Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 421 4TH FLOOR TOWER A 2 SPAZE ITECH PARK SECTOR 49 SOHNA ROAD GURGAON | GURUGRAM | HARYANA | 122001 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance 306 MANISHA BUILDING 75 76 NEHRU PLACE NEW DELHI 110019 | Admitted-Finance |
| 4 | Admitted-Finance F 18 ANSAL COMPLEX OPP JWALA HARI MARKET PASCHIM VIHAR NEW DELHI 110063 | NEW DELHI | WEST DELHI | DELHI | 110063 | Admitted-Finance |
| 5 | Admitted-Finance C 2488 SUSHANT LOK PHASE 1 GURGAON 122001 HARYANA | GURUGRAM | HARYANA | 122001 | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹15 L
Closing Date
13 Mar 2023, 6:00 pmClosed
Chief Engineer
HQ Chief Engineer Delhi Zone, Delhi Cantt-110010
CONSTRUCTION OF DEFICIENT MD ACCN FOR SOs AND CIVILIANS AT NATIONAL CAPITAL REGION (NCR), SECTOR-23, NOIDA UNDER AGE (I) COAST GUARD, NOIDA
2023_MES_573790_2
CA No CEDZ/TOKEN-61 of 2022
Open Tender
Civil Works
760 days
Delhi Cantt
MES contractor enlisted in MES under class SS cat a i having deposited Standing Security of Rs 1500000.00 with department. Contractors not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category
9 documents required · 9 mandatory
₹3,000
AGE (I) Coast Guard Noida
₹15 L
Yes
31 Mar 2023
20 Feb 2023
15 Mar 2023
20 Feb 2023
13 Mar 2023
6 Mar 2023
20 Feb 2023 - 4 Mar 2023
Amount
INTERNAL WATER SUPPLY S&F CP brass pressure return valve (PRV) 25x25mm, self operated control device, maintaining a desired outlet pressure, any colour high pressure screwed both ends for iron/CPVC pipe and fixed with washer as per manufacturer's instruction complete all as specified and directed.
INTERNAL ELECTRIC SUPPLY S & F LED bracket light fitting 1x 12 W, 220V,AC LED Lamp decorative wall mounting fixture made up of Aluminum body including LED 12 watt with System level efficacy of the Luminary is > 90 lm/W , Power Factor >0.95, driver with Voltage range 150-270V, Temperature range 0 to 50 Deg, Driver efficiency >85%, THD<10%, CRI>80, Color Temperature-6500K, Surge protection of 4.0 KV, including connecting up with necessary PVC sheathed 3 core 1.5 Sqmm copper conductor flexible wire fixed complete all as specified and directed.
S & F vertical distribution board, double door, 6 way, VTPN class IP-54, suitable for fixing of MCBs, Isolators etc, confirming As per IEC 61439-3 ,Suitable for Flush Mounting and Surface Mounting, With 200 A Copper Busbar ,With Neutral bar, Earthbar and Cable ties for Cable management,Fully shrouded Neutral bars, Prefitted masking sheet including connection of cable with proper size of lugs complete all as specified and as directed.
S & F vertical distribution board, double door, 4 way, VTPN class IP-54, suitable for fixing of MCBs, Isolators etc, confirming As per IEC 61439-3 ,Suitable for Flush Mounting and Surface Mounting, With 200 A Copper Busbar ,With Neutral bar, Earthbar and Cable ties for Cable management,Fully shrouded Neutral bars, Prefitted masking sheet including connection of cable with proper size of lugs complete all as specified and as directed.
Supply and fix CABLOFIL wire meshed Hot dip Galvanized cable tray 54 mm (h) x 100 mm (w) complete with nuts bolts washers (GI) and all accessories (for mounting/fixing on building rising mains) and supporting the cable tray system, along with vertical bends complete all as specified and directed..
SEWAGE DISPOSAL M & L for steel fibre reinforeced concrete (SFRC) man hole covers medium duty circular of size 600mm dia and 80mm thick with MS handle complete all as specified and directed.
M&L 150mm bore of RCC hume pipe class NP-3 drain pipe laid and jointed with collars and tested complete all as specified and directed.
M&L concrete bed to drain pipe including packing under and haunching against the sides of pipe in cement concrete 1:3:6, type C-2 (using 40mm graded stone aggregate) after they are laid tested in bore pipe 250mm complete all as specified and directed.
ROAD, PATH AND CULVERT S&F road safety 800mm dia convex polycarbonate acrylic unbreakable mirror fixed over and incl 2100mm ht above GL of 75mm dia SS pipe above road surface fixed in ground with PCC 1:2:4 min 450mm deep in ground complete all as specified and directed.
S&F Sign boards made of 3mm thick ACP sheet area exc 1.1 sqm but not exc 1.8 sqm info printed or pasted with high intensity retro-reflective tape computer cut in specified colour & font as directed by Engr-in-charge mounted over all around frame and legs of 50mm SS pipe of max top ht 2100mm above GL complete fixed in ground with PCC 1:2:4 min 450mm deep. complete all as specified and directed.
RAIN WATER HARVESTING SYSTEM M&L for drilling 250mm dia bore hales by DTH cum rotatory method at any depth below the ground level in any kind of rock/ soil upto 40m depth including disposal of surplus soil to a distance not exceeding 50m complete all as specified & directed.
M&Lfor Self perforated unplasticized PVC pipes 250mm dia of pressure rating 10 Kg/Sqm, fixed complete to wall or ceiling or in floors complete all as specified and directed.
EXTERNAL WATER SUPPLY Supply,laying,jointing,testing pipe ductile Iron 100 mm dia ,pressure pipe with spigot and socket ends ,Class “K-7” confirming to IS:8329/2000 suitable for push on rubber gasket jointing with centrifugally applied inside cement mortor lining with portable slag cement as per IS : 455: 1989 and external metallic zinc coating with finshing layer of bituminous coating including EPDM rubber joint complete all as specified and directed.
S & F DI fitting for spigot nand socket/flanged ends pipe like Bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs,connecting pieces one end flanged and other end socket or spigot and bell mouth pieces one end flanged other end tapring as bell mouth suitable for 100 mm dia pipe complete all as specified and directed.
Supply and fix Valve, Gun-metal, globe or gate valves,with iron wheel head, screwed both ends for iron pipe conforming to IS 778/1980, 80 mm bore Pipe complete including connecting all as specified and directed.
Supply,install,testing and commisioning of openwell submersible pump set electric driven 3 phase 415 Volts 50 Hz 2900 RPM having head not less than 60 meter and discharge not less than 7 LPS having cast iron cashing, cast iron impeller,stainless steel C40 shaft,Bronze shaft sleeve complete including provision of necessary foundation of pump set including MS pipe medium grade from delievery side of pump to discharge header with connected flanges,nut bolts,gasket etc. including necessary foundation work and other associated work complete with provision of following all as specified and directed:- (a) Common base plate for motor and pump set-01 No. (b) Suitable gun metal strainer as directed and recommended by manufaturer. (c) MS pipe medium grade from delievery side of pump to discharge header with connected flanges,nut bolts,gasket etc. (d) Suitable size copper cable from motor to starter. (e) Suitable size Non return valve recommended by manufaturer. (f) Suitable size cast iron foot valve recommended by manufaturer. (g) Suitable size sluice velve on discharge side recommended by manufaturer.
Supply, installing, testing and commissioning factory made, floor mounted indoor type LT panel board, cubicle type, suitable for 415 Volts, 3 Phase, 4 wire, 50 Hz, AC supply system, and tested at CPRI, having 200 Amps capacity copper bus bar for phase and 200 Amps copper bus bar capacity for neutral , colour coded for each phase and neutral, insulated on epoxy type insulators. The bottom of the outer shell contains a detachable plate having provn for entry of cable of adequate size with glands, The panel shall be dust and vermin proof, IP-65 class protection and made 2.00 mm thick CRCA MS sheet, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, both side opening type, provision of connecting earth strip from 2 sides, including internal wiring with PVC insulated solid copper conductor cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 sqmm) including grouting of panel 45 cm above ground level by providing 90 cm long angle iron frame of size 40x40x6 mm, welded on all the four corners, embedded in PCC 1:2:4 using 20 mm stone aggregate upto 30 cm above ground level complete all as specified and directed including the following accessories:-
a) MCCB 3 pole motor protection circuit breaker 415 Volts 16 KA 100 Amps with extendable terminal -01 Nos (In coming)
(b) Provn of fully automatic star delta starter with 63 amps TP power contactors ,NO/NC Aux contact , O/L relay & SD timer etc for 15 HP submersible pumpset -02 Nos.
(d) Start/Stop push buttons - 02 Nos each
(e) Phase indication -RYB & Motor ON/ OFF/Trip indicating lamps LED type - 09 Nos.
(f) Control fuse with link- -03 Nos
(h) Phase sequence corrector switch 3 pole, on load type, open execution, 100 Amps - 01 No.
(j) Single phasing preventer- 01 No
(k) MCB of desired rating -04 Nos & connectors as per requmt
(l) One no. danger notice plate
Supply,install,testing and commisioning of Heavy duty Chemical Dosing system plunger type suitable to inject solution upto 25 LPH working pressure 10 kg /cm2 comprising dosing pump coupled with three phase electric motor of capacity 0.5 HP,1440 RPM assembly with agitator in one motor , agitator with SS sweep blade duly FRP coated, FRP tank 150 ltrs capacity, complete unit mounted on heavy duty MS fabricated frame duly anticorrosive paint complete with Chemical grade PVC NRV. along with Control panel for Dosing Pump suitable for Model SSAPS/CDSPT/25 made of powder coated MS fabricated box consisting of LED indicator, digital Volt meter, Amp meter, single phase preventor, High voltage low voltage protection.. Make : SatyaSai Aqua Pura Services Model No:- SSAPS/CDSPT/25 or equivalent of make as approved by E in C till last date of bid submission.
EXTERNAL ELECTRIC SUPPLY Supply, installing, testing and commissioning factory made, floor mounted indoor type LT panel board, cubicle type, suitable for 415 Volts, 3 Phase, 4 wire, 50 Hz, AC supply system, and tested at CPRI, having 600 Amps capacity Alluminium bus bar for phase and 600 Amps alluminium bus bar capacity for neutral , colour coded for each phase and neutral, insulated on epoxy type insulators. The bottom of the outer shell contains a detachable plate having provn for entry of cable of adequate size with glands, The panel shall be dust and vermin proof, IP-65 class protection and made 2.00 mm thick CRCA MS sheet, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, both side opening type,provision of connecting earth strip from 2 sides, including internal wiring with PVC insulated solid copper conductor cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 sqmm) including grouting of panel 45 cm above ground level by providing 90 cm long angle iron frame of size 40x40x6 mm, welded on all the four corners, embedded in pcc 1:2:4 using 20 mm stone aggregate upto 30 cm above ground level complete all as specified and directed including the following accessories:-
a) MCCB 4 pole 35 KA 400 Amps with thermal magnetic type -01 No (In coming)
b) MCCB 4 pole 25 KA 200 Amps with thermal magnetic type -01 No (Out coming)
c) MCCB 4 pole 25 KA 100 Amps with thermal magnetic type -04 Nos. (Out coming)
d) MCCB 4 pole 16 KA 63 Amps with thermal magnetic type -01 No (Out coming)
e) MCB 4 pole 10 KA 32 Amps C Curve -01 Nos. (Out coming)
f) MCB 4 pole 10 KA 16 Amps C Curve -02 Nos. (Out coming)
g ) Multifunction meter with Modbus RS485 port & class 0.5 accuracy with Suitable CT. - 1 set
h) Indicating lamp Red,yellow,green - 01 Set
j) Protection MCB 6 Amps Single pole- 03 Nos.
k) CT 400/5 A- 03 Nos.
l) One no. danger notice plate
Supply, installing, testing and commissioning factory made, floor mounted indoor type LT panel board, cubicle type, suitable for 415 Volts, 3 Phase, 4 wire, 50 Hz, AC supply system, and tested at CPRI, having 150 Amps capacity alluminium bus bar for phase and 150 Amps alluminium bus bar capacity for neutral , colour coded for each phase and neutral, insulated on epoxy type insulators. The bottom of the outer shell contains a detachable plate having provn for entry of cable of adequate size with glands, The panel shall be dust and vermin proof, IP-65 class protection and made 2.00 mm thick CRCA MS sheet, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, both side opening type, ,provision of connecting earth strip from 2 sides,including internal wiring with PVC insulated solid copper conductor cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 sqmm) including grouting of panel 45 cm above ground level by providing 90 cm long angle iron frame of size 40x40x6 mm, welded on all the four corners, embedded in pcc 1:2:4 using 20 mm stone aggregate upto 30 cm above ground level complete all as specified and directed including the following accessories:-
a) MCCB 4 pole 25 KA 100 Amps wiyh thermal magnetic type (In coming)-01 No.
b) MCB 4 pole 10 KA 32 Amps C Curve - 04 Nos
c) MCB 4 pole 10 KA 16 Amps C Curve -02 Nos
d Multifunction meter with Modbus RS485 port & class 0.5 accuracy with Suitable CT. - 1 set
e) Indicating lamp Red,yellow,green - 01 Set
f) Protection MCB 6 Amps Single pole- 03 Nos.
g) CT 100/5 A- 03 Nos.
h) One no. danger notice plate
Supply, installation, testing & commissioning of package type/unitised 11kV / 433 V Outdoor sub-station ,630KVA made from G. I. enclosure complete as required conforming to IEC 62271-202 only and relevant IS specifications including K-10 Temperature Class as applicable for the rating, Internal Arc of 21 KA/1 Sec. IAC AB on 1:2:4 PCC foundation of suitable size extending 500 mm all around the outdoor enclosure and 1000 mm height (above ground level) complete with suitable sizes of GI Pipes for incoming/outgoing cables/earthing strips etc. and consisting of following complete as required. Angle iron frame of size 40x40x5mm NS all along the corner of the foundation CSS shall be from OEMs only . Licensed System Integrators of approved OEM are not allowed to supply . Package substation will have the following equipment :- HT SWITCHGEAR 11kV 630Amps 21KA/3 sec. Non-Extensible Ring Main Unit Compact switchgear consisting of 2 nos. fixed motorized Vacuum Circuit Breaker Module and 2 nos. fixed morotized Load break switch module in SF6 insulated stainless steel enclosure with series trip, self powered microprocessor based numerical over current and earth fault relay protection. HT RMU shall preferably have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works. Interconnection between HT Switchgear and primary of transformer shall be done through 1C x 3R x 95 sq.mm Aluminium XLPE cable. - 1 No. Vacuum Interrupter,RMU,LT Switchgear and CSS Enciosure shall be of same make to ensure life cycle optimization. Microprocessor based IDMT Relay for Circuit Breakers - Self Powered along with series trip coil (Modbus RS485 complaint)
Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder. SF6 Gas pressure indicator. Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO Protection CT shall be minimum 40/1A ,2.5VA ,5P10. - 3 nos. All modules of the RMU shall be suitable for cable termination of 3C x 300 sq.mm Al XLPE Cable, incoming cable termination is included within the scope of work - 1 Set TRANSFORMER 630 KVA 11KV/433V DYN-11 Oil type, hermetically sealed energy efficiency level-2 transformer (BEE Star Rated-2) with corrugated wall, without conservator, type of design & Top Bushings for HT & LT with Off load tap switch of rating +5% to -5% @2.5%. Temp Rise - Oil/Winding 40/45 Deg cel. Losses (As per IS-1180 amended up to date) Max Losses @ 50% Load 1745W and Max Losses @ 100% Load 4850 KW and Impedance of 4.5% (Subject to IS Tolerance (as per IS1180-2014) The transformer shall be confirming to IS: 2026 and IS: 1180(part-I). amended up to date. - One No. Winding Temperature Indicator with Alarm and trip Contact LT PANEL LVS PANEL 1000 AMPS 4 pole Aluminium BUSBAR (100% FOR PHASES AND 100% FOR NEUTRAL) - CURRENT DENSITY OF Aluminum as 1 A/sq.mm. ; LT panel made up of 1.5/2 mm thick CRCA sheet
INCOMER FROM TRANSFORMER 1000 Amps 433V 4P 50Hz 50KA Fixed Manual Type Air Circuit Breaker (ACB) - 01 No. Multifunction meter with Modbus RS485 port & class 0.5 accuracy with Suitable CT. - 1 set Outgoing MCCB 400A, 36KA, 4 Pole- 4 nos. 150KVAR APFC panel with minimum 12 steps as per following tentive steps ( 5KVARX4, 10KVARX4, 20KVAR X3, 30KVARX1) All Civil works such as PCC/RCC foundation, Plateform, Filling trench and pedestal etc as per CSS manufacturer's recomandation are included in scope of work. OUTDOOR ENCLOSURE Outdoor type encloser of 1.5 mm (For non load bearing members) & 2.0 mm (For load bearing members) thickness having modular construction of Galvanised Sheet Steel in suitable design for better heat dissipation and providing robust construction. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP 23 degree of protection for transformer compartment. The enclosure exterior shall be painted with epoxy based powder paint (colour RAL 7032). Each compartment will be provided with the door and pad locking arrangement. The design of the enclosure should be type tested for suitablly handling any arcing inside the compartment for providing better safety to the operator. The compartment illumination lamp with door operated switch shall be provided for each compartment. Vacuum Interrupter,RMU,LT Switchgear, Multifunction meter and CSS Enciosure shall be of same make to ensure life cycle optimization.
Supply and fix CABLOFIL wire meshed Hot dip Galvanized cable tray 105 mm (h) x 200 mm (w) complete with nuts bolts washers (GI) and all accessories for mounting on wall and supporting the cable tray system, along with vertical bends complete all as specified and directed..
FIRE FIGHTING E/M WORKS Supply fixing ,tesing ,commisioning of first aid rubber hose reel of 20 mm dia and 30 meter length mounted on and including drum with swing type bracket for housing to withstand 10 kg/Sqcm working pressure fitted with alloy nozzle complete all as specified and directed.conforming to IS 5132 all as specified and directed.
Supply and fix branch pipe with nozzle confirming to IS: 903 suitable for instanteneous connection to hose coupling etc as required.
Supply,laying,cutting to required length ,jointing,testing and commisioning MS Pipe of size 150 mm nominal bore heavy grade as per IS-1239 along with all fittings /special such as bends,tee colars ,reducer etc including welding flanges heavy duty on both ends of pipe and fittings for making joints,complete with nut,bolthigh tensile washer and rubber gasket of superior quality laid on trenches complete all as specified and directed.
Supply,laying,cutting to required length ,jointing,testing and commisioning MS Pipe of size 80 mm nominal bore heavy grade as per IS-1239 along with all fittings /special such as bends,tee colars ,reducer etc including welding flanges heavy duty on both ends of pipe and fittings for making joints,complete with nut,bolthigh tensile washer and rubber gasket of superior quality laid on trenches complete all as specified and directed.
Supply , fixing ,testing and commisioning of single headed gun metal ISI marked oblique pattern hydrant landing valve with 80 mm dia flanged inlet and 63 mm dia instanteneous type female outlet complate with gun metal cap and chain twist release lug and all other accesories as per IS 5290 complete all as specified and directed.
Supply and Install Jockey pump horizontal end suction centrifugal type Confirming to IS- 12469: 1988 with CI casing , bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for automatic operation with nonover loading power characteristics for frequent start / stop operations for 440 V , 3 phase, 50 Hz having head not less than 88 m and discharge not less than 180 LPM all as specified and directed.
Supply, Install,testing and commisioning of Fire pump diesel engine driven horizontal end suction, centrifugal type confirming to IS- 12469 1988 with CI casing , bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for continuous operation with 'range of operation' 0 % to 150 % of rated capacity for 440 V , 3 phase, 50 Hz AC supply having head not less than 70 m and discharge not less than 2280 LPM discharge all as specified and directed.
Supply , installation ,testing and commisioning of electric driven ,high pressure centrifugal fire hydrant pump set for automatic operation comprising the following (i) Horizontal split cashing centrifugal pump suitable for 415 Volts ± 6% 3 phase 50 Hz AC supply The installtion shall be complete with flexible coupling guard as required ,the pump shall have CI Casing , bronze impeller and Stainless steel (SS 304) shaft mounted on heavy duty bearingswith mechanical seal ,capable for delievering 136.8 Cum/Hr at head not less than 88 meter. (ii) Squirrel cage induction motor TEFC type suitable for operation on 415 volts 3 phase 50 Hz AC supply for the above pump with synchronous speed of 3000 RPM confirming to IP-55 protection and class F insulation. (iii) Common base plate for pump and motor. (iv) Suitable cement concrete foundation duly plastered with anti vibration pad . (v) Suction and delievery pipe of suitable size and length. (vi) Connection with PVC cable single core multi stranded copper conductor of suitable size as per manufacturer recommendation from fire pump panel to motor pump set complete.
Supply and fixing ,testing and commisioning ERW/MS pipe (heavy) confirming to IS-1239/IS 3589 with required accesories and pipe fiting like flanges,elbow,tee,elbow,bend,nipple coupling cap,reducers etc andradiography limited to 10% and shall be provided anti corrosive treatment with two coats of hot coal tar and two wraps of hot reinforced fraglan tissues as per IS 10221-1982 and as per hydrostatic testing etc complete all as specified and directed for following sizes:- MS flanged pipe 80mm NB heavy duty for multi storied building duly painted with 2 coats of synthetic enamel paint over coat of zinc chromate primer all as specified and directed. (a) 250 mm dia (As per IS;3589 AND THICKNESS 6.35 MM)
(b) 200 mm dia (As per IS;3589 AND THICKNESS 6.35 MM)
(c) 65 mm dia (Nominal bore)
(d) 50 mm dia (Nominal bore)
Providing , fabrication and fixing single leaf door with frame onle for all internal fire hydrants fabricated from MS section , welded construction ,having glazed panel with reinforced glass,internal locking arrangement stove enamelled FIRE HOSE written on front , suitable to house 2 nos. 15 m length of canvas hose reel laong with coupling 1 no. branch pipe and 1 no. first aid fire hose reel along with the landing valve all complete size 1300x2100 mm (approx) complete all as specified and directed.
Supply and fix air release valve Along with ball valve of length 1.20 meter long dia 150 mm complete including fixing,testing suitable for 150 mm PIPE .
Providing protection of pipe with polythene based coating and wraping system as per manufacturers recommendation including earth work excavation and refilling etc for size upto 100 mm pipe complete in all respects.
Providing and fixing wall mounted signages consisting of Zinc sulphate Photo Luminecent coating on acrylic sheet of size 15cmx30 cm and shall consist of signage on half side and arrow on other half. Signage shall be any of the following : Exit/Staircase/Extinguisher Location/Manual call box/Hydarant etc complete all as specified and directed.all as specified and directed.
Providing and fixing of ISI marked (IS:940) portable fire extinguisher Chemical Fire,water (gas pressure) type capacity 9 Ltrs with gun metal cap and nozzle complete with initial fill and wall suspension bracket complete all as specified and directed.
Providing and fixing of ISI marked (IS 2878) portable fire extinguisher carbondioxide type flat base including valves,discharge hose not less than 10 mm dia 1 meter long and complete in all respect including initial fill with CO2 gas confirming to IS;307 1966 filling to filling ratio not more than 0.667 and wall suspension bracket of capacity 4.5 Kg.
Providing and fixing of ISI marked (IS:2878) portable fire extinguisher Mono Ammunium Phosphate (ABC)type of stored pressure type with discharge tube and perssure gauge wall suspension type capacity 5 Kg
Providing and fixing MS structural work fabricated from standard sections i.e. round,solid angle ,slotted angles,chanells including cuttinh to size drilling,welding,fixing and welded to insert plates in RCC structure members all as speccified and directed.
Providing and fixing 25 mm dia inspection and testing assembly with ball valve (3 nos. ) ,gun metal sight glass, by pass valve and connected to drain pipe complete all as specified and directed.
Supply and fix 10 watt wall mount CD Speaker all as specified and directed.
Supply and fix 100 watt amplifier all as specified and directed.
Supply and fix microphone set all as specified and directed.
Supply and fix control consule all as specified and directed.
Supply and fix loudspeaker cable of size 24/0.2 mm all as specified and directed.
DG SET Supply and install, testing and commissioning of diesel Engine driven generating set of capacity 125 KVA 3 phase, 4 wire, 415 V, 1500 RPM AC power supply with power factor 0.8 coupled directly to alternator mounted on a common base plate complete with integral acoustic enclosures (should have salient features) modular bolted construction, & pure polyester based coating to ensure long life in all weather conditions & for outdoor application / installation, integrated design thereby facilitating / easy handling. The design of integral acoustic enclosure should be approved by National Physical laboratory as per central pollution control board (CPCB) latest regulation /norms (NO x+HC<4.0, CO < 3.5 ,PM < 0.2& smoke limit < 0.7 ) with fuel tank, battery & standard accessories, tools & spares as provided by manufacturer complete all as specified and directed. with the following specifications:
(A) ENGINE- Water cooled diesel engine of at 1500 RPM capacity to match the 125 KVA alternator under NTP conditions with provision of 10 % over load for 1 hour in every 12 hours running confirming to BS 5514/ IS 10001/ 10002 the Engine shall consist of the following :- (i) Fly wheel with starter ring (ii) Flexible coupling with guard (iii) Cooling fan (iv) Radiator with guard and water pump engine mounted (v) Dynamo of suitable capacity (vi) Air cleaner heavy duty dry (vii) Fuel injection pump (viii) Radiator fan ( Blower type ) with guard (ix) Pneumatic governor (x) Fuel filter (Mounted) (xi) Lubricating oil filters ( mounted) (xii) 12 volts self regulating alternator belt driven by engine
(xiii) Exhaust silencer heavy duty residential type
(xiv) Corrosion resistor /scale inhibitor
(xv) Starter 12 volts DC
(xvi) Lubricating oil cooler
(xvii) Lubricating oil pump (Gear type )
(xviii) Turbo charger
(xix) Exhaust piping shall be insulated with asbestos rope duly cladded with aluminium sheet.
(xx) Instrument panel complete with :-
(a) Auto manual Starting switch with key
(b) Lubricating oil temperature gauge
(c) Lubricating oil pressure gauge
(d) Water temperature gauge
(e) Battery charging ammeter
(f) Bettery charging indicating lamp
(g) Hour meter with RPM indicator
(h) Safety control against high temperature of water.
(j) Safety control against low lubricating oil pressure .
(k) Over speed stop with double driven adopter .
(B) BRUSH LESS ALTERNATOR
(i) Alternator coupled to engine indigenous make through a flexible coupling mounted on sturdy steel fabricated base frame suitable for mounting on a permanent foundation brushless alternator shall be confirming to BS -2613 or relevant of IS-4722/ IS 13364
(ii) Type ;- Self excited self regulated with automatic voltage regulator .
(iii) Rating :- 125 KVA at 0.8 PF lagging 4 pole horizontal at NTP condition .
(iv) Speed;- 1500 RPM
(v) System :- 415 V +/- 2.5 % AC 3 phase 4 wire 50 Hz.
(vi) Connection :- 4 wire star connected .
(vii) Enclosure ;- Screen protected drip proof .
(viii) Ventilation :- Self ventilated.
(ix) Insulation :- Insulation class H
( c) CONTROL PANEL
The control panel with aluminium bas bar, bottom entry and exit of cable, current transformer, set of control fuses, Multifunctional Meter, it should display time and date, Volts, Frequency, Current, KW, KWH, PF, RPM, Cumulative Run Hours, Oil Pressure, Coolant Temp, Charging current (DC Amp Meter). Emergency off, factory made floor mounted, totally enclosed, epoxy powder coated suitable for 125 KVA DG Set including all necessary operating controlled devices as stated above and MCCBs as out going with protection fuse for panel instruments duly wired with flexible copper conductor cable and cable connection with lugs/thimbles complete as per latest IS/BS and all as specified and directed.
(D) ONE SET OF ACCESSORIES COMPRISING OF :-
(a) Fuel tank -one No. fabricated with 3 mm thick MS sheet with necessary mild steel structure for mounting the tank higher than the DG set) with piping. Capacity of tank shall be to hold diesel sufficient for 16 hours running at full load, with following features
(i) Level indicator.
(ii) drain plug .
(iii) MS class 'C' piping for inlet from pump to tank to engine.
(iv) Fuel strainer.
(v) Air vent.
(b) FUEL PUMP;-
Electrical operated fuel pump for filling diesel in the tank of adequate capacity with inlet connection to the tank with 5 meter flexible hose pipe heavy duty for suction of diesel from barrel.
(c) Sealed maintenance free Battery :-
Heavy duty battery 24 plates 12 v 180 AH (1 Nos) connected to the system fully charged including lead and bty terminal's complete .
M & L for Fabrication, Installing, Testing & Commissioning of Indoor type 2.00 mm thick CRCA MS sheet, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, both side opening type automatic mains failure (AMF) control including auto by pass panel, suitable for 125 KVA DG Set 3 Phase 415 volts 50 Hz having 400 Amps copper bus bar for phase and 200 Amps copper bus bar for neutral complete with relays, timers, set of CTs for metering & protection and energy analyzer to indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH, KVAH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF panel to diesel engine and elsewhere if required, all complete and inter locking, connecting the existing power cables including the following:- a) 200 Amps. 3 Pole thermal magnetic setting -02 Nos. (b) Power contactor 200 Amps 3 pole-02 Nos. (c) Onload change over switch 200 Apms bypass-02 Nos. (d) Under voltage relay 415 Volts AC for main and DG set_ 02 Nos. (e) AC Timer 230 volts 02 NO+02 NC-01 no. (f) DC Timer 12/24 Volts-01 No. (g) Engine start relay 12/24 volts- 01 No. (h) Control MCB SP SP 6 Amps 230 Volts-09 Nos. (j) Control MCB SP SP 16 Amps 230 Volts-02 Nos.
LIFT Design, Supply ,install, tesing and commissioning of eletrically operated passenger lift of capacity 8 passenger lift (544 kgs Capacity) in the existing lift well, 1.5 m/s speed with automatic GIEN micro stroke button control, micoprocessor based controller, simplex full collective control suitable for 3 phase, 50 HZ 415 volts AC supply independent operation with AC variable voltage variable frequency(AC VVVF) control closed loop with power saving regenerative drive with suitable motor and gear unit to serve ground plus Thirteen upper floors i.e with 14 stops and 14 landings with or with out attendent suitable for synchronised operation automatic power operated centre opening sliding stainless steel door with Moon Rock finish of 16 gauge (not less than 1.5 mm) with infra-red sensors all along the height for car door with automatic rescue/leveling device (ARD) (with + or -5 mm) with suitable dry maintenance free batteries,haul position digital indicators in car and all landing with call indicating lights etc including necessary joists and beams for mounting machine in the machine room including all civil works required in connection with erection of lifts complete all as specified. The lift shall be provided with and including the following : (Size of well available is 2100 mm x 1800 mm ) Type of Drive: Regenerated AC variable voltage and variable frequency drive along with converter unit.The regenerated power shall be used to charge the battery of UPS,ARD and emergency lights. Type of Machine: Gearless permanent magnet and directly coupled to horizontal traction machine. Note 1: Counter weight shall be of cast iron block
(a) Fire man switch. (b) Automatic rescue device (A.R.D) during power failure including manual operation provision with suitable capacity of battery designed for running the lift with full load. (c) Seperate Battery operated emergency light (LED ceiling fitting ), alarm (speaker for emrgency alarm system to be fixed) and stop buttion in car with rechargeable arrangement for battery .( This system shall be seperate from ARD batteries.)
(d) Integrated Roof RL20 Stainless Steel Ring Lighting LED (e) One sleek circular PVC heavy duty fan in false ceiling. (f) Aluminium chequered plate (3mm thick) as flooring joint in chequered plate should not more than one and top covering with 20 mm Recess & Granite Stone.Car skirting material: Brushed stainless SUS304 (g) Non stop button /independent operation (h) Over load warning indicator both audio and visual type with tripping system having relays etc (overload protection/tripping system). (j) Front landing door of stainless steel moon rock finish operations with a minimum time of 10 seconds and up to a maximum time of 30 seconds. (k) Car size shall be in confirmity with IS -3534-1976 and body to be stainless steel of 16 gauge moon rock finish with stainless steel hand rail 38mm hairline finish (l) Limit switches as specified in IS
(m) Mirror of 6mm thickness of suitable size. (n) Hand rail 38mm hairline finish. (o) Opening with see through glass of 8 mm thick 200 x 600 mm size in all the doors (Car/Landing doors) (p) Specification plate with complete details. (q) Continuous earthing for machine and equipments. (r) Steel Wire rope of adequate size as per relevent IS and as per manufacturer specification
(s) Other standard fixtures and fittings like guide rails, sheaves, counter weights with guards ,buffers, gear unit brakes, control panel ,locks ,governor ,car operational panel,power, control and trailing cables complete. (t) Car operating Panel 1 Full Height Dark grey brushed StSt Tempering glass Segmented LCD display Round flush mounted KDS96 – stylish touch panel Landing Signalization-Tempered glass Segmented LCD display Flush Mounted Tempered glass Round flush mounted KDS96- stylish touch panel (u) Main drives and control shall be of latest , high effective and low power consumption. (v) Suitable phase reversal relay shall be provided on the controller to protect lift/equipment against phase reversal, phase failure and low voltage. (w) Over load and floor announcement audio and visual arrangement.
Features Common to Specifications 1. Digital Direction & Position Indicator in Car and at all landings 2. Emergency Alarm at the main landing 3. Facia Plate 4. 2 Phase Fireman Drive, Fireman’s switch at the main landing. (In case Fireman Drive is activated the elevator will come to the main landing and open the door). 5. Advanced door operation (Ensures smooth opening & closing of the doors at adjustable door speed) 6. Additional Pressure Sensing Device 7. Load Weighing Device (Audio visual over load indicator in the car for better safety) 8. Full Height Infra-Red Curtain 9. Pit Ladder 10. Emergency Light, Intercom and Alarm with Maintenance Free Rechargeable Battery operation.
11. +6% To-10% Volt. Fluctuation Withstand Capacity 12. Over speed governor (Electro-mechanical device that prevents free fall in case the elevator is travelling at speed more than 10% of the rated speed in downward direction) 13. Automatic Rescue Device (To rescue the passengers in case of emergency- this device will bring the car to the nearest floor automatically and will open the doors). 14. Steel Ropes 15. Special Car Door Lock 16. Fire Rated Doors-2 hour. 17. Automatic Brake Testing. 18. PMS MOTOR with ECO Disk Drive 19. Linear Motor Technology & Close Loop Arrangement. 20. 24x7 Connected Services. 21. Car & Landing Doors –Moon rock finish
Design, Supply ,install, tesing and commissioning of eletrically operated passenger lift of capacity 13 passenger lift (884 kgs Capacity) in the existing lift well, 1.5 m/s speed with automatic GIEN micro stroke button control, micoprocessor based controller, simplex full collective control suitable for 3 phase, 50 HZ 415 volts AC supply independent operation with AC variable voltage variable frequency(AC VVVF) control closed loop with power saving regenerative drive with suitable motor and gear unit to serve ground plus thirteen upper floors i.e with 14 stops and 14 landings with or with out attendent suitable for synchronised operation automatic power operated centre opening sliding stainless steel door with Moon rock finish of 16 gauge (not less than 1.5 mm) with infra-red sensors all along the height for car door with automatic rescue/leveling device (ARD) (with + or -5 mm) with suitable dry maintenance free batteries,haul position digital indicators in car and all landing with call indicating lights etc including necessary joists and beams for mounting machine in the machine room including all civil works required in connection with erection of lifts complete all as specified. The lift shall be provided with and including the following : (Size of well available is 2100 mm x 1800 mm ) Type of Drive: Regenerated AC variable voltage and variable frequency drive along with converter unit.The regenerated power shall be used to charge the battery of UPS,ARD and emergency lights. Type of Machine: Gearless permanent magnet and directly coupled to horizontal traction machine. Note 1: Counter weight shall be of cast iron block.
(a) Fire man switch. (b) Automatic rescue device (A.R.D) during power failure including manual operation provision with suitable capacity of battery designed for running the lift with full load. (c) Seperate Battery operated emergency light (LED ceiling fitting ), alarm (speaker for emrgency alarm system to be fixed) and stop buttion in car with rechargeable arrangement for battery .( This system shall be seperate from ARD batteries.)
(d) Integrated Roof RL20 Stainless Steel Ring Lighting LED (e) One sleek circular PVC heavy duty fan in false ceiling. (f) Aluminium chequered plate (3mm thick) as flooring joint in chequered plate should not more than one and top covering with 20 mm Recess & Granite Stone.Car skirting material: Brushed stainless SUS304 (g) Non stop button /independent operation (h) Over load warning indicator both audio and visual type with tripping system having relays etc (overload protection/tripping system). (j) Front landing door of stainless steel moon rock finish operations with a minimum time of 10 seconds and up to a maximum time of 30 seconds. (k) Car size shall be in confirmity with IS -3534-1976 and body to be stainless steel of 16 gauge moon rock finish with stainless steel hand rail 38mm hairline finish (l) Limit switches as specified in IS
(m) Mirror of 6mm thickness of suitable size. (n) Hand rail 38mm hairline finish. (o) Opening with see through glass of 8 mm thick 200 x 600 mm size in all the doors (Car/Landing doors) (p) Specification plate with complete details. (q) Continuous earthing for machine and equipments. (r) Steel Wire rope of adequate size as per relevent IS and as per manufacturer specification
(s) Other standard fixtures and fittings like guide rails, sheaves, counter weights with guards ,buffers, gear unit brakes, control panel ,locks ,governor ,car operational panel,power, control and trailing cables complete. (t) Car operating Panel 1 Full Height Dark grey brushed StSt Tempering glass Segmented LCD display Round flush mounted KDS96 – stylish touch panel Landing Signalization-Tempered glass Segmented LCD display Flush Mounted Tempered glass Round flush mounted KDS96- stylish touch panel (u) Main drives and control shall be of latest , high effective and low power consumption. (v) Suitable phase reversal relay shall be provided on the controller to protect lift/equipment against phase reversal, phase failure and low voltage. (w) Over load and floor announcement audio and visual arrangement.
Features Common to Specifications 1. Digital Direction & Position Indicator in Car and at all landings 2. Emergency Alarm at the main landing 3. Facia Plate 4. 2 Phase Fireman Drive, Fireman’s switch at the main landing. (In case Fireman Drive is activated the elevator will come to the main landing and open the door). 5. Advanced door operation (Ensures smooth opening & closing of the doors at adjustable door speed) 6. Additional Pressure Sensing Device 7. Load Weighing Device (Audio visual over load indicator in the car for better safety) 8. Full Height Infra-Red Curtain 9. Pit Ladder 10. Emergency Light, Intercom and Alarm with Maintenance Free Rechargeable Battery operation.
11. +6% To-10% Volt. Fluctuation Withstand Capacity 12. Over speed governor (Electro-mechanical device that prevents free fall in case the elevator is travelling at speed more than 10% of the rated speed in downward direction) 13. Automatic Rescue Device (To rescue the passengers in case of emergency- this device will bring the car to the nearest floor automatically and will open the doors). 14. Steel Ropes 15. Special Car Door Lock 16. Fire Rated Doors-2 hour. 17. Automatic Brake Testing. 18. PMS MOTOR with ECO Disk Drive 19. Linear Motor Technology & Close Loop Arrangement. 20. 24x7 Connected Services. 21. Car & Landing Doors – Moon Rock Finish
TV CABLE S&F TV cable co axial complete all as specified and directed.
S&F TV sockets any type complete all as specified and directed.
ELECTRIC METER Supply and Installation of RF /Sim based Smart Single Phase Meter with the following specifications: • AC Single Phase Two Wire, Tamper Proof, Static Meter of Class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt 865-867 MHz Radio Frequency communication facility with self healing Mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry. • Meter Should support sending the the following data to the software : 15/30 min instantaneous data for voltage, current, power factor, power, cumulative energy and frequency, monthly billing survey for Cumulative Energy and Max Demand • Meter should have connect / disconnect functionality operable from prepaid billing software • The meter should support open communication protocol DLMS with the software Note: (a It would be possible to run the meter in both prepaid and postpaid mode (b) The meters would carry 5 year warranty.
Supply and Installation of IP-67 protection Data Concentrator Units (DCU) compatible for remote Automatic Metering Infrastructure (AMI) solution and capable of communicating with the smart energy Meter in the corresponding frequency band and with the data server through GPRS/Ethernet. It would have internal memory to store data of at least 200 modules. It would have inbuilt battery back-up. It would have IP-67 protection. It would support auto discovery of the meters and self healing mechanism for the breaks in the RF network.
Supply and Installation of single phase meter (Dummy meter in case of poor/No signal) as repeaters.
Supply and Configuration of the Web based Software with following modules: (i) Meter Data Management Module The meter data management module would be responsible for collecting the data from the concentrator and make the data available to the billing system. The meter data management system would capture and provide the following data: (a) 30 min instantaneous data from all the meters for seven parameters – Cumulative Energy, Cumulative Apparent Energy (as applicable), Power, Current, Voltage, Power Factor and Frequency (b) Monthly billing survey data for cum energy and max demand (ii) Postpaid /Prepaid Billing Module The billing module would collect the data from the meter data management module, calculate the energy consumption, calculate billing determinant and make energy data / billing data available to admin and end users. The billing module would include functionalities for tariff setup, bill format setup, bill adjustment, occupation billing and vacation billing. It would allow postpaid and prepaid functionality as required. (iii) Occupation and Vacation Module The system would support occupation / vacation and billing reports. the software would be collecting data from DCU. The software would provide access to staff as well as the occupant for the data. (iv) Web site: There would be a dedicated website for the AGE and BSO team to view all the data and information. The designated users in MES would have the admin access to the application. The MES staff would also have the access of the key information on an android mobiles app (for admin use). (v) Customer Portal The system would include a customer portal for the resident /occupant to log in and view their own energy / billing data. There would be android and iOS mobile apps for the user to monitor its own data and balance on regular basis.
(vi) Energy Accounting Module The system would include features of energy accounting. The system would be able to account for total energy block wise, facility wise and would also allow calculations of unaccounted energy in case total energy meter is also available. (vii) Communication Module The system would provide communication of energy data and bills via print, email and sms methods. (viii) Meter Master Data The system would support meter master data repository. The system would support meter replacement process. (ix) Excel Export The system would support export of metering and billing data in excel format. (x) Customer Care Module - the software would include a customer care module where the user would be log in any complaints. The service provider would monitor the complaints and carry out the necessary activities for the complaints resolution. (xi) Meter Installation Module - The software would include an app based meter installation module where the meter installation or changes can be captured on the app itself and the readings may be demonstrated to the user if required on the app itself. (xii) Activities Communication - The software support communication of the various activities such as occupation, vacation, meter change. personal detail change etc. with the user as well as the department on email.
STP (SEWAGE TREATMENT PLANT) Designing, Supply, installation, testing and commssioning of package type Sewage Treatment Plant of capacity 100 KLD including all civil works, treated water tank, electrical and mechanical works for STP having following input and output parameters: (a) Inlet Parameter (i) BOD - 200 mg/ltr (ii) COD - 450 mg/ltr (iii) TSS - 250-300 mg/ltr (iv) Oil & Grease - 20-30 mg/ltr (v) PH - 6 to 9 (vi) Coliform - 1 x 10 6 MPN/100ML
(vii) Temp- 20 Degree Centigrade (viii) TKN - 45 (b) outlet parameter of sewage treated water are as follows : (i) BOD < 10 mg/ltr (ii) COD < 50 mg/ltr (iii) TSS < 10 mg/ltr (iv) Oil & Grease < 10 mg/ltr (v) PH - 6.5 to 8.5 (vi) Coliform - 1000 MPN/100ML (vii) Residual Chlorine - > 0.5 mg/ltr (viii). TKN < 10 mg/Ltrs (ix). Phosphours < 1 mg/Ltrs Notes :- All Design parameters and specifications are as per Annexure "I" of Particular Specification.
Supply , install , testing and commissioing Non clog vertical submersible pumps Duty (Flow and head) 140 LPM, 12 Mtr head of 3 Phase, 415 V, Max solid size 35 MM with chrome steel impeller , including Supply, installation HDPE discharge Pipe upto header Appx 10 Mtr.of suitable dia as per OEM recoomendation and SS 306 lifting chain 10 Mtr length, water proof Control and power cables Appx 10 Mtr including NRV & Sluice valves as recommended by OEM, Control and power panel for pump as supplied by OEM, , Necessary Support ,clamps and rubber gaskets and SS Nut bolts as suggested by OEM all as specified and directed PUMP CASING The radially split casing is provided with delivery nozzle cast integral with it. Suction is axial and delivery nozzle is central and horizontal .Specially designed semi-concentric casing results in reduced radial thrust and ensures vibration-free performance. Wide volute passage ensures non-clogging operation of the pump. IMPELLER Impellers are of non-clog type which allow smooth passage of solids .Impellers are with single or multi vanes in semi-open, enclosed, or free flow designs to cater to wide applications. SHAFT The high tensile steel shaft accurately machined and ground is supported by two ball bearings in the motor above the impeller. Shaft is designed to transmit the power without undue vibrations and deflections. The shaft is common for pump and motor of monoblock design.
MECHANICAL SEALS Two mechanical seals in tandem arrangement are provided to ensure no ingress of water or sewage in motor. BEARINGS Bearings are grease lubricated and sealed for life, hence maintenance free. DRIVE Motor is dry type submersible and cooled by liquid being handled. Motors are air tested for leakfree operation. Degree of protection for motor is IP68 as per IS:2147 Class of insulation : F Voltage : 415V 10% Frequency : 50 Hz. 5% CABLE A specially designed cable, 1.1 kV grade having annealed tinned copper conductor, insulated with Electron Beam Irradiated crosslinked elastomeric compound (compatible for continuous operation at 1200 C) cores laid up with a proof cotton binder tape and sheathed overall with Electron Beam Irradiated Cross-linked HD HOFR elastomeric compound and generally conforming to IS 9968 Part l. The cable with this unique combination of insulating and sheathing material offers best resistance to acidic or alkaline sewage medium and to the effluent gases coming out of the sump. The cable is more flexible than PVC cable making coiling and handling easier and light in weight compared to PVC cable of the same size.
FLANGES Standard drilling to IS 6392 table 15. Out door type CONTROL PANEL Control panel consists of suitable capacity of starter as per OEM recommendation , MCCB,Multifunction digital meter and safety features. Safety features are: Single phasing prevention Overload relays Moisture sensing unit for detecting ingress of moisture or water into oil chamber. Liquid level controllers to avoid dry running. Under voltage / Reverse phasing
Supplying and laying of CPVC pipes of outer dia 50 mm SDR 11 & Plain CPVC SDR 11 fittings (like Elbow, Tee, Socket, Reducer, Bushing, Step over bends, End cap, End Plugs etc), laid in trenches complete all as specified
Supplying and laying of CPVC pipes (Red Colour) of outer dia 50 mm SDR 11 & Plain CPVC SDR 11 fittings (like Elbow, Tee, Socket, Reducer, Bushing, Step over bends, End cap, End Plugs etc), fixed on wall/laid on floors(fixed by clamps whose thickness not less than 3 mm and clamping will be provided after 1.5 meter on pipe) complete all as specified
Supply,install,testing and commisioning of openwell submersible pump set electric driven 3 phase 415 Volts 50 Hz 2900 RPM having head not less than 60 meter and discharge not less than 18 Cum/Hr having cast iron cashing, cast iron impeller,stainless steel C40 shaft, Bronze shaft sleeve complete including provision of necessary foundation of pump set including CPVC pipe heavy grade from delievery side of pump to discharge header with connected flanges,nut bolts,gasket etc. including necessary foundation work and other associated work complete with provision of following all as specified and directed:- (a) Common base plate for motor and pump set-01 No. (b) Suitable gun metal strainer as directed and recommended by manufaturer. (c) CPVC pipe heavy grade from delievery side of pump to discharge header with connected flanges,nut bolts,gasket etc. (d) Suitable size copper cable from motor to starter. (e) Suitable size Non return valve recommended by manufaturer. (f) Suitable size cast iron foot valve recommended by manufaturer. (g) Suitable size sluica valve on discarge side recommended by manufaturer.
Supply and fix CABLOFIL wire meshed Hot dip Galvanized cable tray 54 mm (h) x 100 mm (w) complete with nuts bolts washers (GI) and all accessories (for mounting/fixing on building rising mains) and supporting the cable tray system, along with vertical bends complete all as specified and directed..
Supply, installation, testing and commissioning of ultra sonic level sensor with following specifications: Rust proff, Maintenance free suitable for up to 6 meter water level depth of OHTS/ U/G sump, with dead band of less than 0.6meter, IP67 protection, accuracy of 0.25% of F.S. and 4-20mA current output, No of wires: 4 wire, Beam angle: less than 7.5 degree, Capable for working in ambient temperature of 0 degree Centigrade to 75 degree Centigrade, non-condensing at 25 degree Centigrade and humidity up to 95% with response time of less than 1 sec with 230VAC to 24VDC, 50Hz power supply, Non display type, in built temperaure & voltage variation compensation, vertical type mounting on top of OHTS/ Sump, suitable for measuring water/ waste water in Sump /OHT, with all connections and fixing including clamp. nut-bolt etc complete all as specified and as directed. (Scope of work include all accesories required for the correct operation of the sensor)
Supply, Installation Testing & Commissioning of indoor type PLC ( Programmable Logic Controller) /RTU (Remote terminal Unit) based Automation, Protection Panel for lift well/sewage pumping installation with feature of Dual mode communication i.e. wireless Dual SIM Card based communication and wireless Radio Frequency based communication (The module should be programmed to automatically toggle between the two communication mode based on the actual signal strength available), suitable for control and monitoring of upto 4 Nos pumps with electrical parameters, 1No Energy meter, 1 No electromagnetic flow meter with totalizer & 1 No ultrasonic level sensor The panel shall be 500 x 800x 300 MM front opening type as per MES enclosure guideline as per given specification:- (1) The Panel should be capable of performing following functions in Liftwell all as specified and directed:- (a) time & level based operation of lift well. (b) online monitoring of electromagnetic flow meter parameters & energy consumption pumps in desired format
c) Automatic Operation of Motor Actuated Butterfly Valves /DO sensors! compressors, etc (if required) (d) Automatic duty cycle based operations of Pumps (e) Auto Change Over In Case of Pump Failure (1) Single Phasing Prevention, phase sequence corrector, voltage unbalancing protection (g) Manual Mode Operationof pumps (all connected sub systems & operations in Sewage treatment plant) from the PLC/ RTU based Control Panel. (i) the panel shall have 01 No. PLC/ RTU with following specifications:- (a). Discrete Input Logic (b). Should have suitable No. of Discrete Input and Discrete Output:- Relay/Transistor (c). Protocol supported: isolated serial/ TCP link: Modbus master/slave and DNP 3.0
ARBORICULTURE Supply of fine sand at site including royalty and carriage for preparing compost at site (sand shall be brought at site and stacked for measurment before incorporating in the work) complete all as specified and directed.
Supply only sweet/good earth at site including royalty and carriage for preparing compost for pits/required for planting trees and shrubs etc (sweet/good earth free from objectionable extraneous matter, toxic material and termites shall be brought at site and stacked for measurment before incorporating in the work 20% of computed volume shall be reduced for loose stacking complete all as specified and directed.
Supply only manure at site inculding royalty and carriage for prepaing compost at site (manure shalll be brought at site and stacked for measurement before incorporating in the work 8% computed volume shall be reduced for loose stacking complete all as specified and directed.
Preparing compost pits of size 600 x 600 x 600 mm by excavation in ordinary soil, applying and termite treatment, planting tree & refilling of the pit with compost (manure, sand & sweet earth) mixed in ratio (1:1:4) breaking colds, ramming and flooding with water filling with more compost if necessary and fine dressing including removal of rubbish unserviceable materials & surplus soil to a distance n.exe100mtr. ATT shall be uniform of 200 gms neem cake mixed 2 ml per litre in the first watering of 20 liters per pit complete all as specified and directed.
Preparing compost pits of size 900 x 900 x 900 by excavation in ordinary soil , applying and termite treatment, planting the tree & refilling of pit with compost (manure sand & sweet earth mixed in ratio 1:1:4) breaking clods, ramming and flooding with water with more compost if necessary and fine dressing including removal of rubbish unserviceble lnaterials and surplus soil to a distance n.exe 100mtr ATT shall be in form of 200gms neem cake mixed with every Cum of compost followed by Dussban or equivalent applied at 2 ml Pee litre in the first watering of 20 litrs per pits complete all as specified and directed.
Supply & Planting following trees/ shrubs/ plants/ hedge in location as shown on drawing and as specified & directed by Engineer-in-Charge including preparing of composit pit of required size(1.20m x1.20m x1.20m or 0.45m x0.45m 0.45m) as per required size in any type of soil applying anti termite treatment, refilling the pit with compost (manure, sand & sweet earth mixed in ratio of 1:1:4) breaking clods, ramming, & flooding with water filling fine dressing & removal of rubbish, unserviceable materials & surplus earth complete all as specified & directed by Engr-in Charge. NOTE-1. ATT shall be in form of 200gm neem cake mixed with one cum of compost followed by Dursban applied @2ml per litre in first watering of 30 litre per pit, NOTE-2. Rates for following items includes supply and application of manure / sweet earth ,ATT chemicals, sand, fertilisers etc complete all as specified and directed.. :-
Dwarf Gulmohar (i) Spacing @ 10 to 15 feet (ii) Height : 5 feet, Girth : 8 to 12 cm, Pit Size :(1.20m x 1.20m ) complete all as specified and directed.
Bougainvilla (i) Spacing @ 08 to 10 feet (ii) Height : 5 feet, Girth : 8 to 12 cm, Pit Size :(1.20m x 1.20m ) complete all as specified and directed.
Champa (i) Spacing @ 08 to 10 feet (ii) Height : 5 feet,Girth : 02 to 04 cm, Pit Siz :(0.45m x 0.45m) complete all as specified and directed.
Guava tree (i) Spacing @ 08 to 10 feet (ii) Height : 5 feet, Girth : 8 to 12 cm, Pit Siz :(1.20m x 1.20m ) complete all as specified and directed.
Silver Oak (i) Spacing @ 08 to 10 feet (ii) Height : 5 feet, Girth : 8 to 12 cm, Pit Siz :(1.20m x 1.20m ) complete all as specified and directed.
Ashoka Pandula tree (i) Spacing @ 10 to 15 feet (ii) Height : 5 feet, Girth : 8 to 12 cm, Pit Siz :(0.45m x 0.45m ) complete all as specified and directed.
Bottal brush (i) Spacing @ 05 to 10 feet (ii) Height : 5 feet, Girth : 8 to 12 cm, Pit Siz :(0.45m x 0.45m ) complete all as specified and directed.
FERTILIZERS :- (i) Neem Khali @2Kg for 10 Sqm, (ii) Seomeal @1Kg for 10 Sqm (iii) D.A.(16.42) @ 0.15Kg for 10 Sqm, (iv) BHC dust 10% or lindance dust @ 0.15Kg for 10 Sqm, (v) Fine dressing a top soil after mixing the manure and fertilizers to requisited slope, (vi) watering the area for fine dressing of soil after one week till the soil get water upto root zone depth, (viii) Plantation of grass @ 10cm on both way by dibbing root method.
Description of Work / Item(s)
Amount
Total amount of REVISED Sch 'A' Section I (Building work) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section I)
Total amount of REVISED Sch 'A' Section II (Internal Water Supply) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section II)
Total amount of REVISED Sch 'A' Section III (Internal Electric Supply) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section III)
Total amount of Sch 'A' Section IV (Area Drainage) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section IV)
Total amount of REVISED Sch 'A' Section V (Sewage Disposal) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section V)
Total amount of REVISED Sch 'A' Section VI (Road, Path & Culvert) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section VI)
Total amount of Sch 'A' Section VII (Compound wall, fencing & Gate) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section VII)
Total amount of Sch 'A' Section VIII (Rain Water Harvesting System) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section VIII)
Total amount of REVISED Sch 'A' Section IX (External Water Supply) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section IX)
Total amount of REVISED Sch 'A' Section X (External Electric Supply) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section X)
Total amount of REVISED Sch 'A' Section XI (Fire Fighting E/M WORKS) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section XI)
Total amount of Sch 'A' Section XII (DG Set) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section XII)
Total amount of REVISED Sch 'A' Section XIII (Lift) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section XIII)
Total amount of Sch 'A' Section XIV (LIGHTENING PROTECTION) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section XIV)
Total amount of REVISED Sch 'A' Section XV (Geyser (Hot Water Supply), Aviation Obstruction Light, TV Cable, Tele Cable, Fresh Air Fan & AC Point Tender ) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section XV)
Total amount of REVISED Sch 'A' Section XVI (STP (SEWAGE TREATMENT PLANT) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section XVI)
Total amount of Sch 'A' Section XVII (SHIFTING OF EXTERNAL SERVICES) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section XVII)
Total amount of REVISED Sch 'A' Section XVIII (Demolition & Dismantling) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section XVIII)
Total amount of Sch 'A' Section XIX (Excavation, Earth work & Site Clearance) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section XIX)
Description of Work / Item(s)
Amount
LIFT Comprehensive mainenance of electrically operated passenger lifts (4 Nos) 8 passenger lift (544 Kgs) & electrically operated passenger lifts (2 Nos) 13 passenger lift (884 Kgs) installed under Sch 'A' part -XX (Miscellaneous) complete including attending the following services to lifts all as mentioned vide Notes mentioned below and as specifed in PS including (A) FORTNIGHTLY MAINTENANCE, (B) MONTHLY MAINTENANCE (C) QUARTERLY MAINTENANCE (D) HALF YEARLY /YEARLY MAINTENANCE including MOU complete all as specified and directed for :-First year after expiry of defects liability period Note:- Execution of this item shall be commenced immediately after expiry of defect liability period (i.e. 24 Months after the date of satisfactory completion of Ph-I
All as per item No. 1.01 here-in-before but for 2nd year
All as per item No. 1.01 here-in-before but for 3rd year
Notes (a) for item No 1.01 TO 1.03 are as under :- (i) Comprehensive maintenance consists of preventive and breakdown services including repair and replacment of all consumables like topping of gear oils/grease/door rollers/relays/contactors/door belts/gate lock/contacts/PCB's and any hardware including rewinding of motor etc and load testing of lift for satisfactory performance once in a year complete and rate quoted by the tenderer includes the following
(ii) Preventive maintaince consists of carrying out routine check by skilled personnel deputed by OEM as specified in Particular specifications and as recommended by Engineer-in-Charge and lubricating to all moving parts,topping up of oils as per Lubrication chart.
(iii) Breakdown maintaince consists of attending to the faults that may occur and carrying out necessary repairs/replacement to electrical control circuits and electrical/mechanical components of the lift that may occur during the operation.
(iv) Fortnightly,monthly,quarterly,halfyearly and yearly maintaince registeres shall be maintained and signed by site engineer and contractor.
(v) Load testing shall be arranged by the contractor to the Lift for whose repairs were carried out as and when directed by Engr-in-charge.
(vi) Any delay in attending breakdown will attract penalty @ Rs 500 for first 8 to 16 Hrs after receiving complain and @Rs 1500 for every 24 Hrs of delay in rectification of complain.
(vii) Payment will be released only after successull completion of maintenance as per schedule described here in before and submission of record signed by all concern persons
Note-(b) The contractoR has to submit the AMC agreement with the OEM before the completion defect liability period for commencement of Phase- II
Manning and Operation of electrically operated passenger lifts (4 Nos) 8 passenger lift (544 Kgs) & electrically operated passenger lifts (2 Nos) 13 passenger lift (884 Kgs) installed under Sch 'A' part -XX (Miscellaneous), for the duration of 24 hours in 03 (Three) shifts including sunday and holiday and including Reliver For:- (a) Ist Shift from 0600 Hrs to 1400 Hrs, (b) IInd shift from 1400 Hrs to 2200 Hrs and (c ) IIIrd shift from 2200 Hrs to 0600 Hrs per day (with deploying one well experienced operator in each shift) Note :- Execution of this item shall be commenced after satisfactorly completion of Phase-I
All as per item No. 2.01 here-in-before but for 2nd year
All as per item No. 2.01 here-in-before but for 3rd year
All as per item No. 2.01 here-in-before but for 4th year
All as per item No. 2.01 here-in-before but for 5th year
Notes for item No 2.01 TO 2.05 are as under :- Keeping in view the emergency services of lift work the following points shall be noted as mandatory requirement to the tendror for the subject work :-
(i) The contractor has to make necessary arrangement for undergoing oprators training enabling them to be well versed with rescue opration of trapped person and other lift safety mechanism. The training is required to be given by the OEM.
(ii) All the training certificate of the operators shall be submitted to the Engr in Charge prior to the deployment in the work, it may be noted that it is sole responsibility of the contractor if any miss happening occurs including accident/ Injury due to deployment of inexperienced/ unskilled persons. Nothing shall be admissible from the department.
(iv) The contractor shall provide the service of personnel's, duly trained by the OEM, necessary certificate from OEM to be enclosed.
(viii) Contribution towards Bonus that the amount is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, ie proof of payment similarilly items /sub items of contribution towards EPF and contribution towards ESIC shall also be payable after submission of valid & authentic document in support of proof of payment.
(ix) If Lift operatore found absent during duty hrs following penalties will be imposed and deducted from payment to the contractors ;- (i) Rs 500/- for absentees of 02 hours to 04 hrs per shift. (ii) Rs 1000/- for absenty more than 04 hrs per shift.
STP Manning and Operation of Sewage treatment plant having capacity 100 Cubic meter/day installed under Sch 'A' part XX (Miscellanous Items), for the duration of 24 hours in 03 (Three) shifts including sunday and holidays and including necessary reliver For (i) Ist Shift from 0600 Hrs to 1400 Hrs, (ii) IInd shift from 1400 Hrs to 2200 Hrs and (iii) IIIrd shift from 2200 Hrs to 0600 Hrs per day (with deploying one well experienced operator in each shift) for Ist year from next date of certified date of completion all as specified and directed. Note : Execution of this item shall be commenced after satisfactorly completion of Phase-I (ii) Water and Electric required for operation of plant shall be provided free of cost by the Department. (iii) All Consumable such as Sodium Hypochlorite PAC and any other chemical required, compressure oil and grease etc required for operation of plant shall be provided by contractor at his own cost as per the manufacturer's instruction and direction of AGE (I) during the period of manning & Operation, cost of the same shall be deemed included in the unit rates quoted by contractor. (iv) Please ensure that all trade men engaged in subject work covered in EPF scheme. Proper doc should be maintained in this regard and submitted alongwith each payment.
All as per item No. 3.01 here-in-before but for 2nd year
All as per item No.3.01 here-in-before but for 3rd year
All as per item No.3.01 here-in-before but for 4th year
All as per item No. 3.01 here-in-before but for 5th year
Notes for item No 3.01 TO 3.05 are as under : Execution of this item shall be commenced after satisfactorly completion of Phase-I (ii) Water and Electric required for operation of plant shall be provided free of cost by the Department. (iii) All Consumable such as Sodium Hypochlorite PAC and any other chemical required, compressure oil and grease etc required for operation of plant shall be provided by contractor at his own cost as per the manufacturer's instruction and direction of AGE (I) during the period of manning & Operation, cost of the same shall be deemed included in the unit rates quoted by contractor. (iv) Please ensure that all trade men engaged in subject work covered in EPF scheme. Proper doc should be maintained in this regard and submitted alongwith each payment.
Mukul Builders Private Limited
City Promoter and Buildwell Pvt. Ltd.
S T Constructions Private Limited
Bahl Builders Pvt Ltd
Ktech Engineer Builders Co. Pvt. Ltd
ARCHON POWERINFRA INDIA PRIVATE LIMITED
NITYA NAND AND SONS CONTRACTORS PVT LTD
S T Constructions Private Limited
City Promoter and Buildwell Pvt. Ltd.
ARCHON POWERINFRA INDIA PRIVATE LIMITED
Aalaya Engineering Project Private Limited
Ktech Engineer Builders Co. Pvt. Ltd
Bahl Builders Pvt Ltd
NITYA NAND AND SONS CONTRACTORS PVT LTD
ARCHON POWERINFRA INDIA PRIVATE LIMITED
Ktech Engineer Builders Co. Pvt. Ltd
Mukul Builders Private Limited
City Promoter and Buildwell Pvt. Ltd.
Aalaya Engineering Project Private Limited
S T Constructions Private Limited
Bahl Builders Pvt Ltd
Bidder Name
Ktech Engineer Builders Co. Pvt. Ltd
City Promoter and Buildwell Pvt. Ltd.
NITYA NAND AND SONS CONTRACTORS PVT LTD
Bahl Builders Pvt Ltd
Aalaya Engineering Project Private Limited
ARCHON POWERINFRA INDIA PRIVATE LIMITED
Mukul Builders Private Limited
S T Constructions Private Limited
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid