Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1st₹10.4 LAccepted-AOC 1001 B BHAVESHWAR BLDG NO 03 BHAVESHWAR LANE GHATKOPAR EAST MUMBAI 400077 | MUMBAI SUBURBAN | MAHARASHTRA | 400077 | 1st | Accepted-AOC The Everest Power Control Engineers is L1 bidder being accepted pl | |
| 2 | 2nd₹14.5 L+₹3.7 L (34.9%)Rejected-Finance | 2nd | Rejected-Finance Not being L1 |
| Sl No | Description | Qty | Unit | EVEREST POWER CONTROL ENGINEERS L1 | Chaudhary Enterprises L2 |
|---|---|---|---|---|---|
| 1.00 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in deep for laying UG cables and getting out in soft/loose soil complete all as specified and as directed by Engineer-in-Charge | 30 | Cum | 200 ₹6,000 Lowest | 333 ₹9,990 |
| 2.00 | Returning, filling in, including, spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick in any soil all as specified and as directed by Engineer-in-Charge. | 14 | Cum | 55 ₹770 Lowest | 69 ₹966 |
| 3.00 | Removing excavated material to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and as directed by Engineer-in-Charge | 16 | Cum | 65 ₹1,040 Lowest | 99 ₹1,584 |
| 4.00 | Material and labour for crushed sand filling in trenches for cable crushioning below and above the cable complete all as specified and directed by Eng- in -charge. | 12 | Cum | 900 ₹10,800 Lowest | 1,500 ₹18,000 |
| 5.00 | Supply & laying un -inforced pre cast concrete with flat cover Factory made Class HV, type 1, size 300x180x40 mm complete all as specified and directed by Eng- in -charge. | 175 | Each | 32 ₹5,600 Lowest | 45 ₹7,875 |
| 6.00 | Supply & laying un -inforced pre cast concrete cable cover LV type flat size, class type I 250x150x40 mm complete all as specified and directed by Eng- in -charge. | 450 | Each | 23 ₹10,350 Lowest | 31 ₹13,950 |
| 7.00 | M & L for disconnecting the HT & LT supply of capacity 400 to 750 KVA 11KV/ 0.433 KV transformer, draining out complete insulating oil from transformer kept on plinth including removing transformer top cover, explosion vent pipe and lifting the core from the shell/ tank , wash/ cleaning the core winding, internal surface of shell container with clean dry oil by flushing out by means of pump set, removing complete composite sludge through drain valve, stopping the leakages Reassembling top cover with conservator and explosion vent pipe, change of gasket for the top plate, cleaning oil level indicator and tightening all bolts and nuts & refilling new transformer oil through stream line filer to a required level with out any oil leakage, test & commissioning complete all as specified & directed by the Engr-in-Charge. | 3 | Job | 4,000 ₹12,000 Lowest | 5,000 ₹15,000 |
| 8.00 | Material & Labour for TOP Up ( topping) insulating oil for transformer conforming to IS-3356 at different Transformers & different locations complete all as specified and directed by Engr-in-Charge. | 310 | Ltrs | 200 ₹62,000 | 21 ₹6,510 Lowest |
| 9.00 | Earthing complete with GI earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (Earth pit not less then 2.25m deep below ground level ) with top edge not less than 1.5m below ground level connected to GI earth strip 32 x 6 mm by means of GI bolts,nuts, check nuts,washers & GI strip ,protected by 50 mm bore medium grade GI pipe up to 7,5mtr distace including necessary charcol, salt & 20Kg Benzonite powder Funnel with wire mesh , watering pipe20mm dia medium grade excavation earth work PCC (1:3:6) type C-1 earth chamber , 50mm thick RCC cover with 6mm nominal reinforcement etc complete all as shown electrical plate No. 5 of MES schedule part I all as specified and directed . . | 8 | Each | 5,000 ₹40,000 Lowest | 6,900 ₹55,200 |
| 10.00 | M&L for replacement of breather assembly transparent MS body with top and bottom portion pressed with metallic cover, filled with silica gel blue in colour and suitable for fixing on existing pipe of size 15/20/25 mm dia or as per site requirement/ capacity of Transformer up to 750 KVA including taking down UNSV breather assembly complete all as specified & directed by the Engr-in-Charge. | 3 | Each | 2,000 ₹6,000 | 1,500 ₹4,500 Lowest |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
6 Dec 2025, 6:00 pmClosed
Shri Vinay Kumar, IDSE, SE (SAG), CWE
HQ Commander Works Engineer (Army) Mumbai, 24 Assay Building Colaba, mumbai-05
MAINTENANCE AND UPKEEP OF HT DISTRIBUTION SYSTEM, TRANSFORMER AND ALLIED WORKS AT DGQA GHATKOPAR AND VIKHROLI UNDER GE (N) MUMBAI
2025_MES_731503_3
85250/N/E8
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
North Santacruz
As per NIT and tender documents
9 documents required · 9 mandatory
₹500
GE NORTH SANTACRUZ
₹20,000
Yes
27 Feb 2026
24 Nov 2025
8 Dec 2025
24 Nov 2025
6 Dec 2025
1 Dec 2025
Amount
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in deep for laying UG cables and getting out in soft/loose soil complete all as specified and as directed by Engineer-in-Charge
Returning, filling in, including, spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick in any soil all as specified and as directed by Engineer-in-Charge.
Removing excavated material to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and as directed by Engineer-in-Charge
Material and labour for crushed sand filling in trenches for cable crushioning below and above the cable complete all as specified and directed by Eng- in -charge.
Supply & laying un -inforced pre cast concrete with flat cover Factory made Class HV, type 1, size 300x180x40 mm complete all as specified and directed by Eng- in -charge.
Supply & laying un -inforced pre cast concrete cable cover LV type flat size, class type I 250x150x40 mm complete all as specified and directed by Eng- in -charge.
M & L for disconnecting the HT & LT supply of capacity 400 to 750 KVA 11KV/ 0.433 KV transformer, draining out complete insulating oil from transformer kept on plinth including removing transformer top cover, explosion vent pipe and lifting the core from the shell/ tank , wash/ cleaning the core winding, internal surface of shell container with clean dry oil by flushing out by means of pump set, removing complete composite sludge through drain valve, stopping the leakages Reassembling top cover with conservator and explosion vent pipe, change of gasket for the top plate, cleaning oil level indicator and tightening all bolts and nuts & refilling new transformer oil through stream line filer to a required level with out any oil leakage, test & commissioning complete all as specified & directed by the Engr-in-Charge.
Material & Labour for TOP Up ( topping) insulating oil for transformer conforming to IS-3356 at different Transformers & different locations complete all as specified and directed by Engr-in-Charge.
Earthing complete with GI earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (Earth pit not less then 2.25m deep below ground level ) with top edge not less than 1.5m below ground level connected to GI earth strip 32 x 6 mm by means of GI bolts,nuts, check nuts,washers & GI strip ,protected by 50 mm bore medium grade GI pipe up to 7,5mtr distace including necessary charcol, salt & 20Kg Benzonite powder Funnel with wire mesh , watering pipe20mm dia medium grade excavation earth work PCC (1:3:6) type C-1 earth chamber , 50mm thick RCC cover with 6mm nominal reinforcement etc complete all as shown electrical plate No. 5 of MES schedule part I all as specified and directed . .
M&L for replacement of breather assembly transparent MS body with top and bottom portion pressed with metallic cover, filled with silica gel blue in colour and suitable for fixing on existing pipe of size 15/20/25 mm dia or as per site requirement/ capacity of Transformer up to 750 KVA including taking down UNSV breather assembly complete all as specified & directed by the Engr-in-Charge.
Supply and fix Transformer Gaskets and seals made from a blend of nitrile rubber and cork complete for capacity 400KVA to 750KVA transformer including taking down UNSV gasket complete all as specified & directed by the Engr-in-Charge.
M & L for finding cable fault with electronic fault detector in LT/HT UG cable of any size ranging from 25 to 400 Sqmm 3/ 3.5 core, complete including necessary earthwork all as specified and directed by Engineer-in-charge.
Supply only discharge rod suitable for 11 KV, having upper body made up of cast aluminium and lower body made up of FRP material with copper wire not less then 16 sqmm with clamp to fix on earthing, having length not less then 18 ft and diameter 40mm complete all as specified and directed by Engr-in-charge.
Supply & fix in repairs gate valve (Gun metal), ISI marked of size 25mm including taking down old UNSV gate valve complete all as specified and directed by Engr-in-Charge.
Supply, laying & testing XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade, of size 120 sqmm, 3.5 core incl taking down unsv LT cable complete all as specified and directed by Engr-in-Charge.
S&F Cable jointing Kit for 11KV (E) grade cable for indoor cable End termination heat shrink type joint complete with jointing material and accessories suitable for 11 KV(E) XLPE cable of size 50 sqmm to 95 sq mm 3 core with aluminium conductor complete all as specified and directed by Engr-in-Charge.
M&L for cleaning of E/M installations / campus surface dressing or trimming of branches of trees, cutting/ dressing of natural grass from ground to remove small unequalities n.exc 15 cm deep ( including removing vegetation / shrubs / brush wood / under-growth ), cleaning of drains & carrying away the rubbish to a distance of n.exc 50 mtr away complete, the area of installation up to 700sqm. at least 2 times in each installation at a interval of 3 months
Dismantling and taking down old UNSV and Supply, install, testing and commissioning of suitable size factory made in door type, dust and vermin proof, LT feeder pillar box double door, cubical and compartmentalized type with minimum depth size 500mm, 415 volts, AC, 50 Hz, fabricated with 3.15mm thick CRCA sheet for outer side and 2mm thick inside complete with and including mounted on angle iron frame stand of size 50 x 50 x 6 mm thick 50 cm long leg, grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate), spray painted inside and outside, powder coated of approved colour by Engineer-in-Charge, enclosed bus bar chamber with aluminium bus bar (04 Nos of rating capacity 400 Amps), mounted on PVC insulators, electric connection complete with from MCCB to main bus bar, cable glands, thimble complete with and including openable shutters butt hinged, locking arrangement including PCC work, excavation & earth work, taking down old rusted feeder pillar box complete and comprising supply and fix at P1 bldg staircase, Vikhroli for following complete all as specified and as directed by Engineer-in-Charge. :-
INCOMING: (a) MCCB 4 pole, 400 Amps, 415 volts, 50 Hz, 36 KA, adjustable thermal & adjustable magnetic settings - 01 No. BUSBAR : (b) Bus bar chamber with 400 Amps aluminium strip with heat shrinkable insulating sleeve size 50 x 10mm - 4Nos of required length supported on FRP insulators, internal wiring for indicators with 2.5 Sqmm copper cable single core. (c) CT coil of ratio 200/5 Amps - 03 Nos (d) Digital type Multifunction meter of class I - 1 Nos Make : L & T Model : 4400 LED series or equivalent in Seimens/ Scneider (e) LED type indicator lamps RYB - 01 Set OUTGOING: (a) MCCB 4 pole, 200 Amps, 415 volts, 50 Hz, 36 KA, adjustable thermal & adjustable magnetic settings - 03 Nos (b) MCCB 4 pole, 100 Amps, 415 volts, 50 Hz, 16 KA, adjustable thermal & adjustable magnetic settings - 04 Nos (c) MCCB 4 pole, 63 Amps, 415 volts, 50 Hz, 16 KA, adjustable thermal & adjustable magnetic settings - 03 Nos (d) Capacitor Bank of Capacity 25 KVAR Note: (i) Contactor shall be submit the drawings of panels for approval before fabrication in factory. (ii) LT panel board shall be CPRI approved.
Dismantling and taking down old UNSV and Supply, install, testing and commissioning of suitable size factory made in door type, dust and vermin proof, LT feeder pillar box double door, cubical and compartmentalized type with minimum depth size 500mm, 415 volts, AC, 50 Hz, fabricated with 3.15mm thick CRCA sheet for outer side and 2mm thick inside complete with and including mounted on angle iron frame stand of size 50 x 50 x 6 mm thick 50 cm long leg, grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate), spray painted inside and outside, powder coated of approved colour by Engineer-in-Charge, enclosed bus bar chamber with aluminium bus bar (04 Nos of rating capacity 400 Amps), mounted on PVC insulators, electric connection complete with from MCCB to main bus bar, cable glands, thimble complete with and including openable shutters butt hinged, locking arrangement including PCC work, excavation & earth work, taking down old rusted feeder pillar box complete and comprising supply and fix at Veh section staircase, Vikhroli for following complete all as specified and as directed by Engineer-in-Charge. :-
INCOMING: (a) MCCB 4 pole, 400 Amps, 415 volts, 50 Hz, 36 KA, adjustable thermal & adjustable magnetic settings - 01 No. BUSBAR : (a) Bus bar chamber with 400 Amps aluminium strip with heat shrinkable insulating sleeve size 50 x 10mm - 4Nos of required length supported on FRP insulators, internal wiring for indicators with 2.5 Sqmm copper cable single core. (b) CT coil of ratio 200/5 Amps - 03 Nos (c) Digital type Multifunction meter of class I - 1 Nos Make : L & T Model : 4400 LED series or equivalent in Seimens/ Scneider d) LED type indicator lamps RYB - 01 Set OUTGOING: (a) MCCB 4 pole, 100 Amps, 415 volts, 50 Hz, 16 KA, adjustable thermal & adjustable magnetic settings - 08 Nos Note: (i) Contactor shall be submit the drawings of panels for approval before fabrication in factory. (ii) LT panel board shall be CPRI approved.
Supplying, installing, testing & commissioning WALL MOUNTED cubical type double door LT feeder piller box factory made modular construction fabricated out of 2 mm thick CRCA sheet, epoxy powder coated to give a superior finish , indoor type , totally enclosed dust & vermin proof with locking arrangements (compartment wise) front side opening system, overall size of each incoming & outgoing modules should not less than (1050mmx450mmx 1000mm). and busbar chamber should be suitable for accomodating all Aluminium bus bar strips (40mm x 10mm x 04 Nos) duly covered by PVC sleeves, fixed on porcelain insulators and one independent metering module suitable for accomodating indicator lamps, cable entry/exits, cut outs at bottom or upper part as mentioned below, complete electrically inter connected suitable size for all incoming and outgoing MCBs and accessories with fixing arrangement on wall with bolts, nuts & washers, Danger notice board with scull suitable for 415 volts or required size to be fixed on Panel and consisting of the following accessories including dismantling of old panel all as directed. Location- Vikhroli offr accn Pump House Note:- (a) Panel shall be Manufactured from CPRI approved manufacturer and Drawing for Feeder pillar box shall be first approval by Engr-in-Charge (b) The cost of dismantling of old panel/F/piller Box is deem to be included above. (c) Panel indicating lamp neon/LED type (Red ,Yellow & Blue) with lamp holders - 03 Nos (d) Panel instrumental wiring with FRLS suitable size but not less than 2.5 sqmm copper wire single core - 01 Job
Incoming:- (a) MCCB 4 pole 25 KA, 415 Volts, 100 Amps , with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos. (Make: L&T) Outgoing:- (a) MCCB, 415 Volts,10 KA, 63 Amps -02 Nos. Make : Legrand / L&T / Havells / ABB / Siemens / Schneider (b) DOL starter 5 HP 3 Phase for open execuision in panel with push button switch ON/OFF indicator on door of each module with single phase protection relay- 2 Nos. Make-Havells/ Siemens/ Larsen &Tubro/ ABB/ Crompton Greaves/ GE (c) Intelligent automatic factor controller relay 6 pole voltage 220-440. Make : Runcon, Type- APFC Relay)-1 Nos (d) Digital Type energy meter - 01 Nos (e) Multifunctional meter (VAF + PF meter) for main incomming- 01 Nos. (Make- L&T Cat Part- WL41010OOOO) Note: (i) Contactor shall be submit the drawings of panels for approval before fabrication in factory. (ii) LT panel board shall be CPRI approved.
Supplying, installing, testing & commissioning WALL MOUNTED cubical type double door LT feeder piller box factory made modular construction fabricated out of 2 mm thick CRCA sheet, epoxy powder coated to give a superior finish , indoor type , totally enclosed dust & vermin proof with locking arrangements (compartment wise) front side opening system, overall size of each incoming & outgoing modules should not less than (600mmx450mmx 1100mm). and busbar chamber should be suitable for accomodating all Aluminium bus bar strips (40mm x 10mm x 04 Nos) duly covered by PVC sleeves, fixed on porcelain insulators and one independent metering module suitable for accomodating indicator lamps, cable entry/exits, cut outs at bottom or upper part as mentioned below, complete electrically inter connected suitable size for all incoming and outgoing MCBs and accessories with fixing arrangement on wall with bolts, nuts & washers, Danger notice board with scull suitable for 415 volts or required size to be fixed on Panel and consisting of the following accessories including dismantling of old panel all as directed. Location- Vikhroli offr accn Panel room Note:- (a) Panel shall be Manufactured from CPRI approved manufacturer and Drawing for Feeder pillar box shall be first approval by Engr-in-Charge (b) The cost of dismantling of old panel/F/piller Box is deemed to be included above. (c) Panel indicating lamp neon/LED type (Red ,Yellow & Blue) with lamp holders - 03 Nos (d) Panel instrumental wiring with FRLS suitable size but not less than 2.5 sqmm copper wire single core - 01 Job
Incoming:- (a) MCCB 4 pole 25 KA, 415 Volts, 100 Amps , with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos. (Make: L&T) Outgoing:- (a) MCCB, 415 Volts,10 KA, 63 Amps -03 Nos. Make : Legrand / L&T / Havells / ABB / Siemens / Schneider (b) onload front operated CHANGE OVER SWITCH 100 Amps front operated -1 Nos (c) Multifunctional meter (VAF + PF meter) for main incomming- 01 Nos. (Make- L&T Cat Part- WL41010OOOO) Note: (i) Contactor shall be submit the drawings of panels for approval before fabrication in factory. (ii) LT panel board shall be CPRI approved.
Supply & Fix ABC type Fire Extinguisher of capacity 6 Kg, dry powder type, wall mounted ISI marked, IS-15683 complete in all respect.
Supply & Fix, in repairs, CO2 type Fire Extinguisher capacity 4.5 Kg dry powder type, wall mounted, ISI marked, IS-15683 with 01 mtr hose pipecomplete in all respect.
Supply, laying & testing XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade, of size 185 sqmm, 3 core incl taking down unsv complete all as specified and directed by Engr-in-Charge.
S&F Cable jointing Kit for 11KV (E) grade cable for outdoor cable straight through heat shrink type joint complete with jointing material and accessories suitable for 11 KV(E) XLPE cable of size 70 sqmm 3 core with aluminium conductor complete all as specified and directed by Engr-in-Charge.
Material and labour for straight Through Heat shrinkable type Cable Joint Kit including Jointing Materials for making Joints of LT UG Electric Cable 1100 Volt Grade Heavy Duty with XLPE insulated Aluminium Stranded Conductor size 50 Sqmm to 120 Sqmm x 3.5 Core and Testing complete all as specified and as directed.
Refixing / relaying of existing disturbed / uprooted existing LT/HT electric cable of size upto 300 Sqmm to the existing places like uprooted from ground or out with the steel saddles from ground level to four storey bldg distribution box,etc complete with using/ electric drill machine, nut & bolt and proper grouted complete all as specified and as directed by engr-in-charge.
Supply & fix anti skid electrical insulating mat confirming to IS 15652/2006 (superceding IS : 5424-1969 ) BIS + CPRI+NTH+ERDA approved of C class of mats having dielectric strength 65 KV, sheet thickness not less than 2.5 mm using at power house including pasting of rubber mats with adhesive resin including taking down old UNSV rubber mats complete all as specified and directed by Engr-in-Charge.
Material and labour for GI sheet of size 10 x 8 inch welded with 2.5 foot of angle iron for marking earth pit grouted on ground with PCC at different area complete all as specified and directed by Engr-in-Charge
Supply and fix plastic coating print in GI sheet of size 10 x 8 inch for marking earth pit grouted on ground at different area complete all as specified and directed by Engr-in-Charge
Supply and fix Rolled mild steel plates (Plain or chequered) channels Fe 410-W (Gde-E-250)quality A, square cut or notched (ordinary and counter sunk) forming holes, without any attachment without disturbing existing electric system including applying two coats of black paint over a coat of red oxide complete all as specified and directed by Engr-in-Charge.
Supply and fix 11 KV HT bushing & brass/copper studs, gasket with-400 to 750 KVA including taking down UNSV HT Bushing complete all as specified & directed by the Engr-in-Charge.
Supply & fix LT bushing and brass/copper studs, washer & Rubber bush etc for 400 to 750 KVA including taking down UNSV LT Bushing complete all as specified & directed by the Engr-in-Charge.
M & L for dehydration of transformer oil through on load mobile stream line transformer oil filtration plant at site with all accessories connected to transformer and carrying out filtration of oil for desired dielectric strength ie not less than 45 KA at 4 mm gap.
Chaudhary Enterprises (BID ID -3495812)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.32 MB
BOQ_830052.xls
BOQ • 0.31 MB
Tenderdocu85250.pdf
Tender Documents • 0.98 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .