| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.0 LAccepted-AOC TAILOR MARKET MAIN BAZAAR MANDI ADAMPUR 125052 | HISAR | HARYANA | 125052 | L1 | Accepted-AOC L1 | |
| 2 | L2₹5.4 L+₹41,401 (8.32%)Rejected-Finance 209 210 AGGARWAL TOWER PLOT NO 2 SECTOR 5 ROHINI NORTH WEST DELHI DELHI 110085 | DELHI | NORTH WEST DELHI | DELHI | 110085 | L2 | Rejected-Finance L2 | |
| 3 | L3₹5.8 L+₹86,376 (17.4%)Rejected-Finance 315 INDUSTRIAL AREA II PANCHKULA 134113 | PANCHKULA | HARYANA | 134113 | L3 | Rejected-Finance L3 |
Tender Value
₹4.8 L
EMD Value
₹9,700
Closing Date
6 Sept 2019, 5:00 pmClosed
Bhim Sain
Executive Engineer Elect. Division PWD B and R Hisar
Construction of SDO Civil Complex in Sub Division Narnaund in Distt. Hisar (Pdg. Addressable Fire Alarm only).
2019_HRY_99902_1
PWD/Elect-KNL/Elect-HSR/16355
Open Tender
Construction Works
Works
120 days
Hisar
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Executive Engineer, Elect. Division PWD B and R Br
₹9,700
25 Feb 2021
31 Aug 2019
11 Sept 2019
31 Aug 2019
6 Sept 2019
31 Aug 2019
Amount
S/E of PVC unsheathed copper conductor cable single core 1100 volts grad in pipe of suitable size excluding cost and erection of pipe. (HSR 31.40). i) Cable size 1.5 sqm(3/0.81 mm)
Supply and erection of PVC conduit pipe ISI marked (Medium) recessed in wall /ceiling etc. including cost of PVC bends, inspection box and all other material required to complete the job in all respect to the entire satisfaction of Engineer-in-Charge of work. (HSR 31.44). b) 25 mm dia
Non Schedule Items Fire Alarm System: SITC of Micro processor based 2 wire fault tolerant, networkable type Fire Alarm / Detection Control Panel (having nos. of loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 characters LCD unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80 LED Indicators. The Panel shall have 3 Serial Ports. The pane\l shall have a built in power supply and battery charger along with maintenance free 24 AH,2 x 12 volt SMF lead acid batteries capable of running for a minimum of 24 hours with battery charger complete as required. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS/ as per specifications complete in all respect up to the entire satisfaction of Engineer-in –charge of work. Make: Bosch FPA 1000 / Cerberus by siements/ Edwards EST3/Honeywell Morley Zxe series.
SITC of addressable multisensor detector with a combination of optical and thermal including base, auto addressing features as required. Detectors should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elemnets in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005. EMC safety for detector shall be 50 V/m. shall be EN54/VDS/UL certification. ((Detectors without inbuilt isolators may be considered with an additional isolator module after 20 devices) Make: Bosch FAP-440+T+FAA-440, Siemens Cerberus OH921+DB-11, Honeywell Morley HM-PTSE+B501, Edwards SIGA PHD+SIGA
SITC of intelligent analog addressable type Manual Call point having surface or flush mounting option fully compliant to EN54 having rotary decade switches for addressing with back box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect upto the entire satisfaction of Engineer-in-Change of the work. Make Siemens cerberus/ Morely/ Edwards
SITC of addressable Loop powered hooter with strobe complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required complete the of in all respect upto the entire satisfaction of Engineer - in - charge of work. Make: Make Bosch/ Morley/ Siemens/ Cerberus/ Edward
SITC of Glow Type EXIT Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink sulphate as bare chemical class 1 material PSPA fixed on 3mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour & material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. (Make: Glolite / Pearl / Devi)
SITC of minimum 1000 Mtr. Range Kheraj make SIRON generator provided at the roof of the building with separate Power Supply, relay etc. complete the in all respect up to the entire satisfaction of Engineer-in-Charge of work.
SITC of 2 KVA UPS with 2 hour backup on line with 6 Nos. 17 Ah batteries of Exide including the cost of stand made with MS Angel Iron duly painted. Make: Microtek / Luminous / APC / Elnova )
Hytek Turnkey Projects Pvt. Ltd.
Insat Techno Services
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .