| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.3 LAccepted-AOC D1C 47A JANAK PURI NEW DELHI 110058 | NEW DELHI | DELHI | DELHI | 110058 | L1 | Accepted-AOC L1 | |
| 2 | L2₹31.9 L+₹7,360 (0.23%)Rejected-Finance 205 PARSHAV VIHAR PLOT NO 50 1 P EXTN PATPARGANJ DELHI 110092 | DELHI | EAST DELHI | DELHI | 110092 | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹42.7 L+₹10.8 L (34.0%)Rejected-Finance BASEMENT PLOT NO 17 4657 21 ANSARI ROAD CENTRAL DELHI NEW DELHI 110002 | CENTRAL DELHI | DELHI | 110002 | L3 | Rejected-Finance Other than L1 |
Tender Value
₹38 L
EMD Value
₹76,000
Closing Date
1 Mar 2024, 10:00 amClosed
CWE NO 2 DELHI CANTT-10
HQ CWE NO 2 DELHI CANTT-10
REPAIR / MAINT OF HT VCBs AND ACBs INCLUDING TRANSFORMER VOLTAGE STABILIZERS AND ITS ALLIED WORKS AT CAB SECTT (MBC) UNDER GE SOUTH WEST NEW DELHI
2024_MES_641241_1
CWE/SW/TOKEN-37/2023-24
Limited
Electrical and Maintenance Works
Turn-key
330 days
GE SOUTH WEST NEW DELHI
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE SOUTH WEST NEW DELHI
₹76,000
Yes
15 Apr 2024
7 Feb 2024
4 Mar 2024
7 Feb 2024
1 Mar 2024
23 Feb 2024
Amount
M&L for preventive maintenance, servicing and testing of 1500 KVA, Indoor Type, 11/0.433 KV, Dry Type Air Cooled Transformer by disconnection of its HT / LT Bus Bar /Cable connection, opening of doors etc complete cleaning of the inside compartment, core and coils by applying high pressure blower including lead supports, tap changer terminal boards, bushings and other insulated surfaces clean with a dry cloth and all connections must be checked for tightness after cleaning upto the satisfaction of Engr-in-Charge through authorised dealer / service engineer complete all as specified and directed. Conducting the test on core and windings as per standard in presence of Engr-in-Charge and result must be submitted to Engr-in-Charge. Note :- Shutdown must be taken properly and all safety precautions must be adhered for humen safety during entire maint time. Make of Transformer : Voltamp
Supply only in replacement of Transformer Protection / WTI Relay, suitable/Compatible for existing Transformer 1500 KVA, 11/0.433 KV, Dry /Air Cooled type including its control wirirng complete all as specified and directed. Make of Transformer : Voltamp
M&L for preventive maintenance, servicing and testing of 1500 KVA, Outdoor Type, 11/0.433 KV, Oil cooled type Transformer by disconnecting of its both side HT/LT Cable /bus bar connection, tap changer terminal boards, bushings and other insulated surfaces be wiped with a dry cloth and all connections must be checked for tightness after cleaning up to the satisfaction of Engr-in- Charge. through authorised dealer / service engineer complete all as specified and directed. Conducting the test on core and windings as per standard in presence of Engr-in-Charge and result must be submitted to Engr-in-Charge. Note :- Shutdown must be taken properly and all safety precautions must be adhered for humen safety during entire maint time. Transformer Make- CGL
Supply only in replacement of LV bushing with studs and rod including suitable size of nut, bolts and washers, gasket etc for the Transformer of capacity 1500 KVA, 11/0.433 KVA complete all as specified and directed. Make of Transformer : CGL
Supply only in replacement of HV bushing with studs and rod including suitable size of nut, bolts and washers, gasket etc for the Transformer of capacity 1500 KVA, 11/0.433 KVA complete all as specified and directed. Make of Transformer : CGL
Supply only in replacement of silica gel breather assembly suitable/compatible to 1500 KVA, 11/0.433 KV Transformer including any modification required to fix the same complete all as specified and directed.
M&L for collecting the sample of Transformer Oil from 1500 KVA, 11/0.433 KV Transformer and carrying out the Acidity Test according to relevant IS Standard through Approved/Authorised Laboratory and submitting test result to the Engr-in-Charge.
Supply and filling /topping up of transformer oil low viscosity type conforming to IS 335 with di-electric strength not less than 60 KV in to the conservator tank / body tank of the transformer including maintaining and sumitting the test results to Engr-in-charge. Note : (i) New Transformer oil will be filled in the transformer only after filteration and de-hydration of existing transformer oil of the transformer dehydration shall be measured and paid separately. (ii) Transformer oil shall be supplied in sealed container /barrel with relevant test certificate.
Labour & Plant/Machinery for online dehydration of Transformer Oil of 1500 KVA, 11/0.433 KV Transformers. Desired di-electric strength of transformer oil must not be less than 60 KV including maintain and submit the test results of each transformer before and after the dehydration of transformer oil to Engr-in-Charge.
M&L for preparation of existing surface of 1500 KVA, 11/0.433 KV transformers by scrapping down peeled off old paint, grease, oil & cleaning etc and applying one coat of smoke gray paint by spray to complete external body of the transformer complete all as specified and as directed.
M&L to arrest the leakage of transformer oil from LT/HT side bushing, drain valve, conservator tank etc of 1500 KVA, Outdoor Type, 11/0.433 KV, Oil Cooled type Transformer by disconnection of its HT / LT Bus Bar /Cable connection, opening of doors, change of gaskets, nut-bolts and washers etc and rectifying the oil leakages issues and cleaning through dry cloth and all connections must be checked for tightness after cleaning upto the satisfaction of Engr-in-Charge through authorised dealer / service engineer complete all as specified and directed. Note :- Shutdown Must be Taken properly and all safety precautions must be adhered for humen safety during entire Job. Make of Transformer : CGL
Preventive maintenance and servicing of 11 KV HT VCB, MDO Type, Rated Current 1250A, 50 Hz, Indoor type by taking out the breaker trolley of 11 KV HT VCB, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of VCB. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases adjusting electrical/ electronic/mechanical components all as per manufacturer's instruction manual and standard practice including testing, rectifying the fault and calibration of relay of any type/make (e.g. Earth Fault relay / Over current relay/ Master Trip relay etc) of 11 KV VCB Panel. The fault level setting of these relays shall be as per the BSES Pvt Ltd Norms so that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main breakers at BSES Power Feeder. This Job must be carried out through authorised dealer / service engineer including maintain and submit the test report to the entire satisfaction of Engr-in-Charge. Make of VCB : CG as OEM Note :- Major Spares used during servicing will be measured and paid separately under respective item of BOQ.
Supply only in replacement of Closing coil assembly suitable /compatible to existing make and model of 1250A, 11 KV HT VCB complete all as specified and directed.
Supply only in replacement of terminal contact block suitable / compatible to existing Make & Model of 1250A, 11 KV HT VCB complete all as specified and directed.
Preventive maintenance and servicing of 11 KV HT VCB, MDO Type, Rated Current 630/800A, 50 Hz, Indoor type by taking out the breaker trolley of 11 KV HT VCB, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of VCB. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases adjusting electrical/ electronic/mechanical components all as per manufacturer's instruction manual and standard practice including testing, rectifying the fault and calibration of relay of any type/make (e.g. Earth Fault relay / Over current relay/ Master Trip relay etc) of 11 KV VCB Panel. The fault level setting of these relays shall be as per the BSES Pvt Ltd Norms so that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main breakers at BSES Power Feeder. This Job must be carried out through authorised dealer / service engineer including maintain and submit the testing report to the entire satisfaction of Engr-in-Charge. Make of VCB : ABB as OEM Note :- Major Spares used during servicing will be measured and paid separately under respective item of BOQ.
Supply only in replacement of Closing coil assembly suitable /compatible to existing make and model of 630/800A, 11 KV HT VCB complete all as specified and as directed.
Supply only in replacement of Triping coil assembly suitable /compatible to existing make and model of 630/800A, 11 KV HT VCB complete all as specified and as directed.
Supply only in replacement of terminal contact block suitable / compatible to existing Make & Model of 630/800A, 11 KV HT VCB complete all as specified and as directed.
Supply only in replacement of moving Jaw contact block suitable /compatible to existing 630/800A 11 KV HT VCB complete all as specified and as directed.
Supply only in replacement of Vacuum Interrupter Bottle / Pole (4 inch dia), 12 KV rated voltage or suitable /compatibe to existing 630/800A, 11 KV HT VCB complete all as specified and as directed.
Supply only in replacement of limit switch suitable/compatible to existing make & Model of 630/800A, 11KV HT VCB complete all as specified and as directed.
Supply only in replacement of Spring charging motor including assembly and push button etc suitable /compatible to existing 11KV HT VCB of 630/800A capacity complete all as specified and as directed.
Supply only in replacement of TNC Switch suitable /compatible to existing 11KV HT VCB of 630/800A capacity complete all as specified and as directed.
Supply only in replacement control wiring of 1.5 Sqmm single core multi-stranded FRLS copper conductor insulated with heat shrinkable PVC sleeve tagged and secured for indicators / meters including suitable size of copper lugs, PVC cable ducts, galvanised or cadmium plated high tensile nuts, bolts and washers etc complete all as specified and as directed.
S & F in replacement of 11 KV PT unit with PT fuse, Ratio 11000/rt3/110/rt3 Volts (Potential Transformer), Nominal system voltage (KV rms) : 12 KV, frequency 50 Hz, burden 10 VA, Class 1, Voltage Factor : 1.2 Continuous & 1.9 for 8 hrs conforms to IS : 3156 or suitable/ compatible to existing system, termination S1 & S2 shall be clearly marked including disconnecting of 11 KV cable by taking proper shutdown with all safety aspects and reconnecting it after installation of PTs complete all as specified and as directed.
S & F in replacement of 11 KV CT Ratio 100/5 Amp (Current Transformer), Nominal system voltage (KV rms) : 11 KV, frequency 50 Hz, Rated output (VA burden) : 10 VA, Class of accuracy : 0.5S, Resin Cast, Ring Type CT, Termination S1 & S2 shall be clearly marked including all required controll wiring and dismentaling of 11 KV cable by taking proper shutdown with all safety aspects of any size and refixing it after installation of CT's complete all as specified and as directed.
M & L in replacement for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed on Transformer/Sub Stn Fencing/VCB Panels etc with M.S. clamps, bolts and nuts of required size, for 11 KV HT of size 250 X 200mm complete all as specified and as directed.
M & L in replacement of warning board, written as "Don't Switch On Men work on Line" size (300x300) mm and 1.6mm thickness made up of MS Sheet and welded with suitable size of MS angle stand and hanging arrangement also including painting on both side with Post Office Red Colour make as per sample complete all as specified and as directed.
S & F in replacement LED Indicator lamp Red/Yellow/Blue size as per site requirement including suitable size of nuts, bolts including drilling and cutting/welding etc in panel without disturbing to other existing fitments complete all as specified and as directed.
S & F in replacement of old broken cold rolled mild steel Hinges, suitable/compatible to existing 11 KV HT VCB Panel /LT Panel etc including welding and painting to match with existing colour etc complete all as specified and as directed.
Supply & Laying in replacement Synthetic Rubber Insulated Mats 2.5 mm thick for Voltage upto 11KV working pressure conforms to IS 15652-2006 (Superseding IS 5424) suitable for Electrical Shock Safety including applying adhesive to fix before laying the new one complete all as specified and as directed.
M & L for demolition of un-reinforced PCC, floors etc in any position and any description including removal of demolished material atleast 1 Km away from site at Garwage dumping area outside the main gate complete all as specified and as directed.
M & L for Plain Cement Concrete (1:3:6) type C2 (40 mm graded aggregate) for foundation of Pole, Stay Assembly, filling and mass concrete including necessary form work etc complete all as specified and as directed.
Labour for tree branch cutting of high rise trees, overhanging/interferences to the 1500 KVA Transformer /Cooling Tower etc (size of tree branch approx 50 mm to 80 mm dia and 3 to 5 mtr long) without damages to the electrical equipment/machinery including thrown away the same alteast 1 Km away from the Sub Stn Yard at Garwage dumping area outside the main gate complete all as specified and as directed. Note : Suitable arrangement i.e ladder, scafolding or any other working plateform required for climbing on high rise trees for carryout said work is the responsibility of vendor/contractor and the rates are deemed to be included in this quoted rate.
M&L in replacement nuts, bolts and washers made up of GI or Cadmium plated, high tensile as per sample complete all as specified and as directed.
M&L for Fault finding/tracing of 11 KV HT UG XLPE(E) Cable of size 3 Core 120 to 185 Sqmm from one End termination to another End termination and identifying the fault location complete all as specified and as directed. Note :- (i) Disconnection of cable from both side of Transformer/VCB/HT Meter etc and reconnection the same cable after tracing fault/jointing work according to existing system or as directed at site is the responsibility of contactor and cost of the same included in this job. (ii) Job will be measured and paid after fault detection/tracing only.
M & L for STRAIGHT THROUGH Jointing Kit for 11 KV HT (Earthed) grade power cable for OUTDOOR termination heat shrinkable type joint complete with jointing material and accessories suitable for 120 to 185 Sqmm 3 Core (Earthed), XLPE armoured aluminium conductor cable and including taking out/down or opening the cable from VCB's/Transformers after taking proper electric shut down for humen safety and reterminated the same cable according to existing system after cable jointing work complete all as specified and as directed.
M&L for End joint heat shrinkable indoor type suitable for 11 KV HT armoured Cable XLPE (Earthed) multistranded aluminium conductor of size 120 to 185 Sqmm x 3 core and including taking out/down or opening the cable from VCB's/Transformers after taking proper electric shut down for humen safety and reterminated the same cable according to existing system after cable jointing work complete all as specified and as directed.
M&L for High Pot/Pressure Test of 11 KV (E) XLPE HT Power Cable, armoured aluminium conductor cable of size from 120 to 185 Sqmm 3 Core (E) complete all as specified and as directed. Note - (i) Disconnection of cable from both side of Transformer/VCB/HT Meter etc and reconnection the same cable after Hot Pressure test/jointing work according to existing system or as directed at site is the responsibility of contactor and cost of the same included in this job.
Labour for Cleaning carefully Eelectrical Cable Gallery (approx size 30 x 15 Mtrs) by removing mud, foreign mtaterial or other waste acrticles etc and thrown away atleast 1 Km from working site to garwage dumping area outside the main gate complete all as specified and as directed.
Preventive maintenance and servicing of LT ACB, MDO Type, Rated Current 800/1250A, AC, 50 Hz, Indoor type by taking out the LT ACB trolley from Panel, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of ACB. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases & Neutral, adjusting electrical/ electronic/mechanical components all as per manufacturer's instruction manual and standard practice including testing, rectifying the fault and calibration of relay of LT ACB. This Job must be carried out through authorised dealer / service engineer including maintain and submit the test report to the entire satisfaction of Engr-in-Charge. Make of ACB : Legrand Note :- Major Spares used during servicing will be measured and paid separately under respective item of BOQ.
Supply only in replacement Arc Chutes, suitable /compatible to existing LT ACB, MDO Type capacity 800/1250 Amps as per existing make and model complete all as specified and as directed.
Supply only in replacement TNC switch notifying position of ON/OFF/Trip position, suitable/ compatible to existing 800/1250 Amps LT ACB Panel complete all as specified and as directed.
Supply only in replacement Jaw Contacts (Upper and Lower), suitable /compatible to existing LT ACB, MDO Type capacity 800/1250 Amps as per existing make and model complete all as specified and as directed.
Supply only in replacement of operating handle made up of high tensile steel, suitable /compatible to existing LT ACB, MDO Type capacity 800/1250 Amps as per existing make and model complete all as specified and as directed.
S & F in replacement ACB 800 Amps, 4 Pole, 415 V, 50 KA, 50Hz, AC, horizontal manual drawout type, front handle operated with microprocessor based LCD protection release for adjustable over current short circuit and earth fault protection. The braker shall have minimum breaking capacity 50 KA (RMS) symmetrical. The ACB should have Ics=Icu=Icw. The ACB shall confirm to IEC 60947 Part-II, Cat 'B' latest version. Protection release should having battery back-up and tripping details memory. Including link and reqd size of nut & bolt and any type of retrofitting required to fix the breaker in existing slot etc including complete connection & relay setting etc complete all as specified and as directed.
S & F in replacement of 25 Sqmm 4 Core PVC round sheathed flexible Copper multistranded Industrial Power Cable including fixing on Cable Tray/trench/any type of wall/pole etc with suitable size of PVC/GI Saddle, screw etc from UPS Room to ESR Room of Top Floor of MBC Bldg complete all as specified and as directed.
Preventive maintenance and servicing of LT ACB, MDO Type, Rated Current 1250/ 1600A, AC, 50 Hz, Indoor type by taking out the LT ACB trolley from Panel, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of ACB. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases & Neutral, adjusting electrical/ electronic/mechanical components all as per manufacturer's instruction manual and standard practice including testing, rectifying the fault and calibration of relay of LT ACB. This Job must be carried out through authorised dealer / service engineer including maintain and submit the test report complete all as specified and as directed. Make of ACB : L & T Note :- Major Spares used during servicing will be measured and paid separately under respective item of BOQ.
Supply only in replacement of Spring charging motor including assembly and push button etc suitable /compatible to existing LT ACB of 1250/1600A capacity complete all as specified and as directed.
Supply only in replacement of Triping coil assembly suitable /compatible to existing make and model of 1250 /1600A, LT ACB complete all as specified and as directed.
Supply only in replacement of Under Voltage Release (UVR) Coil assembly, suitable /compatible to existing make and model of 1250 /1600A, LT ACB complete all as specified and as directed.
Supply only in replacement earth fault release, suitable / compatible to existing LT ACB MDO type of 1250/1600 Amps capacity as per existing make & model complete all as specified and as directed.
S&F in replacement of Monoblock Pump Set of Capacity 3 HP, 3-Ph, 415 Volts, AC, 50 Hz including fixing /installation at existing place in HT Cable Trench/Main Electrical Panel trench etc including any type of modification required i.e. cutting welding and threading etc as per site requirement complete all as specified and as directed.
Preventive maintenance and servicing of LT ACB, MDO Type, Rated Current 1250/1600A, AC, 50 Hz, Indoor type by taking out the LT ACB trolley from Panel, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of ACB. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases & Neutral, adjusting electrical/ electronic/mechanical components all as per manufacturer's instruction manual and standard practice including testing, rectifying the fault and calibration of relay of LT ACB. This Job must be carried out through authorised dealer / service engineer including maintain and submit the test report complete all as specified and as directed. Make of ACB : C & S Note :- Major Spares used during servicing will be measured and paid separately under respective item of BOQ.
Supply only in replacement of Spring charging motor including assembly and push button etc suitable /compatible to existing LT ACB of 1250/1600A capacity complete all as specified and as directed.
Supply only in replacement of Triping coil assembly suitable /compatible to existing make and model of 1250 /1600A, LT ACB complete all as specified and as directed.
Supply only in replacement of Under Voltage Release (UVR) Coil assembly, suitable /compatible to existing make and model of 1250 /1600A, LT ACB complete all as specified and as directed.
Supply only in replacement earth fault release, suitable / compatible to existing LT ACB MDO type of 1250/1600 Amps capacity as per existing make & model complete all as specified and as directed.
Supply only in replacement of operating handle made up of high tensile steel, suitable /compatible to existing LT ACB, MDO Type capacity 1200/1600 Amps as per existing make and model complete all as specified and as directed.
M & L in replacement for Synthetic insulation mat of size 2m x 1m x 19mm complete all as specified and as directed.
Supply and laying in replacement (laying in ducts/trenches/on Cable trays/ on walls etc with new saddles & clamps etc as per site requirement) including testing & commissioning of 11000 Volts grade HT, multistranded AL Conductor, Electric Power Cable (Heavy Duty), XLPE insulated screened PVC bedded, galvanized steel strip or wire armored of size 120 Sqmm 3 Core (Earthed) complete all as specified and as directed.
All as per item N0. 33.00 here-in-before but of size 185 Sqmm 3 Core (Earthed).
M&L for Cutting of existing road/PCC/RCC/Hard standing etc (size 0.45 x 0.45) Mtr (WxD) for laying of cable/pipe including making good the disturbed surface to match with the adjoining surfaces with PCC (1:2:4), type B2 complete all as specified and as directed.
Supply and laying in replacement G.I pipe light grade with all fittings required for protection of under ground cable of size 80 mm dia complete all as specified and as directed.
S & F Wire mesh Cable Tray Hot Dipped Galvanized size 105 (h) X 600 (w) mm, Trays should comply Standard EN ISO 14 61: at least 550 h of SST. The deflection of cable tray must be not more than 1/200th of the distance between two supports and tested in accordance with the atandard IEC 61537, Wire cable trays must be designed with an optimum span of 1.5 m, taking into account the maximum carrying capacity authorised by the manufacturer including all standard wall mounting accessories e.g. Mounting Bracket (Horizontal & Vertical Both), bends, Fastners, kitastar, nut, bolts and washers etc at suitable intervals complete all as specified and directed. It shall be manufactured with a longitudinal 'T- welded' safety edge. complete all as specified and as directed.
S & F in replacement of MS sheet of 10 mm thick, chequered type including cut to shape as required at site to cover the gaps between bus bar riser in ESR Rooms at every floor of MBC bldg and 2 coat of anticorrosive black paint on complete MS Sheet on both side complete all as specified and as directed.
Preventive Maintenance and Checkup of Bus Bar Risers at 'E' 'D' & 'F' Block Electrical Switch Rooms by checking loose connection, earth leakage, Votage, nut bolts and washers etc complete all as specified and directed at site by Engr-in-Charge through authorised Dealer /Service Engineer and submit the test result. complete all as specified and as directed.
Supply only 11 KV HT Insulation tape roll of size 38 mm width and 9.15 Mtr Long for day to day use during complaints.
Preventive Maintenance and Servicing of Servo Voltage Stabilizer, Oil Cooled & Indoor type of Capacity 100 KVA, 3-phase, 415 Volts, 50 Hz, AC Supply by disconnecting carefully its electric cable connection on primary & secondary side, Checking both side bushing, bus bar connections, opening top cover of the Voltage Stabilizer by unscrewing its nuts, bolts, washers etc, rectify the oil leakages issues, if noticed any, during servicing and re-fixing the top cover of transformer according to previous system. Servicing of the Servo Voltage Stabilizer must be done through authorised dealer / service engineer including maintain and submit the inspection and test records of each Servo Voltage Stabilizer to the Engr-in-Charge. Make of Stabilizer : Chime Electronics (Sinetrac) Note 1. :- Inspection of Servo Voltage Stabilizer shall comrpising :- (a) Checking of all clamps, nuts, bolts including core bolts & cover fixing bolts etc. (b) Checking all brazings, joints, tap heads, gaskets and connection joints etc. (c) Checking all terminations / connections inside Voltage Stabilizer. (d) Checking moving and fixed contacts for contact wear and connection to winding etc. (e) Conducting the test on dimmer/windings as per relavent IS like, short circuit, IR Value and Voltage regulation test etc. in presence of Engr-in-Charge. Note 2. : (a) Major Spares found faulty during service, will be replaced and paid separately under respective item of BOQ. (b) The rates quoted against the item is deemed to be included for cost of Labour for replacement of Faulty spare parts & lifting/transporting to civil workshop and vice-versa from Machine Room at 11th Floor of MBC Bldg by using stairs manually/mechanically, if required as per site requirement without any extra cost to the department.
Supply only in Synchronous motor single phase, 10 Kg torque motor, 1-ph, 230V, suitable/compatible to existing 100 KVA Valtage stabilizer as per existing make /model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
Supply only High/Low Voltage cut off PCB Card, suitable / compatible to existing 100 KVA stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
Supply only RC Network for motor 10 Kg torque, suitable/compatible to existing 100 KVA Voltage stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
Supply only I.C. Electronic Control Card, suitable /compatible to existing 100 KVA voltage stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
Supply only Micro switch, suitable / Compatible to existing 100 KVA Voltage stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
Supply only Carbon brush, suitable / Compatible to existing 100 KVA Voltage stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
Supply only Neon Indicator, suitable /compatible to existing 100 KVA voltage stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
Supply only Voltmeter analogue type, suitable /Compatible to existing 100 KVA Voltage Stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
Supply only Ammeter with suitable size of CT, suitable for 100 KVA Voltage Stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
Supply only complete set of Gear of 10 Kg Torque Motor, suitable /Compatible to existing 100 KVA Voltage Stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
Supply only in control wiring of 1.5 Sqmm single core multi-stranded FRLS copper conductor insulated with heat shrinkable PVC sleeve tagged and secured for indicators / meters/Voltage Stabilizers etc including suitable size of copper lugs, PVC cable ducts, galvanised or cadmium plated high tensile nuts, bolts and washers etc complete all as specified and as directed.
All as per item No 41.00 here-in-before but of capacity 50 KVA . Make : Chime Electronics (Sinetrac).
Supply only in replacement of I.C. Electronic Control Card, suitable /compatible to existing 50 KVA voltage stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
Supply only Synchronous motor single phase, 6 Kg torque motor, 1-ph, 230 V, suitable/compatible to existing 50 KVA Valtage stabilizer as per existing make /model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
Supply only High/Low Voltage cut off PCB Card, suitable / compatible to existing 50 KVA stabilizer as per existing make and model (Chime Electronics (Sinetrac)) complete all as specified and as directed.
All as per item No-41.00 here-in-before but of capacity 25 KVA, 1-Phase, 220 Volts . Make : Chime Electronics (Sinetrac).
Supply and filling /topping up of voltage stabilizer oil with di-electric strength not less than 50 KV in to the body tank of the voltage stabilizer installed in Machine Room at 11th Floor of MBC Bldg including maintain & submit the test result complete all as specified and as directed. Note : (i) New Stabilizer oil will be filled in the Voltage Stabilizer only after filteration and de-hydration of existing oil of the Voltage Stabilizer, filteration/dehydration shall be measured and paid separately. (ii) Voltage Stabilizer oil shall be supplied in sealed container /barrel with test result and test certificate etc.
M & L in replacement of complete Earthing with galvanized steel earth plate electrode 600 X 600 X 6.3 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.50 m deep below normal ground level in any type of soil strata, connected to galvanized iron strip 32 x 6mm by means of bolts, nuts and washers of galvanised iron or steel all as shown in earth plate No 3 of MES schedule 1991 Part – I connected to machinery/equipment for transformer, LT Panel, Feeder Pillars, Sub Feeder Pillars etc. as required including necessary excavation and earth work including Pit Cover with lifting handle and Earth lead and 20mm Dia GI watering pipe medium grade, Funnel, wiremesh, etc. complete all as specified and as directed.
M&L in replacement of GI Earth Strip of size 32 x 6 mm as earth electrode for interconnection the various Eqpts / Machinery/Panel etc with earthing electrode including fixing on any type of wall with suitable size of GI Saddle /clamps, nut, bolts and washers etc complete all as specified and as directed.
M & L for dehydration/filteration of voltage stabilizer oil at site by taking proper shutdown of various capacity of Voltages Stabilizers installed in Machine Room at 11th Floor of MBC Bldg, desired di-electric strength of oil not less then 50 KV complete all as directed and specified and also submit the test result before and after the de-hydration of the stabilizer oil.
Preventive Maintenance & repair of Battery Bank Panel, Batteries, Fuse & Control wiring, suitable /Compatible to existing 11 KV HT VCB Main Panel complete all as specified and direcetd. Note : Cost of transportation from work site to Civil workshop and vice-versa deemed to be included in the quoted rate.
S & F in replacement of PVC insulated 50 Sqmm FRLS single core bright annealed bare copper conductor heavy duty multistranded cable 1100 Volts grade with suitable size of copper lugs complete all as specified and as directed.
M&L for preparation of existing surface of Voltage stabilizer of 100 KVA, Oil Cooled type by srapping down /peeled off old paint, loose scale grease, Lubricants etc by abrasive paper and applying one coat of smoke gray paint by spray complete all as specified and as directed.
Preventive Maintenance and Servicing of On Line UPS of 60 KVA Capacity, 3-phase, 415 Volts, 50 Hz by disconnecting carefully its electric cable connection from In/Out side, Checking, opening top cover of the On Line UPS by unscrewing its nuts, bolts, washers etc, rectify the fault if noticed any, during servicing and re-fixing the top cover of UPS according to previous system including testing of 12V, 120 Ah maintemance free batteries after applying full load and duration of bakeup. Servicing of the 60 KVA On Line UPS must be done through authorised dealer / service engineer including maintain and submit the inspection and test records complete all as specified and as directed. Make : Vertiv Note 1. :- Inspection of On Line UPS shall be comrpising :- (a) Checking of all clamps, nuts, bolts including core bolts & cover fixing bolts etc. (b) Checking all brazings, joints, tap heads, gaskets and connection joints etc. (c) Checking all terminations / connections inside UPS. (d) Conducting the test as per relavent mfg Instr manual in presence of Engr-in-Charge. Note 2. : (a) Major Spares found faulty during service, will be replaced and paid separately under respective item of BOQ. (b) The rates quoted against the item is deemed to be included for cost of Labour for replacement of Faulty spare parts & lifting/transporting to civil workshop and vice-versa from ESR, 1st Floor of MBC Bldg by using stairs manually/mechanically, if required as per site requirement without any extra cost to the department.
Supply only Cooling fan, 230 Volts (NISIKI, NISI2038HB2 Model), 19/16 Watt including connecting wiring, suitable /Compatible to existing 60 KVA On Line UPS as per existing make, size and model etc complete all as specified and as directed.
Supply and fixing in repair of PCB Card, Fuse & Control wiring, suitable /Compatible to existing 60 KVA On Line UPS as per existing make & model etc complete all as specified and as directed. Note : Cost of transportation from work site to Civil workshop and vice-versa deemed to be included in the quoted rate.
Reboot and re-installation of Vertiv Software after replacement of faulty parts, suitable /Compatible to existing 60 KVA On Line UPS as per existing make & model etc complete all as specified and as directed.
Supply and fixing in repair of Digital Display Screen of 60 KVA On Line UPS of Vertiv Make by OEM or authorised service dealer complete all as specified and as directed. Note : Cost of transportation from work site to Civil workshop and vice-versa deemed to be included in the quoted rate.
Attending breakdown /inspection of 1500 KVA, 11/0.433 KV, Step down, Oil Cooled type Transformer by authorised dealer / service engineer and rectify the any type of fault and replace any spares related to breakdown complete all as specified and as directed.. Make of Transformer : CG Ltd
Supply and laying in replacement (laying in ducts/trenches/on Cable trays/ on walls etc with new saddles & clamps etc as per site requirement) including testing & commissioning of 1100 Volts grade LT, multistranded AL Conductor, Electric Power Cable (Heavy Duty), XLPE insulated, galvanized steel strip or wire armored of size 150 Sqmm 3.5 Core complete all as specified and as directed.
Attending breakdown /inspection of 1500 KVA, 11/0.433 KV, Step down, Air Cooled /Dry type Transformer by authorised dealer / service engineer and rectify the any type of fault and replace any spares related to breakdown complete all as specified and as directed. Make of Transformer : Voltamp
Attending breakdown /inspection of 11KV/12KV HT VCB, MDO Type, 630 to 1250 Amps by authorised dealer / service engineer and rectify the any type of fault and replace any spares related to breakdown complete all as specified and as directed. Make of VCB : CG /ABB
Attending breakdown /inspection of Servo Voltage Stablizer, Oil Cooled Type, Indoor type of capacity 25 KVA to 100 KVA, 3-phase, 415 Volts by authorised dealer / service engineer and rectify the any type of fault and replace any spares related to breakdown complete all as specified and as directed. Make of Voltage Stabilizer : Chime Electronics (Sinetrac)
M&L in replacement of GI earthing with New Chemical earthing with copper bond pipe of dia 76 mm & 3 Mtr long including excavation in any type of soil starta. Filled with highly conductive compound which Increase the life of earthing electrode. Composition of chemical filled in electrode water solubility, acid solubility, Grain size 100 mesh, along with BFC Compound non toxic, non reactive, non explosive and non corrosive, longer life easy to maintain less space consistent results including earthing pit and chamber cover complete all as specified and as directed.
M&L in replacement of old GI Strip with New Copper strip of size 20 x 3.15 mm as earth electrode for interconnection the various Eqpts / Machinery/Panel etc with earthing electrode including fixing on any type of wall with suitable size of Cu Saddle /clamps, nut, bolts and washers etc complete all as specified and as directed.
M&L of MS Angle of any size fabrication of cable rack and any other shape of fabrication work including cut to shape including welding as required at site in Main Electrical sub Stn including two coat of anticorrosive black paint over a coat of red oxide primer on complete MS structure on both side etc complete all as specified and as directed.
M&L in replacement of old GI Strip with New Copper strip of size 32 x 6 mm as earth electrode for interconnection the various Eqpts / Machinery/Panel etc with earthing electrode including fixing on any type of wall with suitable size of Cu Saddle /clamps, nut, bolts and washers etc complete all as specified and as directed.
S & F in replacement of cylindrical panel locks of suitable size or as per sample including drilling, cutting and welding etc in panel sheets without disturbing to other existing fitments complete all as specified and as directed.
SANJEEV ENTERPRISES
VINAY ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .