Providing sewerage network and construction of STP Providing sewerage network and construction of STP Independent canal based water works Independent canal based water works
2026_HRY_505130_1
202637B2AC2A 1135 4376 8F11 8EBD12E858A8594PUH
Open Tender
Civil Works
Works
950 days
DHANAURI DHANAURI DHANAURI DHANAURI
2 documents required · 2 mandatory
₹20,000
₹84.1 L
Yes
Kaithal
19 Mar 2026
28 Feb 2026
24 Mar 2026
28 Feb 2026
24 Mar 2026
28 Feb 2026
9 Mar 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Water Treatment Plant (WTP) - Designing, Testing, Construction and Commissioning of 3.75 MLD capacity water treatment plant including inlet channel alum dozing, flash mixing, clari floculator, filtter box, over head reservoir for back wash, waste water tank, including all civil work pumping machinery and electric cabling, control panel, entire piping network of suitable
size, laying of DI pipes from raw water pump to inlet box of WTP, WTP to CWT and Suction well for CW incluidng, DI specials suitable size sluice valves, hodies, manhole covers, air scour equipment, chemical house including chlorination equipment and arrangement of flow measurement and sand bed with automation complete in all respects as per approved NIT. (Sluice valve of make IVCAWAG). | 1 | Job | - | - |
| 2 | Supply and Erection of Horizontal spindle split casing type pumping sets of following duties directly coupled to AC squirrel cage induction type motor with accessories as described in Schedule No. II complete in all respect withpriming arrangement with complete base frame.
Raw Water Set :- 3000 LPM, 55 HP, 12 mtrs head with squirrel cage induction
motor 1440 RPM, 3 phase 50 Hz of suitable rating (H.P.) | 2 | Each | - | - |
| 3 | Supply, erection testing and commissioning of copper wire for 2 No. Panel boards from main switch to panel and wiring of panel with 16 mm2 ISI marked for making connection underground covered with sand and brick in trenches/in pipes complete in all respects with all accessories like thimble etc | 80 | Metre | - | - |
| 4 | Supply erection testing of light fitting including wire in the pump chamber with material 10 points including switch button plug PVC conduit pipe and copper wire etc as per approved specifications | 1 | Job | - | - |
| 5 | Providing and fixing water level indicator complete in all respect as
approved by Engineer-in-charge | 2 | Job | - | - |
| 6 | Provdiing and fixing measure gauge inside SandS tank complete in all respect as approved by Engineer-in-charge. | 1 | Each | - | - |
| 7 | Supply and Erection of Horizontal spindle split casing type pumping sets of following duties directly coupled to AC squirrel cage induction type motor with accessories as described in Schedule No. II complete in all respect with priming arrangement with complete base frame.
Clear Water Set :- 3800 LPM, 55 HP, 40 mtrs head with squirrel cage induction
motor 1440 RPM, 3 phase 50 Hz of suitable rating (H.P.) | 2 | Each | - | - |
| 8 | Supply and erection testing and commissioning wall mounted electrical panel board fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200 x 900mm and 400 mm deep having following items. Raw water pump set 3000 LPM 12 Mtr Head = 2 Nos (One for each pump set)
a)Main switch 100 Amp 1 No. (LandT Siemens ABB)
b) Volt meter 100x100mm range 0 to 500 volt 1 No.
(AE/KAPPA/LandT)
c)Amp meter 100x100mm range 0 to 100 volt 2 nos
(AE/KAPPA/LT)
d) CT 100/ 3 no. (AE/KAPPA/LandT)
e) VSS andASS 1 NO. each of approved make
f) SPP 4 No. of approved make / Minilac
g) Motor starter star delta 1 nos. for 3000 LPM x 12 mtr Head
motor (Landamp:T Siemens ABB)
h) Capacitor KVAR as per site requirement
i) Indicating Lamp one set
j) Change over Switch 1 No. | 2 | Each | - | - |
| 9 | Supply and erection testing and commissioning wall mounted electrical panel board fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200 x 900mm and 400 mm deep having following items. Clear water pump set 3800 LPM 40 Mtr Head = 2 Nos (One for each pump set)
a)Main switch 250 Amp 1 No. (LandT Siemens ABB)
b) Volt meter 100x100mm range 0 to 500 volt 1 No.
(AE/KAPPA/LandT)
c)Amp meter 100x100mm range 0 to 100 volt 2 nos
(AE/KAPPA/LT)
d) CT 100/ 3 no. (AE/KAPPA/LandT)
e)VSS and ASS 1 No. each of approved make
f) SPP 4 No. of approved make / Minilac
g) Motor starter star delta 1 nos. for 3800 LPM x 40 mtr Head
motor (LandT Siemens ABB)
h) Capacitor KVAR as per site requirement
i) Indicating Lamp one set
j) Change over Switch 1 No. | 1 | Each | - | - |
| 10 | Designing, providing, fixing, testing and commissioning of GASEOUS CHLORINATION SYSTEM
having capacity upto 2000 grams/ hrs. as designed having the control of gas upto 20th part of max. dose . The complete system consists of (a) Vacuum regulator (b) Measuring Glass
Tube (c ) Ejector (d) PF tubing (e) Spanner with cylinder opening key (f) Ammonia Gas (Liquid for leaking test) (g) 1’ dia PVC pipe with PVC fitting, ball valves etc. (h) 2 Nos. chlorine gas cylinder capacity 100 Kg. duly certified and approved by BIS and Explosive Department Govt. of India (i)
Electronic Chlorine gas leak detector with sensor and hooter (j) Full face mask with canister as per technical specifications issued by Head Office, PHED, Haryana Memo No.-23070-
23142 dated 28-02-2024.... | 1 | Job | - | - |
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.75 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.94 MB
BOQ_583853.xls
BOQ • 0.28 MB
777981Z135158.pdf
Additional Documents • 5.20 MB
OT0135158.pdf
Other Document • 6.44 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .