| # | Company | Status |
|---|---|---|
| 1 | Rejected-Technical 77 FORT VIEW COLONY NEAR KOTESWER TEMPLE ASRAM GWALIOR FORT RODE KOTESWER GWALIOR MADHYA PRADESH 474012 | GWALIOR | MADHYA PRADESH | 474012 | Rejected-Technical Documents not found in order |
| 2 | Rejected-Technical 0 BHUTA BAZZAR BHIND BHIND MADHYA PRADESH BHIND MADHYA PRADESH 477001 | BHIND | MADHYA PRADESH | 477001 | Rejected-Technical Documents not found in order |
Tender Value
₹60.0 L
EMD Value
₹1.2 L
Closing Date
11 Jun 2026, 11:00 amClosed
Executive Engineer Electrical
BSF Academy Tekanpur
Amalgamation of Type I 120 Nos Qtrs into Type II 60 Nos Qtrs AT STC BSF Tekanpur Sh Electrical Installation
2026_BSF_911216_1
02/NIT/ELECT/STC/2026-27
Open Tender
Electrical Works
Item Rate
365 days
STC BSF Tekanpur
2 documents required · 2 mandatory
₹0
₹1.2 L
14 Jul 2026
2 Jun 2026
12 Jun 2026
2 Jun 2026
11 Jun 2026
2 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group A | 60 | Point | - | - |
| 2 | Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. | 90 | Point | - | - |
| 3 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. | 840 | Each | - | - |
| 4 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required.(i) 125 A,36 KA,FPMCCB | 40 | Each | - | - |
| 4.2 | 250 A,36KA,FPMCCB | 14 | Each | - | - |
| 4.3 | 400 A,50 KA,FPMCCB | 1 | Each | - | - |
| 5 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (i) 8 way (4 + 24), Double door | 30 | Each | - | - |
| 6.1 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (i) 40 Amp | 30 | Each | - | - |
| 6.2 | 63 Amp | 60 | Each | - | - |
| 7 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.(i) 100 Amp | 30 | Each | - | - |
stage.html
html • 0.02 MB
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.55 MB
BOQ_957653.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .