smoke sensors and heat detector
sensor with inbuilt short circuit fault isolator as per NFPA (Note :
Detectors without built-in fault isolator is also acceptable with one
independent short circuit fault isolator after every four (04) detector is
to be provided without extra cost) the detectors should have built in
response indicator with LED indicator. The detector should have 360
degree optical view with single / multiple LED that blinks on
actuation of detector. Reverse polarity or faulty zone wiring shall not
damage the detectors. Degree of protection as per OEM Standard. | 20 | each | - | - |
| 3 | Supply, Installation, Testing & Commissioning of Addressable Loop
Powered /panel powered Hooter (sound output of minimum 90 db )
cum strobe (strength of light 10 cd) complete with inbuilt short circuit
fault isolator as per NFPA (Note :Hooter without built-in fault isolator
is also acceptable with one independent short circuit fault isolator is
to be provided without extra cost). ( VDS / UL / LPCB / FM approved
) approved. Degree of protection as per OEM Standard. | 2 | each | - | - |
| 4 | Supply, Installation,Testing & Commisioning of Addressable Manual
Call Point ( VDS / UL / LPCB / FM approved ) with in built short
circuit fault isolator as per NFPA (Note : MCP without built-in fault
isolator is also acceptable with one independent short circuit fault
isolator is to be provided without extra cost). Degree of protection as
per OEM Standard. | 2 | each | - | - |
| 5 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab ) through 19 mm dia PVC 'FR' type Rigid Conduit pipe with necessary arrangement as per G.S. (Make : Precision MMS) on the surface of the wall. | 160 | Mtr | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.38 MB
2911_.pdf
Tender Documents • 0.50 MB
BOQ_5087072.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .