Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹57.9 LAccepted-AOC GR 8 ADDA BUILDING 1ST FLOOR CITY CENTRE DURGAPUR 16 | DURGAPUR | PASCHIM BARDHAMAN | WEST BENGAL | L1 | Accepted-AOC 1st lowest | |
| 2 | L2₹63.1 L+₹5.2 L (8.99%)Rejected-Finance | L2 | Rejected-Finance 2nd lowest | |
| 3 | L3₹63.8 L+₹5.9 L (10.1%)Rejected-Finance METHOPARA GANGANAGAR KOLKATA 700132 | KOLKATA | NORTH 24 PARGANAS | WEST BENGAL | 700132 | L3 | Rejected-Finance 3rd lowest |
Tender Value
Refer Docs
EMD Value
₹1.2 L
Closing Date
12 Oct 2022, 12:30 pmClosed
EE/BED/PWDTE
PWD Compound, Kenduadihi, Near Bhairabsthan,Bankura-722102
Electrical Installation work for A.C machine, SITC of Lightning Arrester, DG, Feeder pillar with allied electrical work at Central Library, Bankura University in the District of Bankura.
2022_WBPWD_409960_1
WBPWDTE/EE/BED/NIQ_88/Q of 2022-23
Open Tender
ELECTRICAL WORKS ORG
Item Wise
60 days
BANKURA
Please refer Tender documents.
3 documents required · 3 mandatory
₹1.2 L
22 Nov 2022
23 Sept 2022
14 Oct 2022
23 Sept 2022
12 Oct 2022
23 Sept 2022
Amount
S & F Lightning conductor Air-terminals made of 15 mm dia 1500mm long GI pipe (ISI Medium) having five prongs of 4 SWG GI(Hot Dip) wire at top with 85 mm dia 6 mm thick GI base plate atbottom incl. necessary holes etc. duly grouted on the parapet etc.in CC mortar (4:2:1) [J-1/1]
Supply & fixing GI (Hot Dip) strips 20 mm x 3 mm thick for horizontal run on the Parapet/Roof/ Wall with GI Saddles 1100mm apart incl. mending good the damages to building works [J-1/9]
Supply & fixing GI (Hot Dip) strips 20 mm x 3 mm thick for vertical run on Wall with GI Saddles spaced not exceeding 1000mm apart incl. mending good the damages to building works [J-1/11(a)]
Cutting cornices/ steps etc. including cutting recess in buildings etc. & supply & fixing 15 mm bore (ISI-Medium) GI pipe protection as below and mending good damages to the building works:[ J-1/4] Length upto 0.5 Mtr
Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage, for LC installation, per storey of building per vertical run [J-1/7]
Supply & Fixing of Testing Joints by 20 mm x 3 mm thick GI (Hot Dip) strip 125 mm long grouted on wall having clearance of 6 mm from wall for making connection with thimbles at the end of 7/10 SWG GI (Hot Dip) stranded Wire and 4 SWG GI (Hot Dip) wire of vertical conductor and conductor from earth electrode complete with S & F thimbles, GI bolts, nuts, check-nuts, spring washers etc. as required. [J2/13]
Making soldered joints between conductors and down pipes/other metallic objects for 4 SWG GI (Hot Dip) wire includingsupply of necessary 4 SWG GI (Hot Dip) wire, jointing materialsand painting with 2 (two) coats of bituminous paint . [J-1/6]
Supplying & installation complete of Blue Star 80 Ltr. FSS ( Full Stainless Steel ) water cooler with Aquaguard Reviva 50 Lph Insta RO And Hi-flow UV water purifier mfd by Eureka Forbes Ltd. including iron remover & all other needful accessories
Timer Panel:Supplying and fixing 2+6 way Legrand/ Cabtree/ simens DB with acrylic cover enclosure for housing the following A) One no.single dial analog timer (Legrand/ Havells/ Simens) B) 1 no 32A . DP, conctractor, (Legrand/ Havells/ Simens) C) One no. DP 40A MCB Isolator (Legrand/ Havells/ Simens) D) One No indicator F) One no 10 A MCB Changeover (Legrand/ Havells/ Simens) and other required material The complete arrangement must be wiring by PVC insulated Cu wire as per GS
Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. [G-3/5©] (for connecting between earth for SPD to existing earth bus)
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below By ISI-M GI Pipe [G-1/ 2(a)]
Excavation of soil for installation of Earth Electrode and filling & ramming. a) for morrum soil . [G-1/1(b)]
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 40 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. [G-2/4(b)]
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings as per GS 40mm dia [11(c)/F-6]
Cutting of 8 '' PCC Concrete & mending good damages as per G.S
Distribution wiring in 1.1 KV single core stranded 'FRLS' PVC\ insulated & unsheathed "FRLS' copper wire (make-Finolex / Havells /KEI/ Gloster / Mescab ) in 20mm / 25 mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required 2 x 4 sqmm + 1 x 2.5 sqmm ( For A.C Point ) [ 1 (v) / E- 9 ]
S & F PVC Rigid Conduit/ Casing Capping FR Precesion Make on Wall Celling with saddle And Other Accessories as Required and Mending good damages to Building Works (a) 20mm Size E-16/7(a)
S&F OLP-3 incorporated in a box having a 20amp MCB SPN ,composit flash type 250 V. 6 pin 25 Amp. Plug socket with 25Amp MCB. in the box made of 16 SWG CRC sheet with bakelite top cover and earthing attachment in surface as per G.S.
S&F sheet metal 2 module Anodised box in conceal in wall incl S & Fbase & top incl S & F 25A capacity 5 pin base & Top North Make and earthing attachment as per G.S.
S& F OLP - 3 stater and 25 A plug Socket and top (make- North West) in Existing modular box as per direction of E.I.C
Supply, installation, testing and commissioning of new CPCB-II compliant 3Phase, 415V, 50Hz, 125KVA Silent Diesel Generator Set comprising of Engine, Alternator, STD AMF Panel, Base Frame, Fuel Tank, Batteries, CPCB approved Acoustic Enclosure having following specification and engine should not derate at 50Deg C ambient temperature. Engine: a) Make: CUMMINS/ASHOK LEYLAND/CATER PILLAR b) BHP - Minimum 155BHP c) Aspiration - Turbo charged air to air cooled d) No. of Stroke / Cylinder - 4 Stroke/6 Cylinder in line e) RPM - 1500 f) Battery - As per manufacturer standard. g) Type of Cooling - Water/Liquid cooled. h) Air Intake System - Air intake manifold with air airfilter system. i) Exhaust System - Provided with turbo charger & residential exhaust silencer with flexible bellow and companijon flanges insijde the acoustic enclosure. j) Coupling & Flywheels - Befitting coupling with single bearing system. k) Lubricating system - Provided with Oil Pan, engine mounted lube oil pump and lube oil filter along with first fill of lube oil. l) Fuel System - Comprising of manufacturers standard fuel pump with electronic governor, 12V Solenoid coil and replaceable fuel filter. m) Starting system - 12V DC Electric Start. n) Engine Protections - Low lube oil pressure/high coolant temp./over speed. Alternator a) Make: Stamford/Leroy Somer/Crompton Greaves b) Rating - 125KVA c) Type of Alternator - Brushless, self excited & self regulated. d) Voltage Regulation - ±1% (max) in static condition. e) Overload - Permissible overload of 10% for 1 hour in 12 hours of operation. f) Protection - IP-23 protection with Class-H insulation. g) Enclosure Type: SPDP Base Frame Common MS Channel fabricated base frame, primer coated & painted, containing the engine and the alternator mounted through AVM Pads. Fuel Tank - Minimum 175Ltrs detachable tank built inside acoustic enclosure complete with drain valve, air vent, inlet & outlet connections, fuel gauge. Acoustic Enclosure Specially designed to meet stringent MOEF/CPCB Norms of 75dBA @ 1Mtr. At 75% load under free field conditions. The Acoustic Enclosure is made of CRCA sheets and structural sheet metal base frame painted in black. a) High quality noise absorbant and fire retardant grade acoustic insulation material (PU Foam/Rock Wool complying to IS:8183. b) Two point lifting for easy handling at customer site. c) Designed to have optimum serviceability. d) Air inlet louvers specially designed to operaate at rated load. e) 9/11 tank pretreatment process and UV resistant Powder coating of all parts to withstand extreme environment. f) Use of special hardware for longer life. g) Fluid drains for lube oil and fuel. h) Fuel filling arrangement inside the enclosure. AMF Panel AMF Control Panel fabricated from 16SWG CRCA sheet and powder coated after 7 tank treatment process and to be accommodated inside the canopy. The panel comprises of following items :- a) 200Amps, 4Pole, 36ka Microprocessor based MCCB with all protections for Mains & DG - 2 Nos. a.1) 200Amps, 4Pole, AC-1 Duty Power Contactor with NO+NC Contacts for DG & Mains - 2 Nos. b) Electronic Voltage Regulator for Mains Contactor. 1 No. c) Required Add on Blocks for Contactors d) Required 6A-SP & 16A-DP MCB of 10Ka e) Indicating lamps 230V AC (LED type) - Mains ON, DG ON, Mains Load ON/DG Load ON f) Start/Stop Push Button should be available in the AMF Controller. g) Aux. Relay as required. h) 3Phase Voltage monitoring Relay. i) ON Delay Timer, Coil voltage 230AC j) Auto Trickle & Boost type Battery charger, 12V k) Microprocessor based AMF Controller having all inbuilt display features for engine & alternator and protections for Engine & alternator. l) Aluminium Bus Bar of rated capacity and size m) Make - OEM Make. AMF Panel should have bypassing Changeover system with 2 nos 200 Amp changeover switch a) Efficiency: As per manufacturers declared value. b) Warranty - 18 months from the date of supply or 12 months from the date of commissioning, whichever is earlier. c) Test Certificates of Engine & Alternator should accompany the Bill.
Filling of HSD oil for initial refill with transportation.
Supply and delivery of best quality oil hand pump with 1" dia PVC flexible pipe (10 mtr. approx.)
Supply and delivery of 200 ltr. Capacity heavy gauge MS sheet barrel.
S& laying 50 sq. mm. single core multistrand PVC insulated flexible Cu cable in uPVC / GI pipe from earth electrode to neutral earth busbar and from earth busbar to DG neutral point as required (for neutral earthing)
S& laying 2.5 sq. mm. 10core multi core multistrand PVC insulated flexible Cu cable in uPVC / GI pipe from DG to separate AMF panel.
Finishing the cable ends by crimping method incl. S&F copper socket, insulating tape and jointing materials etc. as required suitable for single core 70 sq. mm. copper wire.
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. Long With TATA-Medium GI pipe as per GS [ 2(a)/G-1]
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) Cl hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. [3(a)/G-2]
Excavation of soil for installation of Earth Electrode and filling & ramming. (For Soft Soil) [1(a)/G-1]
Extra for treatment of soil by using salt & charcoal or coke for plate electrode [3(b)/G-2]
Connecting the equipments to earth busbar including S & F Solid GI (Hot Dip) wire of size as below as per GS No.-4 SWG [5(a)(i)/G-2]
No.-6 SWG [5(a)(ii)/G-2]
Connecting the equipments body to earth busbar including S&F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. [5(d)/G-3)]
Earth work in excavation of foundation trenches of drains, in all sorts of soil including removing, spreading or stacking the spoils within a lead of 75m as directed. The item includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as required complete.( Depth of Excavation not exceeding 1500 mm ) [ Page- 1, Item no.- 2(a) of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
Earth work in filling in foundation trench or plinth with good earth in layers Board a) With earth obtained from excavation of foundation 1/5th of excavated earth [ Page 1, Item no.3(a) of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
Filling in foundation or plinth by silver sand in layer a) With earth obtained from excavation of foundation 1/5th of excavated earth [ Page- 2, Item no.- 4(A) of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
Single Brick flat soling of picked jhama bricks including ramming and dressing bed to proper level and filling joints with local sand [ Page- 14, Item no.1 of PWD Schedule of Rates, Volume-I of Building Works, 2017]
Base foundation for the installation of D.G ( appx Base size L-4000 mm x W- 2000 mm x H-800mm Reinforcement for reinforced concrete work in all sorts of structures including distribution bars, stirrups, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection, complete as per drawing and direction.. A)For works in foundation and top of ground floor / upto 4 m i) Tor steel/ Mild steel SAIL/ TATA/RINL. [ Page- 43, Item no.40(a)(i)(I) of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
Ordinary Cement concrete pakur variety (mix 1:1.5:3) with graded stone chips (20 mm nominal size) excluding shuttering and reinforcement if any, in ground floor as per relevant IS codes.
125 mm. thick brick work with 1st class bricks in cement mortar (1:4) in ground floor. [ Page- 16, item no.-16 of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
Plaster (to wall, floor, ceiling etc.) of 10 mm thick with sand and cement with 1:4 cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, nosing and drip course, scaffolding/staging where necessary (Ground floor).[Excluding cost of chipping over concrete surface] [ Page- 189, item no.-1(ii)-(c) of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
Neat cement punning about 1.5mm thick in wall, dado, window sill, floor etc. NOTE: Cement 0.152 cu.m per 100 sq.m. [ Page- 192, item no.-15 of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
SUB-HEAD 3-- SUPPLY & LAYING OF CABLES Supply of 4/3.5 Core XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [ Make / Fort Gloster/KEI/polycab/Havells] 4Core 10 Sq. mm [ NS ]
4Core 240 Sq. mm [ NS ]
4Core 120 Sq. mm [ NS ]
4Core 150 Sq. mm [ NS ]
4Core 95 Sq. mm [ NS ]
Laying of cable upto 35 sqmm in underground trench as per GS for the following numbers of Cables. 1 No Cable [ 1(a)/ F- 2 ]
Laying of cable above 35 and upto 185sqmm in underground trench as per GS for the following numbers of Cables. 1 No Cable [1(b)/F-2 ]
Laying of cable above 185 sqmm in underground trench as per GS for the following numbers of Cables. 1 No Cable [1(c)/F-2]
Supplying and fixing compression type gland and finishing those for following XLPE / PVC armoured cable (2/4 / 3.5)Core as per GS. 4Core 10 Sq. mm [7(c)/F4 & 8(b) /F5]
4 Core 120 Sq. mm [7(d)/F4 & 8(b) /F5 ]
4 Core 240 Sq. mm [7(d)/F4 & 8(b) /F5 ]
4Core 150 Sq. mm [7(c)/F4 & 8(b) /F5 ]
4Core 95 Sq. mm [7(c)/F4 & 8(b) /F5 ]
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings as per GS 80mm dia [11(f)/F-6]
Cutting of 10'' PCC & mending good damages as per direction of E.I.C
Supplying & delivery of 150 watt LED Outdoor Flood Light fittings (Havells Make CAT No : JETAIRISFLS150WLED757APWBMLTG SPD additional 10 KV / Cormpton/ Bajaj/ Havells Make complete with all 0accessories as per direction of EIC .
Supplying & delivery of 100 watt LED Outdoor Flood Light fittings (Havells Make CAT No : JETAIRISFLS100WLED757PSYMLTG SPD additional 10 KV / Cormpton/ Bajaj/ Havells Make complete with all 0accessories as per direction of EIC .
Supplying & delivery of 70 watt LED Outdoor Flood Light fittings (Havells Make CAT No : JETAPRO70WLED757LTG SPD additional 10 KV / Cormpton/ Bajaj/ Havells Make complete with all accessories as per direction of EIC .
Fixing of Street Light Fitting on Pole as per EIC.
S& F 63A changeover switch with sheet steel enclosure on flat iron frame on wall as per G.S make L&T/ Simens/ Havells ( For Lift )
Timer Panel:Supplying and fixing 2+10 way Legrand/Cabtree / simens DB with acrylic cover enclosure for housing the following A) One no.single dial analog timer (Legrand/ Havells/ Simens) B) 1 no 50 A . TP conctractor, (Legrand/ Havells/ Simens) C) One no. FP 63A MCB Isolator D) One No indicator F) One no 25 A DP MCB Changeover and other required material The complete arrangement must be wiring by PVC insulated Cu wire as per GS
Supply & Erection of Self Supporting Special type MS Structure with suitable height made from 50 mm dia hollow pipe 50 x 50 x 8 mm & 40 x 40 x 6 mm MS angle incl. S&F Anodised GI sheet for cover up the D.G set incl other necy materials as per direction of E.I.C ( Drawing & Details of Structure to be submitted & approved by E.I.C before taking up the work)
RS SYSTEMS AND PROJECTS
R K ENTERPRISE
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .