Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.6 LAccepted-AOC 0 PRAGATIPUR DHARMA SARMA PATH BIRUBARI KAMRUP ASSAM 781016 | KAMRUP METRO | ASSAM | 781016 | ₹9.6 L Quoted ₹9.8 L | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹13.8 L+₹4.0 L (41.2%)Rejected-Finance | ₹13.8 L+₹4.0 L (41.2%) | L2 | Rejected-Finance Other than lowest bidder |
| 3 | L3₹13.9 L+₹4.1 L (41.5%)Rejected-Finance HOUSE NO 29 A SIJUBARI NIZARA PATH PO PS HATTIGAON GUWAHATI 38 | KAMRUP METRO | ASSAM | 781038 | ₹13.9 L+₹4.1 L (41.5%) | L3 | Rejected-Finance Other than lowest bidder |
| 4 | L4₹14.0 L+₹4.2 L (43.2%)Rejected-Finance AZARA GUWAHATI ASSAM 781017 | KAMRUP METRO | ASSAM | 781017 | ₹14.0 L+₹4.2 L (43.2%) | L4 | Rejected-Finance Other than lowest bidder |
Tender Value
Refer Docs
EMD Value
₹20,000
Closing Date
8 Feb 2022, 6:00 pmClosed
GE GUWAHATI
GE GUWAHATI, PO SATGAON, DISTT KAMRUP - 781027
REPAIR/MAINT OF LT UG CABLE, LT PANELS, EARTHING AND ALLIED WORKS AT BASISTHA AREA AND OTHER THAN BASISTHA AREA UNDER GE GUWAHATI
2022_MES_500893_1
GE/GUW/49/8178/E8
Open Tender
Electrical and Maintenance Works
Item Rate
150 days
GE GUWAHATI
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE GUWAHATI
₹20,000
Yes
2 Mar 2022
11 Jan 2022
10 Feb 2022
11 Jan 2022
8 Feb 2022
25 Jan 2022
11 Jan 2022 - 17 Jan 2022
Amount
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc laying of cables etc and getting out in soft/loose soil complete all as specified and as directed.
Returning, filling in, including, spreading, levelling, watering and well ramming in layers not exceeding 25cm complete all as specified and as directed.
Removing excavated material n.exc 50m and depositing were directed at a level not exceeding 1.5m above the starting level complete all as specified and as directed.
M&L for providing sand cushioning for protection of UG cable (8 cm deep before laying & 15 cm above the top edge of cable after laying) in trenches with dry (coarse) sand approved quality including filling, spreading and punning down to desired thickness complete all as specified & as directed. (NOTE : Punned thickness of 18 cm only shall be considered for payment purpose)
Supply and laying brickwork with locally (Sub Class B Bricks) available best quality bricks in trenches for protection of UG Cable with width equal to length of bricks, laid dry & flat complete all as specified & as directed.
M&L cutting as in road surfaces, pavements etc for laying UG cable, Pipes etc, minimum width 45cm and depth 60cm, returnin filling in where required with materials of existing specifications and making good the distrubed surfaces with plain cement concrete type C2, (1:3:6), (using 40 mm graded stone aggregate), (thickness of PCC not less than 100mm) after laying of UG cable, pipe etc complete all as directed.
M&L making hole by suiable means for insertation of GI pipe 80mm bore for passing cable across the road surface without cuttting the road complete all as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150sqmm 3.5 core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120sqmm 3.5 core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95sqmm 3.5 core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70sqmm 3.5 core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50sqmm 3.5 core complete all as specified and as directed.
M&L Cable jointing kit for 1100 Volts grade cable for straight through joint, cold shrinkable type complete with jointing material and accessories suitable for 3.5 core XLPE/PVC armoured aluminium conductor cable of size 25 sqmm to 50 sqmm, and testing after jointing complete all as specified and as directed.
M&L Cable jointing kit for 1100 Volts grade cable for straight through joint, cold shrinkable type complete with jointing material and accessories suitable for 3.5 core XLPE/PVC armoured aluminium conductor cable of size 70 sqmm to 120 sqmm, and testing after jointing complete all as specified and as directed.
M&L 80mm bore GI pipe light grade with all necessary fittings (ISI marked) as in cable protection fixed to pole,laid in trenches/road/floor complete all as specified and as directed.
M&L 40mm bore GI pipe light grade with all necessary fittings (ISI marked) as in cable protection fixed to pole,laid in trenches/road/floor complete all as specified and as directed.
M&L cement concrete in foundation, filling mass concrete type-C2, 1:4:8, (using 40mm graded crushed stone aggregate) for pole foundation, bed concrete etc including necessary formwork complete all as specified & as directed.
M&L PCC (1:2:4) Type B-1 (using 20mm graded crushed stone aggregate) for coping of poles etc & finishing the surface even & smooth without using extra cement including necessary formwork complete all as specified and as directed.
Supply & Erecting Steel Tubular Swaged Pole Type 410-SP-31 (9.0 METRE long) including Cast Iron Base Plate, Finial Taper Plug, Cap, Mild Steel Bolts, Nuts, Screws including applying two coats of Black Bituminous Paint Internally and Externally from bottom End of Pole upto PCC Coping (embedded in conrete) and applying one Coat of Red Oxide Zinc Chrome Primer, painting with syntheic enamel paint in alternate Yellow & Black Strips Painting (4 No. Each Strip 150 mm wide) and remaining portion of Pole treated with Two Coats of Aluminium Paint over a coat of aluminum primer, including writing MES Pole No. with synthetic Enamel Paint (First Grade/quality), including dismantling the unservicable pole complete all as specified and as directed. NOTE: Earthwork, Cement Concrete, etc. will be measured and paid under approprite Items.
M&L Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint including dismantling the existing unserviceable cross arm, bracings etc complete all as specified and as directed.
M&L Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade complete all as specified and as directed.
M&L Earthing with Galvanised Steel Earth Plate Electrode 600x600x6 mm thick, buried directly in ground vertically to a depth not less than 2.25 METRE below Ground Level with Top Edge of Earth Plate at depth not less than 1.50 METRE below normal ground level, connected to GI Earth Strip 32 x 6 mm drawn through and including GI Pipe 40 mm bore (dia) ‘light grade’ for protection upto 1.00 METRE above the Floor Level of the Building where Main Switch/DB situated, by means of Bolts, Nuts, Check Nuts and Washers etc., Earth Plate surrounded by a packed thickness of Char Coal or coke dust mixed with common Salt in alternate layers of not exc. 150 mm thick, PCC Pit in Cement Concrete 1:3:6 (20 mm graded aggregate) and Pre-cast RCC 1:2:4 (20mm graded aggregate) Cover Slab 350x350 x50mm, reinforced with and including 8.0 mm dia TMT Bars @ 100 mm centre to centre both ways, GI wire mesh, Funnel with GI Watering Pipe 20mm bore (dia) ‘medium grade’, necessary excavation in soft/loose soil, returning, filling in and removal of Surplus Spoil upto a distance of 50 METRE and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on completion, including taking dismantling unserviceable Earthing and connected Items, complete all as specified and as directed
M&L Earthing complete with Copper Earth Plate Electrode 600x600x3mm thick buried directly in ground vertically to a depth not less than 2.25 METRE below Ground Level with Top Edge of Earth Plate at depth not less than 1.50 METRE below normal ground level, connected to Copper Earth Strip 20x3mm and drawn through and including Galvanised Iron Protection Pipe 40mm bore (dia) ‘light grade’ upto 1.00 METRE above the Floor Level of the Building where Main Switch/DB situated, by means of Copper or Bronze Bolts, Nuts, Check Nuts and Washers etc., Earth Plate surrounded by a packed thickness of char coal or coke dust mixed with Common Salt in alternate layers of not exc. 150 mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded aggregate) and pre-cast RCC Cover Slab of size 350x350x50mm in Cement Concrete 1:2:4(20mm graded aggre gate) reinforced with and including 8mm dia TMT Bars @10 Cm centre to centre both ways, GI Wire Mesh, Funnel with GI Watering Pipe 20 mm bore (dia) ‘medium grade’, necessary Excavation in Soft/Loose Soil, Returning, Filling in and removal of Surplus Spoil upto a distance of 50.00 METRE and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and testing on completion including taking dismantling unserviceable Earthing and connected Items, complete all as specified and as directed
S&F in repair, 4 pole Power contactors with dust cover, 315 Amps, with AC coil, rating at 415 Volts complete all as specified and as directed.
S&F in repair, on load changeover switch, 320 Amps, 50 KA , 415 Volts, 4 Pole complete all as specified and as directed.
S&F in repair, 3 Pole, 40 Amps street light panel/Distribution board with digital time switch complete all as specified and as directed.
S&F in repair, MCCB 3 Pole with thermal magnetic release, having breaking capacity 36 KA of rating 250 Amps including electric connections complete all as specified and as directed.
S&F in repair, MCCB 4 Pole with thermal magnetic release, having breaking capacity 36 KA of rating 160 Amps including electric connections complete all as specified and as directed.
DEBROYENTERPRISE
M/S SEWAK SINGH
M/s Torrent Inc
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .