Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.6 LAccepted-AOC RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | ₹14.6 L Quoted ₹15.2 L | L1 | Accepted-AOC BEING LOWEST |
| 2 | L2₹15.9 L+₹70,623.20 (4.66%)Rejected-Finance A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | ₹15.9 L+₹70,623.20 (4.66%) | L2 | Rejected-Finance BEING NOT LOWEST |
| 3 | L3₹18.5 L+₹3.3 L (21.8%)Rejected-Finance | ₹18.5 L+₹3.3 L (21.8%) | L3 | Rejected-Finance BEING NOT LOWEST |
| 4 | L4₹21.3 L+₹6.1 L (40.2%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | ₹21.3 L+₹6.1 L (40.2%) | L4 | Rejected-Finance BEING NOT LOWEST |
Tender Value
₹30.6 L
EMD Value
₹61,100
Closing Date
27 Jun 2022, 6:00 pmClosed
ARJUN PATRO,IDSE
GE UTILITY ELECTRIC SUPPLY,DELHI CANTT
MAINTENANCE AND REPAIR OF HTLT SWITCH GEAR OUTDOOR INDOOR DISTRIBUTION TRANSFORMER ALONG WITH CONNECTED ACCESSORIES, EARTHING POLE PAINTING REPLACEMENT OF LT CABLES JOINTS AT ABHM,TPT COMPANY UNDER AGE U ES NOIII OF GEU ELECT SUPPLY DELHI CANTT10
2022_MES_526188_1
GE ELECT/D-19/2022-2023
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE UTILITY ELECTRIC SUPPLY
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE UTILITY ELECTRIC SUPPLY
₹61,100
Yes
4 Oct 2022
28 May 2022
29 Jun 2022
29 May 2022
27 Jun 2022
15 Jun 2022
Amount
Supply and making in replacement new LT 1100 V end termination with suitable size of aluminium lugs duly crimped for LT 3 ½ core armoured aluminium conductor cable after isolating supply to transformer/LT panel and disconnecting brunt/fault cable from the bunch of cables in trenches, galleries, removing cable loop, opening the cable blank and connecting back after end terminals, testing and commissioning for (XLPE) all as specified and directed.
(a) Cable Size 185 Sqmm to 240 Sqmm
(b) Cable Size 300 Sqmm to 500 Sqmm
(c) Cable Size 95 Sqmm to 150 Sqmm
(d) Cable Size 25 Sqmm to 70 Sqmm
Material and labour in replacement for earthing complete with galvanised steel earth plate electrode 60 x 60 cm and 6 mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m below ground level connected to galvanised GI earth strip 32 x 6 mm size by means of nuts, bolts, check nuts and washers of the galvanised iron or steel all as shown in electrical plate No 5 connected to earthing test point all as specified and directed and 20 mm GI pipe medium grade with funnel for watering and 40 mm GI medium grade pipe 7.5 mtr for GI earth strip protection from earth pit to test point & PCC for pit with white wash including CI pit cover 30 x 30 cm by taking down old unserviceable earthing. Note : Contractor should deposited test results of earthings.
Supply and laying in replacement GI earth strip of size 32 x 6 mm in trenches/fixed to walls/ transformer/LT panel /2 pole/4 pole with saddles and fixing screws etc., from earth pit to test point all as specified and directed.
Supply & fixing in replacement danger notice plate of 1.6 cm thick mild steel vitreious enamelled white, with letters, figures and conventional and boxes in signal red colour and fixed with MS clamps, bolts & nuts of approved size for HT 25 x 20 cm size all as specified and directed.
Repairs to LT / HT pillar box / cope point box by opening door hinges and taking rusted portion of door incl removing bends / dents and refixing the door with new hinges, handles, making good surfaces bolting etc all as specified and directed.
Excavation in trenches in soft and loose soil n.exc 1.5 mtr wide and n.exc. 1.5 mtr depth for laying and taking out of electric power cable and getting out all as specified and directed by engineer –in-charge.
Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material not exceeding 50 mtr away and depositing where directed at a level n. exc 1.5 mtr above the starting point .
Material & labour for river washed and screened dry sand for filling under and above the under ground cable for cushioning of cables etc.complete all as specified and directed by engr –in-charge
S&Laying in replacement sub class B bricks having minimum compressive strenth 75 Kg/sqm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge.
Supply and lay in replacement unreinforced precast concrete cable covers class LV Type -1 with peak size 250 x 150 x 40 mm. compete all as specified and directed
Supply, Laying, connecting, testing and commissioning in replacement ( including taking out existing cable) LT cable of PVC sheathed XLPE cable armoured aluminium conductor 1100 V graded after taking out/down old existing unserviceable from trenches / ducks/ road crossing and poles complete all as specified and directed of following size.
3.5 core, 25 sqmm.
3.5 core, 35 sqmm.
3.5 core, 50 sqmm.
3.5 core, 70 sqmm.
3.5 core, 95 sqmm.
3.5 core, 120 sqmm.
3.5 core, 185 sqmm.
3.5 core, 240 sqmm.
3.5 core, 300 sqmm.
4 core, 16 sqmm.
Material and labour in replacement for GI pipe light grade laid in trenches for cable protection of size 50mm dia. complete all as specified and directed
Material and labour in replacement for GI pipe light grade laid in trenches for cable protection of size 80 mm dia. complete all as specified and directed
Material and labour for servicing /testing and calibration of line breaker/control panel including outdoor CT, PT and relays in control panel of indoor VCB of capacity 630/400A Amps and rating 11 KV complete as details mentioned as under:- (a) Details of servicing of breaker :- (i) Checking of Closing/Tripping coil assembly (ii) Adjustment of mechanism if required. (iii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter and insulating materials shall be wiped with a clean cloth. (iv) Checking the contact for wear. Replace if the contact piece has worn out. (v) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts. (vi) Check for rust and wear. (vii) Checking of spring charge mechanism (viii) Visual check for rust and deformation. (ix) Check for loosened bolts and nuts, broken spring washers and snap pins etc. (x) Check for loosened connections, rust, damaged lead wires. (xi) Checking of control circuit & tighten the connections if any. (xii) Check close & trip coil. (xiii) Replacement of Dashpot/shock absorbers . (xiv) Replacement of carbon brush of spring charging motor (xv)Cleaning of porcelain bushing (xvi)Checking of limit switch
Supply only closing coil assembly in replacement 24 v DC for VCB all as specified & directed. Make :- Alstom/schnider/OEM Make/Crompton
Supply only fix tripping coil in replacement 24 V DC for VCB all as specified & directed. Make :- Alstom / English Electric/Schnider /OEM Make / Crompton
Supply only 11 Kv PT HV Back up fuse in replacement cat no 12Kv ABCNA 3.15A 38/10 as per OEM Recomendation / Make: Schnider/Bussmann
Supply only space heaters in replacement of 1 KW, 220Volts along with adjustable thermostat and replacement of burnt wiring of the haeaters complete
Material and labour for painting of LT pannels by duly cleaning the surface from dust and grease and applying one coat of synthetic enamel paint by using spray gun colour as directed by the Eng - in - Charge and lettering the LT pannels with black/white paint using stencils or making lettering by using stickering with minium size of letter to be of 5 Cm all as specified and directed
M&L for cement painting with prepared white ( snow sem ) for transformer /LT /HT poles plinth area/ Copings of any size all as specified ( including scrapping & cleaning with wire brush )
Preparation of surfaces of steel Pole by scraping with emry paper and making free from rust, dust and any foreign material and apply one coat of aluminum paint including letter writing on poles such as Pole No and source point of electric supply with yellow strip radium circumference of poles / mast towers of various heights complete all as specified and directed.
(a) 7.5 Mtr from ground level
(b) 9 Mtr from ground level
Preparation of surfaces RCC Pole of 9 mtr by scraping with emry paper and making free from rust, dust and any foreign material and apply two coats of ceament based weather proof distemper including letter writing on poles such as Pole No and source point of electric supply withyellow strip radium up to 1.5 Mtr height in circumference of poles / mast towers of various heights complete all as specified and directed.
Opening of the side cover of high mast light. Disconnection of the gear assembly of the mast. Cleaning the gear system by using old lub oil, checking its moving components, refilling of gear oil SAE 140 grade 0.5 ltrs
Decarbonising/cleaning complete LT Panel board/ pillar boes of 415/380/230 Volts 3 phase bus bar chamber with electrical connections, complete bus bar from the bus bar chamber, cleaning with CTC and ensure proper decarbonising, refixing the same after applying Backtol Red solution to the bus bar insulator & checking all the connections, tightening the nuts, bolts & thimbles of in-coming/out-going system complete incl replacementof defective rusted bolts & nuts all as specified and directed.
Taking down the old deterioted/damaged rubber mats from the sub stations, supply & lay synthetic insulating rubber matsof size: 2m x 1mx 2.5 mm all as specified & directed
Taking down the LT air circuit breakers of various capacities form 400 amps to 800 amps for repairs, servicing comprising the following and refixing the same, re-orientation and labour for taking down the defective parts and refixing the same spare parts all as specified and directed (a) Checking/repair of mechanical system of ACB. (b) Checking/repair of the manual closing/tripping of breaker.
Taking down the burnt MCCB s from the LT panels/feeder pillar boxes, supply & fix ,test & commissioning of MCCB all as specified & directed.
MCCB 100Amps/16KA, 4 Pole
MCCB 63Amps/16KA, 4 Pole
MCCB 160 Amps/36KA, 4 Pole
MCCB 200 Amps/36KA, 4 Pole
MCCB 250Amps/36KA, 4 Pole
MCCB 350Amps/36KA, 4 Pole
MCCB 400Amps/36KA, 4 Pole
Taking out old street light fittings and supply and fixing of new generation energy saving and environment friendly long life verasalite pressure die- cast aluminium IP 65 road way luminare with high power LEDs of 90 Watts capacity as light source and exclusively designed for poly carbonate cover with electronic drive.along with 1.5mtr bend pipe necessary wiring and clamps for fixing on all as specified and directed
Taking out old street light fittings and supply and fixing of new generation energy saving and environment friendly long life verasalite pressure die- cast aluminium IP 65 road way luminare with high power LEDs of 60 Watts capacity as light source and exclusively designed for poly carbonate cover with electronic drive.along with 1.5mtr bend pipe necessary wiring and clamps for fixing on all as specified and directed
Taking out old and Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete
Taking out old and Supply and fixing post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete
Taking down unserviceable indication lamp and supply, fix and testing indication lamp (LED type) with showing red, yellow and green in colour of 22.5mm dia monitor on LT panel board suitable for 240V AC supply all as specified and directed.
Supply & fix Kiosk box in replacement 140 x 140 x 95mm consisting of 1 No 50 A 4 pole connector and 1 No 32 A TPN taking down the old/corroded junction boxes and fixin with proper clamps and glands all as specified and directed
Supply and fix contactor in replacement, 4 pole, 415V, 40A cap , MCX , 2 NO+2 NC utilsed for heavy duty by taking down the old perished / deteriorated contactor aganist repairs all as specified and directed
M & L for 2 coat of synthetic enamel painting over a coat of red oxide to steel surfaces of cjhain link / mess fencing including preparation of old surface complete all as specified.
M&L for re-painting of HT 11 KV VCB panel consistingnot less than 6 Nos VCB/Bus Coupler of approx size 4 to 6 Sqm with 2 coats of super enamal paint over a coat of red-oxide with sparygun including writing of Inoming/outgoing/Bus cupller Name/numbers in appropriate size of letters as directed and as specified at SP Marg Sub Station.
material and labour for removal of unserviceable service wire of 2 core 4 sqmm and laying of new aluminium service wire of 2 core 4 ss mm from street light fitting to junction box not less than 7 mtr per pole
Material and Labour only for repairing and rectification of faults in 16 / 32 mtr High mast lights by checking the control panel Trailing Cables, timers. contactors and replacing the defective electrical parts, Servicing and greasing to the winch gear wheel mechanisum for electrical and manual operation of the carrier along with replacement of dog clamps of the wire rope and replacment of the existing old unserviceable light fittings with controll gears with new LED light fitiings complete and fixing of the control panel for desired operation all as specified anddirected by the Eng-in-Charge Note :(I) Necessary Digital timers /Power contactors and LED light Fittings shall be measured under Relevant Items. (II) Necessary arrangements for Safety and T&P repairs shall be under taken by contractor
M & L in replacement Energy Efficient LED High MAST Light Fitting of 200 W capacity consisting of high power LEDs with choice of general spread optics to ensure uniform distrubution, IP 66, comprising of clear heat ressistant toughened glass, die caste aluminium construction and maintanance free operatable at 120-270VAC Pf > 0.95 Integral driver Surge protector along with necessary 3 Core 2.5 sqmm copper cable connections up to junction box along with mounting GI bracket all as specified and directed Make: Cat no. LSFO-200-CDL/60 in CG or Cat No. LHEPCZU7J150 in Havells/ Philips/ Bajaj Make: Havells/polycab/finolex for 3 core 2.5 sqmm cable
Sipply and fix in replacement LED Aviation Light Fitting with wattage not less than 10 Watts IP 66, comprising of clear heat ressistant toughened glass, die caste aluminium construction and maintanance free operatable at 120-270VAC Pf > 0.95 Integral driver Surge protector along with necessary 3 Core 2.5 sqmm copper cable connections up to junction box along with mounting GI bracket all as specified and directed
M&L in replacement of Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 120 sqmm to 185 sqmm.
M&L in replacement Cable end jointing kit for 11 KV (Earthed) grade indoor type heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 Sqmm to 300 Sqmm.
Supply and fix in repairs Driver for LED Light fitting 45 Watt all as specifed and directed by Engr in charge. Make:- ENDURA of Havells or equivalent Model of C&S , CG/Bajaj.
Supply and fix in repairs street light timer panel 3 phase 4 pole astronomical prewired with power contactor 32 Amps 3 pole, MCB 40 Amps TPN suitable for street light including all accesories all as specified and directed. Cat part No IHXTS0306A of Make : Havells or Equivalent of L&T/Legrand/Indoasian
M&L for removal green vegetation and dressing around the plinth/PCC hardstanding up to 1.5 mtr of sub stations and 2/4 pole structure etc including disposal of vegitation /material up to 50 mtr distance from the site and levelling/surfacing the ground all as specified and as directed by Engr-in-Charge.
Supply and fixing of MS clamps (duly painted with two coat of aluminium paint over a coat of red oxide primer) for fixing street light fittings/junction boxes/cable pipe on wall/floor /pole including MS nuts, bolts and washers etc as required as per site complete all as directed.
M&L for service cable 6 Sqmm 2 core 1100 volts grade heavy duty cable PVC insulated stranded alumn conductor, served with an inner sheathing of PVC tape and overall PVC sheathed in service connections/perimeter light supply as per site requirement, flat or circular all as required or directed.
Taking down in replacement of LT air circuit breakers micro processor release of various capacities from 800 Amps for repairs, servicing comprising the following and refixing the same, re-orientation and labour for taking down the defective parts and refixing the same spare parts all as specified and directed
Taking down in replacement of LT air circuit breakers micro processor release of various capacities from 1000 Amps for repairs, servicing comprising the following and refixing the same, re-orientation and labour for taking down the defective parts and refixing the same spare parts all as specified and directed
Supplying & installation, testing and commissioning panel outdoor type fabricated 3.15mm thick CRCA sheet compartmentalized with lockable doors, dust and vermin proof, powder coated, single core PVC insulated FRLS copper conductor cables, having suitable mountings for switchgears and accessories and internal control & power wiring with suitable rating PVC insulated FRLS copper conductor, earth terminals numbering etc suitable for operation on 415V 3 phase 50 Hz AC supply with enclosure protection class IP 55 with 400 Amp rating Al bus bar etc complete as required
(a) Incoming :- (i) MCCB 4 pole 415 V breaking cap 36 KA , adjustable typecurrent rating 400 Amps. - 01 No (ii) Digital type Volt meter 0-500 volt - 01 Set. (iii) Digital type Amp meter with CT's - 01 No. (iv) Indicating Lamps : 01 set. (b) Outgoing : (i) MCCB 160 A 4 pole 415 V breaking cap 36 KA ,adjstable type 04 No . (ii) All incoming & outgoing feeders shall be connected by cable through suitable size of gland plate/glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All incoming & outgoing feeders shall be connected by cable through suitable size gland plate/glands. (v) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (vi) multifunctioning meter with communication ports RS 485/232 5 display class-1 - 01 set (vii) Indicating Lamps R Y B , LED type01 set
NOTE :-(i)contractor should provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge.
M/s Adhikari construction co.
Rajindera Enterprises
Vijay Electricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .