Tata Power Delhi Distribution Limited
1 Year Rate Contract (RC) for 66kV & 33kV EHV Bay Extension with associated Electrical & Civil works at Various Locations in TPDDL area
200001981
TPDDL/ENGG/ENQ/200001981/26-27
Delhi
1. The bidder should have an average annual turnover of Rs. 2 crores in last 3 financial years. Copy of audited P&L Account to be submitted in this regard. 2. The bidder should have performance certificates for similar works on 33kV or higher voltage rating for 1-year satisfactory performance from at least 2 reputed companies. The work against these issued certificates should be completed in last 7 years from the date of bid submission. In case the bidder has a previous association with Tata Power DDL for similar products and services, the performance feedback for that bidder by Tata Power DDL’s User Group shall only be considered irrespective of performance certificates issued by any third organization. 3. The bidder should have Valid Electrical Contractor License issued by Govt of NCT of Delhi to execute the electrical works in Delhi. Bidder must submit the copy of license in this regard. In case bidder is not having this License, Bidder shall submit an undertaking that in case they are the successful bidder, same shall be obtained by them before execution of contract by Tata Power-DDL. 4. The Bidder must have all Statutory Compliance like Valid PAN, ESI registration, EPF registration & GSTN Registration.
₹5,000
₹66.1 L
27 Jul 2026
27 Jul 2026
Annexure-1 (Schedule of Item)
NIT No - TPDDL/ENGG/ENQ/200001981/26-27
NIT Description - 1 Year Rate Contract (RC) for 66kV & 33kV EHV Bay Extension with associated Electrical & Civil works at Various Locations in TPDDL area
S. NO. TPDDL Service Code Item Descr. UOM Quantity "A" Unit Rate (Rs.) "a" Applicable GST (in Rs.) "b" Price per Unit (in Rs.) "B"= a+b TPDDL Amt (in Rs.) C=A*B HSN/ SAC code
Electrical Services
1.001 ITC of TRANSFORMER POWER 25/31.5MVA-9 NORMALTAP:Installation ,testing & commissioning of 3 Ph, 'Dyn11 ONAN/ ONAF power Transformer with OLTC including fixing of all loose accessories/parts of transformer (supplied along with the transformer), pre-commissioning checks. There shall be outdoor bushings on HV side which shall be connected with over head conductors or power cables through external open bus bar arrangement comprising of brass palm connectors, 100mm X 10mm Tinned Copper Flat with HS Insulating Sleeve Busbar and on LV side cable box will be available. LV side busbars shall connect to 1CX1000sqmm 3 runs of 11kV Al XLPE cable per phase. This item includes the jumpering/connections/termination on both sides. It also includes testing of transformer at site as per TATA Power-DDL power transformer specifications. This includes oil filtration of transformer. EA 21 0.00 0.00 0.00
1.002 Dragging of TRANSFORMER POWER upto 25/31.5MVA-9 NORMALTAP from unloading point to foundation ( up to 20 meters) or vice versa with complete safety measures as per TATA Power-DDL project in-charge instructions. M 300 0.00 0.00 0.00
1.003 Installation ,testing & commissioning of outdoor neutral CT (NCT) for PTR including its connections with PTR/Reactor & NGR/Earth Pit, etc.. EA 22 0.00 0.00 0.00
1.004 To provide brazing for all joints/connections required as per site condition between NCT and Copper earth plate, for earthing of NCT at as per TATA Power-DDL earthing philosophy. One set means all requirements for one NCT. EA 22 0.00 0.00 0.00
1.005 Installation ,testing & commissioning of LA 60KV 10KA, heavy duty, station class, lightning arrestor(LA) & surge counter including laying & connection of 1CX50 sqmm copper flexible cable with LA surge counter. This item includes jumpering/connections. EA 66 0.00 0.00 0.00
1.006 Installation ,testing & commissioning of 66kV Post Insulator including jumpering/connections. EA 66 0.00 0.00 0.00
1.007 SITC of clamp & connectors required for connection of 66kV BPI with 2.5 inch IPS tube EA 66 0.00 0.00 0.00
1.008 SITC of clamp & connectors required for connection of 66kV LA with 2.5 inch IPS tube EA 36 0.00 0.00 0.00
1.009 SITC of connector for connection of 66kV cable termination lug with 2.5 inch IPS tube EA 36 0.00 0.00 0.00
1.01 LTC of CABLE 66KV AL 1X1000 SQMM ARM XLPE along with trefoil clamp in already excavated trench/available trench/vertical mounting.(cable shall be Free Issued by TATA Power-DDL). Application of Fire paint(including supply) at transformer end it shall be up to sand filling in trench, and in switchgear room it shall be from switchgear to building entry point. Sealing of cable to be provided at entries as per TATA Power-DDL Standard Drawing . Quantity shall be paid per meter of each cable laid. M 4930 0.00 0.00 0.00
1.011 LTC of CABLE 11KV AL 1X1000 SQMM ARM XLPE along with trefoil clamp in already excavated trench/available trench/vertical mounting.(cable shall be Free Issued by TATA Power-DDL.Cable shall be 2 runs / Phase for 20/25 , 16/20 MVA and 3 runs/phase for 25/31.5 MVA power Transformer to 11 kV Switchgear Panel ). Application of Fire paint(including supply) at transformer end it shall be up to sand filling in trench, and in switchgear room it shall be from switchgear to building entry point. Sealing of cable to be provided at entries as per TATA Power-DDL Standard Drawing . Quantity shall be paid per meter of each cable laid M 25820 0.00 0.00 0.00
1.012 LTC of CABLE 1.1KV AL 4CX95 SQMM ARM (For AC & DC Supply) for ACDB to Battery charger & Filtration industrial socket M 1450 0.00 0.00 0.00
1.013 LTC of CABLE 1.1KV AL 4CX16 SQMM ARM M 4100 0.00 0.00 0.00
1.014 LTC of CABLE 1.1KV AL 4CX25 SQMM ARM M 6750 0.00 0.00 0.00
1.015 LTC of CABLE 11KV AL 3CX300/400 SQMM XLPE ARM (cable shall be Free Issued by TATA Power-DDL). From 11 kV Switchgear to 250kVA/160 KVA Transformer in already excavated trench/available trench/vertical mounting. Application of Fire paint(including supply) in cable trench portion shall be in scope of this activity. M 1400 0.00 0.00 0.00
1.016 LTC of CABLE 1.1KV AL 3.5CX300 SQMM XLPE ARM or CABLE 1.1KV AL 4CX300 SQMM XLPE ARM for station transformer M 950 0.00 0.00 0.00
1.017 LTC of CABLE CONTROL 1.1KV CU 4CX2.5 SQMM ARM M 16000 0.00 0.00 0.00
1.018 LTC of CABLE CONTROL 1.1KV CU 12CX2.5 SQMM ARM M 9850 0.00 0.00 0.00
1.019 LTC of CABLE CONTROL 1.1KV CU 19CX2.5 SQMM ARM M 10750 0.00 0.00 0.00
1.02 LTC of CABLE CONTROL 1.1KV CU 6CX4 SQMM ARM M 11950 0.00 0.00 0.00
1.021 LTC of CABLE CONTROL 1.1KV CU 2CX6 SQMM ARM (For D.C.) M 6300 0.00 0.00 0.00
1.022 LTC of CABLE CONTROL 1.1KV CU 2CX50SQ.MM FLEX. M 300 0.00 0.00 0.00
1.023 SITC of 50x6mm CU flat for Transformer neutral earthing including required earth excavation for laying earth flat. This item excludes brazing activity. M 525 0.00 0.00 0.00
1.024 SITC of Earthing with Electrolytic grade copper plate 600mmx600mmx6mm including 50x6mm copper flat and other accessories and providing masonry enclosure with cover plate to be provided in 6 mtr deep earth pit to be filled With earth enhancement material as per IEEE80:2000,14.5(D) and TATA Power-DDL standard earthing philosophy. Earth Enhancement material approval is mandatory before erection activity. EA 44 0.00 0.00 0.00
1.025 SITC of 100 mm dia GI pipe-6 meter length earth electrode with treated earth Pit heavy class with Treated Earth Pits. With earth enhancement material as per IEEE80:2000,14.5(D). This item includes civil goomties required for earth pit as per TATA Power-DDL standard earthing philosophy and specification. Earth Enhancement compound (Minimum Terec-5 KG and Earthcon-12.5KG) is to be used for every earth pit till the earthing value of each pit is achieved below 02 Ohms EA 74 0.00 0.00 0.00
1.026 SITC of 100 mm dia GI pipe-3 meter length earth electrode with treated earth Pit heavy class with Treated Earth Pits. With earth enhancement material as per IEEE80:2000,14.5(D). This item includes civil goomties required for earth pit as per TATA Power-DDL standard earthing philosophy and specification. Earth Enhancement compound (Minimum Terec-5 KG and Earthcon-12.5KG) is to be used for every earth pit till the earthing value of each pit is achieved below 02 Ohms EA 56 0.00 0.00 0.00
1.027 SITC of 100 mm dia GI pipe-6 meter length earth electrode with treated earth Pit heavy class with Treated Earth Pits without goomty. With earth enhancement material as per IEEE80:2000,14.5(D).. Earth Enhancement compound (Minimum Terec-5 KG and Earthcon-12.5KG) is to be used for every earth pit till the earthing value of each pit is achieved below 02 Ohms EA 44 0.00 0.00 0.00
1.028 SITC of 100 mm dia GI pipe-3 meter length earth electrode with treated earth Pit heavy class with Treated Earth Pits without goomty. With earth enhancement material as per IEEE80:2000,14.5(D).. Earth Enhancement compound (Minimum Terec-5 KG and Earthcon-12.5KG) is to be used for every earth pit till the earthing value of each pit is achieved below 02 Ohms EA 36 0.00 0.00 0.00
1.029 SITC of building spikes, 20mm dia GI rod (2.5Meter length) EA 80 0.00 0.00 0.00
1.03 ITC of TRANSFORMER 250KVA 3PH 11KV/433V with cable box on HV/LV sides as per TATA Power-DDL specifications including jumpering/connections. EA 5 0.00 0.00 0.00
1.031 SITC of Double compression glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables of the sizes (diameter between 12mm to 18mm ) EA 280 0.00 0.00 0.00
1.032 SITC of Double compression glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables of the sizes (diameter between 18mm to 24mm ) EA 650 0.00 0.00 0.00
1.033 SITC of Double compression glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables of the sizes (diameter more than 24mm) EA 380 0.00 0.00 0.00
1.034 SITC of Double compression glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore CU conductor control cables of the various sizes up to 12 mm EA 66 0.00 0.00 0.00
1.035 SITC of cable cleat (Nylon-6) size up to 100mm EA 244 0.00 0.00 0.00
1.036 SITC of cable cleat (Nylon-6) size greater than 100mm EA 74 0.00 0.00 0.00
1.037 ITC of Cable Cleats of various size EA 150 0.00 0.00 0.00
1.038 Supply of Trefoil Clamp for suitable for 66kV and/or 11kV 1Cx1000sq.mm Power Cable as per TATA Power-DDL Specification/Drawing EA 315 0.00 0.00 0.00
1.039 SITC of IP54 Lighting junction box for each Light at tower suitable for out door installation comprising of 8 no. CBT M 4 type terminal connector for light connections or loop in / loop out cable EA 35 0.00 0.00 0.00
1.04 SITC of AC Distribution Board AC 415V, 400A cubicle type Indoor, floor mounted, auxiliary service board as per TATA Power-DDL specification EA 7 0.00 0.00 0.00
1.041 SITC of astro timer control for lighting arrangement. This item shall be executed as per TATA Power-DDL Engineering In-charge. EA 6 0.00 0.00 0.00
1.042 SITC of industrial type Control room lighting including all accessories:- LED luminaire 2x16/18/20W industrial type fitting with LED luminaire. Suitable for Surface/Suspended mounting EA 84 0.00 0.00 0.00
1.043 SITC of industrial type Control room lighting including all accessories:- LED luminaire 2x36/40W industrial type fitting with LED luminaire. Suitable for Surface/Suspended mounting EA 118 0.00 0.00 0.00
1.044 SITC of flame proof fluorescent fitting including all accessories:-LED luminaire 2x36/40W flame proof acid proof fitting with LED lamp for Battery Room/Cable cellar room. Suitable for Surface/Suspended mounting EA 24 0.00 0.00 0.00
1.045 SITC Installation of LED 120W luminaire with required fittings and accessories as per TATA Power-DDL specifications. EA 177 0.00 0.00 0.00
1.046 Supply, Installation ,testing & commissioning of AC 415V 400A Street Light panel AC 415V, 400A ,50 KA for 1 Sec cubicle type Outdoor, Plinth mounted, Street light panel as per specification comprising of the following: Incomer 63A TTPNMCCB -1 No. Metering with RYB indicating lamp LED type, Voltmeter with selector switch, ammeter with selector switch , suitable CT's & 2A TPNMCB for backup protection of voltmeter & indication light. 1 No. 70A FP CONTACTOR -1 No. 24 Hr. timer for auto Operation Auto manual selector switch , I set push button for on/off operation.Outgoing feeder 25A TPNMCB 4 Nos. 63A Power industrial socket with "C" series TPNMCB for Protection & provision of up to 3.5c X 50 sqmm Al Arm cable Termination as per TATA Power-DDL specifications. EA 6 0.00 0.00 0.00
1.047 SITC of IP 54 Lighting Distribution Board for control room lighting control comprising of one no, incomer 63 A TPN MCB & 18 no. out going as 10-32A SP MCB. EA 25 0.00 0.00 0.00
1.048 SITCof Power Distribution Board for control room air conditioner comprising of one no, incomer 63 A TPN MCB & 6 no. out going as 32A TPN MCB. With auto changeover for Air conditioner EA 14 0.00 0.00 0.00
1.049 SITC of IP 54 protected 150A three phase industrial socket with 150A TPN MCB for oil filtration machine with 3x6.0 sqmm PVC insulated copper conductor stranded insulated wires & 2x1.5sqmm Stranded Green earth wire in recessed and/or on surface 40mm dia GI conduit including chasing of wall, filling of chases etc. complete in all respect. EA 6 0.00 0.00 0.00
1.05 SITC of 32A three phase industrial socket with 32A TPN MCB AC power point with 3x6.0 sqmm PVC insulated copper conductor stranded insulated wires & 2x1.5sqmm Stranded Green earth wire in recessed and/or on surface 40mm dia GI/PVC conduit including chasing of wall, filling of chases etc. complete in all respect. EA 42 0.00 0.00 0.00
1.051 Supply & laying of HDPE Pipe Size 200 mm dia (PN-4 PE80) as per TATA Power-DDL specifications M 660 0.00 0.00 0.00
1.052 Supply & laying of HDPE Pipe Size 100 mm dia (PN-4 PE80) for control cables in the out door yard M 350 0.00 0.00 0.00
1.053 Supply, Fabrication and installation of GI structural steel material for gantry tower, beam, equipment's, cable mounting structure, tower mounting structure, LA Structure,BPI , drain crossing structure etc., where ever required as per approved drawing including nuts, bolts, washer & clamps. TON 132 0.00 0.00 0.00
1.054 SITC of 75 x 12 mm G I flat Main Earth mat, Aux Earth mat & Earthing Risers for Main Equipment's & structures etc. This item includes required earth excavation & backfilling for laying earth flat including exothermic wielding ,anticorrosive coatings i.e. red oxide and bitumen KG 38900 0.00 0.00 0.00
1.055 SITC of 50x6 GI flat for Aux earth material Earthing conductor for connection of , L.T panel, Junction box, & building Lightning risers & peak Connection etc. This item includes required earth excavation & backfilling for laying earth flat including exothermic wielding ,anticorrosive coatings i.e. red oxide and bitumen. KG 26300 0.00 0.00 0.00
1.056 Supply and Installation of GI PERFORATED TRAY 150MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 230 0.00 0.00 0.00
1.057 Supply and Installation of GI PERFORATED TRAY 300MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 1050 0.00 0.00 0.00
1.058 Supply and Installation of GI PERFORATED TRAY 600MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 600 0.00 0.00 0.00
1.059 Supply and Installation of GI LADDER CABLE TRAY 300MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 950 0.00 0.00 0.00
1.06 Supply and Installation of GI LADDER CABLE TRAY 600MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 950 0.00 0.00 0.00
1.061 SITC of aluminum IPS tube busbar with endcaps of 2.5 inches suitable for minimum 1600A Rated Current of required length with insulated Raychem BPTM sleeves of 66kV class. The IPS tube shall conform to IS:5082 and IS:2673. M 198 0.00 0.00 0.00
1.062 SITC of One light point by One Switch wiring of above light point, with 1.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 62 0.00 0.00 0.00
1.063 SITC of Two light point by One Switch wiring of above light point, with 1.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1.0 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 51 0.00 0.00 0.00
1.064 SITC of Three light point by One switch wiring of above light point, with 1.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1.0 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 40 0.00 0.00 0.00
1.065 SITC Flood light point -2.5 sqmm cu wiring wiring of above light point, with 2.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1.0 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 90 0.00 0.00 0.00
1.066 SITC of Exhaust fan point wiring of above exhaust fan point, with 1.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1.0 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 45 0.00 0.00 0.00
1.067 SITC of wiring of General power point with 4.0 sq.mm PVC insulated copper conductor single core stranded wires in GI/pVC conduit with 2.5 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling of chases etc. com EA 47 0.00 0.00 0.00
1.068 Supply of Fire barriers at cable entrances in control room ( EA means each entry) for 4 hrs. rating as per TATA Power-DDL specifications M2 22 0.00 0.00 0.00
1.069 SITC of Fire retardant coating on cables with required accessories as per TATA Power-DDL specifications (this item to be used only if not covered in other line items activity) KG 600 0.00 0.00 0.00
1.07 SITC of EPDM based cable entry/exits sealing system for 11kv power cables (for one PTR - 9 cables) including required minor civil works as per TATA Power-DDL specifications. This also includes provision of 20% spares modules for future cables laying or replacement activity EA 23 0.00 0.00 0.00
1.071 SITC of EPDM based cable entry/exits sealing system for 11 kV outgoing power cables for (10 cables) including required minor civil works as per TATA Power-DDL specifications. This also includes provision of 20% spares modules for future cables laying or replacement activity EA 8 0.00 0.00 0.00
1.072 FIRE EXTINGUISHER CO2 CAP 6.5 KG SITC of Fire Extinguishers CO2 type 6.5Kg for switchgear room, control room, engineer room with required accessories as per latest TATA Power-DDL latest specifications. EA 40 0.00 0.00 0.00
1.073 SITC of Fire Extinguishers Dry powder chemical type 25 kg with required accessories as per TPDDL specifications.(For PTR) EA 22 0.00 0.00 0.00
1.074 SITC of Fire Extinguishers CO2 type 22.5 kg with required accessories as per TPDDL specifications.(For PTR) EA 14 0.00 0.00 0.00
1.075 SITC of ISI marked Fire Extinguishers -ABC Type 9 Kg for Switch room and other locations (IS:15683) Approved Make : Ceasefire / Minimax / Safex with required accessories as per TPDDL specifications. EA 36 0.00 0.00 0.00
1.076 SITC of ISI marked Fire Extinguishers -ABC Type 6 Kg for Switch room and other locations (IS:13849) Approved Make : Ceasefire / Minimax / Safex EA 28 0.00 0.00 0.00
1.077 SITC of wall mounted type Micro Processor based fire alarm panel with made of 16 SWG CRCA sheet, inbuilt Battery Box, comprising of Audio/ visual alarm indication of fire & fault etc., min. 16X2 line LCD display, time and date on LCD, complete with 100 event data logger with date and time stamp, indications for fire, fault, main power and battery as per ENG-GEN-4046. The panel shall also contain annunciation, window type indicators for fire and fault. Panel should support (a) NO-NC contact for fire alarm communication to BCPU (b) Capability of Ethernet Communication though RTU to centralized monitoring system (c) Data download to PC through USB. (c) ATX key board for field programming (d) PA system connectivity for announcement and altering (e) GSM functionality as per TPDDL specifications. Panel shall contain built-in battery charger and battery (Approved makes: Exide / Amaron / APC / Su-kam) for 48 hrs. back up in normal case and 30 min back up in case of alarm.Approved Make: Ravel / System Sensor / Agni Suraksha / ASES / Honeywell EA 10 0.00 0.00 0.00
1.078 SITC of Installation, Testing and Commissioning of Manual Call box with push button reset type as per IS 2189 Approved Make : Ravel / System Sensor / Agni Suraksha / ASES / Honeywell with required accessories as per TPDDL specifications. EA 13 0.00 0.00 0.00
1.079 SITC of Electronic Hooters (min 110 db intensity required) made out of ABS (colour RED) Approved Make : Ravel / System Sensor / Agni Suraksha / ASES / Honeywell with required accessories as per TPDDL specifications. EA 13 0.00 0.00 0.00
1.08 SITC of Installation, Testing and Commissioning of Response indicator as per IS 2189 Approved Make : Ravel / System Sensor / Agni Suraksha / ASES / Honeywell with required accessories as per TPDDL specifications. EA 54 0.00 0.00 0.00
1.081 SITC of Cable (FRLS in PO Red Color) cable 2 core* 1.5mm. Approved Makes: Polycab / Finolex / Gloster / RR Kabel / Havells M 2300 0.00 0.00 0.00
1.082 SITC of All safety items like First aid box - 1 no., safety Gloves - 2 pair., Safety Display board / Warning signs - 1 lot, accident prevention chart - 1 nos., shock treatment chart - 2 no., Grid SLD on wooden board- 1 no. on A0 size, (For complete grid) SET 16 0.00 0.00 0.00
1.083 SITC of Sand Bucket along with stand(8 buckets) as per IS2546.The sand bucket should be clearly labeled and contain only clean, dry sand. Fire buckets should be made of heavy gauge galvanized steel, have a 9/10 liter capacity, and be painted red on the outside and white on the inside with the word "FIRE" stamped in large letters EA 22 0.00 0.00 0.00
1.084 SITC of LOTO station as per TATA Power-DDL project In-Charge EA 16 0.00 0.00 0.00
1.085 ITC of electrical panel lock out base with cover as per TATA Power-DDL project In-Charge EA 16 0.00 0.00 0.00
1.086 Supply and Laying of insulated mat Class-A ,IS 15652:2006 as per TATA Power-DDL Specifications. (1 meter wide by 2 meters long) LV(3.3kV)/DC EA 42 0.00 0.00 0.00
1.087 Supply and Laying of insulated mat Class-B ,IS 15652:2006as per TATA Power-DDL Specifications. (1 meter wide by 2 meters long) 11KV EA 122 0.00 0.00 0.00
1.088 SITC of asset numbering- Complete identification of all the assets/equipment’s, RCC cable trench cover marking in the approve color and numbering to be done with detailed description of the asset as per the requirement of project in-charge. This includes Supply of paints and other required material to complete the activity. (This item shall be paid per PTR Bay/ Line Bay,) LOT 22 0.00 0.00 0.00
1.089 SITC of Grid signs boards i.e. safety notices such as "Danger of Death," "High Voltage," and "No Trespassing," along with fire safety signs like "Fire Alarm" and "Fire Exit Keep Clear," and protective equipment information like "Wear Safety Helmet" and "First Aid", Prohibition signs, Hazard signs, Emergency information signs, Fire Equipment signs at various locations. The exact signs may vary by location, but the purpose is to warn of hazards, instruct on safety procedures. LOT 16 0.00 0.00 0.00
1.09 Supply and Fixing of the Danger plates on the poles/tower/structure including fabrication of clamp etc. EA 64 0.00 0.00 0.00
1.091 SITC of Earth Insulator (DMC) EA 205 0.00 0.00 0.00
1.092 Transportation of various items from stores to site or from site to site or from site to store including loading and unloading: with tempo 709/410 EA 28 0.00 0.00 0.00
1.093 Supply of Vacuum Cleaner as per TATA Power-DDL project in-charge instructions. Approved make : Eureka Forbes Pro Vac WD 77 EA 5 0.00 0.00 0.00
1.094 SITC of industrial type continuous heavy duty Exhaust fan with louvers, 18 inches including auto-changeover facility. Approved make: Bajaj/Crompton/Havells EA 61 0.00 0.00 0.00
1.095 SITC of Industrial type Dewatering/submersible/sewage pump (fixed type) 415 V, 2 HP, automatic ON/OFF feature,Pre-fitted float switch ensure that the pump start and stop automatically as per need and including required plumbing items(union, valves, sockets, CPVC pipe etc.) & connections along with outlet flexible nylon braided PVC pipe - 30 meters. including all accessories if required. Approved make - Crompton/Kirloskar EA 7 0.00 0.00 0.00
1.096 SITCof Industrial type Dewatering/submersible/sewage pump (portable type) 415 V, 1 HP, automatic ON/OFF facility and including required plumbing connections along with outlet flexible nylon braided PVC pipe - 30 meters. - Approved make - Crompton/Kirloskar EA 18 0.00 0.00 0.00
1.097 SITC of BLDC ceiling fan, 48 '' as per TATA Power-DDL project in-charge instructions. Approved Make : Crompton/Bajaj/Havells EA 47 0.00 0.00 0.00
1.098 SITC of BLDC wall mounted fan 400 mm, 1350 rpm, auto swing. Approved make : Bajaj/Havells/Crompton EA 14 0.00 0.00 0.00
1.099 Supply of platform type FRP ladder 3M height, extra heavy duty ladder for all industrial application as per TATA Power-DDL specifications. EA 6 0.00 0.00 0.00
1.1 Mounting of 66/33 KV 1Cx1000sqmm & 33KV 3Cx400sqmm Cable on pole,Structure,tower etc. M 155 0.00 0.00 0.00
1.101 Supply of Linear Heat sensing (LHS) cable as per TPDDL SpecificationsApproved Makes: Patol, Alankar, Ravel M 700 0.00 0.00 0.00
1.102 SITC of Multi - Heat and Smoke -Type Fire detectors as per IS 2189.Blinking Type for health indication. Approved Make : Ravel / System Sensor / Agni Suraksha /ASES / Honeywell with required accessories as per TPDDL specifications. EA 130 0.00 0.00 0.00
1.103 SITC of 1-PhLink Box SVL EA 36 0.00 0.00 0.00
1.104 ITC of 3.3 kv XLPE insulated AL watertig M 180 0.00 0.00 0.00
1.105 Supply of 3.3 kv insulated 1CX300. This item is "3.3kV Sheath Bonding Cable’ for sheath bonding of 66kV Single Core Cables". Cable shall be as per Technical specification ENG-EHV-1042. M 180 0.00 0.00 0.00
1.106 ITC of TRANSFORMER 1.6 MVA 3PH11KV/433V CU on existing plinth and making all connection on 11kV & LV side along with associated works EA 2 0.00 0.00 0.00
1.107 Installation ,testing & commissioning of CIRCUIT BREAKER SF6 66KV 1600A with operating mechanism, GI structure, jumpering/connections grouting works and other accessories as per the approved drawing. All the Electrical and mechanical interlock of breaker should be available in working condition and should be checked before commissioning. This item also includes ITC of castle key & interlocking arrangement for breakers & isolators supplied with the equipment. SET 11 0.00 0.00 0.00
1.108 Installation ,testing & commissioning of CT 66KV 750-500-250/1/1/1/1A 0.2CLASS OD including jumpering/connections. EA 33 0.00 0.00 0.00
1.109 Installation ,testing & commissioning of PT RATIO 66KV/1.73 110V/1.73 O/D 0.2 CLA to be used as line PT/bus PT. This items includes jumpering/connections. EA 15 0.00 0.00 0.00
1.11 Installation ,testing & commissioning of ISOLATOR 66KV 1600A 3PH 25KA CB W/O E/S along with gear box arrangement and other accessories including , jumpering/connections. This item also includes ITC of castle key & interlocking arrangement for breakers & isolators supplied with the equipment. EA 26 0.00 0.00 0.00
1.111 301001440 Supply of 72.5KV ,1600A, 3 Ph gang operated , Manual Operated, Center Break Disconnector (Isolator) with solid core post insulator - Without earth switch with gear box arrangement and other accessories including castle key & interlocking arrangement as per latest TATA Power-DDL specifications. SET 26 0.00 0.00 0.00
1.112 Installation ,testing & commissioning of ISOLATOR 66KV 1600A 3PH 25KA CB WITH E/S With earth switch along with gear box arrangement and other accessories including jumpering/connections. this item also includes ITC of castle key & interlocking arrangement for breakers & isolators supplied with the equipment. EA 11 0.00 0.00 0.00
1.113 301001441 Supply of 72.5KV ,1600A, 3 Ph gang operated , Manual Operated, Center Break Disconnector (Isolator) with solid core post insulator - With earth switch with gear box arrangement and other accessories including castle key & interlocking arrangement as per latest TATA Power-DDL specifications. Castle Lock Earth Switch and Isolator (Castle Lock For Mechanical interlock between Isolator main switch and earth switch )- 1 set SET 11 0.00 0.00 0.00
1.114 Stringing of ACSR conductor and its connection with bus ACSR conductor and those equipment which are not covered under other line items of tender BoM. M 3750 0.00 0.00 0.00
1.115 Installation, Testing & Commissioning of SPACER (Rigid & Flexible) as per TATA Power-DDL standard drawing and project in-charge instructions EA 150 0.00 0.00 0.00
1.116 SITC of High Mast (motorized) 16m as per TATA Power-DDL specifications. Approved Makes : Bajaj/Philips/Surya. This item includes SITC of all required accessories including LED lights & structure etc. but excluding civil works. EA 5 0.00 0.00 0.00
1.117 SITC of Industrial type Air-conditioning package unit (capacity 2 x 2 tonnes) make with auto changeover with required accessories (complete wiring and piping) floor standing type as per TATA Power-DDL latest specifications and site requirement. Refrigerant type shall be R32 or R40 only" shall be as per actual. EA 4 0.00 0.00 0.00
1.118 SITC of 1.5 Ton 5 Star Inverter Split AC as per TATA Power-DDL approved make with auto changeover facility. It also includes the arrangement of AC waste water disposal arrangement (including minor plumbing/civil work) EA 2 0.00 0.00 0.00
1.119 SITC of Bay marshalling kiosk made of 2.5 mm. Thick sheet steel , IP 55 enclosure protection as per specification. EA 12 0.00 0.00 0.00
1.12 SITC of CT/PT Junction Box of 2.5 mm thick sheet steel, IP 55 enclosure protection as per specification. EA 15 0.00 0.00 0.00
1.121 ITC of Single anchoring point single tension line hardware fitting compression type with polymeric/Disc insulators suitable for 66KV tension polymeric insulators, Shackle suitable for 20 mm anchoring hole on beam side, without turn buckle for SINGLE ACSR ZEBRA conductor Complete as per specification. EA 21 0.00 0.00 0.00
1.122 ITC of Single anchoring point single tension line hardware fitting compression type with polymeric/Disc insulators suitable for 66KV tension polymeric insulators, Shackle suitable for 20 mm anchoring hole on beam side, with turn buckle for SINGLE ACSR ZEBRA conductor Complete as per specification. EA 21 0.00 0.00 0.00
1.123 ITC of Single anchoring point Double tension line hardware fitting compression type with polymeric/Disc insulators suitable for 2 x 66KV tension polymeric insulators, Shackle suitable for 20 mm anchoring hole on beam side, without turn buckle for TWIN ACSR ZEBRA conductor Complete as per specification. EA 27 0.00 0.00 0.00
1.124 ITC of Single anchoring point Double tension line hardware fitting compression type with polymeric/Disc insulators suitable for 2 x 66KV tension polymeric insulators, Shackle suitable for 20 mm anchoring hole on beam side, with turn buckle for TWIN ACSR ZEBRA conductor Complete as per specification. EA 27 0.00 0.00 0.00
1.125 ITC of Single suspension Hardware fitting complete with Shackle & polymeric/Disc insulators suitable for 20 mm anchoring hole, all hardware suitable for SINGLE ACSR ZEBRA conductor with through clamp suitable for 66KV suspension polymeric Insulators, complete assembly as per specification. EA 30 0.00 0.00 0.00
1.126 ITC of Single suspension Hardware fitting complete with Shackle & polymeric/Disc insulators suitable for 20 mm anchoring hole, all hardware suitable for TWIN ACSR ZEBRA conductor with through clamp suitable for 66KV suspension polymeric Insulators, complete assembly as per specification. EA 30 0.00 0.00 0.00
1.127 ITC of Single suspension hardware fitting complete with Shackle & polymeric/Disc insulators suitable for 20 mm anchoring hole, all hardware suitable for TWIN ACSR ZEBRA conductor with drop clamp suitable for 66KV suspension polymeric Insulators, complete assembly as per specification. EA 21 0.00 0.00 0.00
1.128 ITC of Single suspension hardware fitting complete with Shackle & polymeric/Disc insulators suitable for 20 mm anchoring hole, all hardware suitable for SINGLE ACSR ZEBRA conductor with drop clamp suitable for 66KV suspension polymeric Insulators, complete assembly as per specification. EA 21 0.00 0.00 0.00
1.129 Dismantling of GI/MS structure as per TATA Power-DDL project in-charge. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. TON 3.9 0.00 0.00 0.00
1.13 Dismantling of Steel tubular pole 8/9/10 mtr long with base plate & cross arm with other arrangement EA 15 0.00 0.00 0.00
1.131 SITC of extension module for AC Distribution Board AC 415V, 400A cubicle type Indoor, floor mounted, auxiliary service board as per TATA Power-DDL specification. (O/G MCBs: 150 A x 1; 63 A x 2, 32 A x 2, 16 A x 4) EA 3 0.00 0.00 0.00
1.132 ITC of 11kV 5 MVAR Reactor Installation ,testing & commissioning of as per TATA Power-DDL specifications. There shall be outdoor bushings on HV side which shall be connected with the overhead bus through brass palm connectors and on LV side shorted . Bushing palm connectors shall be provided for HV bushing. This includes oil filtration of reactor also. EA 6 0.00 0.00 0.00
1.133 ITC of CAPACITOR BANK 7.2MVAR 12.65KV O/D along with Capacitor units, support Structure,NCT,Reactor,Interconnecting Bus-Bar/cable, Lightning Arrestor,Insulators,insulation sleaves,cage fencing & other accessories etc. excluding civil works. as per TATA Power-DDL specifications. EA 2 0.00 0.00 0.00
1.134 SITC of 1-PhLink Box EA 1 0.00 0.00 0.00
1.135 ITC of High Mast (motorized) 12/16m as per TATA Power-DDL specifications. Approved Makes : Bajaj/Philips/Surya. This item includes ITC of all required accessories including LED lights & structure etc. but excluding civil works. EA 1 0.00 0.00 0.00
1.136 Dismantling of High Mast (motorized) 12/16m as per TATA Power-DDL specifications.Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site EA 1 0.00 0.00 0.00
1.137 Dismantling of TRANSFORMER POWER upto 20/25MVA 66/11KV including all accessories & cable mounting structure, BPI, bus bar arrangement, MB,opening of HV/LV connections/jumpers/earthing connection,Fan&stand and dragging up to 30m from the foundation to loading point by using required T&P and wooden sleepers. Loading point may be low bed trailer. The scope of work also includes drain of oil & storage into drums. EA 3 0.00 0.00 0.00
1.138 Dismantling of outdoor neutral CT (NCT) for PTR including its disconnections with PTR/Reactor & NGR/Earth Pit, etc..Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. EA 3 0.00 0.00 0.00
1.139 Dismantling and removing of control cables for grid works including rewounding back on drums or in coils. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. M 2000 0.00 0.00 0.00
1.14 Dismantling of Conductor with insulators & hardware (per mtr per conductor) including stacking at site/store. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. M 30 0.00 0.00 0.00
1.141 Dismantling of CIRCUIT BREAKER 66/33KV including structure as per TATA Power-DDL Project in-charge instructions. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. EA 1 0.00 0.00 0.00
1.142 Dismantling of NIFPS system including pipe arrangement and staking at site EA 1 0.00 0.00 0.00
1.143 Dismantling of Equipment like CT, PT, LA & Isolator Loading, Scope of work also include loading, unloading of material/equipment & transportation up to TPDDL Store/site.Dismantling of healthy equipment's also includes the testing of the equipment before handed over to TATA Power-DDL engineer In charge EA 3 0.00 0.00 0.00
1.144 Dismantling and removing of EHV/HT U/G cables for grid works from the earth or existing power cable trench. This also includes earth excavation (if required) to dismantle the cable and rewounding the cable back on drums or in coils .Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. M 1300 0.00 0.00 0.00
1.145 Dismantling of TRANSFORMER POWER upto 20/25 MVA 33/11KV including all accessories & cable mounting structure, BPI,MB, bus bar arrangement, opening of HV/LV connections/jumpers/earthing connection,Fan&stand and dragging up to 30m from the foundation to loading point by using required T&P and wooden sleepers. Loading point may be low bed trailor.The scope of work also includes drain of oil & storage into drums. EA 1 0.00 0.00 0.00
1.146 ITC of TRANSFORMER POWER 20/25 MVA 33/11KV Installation ,testing & commissioning of 3 Ph, 'Dyn11 ONAN/ ONAF power Transformer with OLTC including fixing of all loose accessories/parts of transformer (supplied with the transformer) ,pre-commissioning checks. Transformer shall be equipped with cable boxes on both the primary and secondary sides. This item includes jumpering/connections on both sides. It also includes testing of transformer at site as per TATA Power-DDL power transformer specifications. This includes oil filtration of transformer. EA 1 0.00 0.00 0.00
1.147 LTC of CABLE 33KV AL 3CX400 SQ MM XLPE ARM (as per TPDDL's specification) already in the excavated trench/already laid pipe M 400 0.00 0.00 0.00
1.148 ITC of Distribution Box 160A TP MCCB EA 1 0.00 0.00 0.00
1.149 Supply of TEREC+ earthing compound KG 100 0.00 0.00 0.00
1.15 ITC of 7/3.15 mm GSS wire including clamps as per TATA Power-DDL approved drawings. M 150 0.00 0.00 0.00
1.151 Dismantling and re-installation of switchyard fence including allied civil works as per TATA Power-DDL Project In-charge. M2 350 0.00 0.00 0.00
1.152 Supply and Laying of insulated mat Class-C ,IS 15652:2006 as per TATA Power-DDL Specifications. (1 meter wide by 2 meters long) 33KV EA 2 0.00 0.00 0.00
1.153 Dismantling of existing 11kV, 7.2 MVAR Cap Bank including accessories,Cage fencing, structure etc. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. EA 1 0.00 0.00 0.00
1.154 Installation ,testing & commissioning of 30KV,10KA, heavy duty, station class, lightning arrestor(LA) & surge counter including laying & connection of 1CX50 sqmm copper flexible cable with LA surge counter. This item includes jumpering/connections. EA 3 0.00 0.00 0.00
1.155 Installation ,testing & commissioning of CT 33KV 750-500/1/1/1/1A CLASS 0.2 O/D including jumpering/connections. EA 3 0.00 0.00 0.00
1.156 Installation ,testing & commissioning of PT RATIO 33KV/1.732(110/1.732) OD 0.2 CL to be used as line PT/bus PT. This items includes jumpering/connections. EA 3 0.00 0.00 0.00
1.157 SITC of beam detectors as per IS 2189. Approved Make : System sensor / Apollo / Edward with required accessories as per TPDDL specifications. EA 5 0.00 0.00 0.00
1.158 SITC of 200MM GI Pipe Class C M 10 0.00 0.00 0.00
1.159 Disconnection, lower down of cables & reconnection of 11kV 3Run/Phase of 1Cx1000sqmm cable in11kV Incomer panel along with other associated works.(Per Panel) EA 2 0.00 0.00 0.00
1.16 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. M2 50 0.00 0.00 0.00
1.161 Dismantling of CT JB,MB EA 5 0.00 0.00 0.00
1.162 SITC of castle key lock arrangement for CB, Isolators (CB to bus isolators & line isolators and between isolators) as per TATA Power-DDL project in-charge instructions (this line item will be executed whenever castle key lock arrangement not available with CB/isolator) EA 2 0.00 0.00 0.00
1.163 Dismantling & re fixing of cable tray M 50 0.00 0.00 0.00
A Total All Inclusive Amount (Rs) - Electrical Services 0.00
2.001 205894 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. M2 1815 0.00 0.00 0.00
2.002 205895 Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) M3 1561.6 0.00 0.00 0.00
2.003 205896 Demolishing cement concrete manually/ by mechanical mEAns including disposal of material within 50 metres lEAd as per direction of Engineer - in - charge. Nominal concrete 1:4:8 or lEAner mix (i/c equivalent design mix) M3 27.5 0.00 0.00 0.00
2.004 205897 Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge. M3 315.4 0.00 0.00 0.00
2.005 205898 Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. In cement mortar M3 291.662 0.00 0.00 0.00
2.006 205900 Dismantling stone slab flooring laid in cement mortar including stacking of serviceable material and disposal of unserviceable material within 50 metres lead. M2 13.2 0.00 0.00 0.00
2.007 205913 Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Cost should include breaking of 1m of top pile head. Note: Truck Mounted rotary/TMR/Tubewell boring mchine shall not be used. (Note :- Min. Cement content shall be 400 KG/M3.) 450 mm dia piles M 3000 0.00 0.00 0.00
2.008 205918 Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections M 1498.4229 0.00 0.00 0.00
2.009 205919 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete at all levels. Thermo-Mechanically Treated bars of grade Fe-500D or more. KG 622235.9347 0.00 0.00 0.00
2.01 205920 Extra for making pointed edge of square bars by hEAting & hammering. EA 100 0.00 0.00 0.00
2.011 205921 Structural steel work in single section fixed with or without connecting plate including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. KG 31988.84 0.00 0.00 0.00
2.012 205922 Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. KG 90953.8593 0.00 0.00 0.00
2.013 205923 Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete. KG 25190.0103 0.00 0.00 0.00
2.014 205924 Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. KG 12585 0.00 0.00 0.00
2.015 205925 P/F 2mm thick MS sheet including welding cutting assembling and erection including a coat of primer as directed by Eng. In charge KG 13191.1366 0.00 0.00 0.00
2.016 205926 Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying a priming coat of approved steel primer. M.S. tube. KG 500 0.00 0.00 0.00
2.017 205927 Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. Fixed to openings /wooden frames with rawl plugs screws etc. KG 623.8839 0.00 0.00 0.00
2.018 205928 Providing and fixing IRC fabric (welded mesh) of desired size to the frame of MS angles, channels, tees, flats etc. including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer as required. In frames, gates etc. (Cost of MS frame will be paid separately). Fixed to steel frames by welding. KG 3105.102 0.00 0.00 0.00
2.019 205929 Providing and fixing concertina coil fencing with punched tape concertina coil 600 mm dia 10 metre openable length ( total length 90 m) having 50 no rounds per 6 metre length, upto 3m height of wall with existing angle iron 'Y' shaped placed 2.4m or 3.00m apart and with 9 horizontal R.B.T. reinforced barbed wire, stud tied with G.I. staples and G.I. clips to retain horizontal including necessary bolts or G.I. barbed wire tied to angle iron, all complete as per direction of Engineer-in-charge, with reinforced barbed tape(R.B.T.) /Spring core (2.5mm thick) wire of high tensile strength of 165 KG/ sq.mm with tape (0.52 mm thick) and weight 43.478gm/ metre (cost of M.S. angle, C.C. blocks shall be paid separately) M 399.89 0.00 0.00 0.00
2.02 205930 Providing and fixing T-iron frames for doors, windows and ventilators of mild steel Tee-sections, joints mitred and welded, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with 15x3 mm lugs 10 cm. long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size). KG 969.5603 0.00 0.00 0.00
2.021 205931 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) KG 897.4816 0.00 0.00 0.00
2.022 205932 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately). :Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) KG 85.5499 0.00 0.00 0.00
2.023 205935 Extra for pre finished nosing in treads of steps of Kota stone/ sand stone slab. M 250 0.00 0.00 0.00
2.024 205937 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 150 mm dia. R.C.C. pipe M 63.9496 0.00 0.00 0.00
2.025 205938 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete: 250 mm dia. R.C.C. pipe M 254.45 0.00 0.00 0.00
2.026 205939 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 300 mm dia. R.C.C. pipe M 259 0.00 0.00 0.00
2.027 205956 Providing and fixing G.I. Pipes complete with G.I. fittings and clamps i/c making good the walls etc. concealed pipe including painting with anti corrosive bitumastic paint, cutting chases and making good the wall - 20 mm dia. nominal bore M 83.7909 0.00 0.00 0.00
2.028 205957 Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work - 25 mm dia. nominal bore M 183.5334 0.00 0.00 0.00
2.029 205962 Providing and fixing soil, waste and vent pipes (Sand cast iron S&S pipe as per IS: 1729)b) 75mm dia M 50 0.00 0.00 0.00
2.03 205973 Dismantling barbed/RBT/concertina wire or flexible wire rope in fencing including making rolls and stacking within 50 metres lead. KG 57.112 0.00 0.00 0.00
2.031 205974 Dismantling expanded metal including chain link fencing or I.R.C. fabrics with necessary battens and beading including stacking the serviceable material within 50 metres lead. M2 781.638 0.00 0.00 0.00
2.032 205975 Dismantling steel work in built up sections in angles, tees, flats and channels including all gusset plates, bolts, nuts, cutting rivets, welding etc. including dismembering and stacking within 50metres lead. KG 1305.92 0.00 0.00 0.00
2.033 205978 Collecting, stacking , screening & respreading of existing yard gravel stone. M3 602.272 0.00 0.00 0.00
2.034 205981 Earth work in excavation for all depths in all kinds of soil by mechanical means (Hydraulic excavator) / manual means including dressing of sides and ramming of bottoms including dewatering of water coming from any source such as rains, accumulated rain water, floods, leakages from sewer, drains, water lines, ground water table being high or due to any other cause whatsoever wherever required by means of suitable capacity of pumps and pipe lines etc. or by any other method during excavation, concreting and also keeping the area dry till the construction is over including close timbering including strutting, shoring and packing cavities, soldier piling, sheet piling or by any other suitable method (wherever required) etc. complete and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed. No additional payment shall be made on account of dewatering and method of shoring/piling adopted for retaining earth whatsoever. M3 18211.8095 0.00 0.00 0.00
2.035 205982 Extra over item for "Earthwork in excavation..... adopted whatsoever" in all kinds of soils for every additional lift of 1.5 m or part thereof. No additional payment shall be made on account of dewatering and method of shoring/piling adopted for retaining earth whatsoever. M3 7515.049 0.00 0.00 0.00
2.036 205983 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and for all lifts. M3 17002.7148 0.00 0.00 0.00
2.037 205985 Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. M3 30.273 0.00 0.00 0.00
2.038 205986 Supplying, diluting and injecting chemical emulsion for Pre-constructional Anti-Termite Treatment and creating a continuous chemical barrier under and all around the column pits, wall trenches, basement excavation, top surface of plinth filling, junction of wall and floor, along the external perimeter of building, expansion joints, over the top surface of consolidated earth on which apron is to be laid, surrounding of pipes and conduits etc. complete as per IS codes & specifications (plinth area of the building at ground floor only shall be measured for payment) with Chlorphyriphos Emulsifiable concentrate 20% with 1% concentration. M2 1780.872 0.00 0.00 0.00
2.039 205989 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) M3 8.8 0.00 0.00 0.00
2.04 205991 Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 12.5mm nominal size derived from natural sources) M2 3.3 0.00 0.00 0.00
2.041 205993 Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth. M2 42.35 0.00 0.00 0.00
2.042 205994 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. All works upto plinth level. Concrete of M25 grade with minimum cement content of 330 kg /cum M3 3934.3965 0.00 0.00 0.00
2.043 205995 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. All works above plinth level upto floor V level. Concrete of M25 grade with minimum cement content of 330 kg /cum M3 816.7482 0.00 0.00 0.00
2.044 205996 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 cement : 2 coarse sand (zone-III) including manufactured sand derived from Recycled Concrete Aggregate (RCA) upto 25% : 4 graded stone aggregate 20 mm nominal size Recycled Concrete Aggregate (RCA) upto 25%) M3 71.4535 0.00 0.00 0.00
2.045 205998 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Foundations, footings, bases of columns, etc. for mass concrete. M2 3162.1558 0.00 0.00 0.00
2.046 205999 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. M2 10347.1507 0.00 0.00 0.00
2.047 206000 Centering and shuttering including strutting, propping etc. and removal of form for all heights: Suspended floors, roofs, landings, balconies and access platform. M2 2216.6694 0.00 0.00 0.00
2.048 206001 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Lintels, beams, plinth beams, girders, bressumers and cantilevers. M2 4031.5867 0.00 0.00 0.00
2.049 206002 Centering and shuttering including strutting, propping etc. and removal of form for for all heights : Columns, Pillars, Piers, Abutments, Posts and Struts. M2 6414.6442 0.00 0.00 0.00
2.05 206003 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Stairs, (excluding landings) except spiral-staircases. M2 125 0.00 0.00 0.00
2.051 206004 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Weather shade, Chajjas, Corbels etc., including edges. M2 44.2187 0.00 0.00 0.00
2.052 206005 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) M3 247.0193 0.00 0.00 0.00
2.053 206007 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) M3 1252.0608 0.00 0.00 0.00
2.054 206009 Extra for providing and placing in position 2 Nos. 6mm dia. M.S. bars at every third course of half brick masonry. M2 50 0.00 0.00 0.00
2.055 206010 12 mm cement plaster of mix for all heights: 1:4 (1 cement: 4 fine sand) M2 8705.5604 0.00 0.00 0.00
2.056 206012 15 mm cement plaster on the rough side of single or half brick wall of mix for all heights: 1:4 (1 cement: 4 fine sand) M2 7638.5668 0.00 0.00 0.00
2.057 206014 6 mm cement plaster of mix for all heights: 1:3 (1 cement: 3 fine sand) M2 1153.9891 0.00 0.00 0.00
2.058 206016 Providing and fixing Chicken-mesh of 1.5 mm dia. steel wire with hexagonal or rectangular openings of 20-25 mm 150 mm wide fixed with U nails at 150 mm centre to centre placed and held properly in position at brick and R.C.C joints as per direction of engineer-in-charge. M2 250 0.00 0.00 0.00
2.059 206017 Neat cement punning M2 605.0145 0.00 0.00 0.00
2.06 206018 Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 -part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25mm M.S. laths with 1.25 mm thick top cover. M2 100.92 0.00 0.00 0.00
2.061 206019 Providing and fixing GI chain link fabric fencing of required width in mesh size 75x75 mm, 3.15 mm dia. mesh wire as per drawing conforming to IS:2721, MS stirrups wire 2.5 mm dia. with tying wire 1.6 mm dia. including providing 25x4.75 mm stretcher bars, eye bolt 85 mm half round staples etc. including nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. (MS Flat, angle etc. will be paid separately). M2 349.25 0.00 0.00 0.00
2.062 206021 Providing and fixing stainless steel (SS 304 grade) adjustable friction windows stays of approved quality with necessary stainless steel screws etc. to the side hung windows as per direction of Engineerin-charge complete.255 X 19 mm EA 17.6 0.00 0.00 0.00
2.063 206023 Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 KG., for doors, including cost of cutting floors ,embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. With stainless steel cover plate minimum 1.25 mm thickness. EA 5 0.00 0.00 0.00
2.064 206024 Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS:12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides. M2 125 0.00 0.00 0.00
2.065 206027 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 4.0 mm thickness (weight not less than 10 kg/ sqm) M2 73.7022 0.00 0.00 0.00
2.066 206028 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5 mm thickness (weight not less than 12.50 kg/ sqm) M2 93.47 0.00 0.00 0.00
2.067 206029 Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/M2 (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the rate of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm or both sides of joint and two coats of primer suitable for board, all as per manufacture's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : 12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- Part I.: 2011 (Board with BIS certification marks) M2 129.4046 0.00 0.00 0.00
2.068 206031 Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 KG/M2. of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto300mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to115mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand)admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with waterproofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs c)After two days of proper curing applying a second coat of cement slurry using 2.75KG/ M2 of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge. d)Finishing the surface with 20 mm thick jointless cement mortar of mix1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : With average thickness of 120mm and minimum thickness at khurra as 65 mm. M2 2181.9531 0.00 0.00 0.00
2.069 206033 Providing and fixing GI chain link fabric fencing of required width in mesh size 75x75 mm, 3.15 mm dia. mesh wire PVC coated to achieve outer dia. not less than 4.15 mm in required colour and shadeas per drawing conforming to IS:2721, MS stirrups wire 2.5 mm dia. with tying wire 1.6 mm dia. including providing 25x4.75 mm stretcher bars, eye bolt 85 mm half round staples etc. including nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. (MS Flat, angle etc. will be paid separately). M2 375 0.00 0.00 0.00
2.07 206035 Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet1mx1mx400micron, finished with 12mm cement plaster 1:3 (1 cement :3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. EA 115 0.00 0.00 0.00
2.071 206037 Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade New work (two or more coats) over and including water thinnable priming coat with cement primer. M2 2481.8244 0.00 0.00 0.00
2.072 206039 Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 KG/10 M2). M2 3331.5714 0.00 0.00 0.00
2.073 206040 Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade: Two or more coats on new work. M2 29.3282 0.00 0.00 0.00
2.074 206041 Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work. M2 6207.4005 0.00 0.00 0.00
2.075 206044 Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick. M2 1174.9407 0.00 0.00 0.00
2.076 206045 Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. M2 129.5853 0.00 0.00 0.00
2.077 206046 Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer ) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3KG per M2 including pointing in white cement mixed with pigment of matching shade complete. M2 37.9698 0.00 0.00 0.00
2.078 206047 Providing and laying Ceramic glazed floor tiles 300x300 or 400x400 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS :15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4Coarse sand) including pointing the joints with white cement and matching pigment etc., complete. M2 6.9773 0.00 0.00 0.00
2.079 206053 Supplying, laying & spreading machine crushed 65 mm good quality stone aggregates including compacing the same. M3 130.658 0.00 0.00 0.00
2.08 206054 Disposal of all debris/rubbish/malba/surplus excavated earth/similar unserviceable, dismantled or waste materials arising out of demolition and construction activities, by mechanical means, including loading, transporting, unloading to authorized Construction and Demolition (C&D) waste recycling plant or approved municipal dumping ground as per the directions of TPDDL Engineer-in-charge, for all leads including all lifts involved. Bidder solely shall be responsible for identifying such area and bear all costs involved, TPDDL shall not be liable for the same. Bidder shall clear the site thoroughly of such unwanted materials and rubbish etc. left out of his work and dress the site to the satisfaction of the TPDDL Engineer-in-Charge in all respects before the final handing over. Nothing additional shall be paid on account of disposal of waste material to construction and demolition (C&D) waste recycling plant. M3 4243.3873 0.00 0.00 0.00
2.081 206055 Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. L 8542 0.00 0.00 0.00
2.082 206058 Providing and fixing aluminium tower bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade with necessary screws etc. complete : 200x10 mm EA 50 0.00 0.00 0.00
2.083 206059 Providing and fixing aluminium handles ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete : 125 mm EA 23.2 0.00 0.00 0.00
2.084 206060 Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. EA 5 0.00 0.00 0.00
2.085 206068 Supplying and fixing C.I. cover without frame for manholes : 610x610 mm rectangular C.I. cover (light duty) the weight of the cover to be not less than 23 KG. EA 19.9 0.00 0.00 0.00
2.086 206070 Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm. depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earth with lead upto 50 metres. M2 429 0.00 0.00 0.00
2.087 206071 Supplying and stacking at site. 90 mm to 45 mm size stone aggregate. M3 42.9 0.00 0.00 0.00
2.088 206072 Supplying and stacking at site. 63 mm to 45 mm size stone aggregate. M3 32.175 0.00 0.00 0.00
2.089 206073 Supplying and stacking at site. Stone screening 13.2 mm nominal size (Type A) M3 6.435 0.00 0.00 0.00
2.09 206074 Laying, spreading and compacting stone aggregate of specified sizes to WBM specifications in uniform thickness, hand picking, rolling with 3 wheeled road / vibratory roller 8-10 tonne capacity in stages to proper grade and camber, applying and brooming requisite type of screening / binding material to fill up interstices of coarse aggregate, watering and compacting to the required density M3 75.075 0.00 0.00 0.00
2.091 206075 Providing and laying R.C.C./ C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator, vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-incharge. (The panel shuttering work and steel reinforcement shall be paid for separately). (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately). M3 95.7 0.00 0.00 0.00
2.092 206076 Providing and fixing in position 12mm thick bitumen impregnated per cm fiber board conforming to IS: 1838, including cost of primer, sealing depth per compound Grade-A in expansion joints M2 9.9 0.00 0.00 0.00
2.093 206077 Providing and filling in position bitumen mix filler of proportion 80 KG. of hot bitumen, 1 KG. of cement and 0.25 cubic metre of coarse sand for expansion joints. M3 2.475 0.00 0.00 0.00
2.094 206079 Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge M3 155.7696 0.00 0.00 0.00
2.095 206081 Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -in -charge. M3 5 0.00 0.00 0.00
2.096 206087 Providing and fixing 20 mm dia., 1.2 mtr long each GI rungs as per the directions of Engineer-In-Charge EA 166.6 0.00 0.00 0.00
2.097 206091 Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreouschina flushing cistern & C.P. flush bend with fittings & C.I.brackets,40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal designcomplete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : W.C. pan with ISI marked white solid plastic seat and lid EA 2.2 0.00 0.00 0.00
2.098 206092 Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with white PVC automatic flushing cistern,with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS :2556, C.I. trap with outlet grating and other couplings in C.P. brass, including painting of fittings and cutting and making good the walls and floors wherever required : Single half stall urinal with 5 litre P.V.C. automatic flushing cistern EA 2.2 0.00 0.00 0.00
2.099 206093 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require : White Vitreous China Flat back wash basin size 550x400 mm with single 15 mm C.P. brass pillar tap EA 7.2 0.00 0.00 0.00
2.1 206094 Providing and fixing 600 x 450 mm bevelled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board sheet ground fixed to wooden cleats with C.P. brass screws and washers complete. EA 7.2 0.00 0.00 0.00
2.101 206095 P/F CP brass toilet paper holder of approved quality and make. EA 2.2 0.00 0.00 0.00
2.102 206096 Providing and fixing brass bib cock of approved quality: 15 mm nominal bore EA 2.2 0.00 0.00 0.00
2.103 206104 Providing and filling the joints with spun yarn cement, slurry and cement mortar 1:2 ( 1 cement: 2 fine sand) in S.C.I/C.I pipes b) 75mm dia EA 10 0.00 0.00 0.00
2.104 206105 Providing and fixing plain bend of required degree (Sand cast iron S&S as per IS 1729)a) 100mm EA 10 0.00 0.00 0.00
2.105 206108 P/F PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fitting of approved quality and colour weighing not less than 105 gms. EA 7.2 0.00 0.00 0.00
2.106 206109 Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour 450 mm long towel rail with total length of 495 mm,78 mm wide and effective height of 88 mm, weighing not less than 170 gms EA 7.2 0.00 0.00 0.00
2.107 206110 P/f CP jali for nahni trap with or without hole using white cement and pigment to match the tile colour, complete. EA 13.8 0.00 0.00 0.00
2.108 206112 Providing and fixing gun metal non-return valve of approved quality (screwed end) 25mm nominal bore. Horizontal (ISI) EA 5 0.00 0.00 0.00
2.109 206113 Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 KG and frame to be not less than 2.70 KG as per standard design : 150x100 mm P type. With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 EA 5 0.00 0.00 0.00
2.11 206126 Fencing with angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and end post on one side only and provided with horizontal lines and two diagonals interwoven with horizontal wires, of barbed wire weighing 9.38 KG per 100 m (minimum), between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete. (Cost of posts, struts, earth work and concrete work to be paid for separately) :-Payment to be made per metre cost of total length of barbed wire used. With G.I. barbed wire M 381.7 0.00 0.00 0.00
2.111 206163 Dismantling manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge : Water bound macadam road, Wet mix macadam road, Granular sub-base or any type of base and sub base course laid in between wearing course and subgrade. M2 3725.4 0.00 0.00 0.00
2.112 206174 Dismantling steel work in single sections including dismembering and stacking within 50 metres lead in: Channels, angles, tees an d flats KG 330 0.00 0.00 0.00
2.113 206241 Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter M 633.1468 0.00 0.00 0.00
2.114 206270 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer’s specifications including appropriate priming coat, preparation of surface, etc. complete. On steel work M2 1000 0.00 0.00 0.00
2.115 206352 Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. M2 2513 0.00 0.00 0.00
2.116 206353 Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. EA 102.504 0.00 0.00 0.00
2.117 206373 Providing & fixing mild steel round holding down bolts including nuts & washer plates complete KG 125 0.00 0.00 0.00
2.118 206482 Providing and fixing expansion hold fasteners on C.C. /R.C.C./Brick masonry surface backing including drilling necessary holes and the cost of bolt etc complete. Wedge expansion type Fastener with threaded dia 10 mm EA 50 0.00 0.00 0.00
2.119 206495 Providing & Laying C.C in brick ballast in 1:6:12 (1 Cement : 6 Coarse Sand : 12 Brick aggregate) mix. ( E ) M3 771.242 0.00 0.00 0.00
2.12 206496 Supplying, laying & spreading machine crushed 20 mm good quality blue colour stone aggregates including compacting the same. M3 1098.56 0.00 0.00 0.00
2.121 206497 Supplying chemical emulsion in sealed containers including delivery, diluting and applying for antiweed treatment in yard as specified by manufacturer. M2 3971.664 0.00 0.00 0.00
2.122 206536 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion powder coated aluminium (minimum thickness of powder coating 50 micron) KG 16.5 0.00 0.00 0.00
2.123 206537 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coating 50 micron) KG 16.5 0.00 0.00 0.00
2.124 206624 Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design : With common burnt clay F.P.S. (non-modular) bricks of class designation 7.5 EA 9.4 0.00 0.00 0.00
2.125 206628 Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour : Two coats M2 151.195 0.00 0.00 0.00
2.126 206631 Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. Flexible pipe 40 mm dia EA 5 0.00 0.00 0.00
2.127 206659 Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) : 25 mm nominal bore EA 5 0.00 0.00 0.00
2.128 206660 Providing and fixing GI union in GI pipe including cutting & threading the pipe & making long screws etc. complete (new work). 20mm nominal bore EA 5 0.00 0.00 0.00
2.129 206698 Making construction joint, first cutting groove 5x30 mm deep with special blade in concrete road and then filling the grooves 5x15 mm deep with polysulphide sealant over an expanded polyethene backer rod including rounding of the edges, etc. all complete. M 99 0.00 0.00 0.00
2.13 206853 Add for using extra cement in the items of design mix over and above the specified cement content therein. KG 75484.144 0.00 0.00 0.00
2.131 206871 Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) including manufactured and derived from Recycled Concrete Aggregate (RCA) upto 25% : 4 graded stone aggregate 12.5mm nominal size inclcuding (Recycled Conceret Aggregate (RCA) upto 25%)) M2 50 0.00 0.00 0.00
2.132 206921 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement,water tanks, roof slabs, podiums, reservior,sewage & water treatment plant, tunnels/subway and bridge deck etc., prepared by mixing in the ratio of 5:2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3:1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative ( internal) side with the help of synthetic fibre brush.The material shall meet the requirements as specified in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure in negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry for 10 years against any leakage. For horizontal surface one [email protected] per sqm. M2 250 0.00 0.00 0.00
2.133 206922 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement,water tanks, roof slabs, podiums, reservior,sewage & water treatment plant, tunnels/subway and bridge deck etc., prepared by mixing in the ratio of 5:2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3:1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative ( internal) side with the help of synthetic fibre brush.The material shall meet the requirements as specified in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure in negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry for 10 years against any leakage. For vertical surface two [email protected] kg per sqm per coat M2 250 0.00 0.00 0.00
2.134 206923 Providing and mixing integral crystalline admixture for waterproofing treatment to RCC structures like basement raft, retaining walls, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc. at the time of transporting of concrete into the drum of the ready mixed truck, using integral crystalline admixture @0.80% (minimum) to the weight of cement content per cubic meter of concrete)or heigher as recommended by the manufacturer's specification in reinforced cement concrete at site of work. the material shall meet the requirements as specified in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90%, compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure. The crystalline admixture shall be capable of self- healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the Engineer-in-charge. The product performance shall carry gurantee for 10 years against any leakage. KG 250 0.00 0.00 0.00
2.135 207033 Providing and laying autoclaved aerated concrete (AAC) blocks masonry 100mm/125mm thick with Grade-1 AAC blocks of density 551 to 650 KG/CUM conforming to IS:2185 (Part 3) in super structure above plinth level up to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rate includes providing and placing in position 2 Nos 6 mm dia M.S. bars at every third course of masonry work. M3 50 0.00 0.00 0.00
2.136 207113 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design :150 mm diameter S.W. pipe M 25 0.00 0.00 0.00
2.137 207442 Extra for providing mechanical device chain and crank operation for operating rolling shutters - upto 16.80 sqm in the area M2 7.2 0.00 0.00 0.00
2.138 207462 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 cement : 4 manufactured sand derived from Recycled Concrete Aggregate (RCA) : 8 graded stone aggregate 40 mm nominal size Recycled Aggregate (RCA) M3 728.9509 0.00 0.00 0.00
2.139 207465 Cutting of cores in reinforced concrete structures upto 200 mm dia. and 300 mm depth EA 140.7 0.00 0.00 0.00
2.14 207501 Providing and fixing 25 mm thick Fibreglass Reinforced Plastic grating of mesh size 38X38 mm, rib thickness 5-7 mm complete as per approved drawings in colour as approved by TPDDL EIC. M2 250 0.00 0.00 0.00
2.141 207525 Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 manufactured sand derived from Recycled Concrete Aggregate (RCA) : 6 graded stone aggregate 20 mm nominal size (Recycled Aggregate (RA) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth M2 102.7 0.00 0.00 0.00
2.142 207538 Providing and fixing unplasticised P.V.C. in Stainless Steel finished connection pipe with brass unions: 45 cm length-15 mm nominal bore. EA 5 0.00 0.00 0.00
2.143 208350 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 manufactured sand derived from Recycled Concrete Aggregate (RCA) : 6 graded stone aggregate 20 mm nominal size Recycled Concrete Aggregate (RCA) M3 75.611 0.00 0.00 0.00
2.144 208351 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:5:10 (1 cement : 5 manufactured sand derived from Recycled Concrete Aggregate (RCA) : 10 graded stone aggregate 40 mm nominal size Recycled Aggregate (RCA) ) M3 25 0.00 0.00 0.00
2.145 208352 Providing and fixing precast reinforced cement concrete work in cable trench covers, including the cost of required centering, shuttering but, excluding cost of reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). M3 214.692 0.00 0.00 0.00
2.146 208401 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 200 mm dia (OD-200 mm & ID-175 mm nominal) M3 71.6 0.00 0.00 0.00
2.147 208411 Providing and laying 60mm thick factory made cement concrete paver block of approved shape and colour of M -30 grade made of C&D waste by block making machine with vibratory compaction laid in required pattern and including over 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge. M2 250 0.00 0.00 0.00
2.148 208892 Providing and laying Geotextile membrane, 120 gsm non woven, 100% polyester of thickness 1 to 1.25 mm. M2 15 0.00 0.00 0.00
2.149 208893 Providing and filling Brick bats of 40 mm nominal size under flooring etc. i/c compaction by ramming and levelling top surface complete M3 10 0.00 0.00 0.00
2.15 208894 Supplying and laying charcoal in rain water harvesting recharge pit. M3 5 0.00 0.00 0.00
2.151 208922 Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). KG 500 0.00 0.00 0.00
2.152 208923 Providing and fixing stainless steel (SS-304 grade) friction hinges to the side/ top hung uPVC windows, of approved quality, with necessary stainless steel screws etc. as per direction of Engineer-in-charge. 200 x 19 x 1.9 mm EA 20 0.00 0.00 0.00
2.153 209063 Providing and applying two coats of High Albedo paint having minimum Solar Reflective Index (SRI) 108 (with solar reflectance & thermal emittance tested as per ASTM) C 1549 and ASTM C 1371 respectively), VOC less than 10 cc/gm. The coating thickness and the methodology of application shall strctly as per manufacturer's specifications and as approved by Engineer-in-Charge. Surface preparation includes cleaning with metal wire brush to remove all dust, fungus etc., washing with water all complete. The contractor shall give guarantee for the perfomance of SRI and also the durabitity of coating, all complete as per direction of Engineer-in-Charge. M2 1059.8 0.00 0.00 0.00
2.154 209064 Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour all complete to achieve even shade and colour: new work (two or more coats) over and including water thinnable priming coat with cement primer having COC content less than 50g/L M2 2488.8 0.00 0.00 0.00
2.155 209065 Finishing walls with readymix Premium acrylic emulsion paint (Company Depot Tinted) having VOC less than 50 gm/litre and UV resis tance as per IS:15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade with silicon additives. N ew work (Two or more coats applied @ 1.43 litre/ 10 sqm Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm. M2 71.5 0.00 0.00 0.00
2.156 209068 Brickwork with Recycled CC Bricks of size 230x110x75 mm (M10 Grade) in foundation and plinth in :- (a) Cement Mortar 1:6 (1 cement : 6 coarse sand) M3 205.5 0.00 0.00 0.00
2.157 209069 Brickwork with Recycled CC Bricks of size 230x110x75 mm (M10 Grade) in superstructure above plinth level upto floor V level in all shapes and sizes :- (a) Cement Mortar 1:4 (1 cement : 4 coarse sand) M3 50 0.00 0.00 0.00
2.158 209412 Drilling suitable holes in reinforced or plain cement concrete with power driven drill machine to a minimum depth of 100mm upto 2 00mm in RCC beams, lintels, columns and slabs to introduce steel bars for sunshades/balconies including fixing the steel bars in p osition using epoxy resin anchor grout of approved make but excluding the cost of reinforcement, all complete as per direction of Engineer-In-Charge. Upto and including 12mm dia. (approved make HILTI) EA 275 0.00 0.00 0.00
2.159 209413 Design & detailing, testing and installation of appropriate sizes of reinforcement anchorages or splices fixed into existing hard ened concrete by injecting adhesives in drilled holes after cleaning of the holes to connect new reinforcement to existing walls a nd slab. BA shall visit the site and collect necessary details required for carrying out the work and submit complete proposal for TPDDL approval before execution of work at site. (approved make HILTI) - 16 to 28 dia. bar EA 825 0.00 0.00 0.00
2.16 209415 Supplying and Filling screened soil procured from MCD approved C&D waste recycling plant and carriage for all leads including spreading in required thickness as per the directions of TPDDL Engineer-In-Charge and compacting under optimum moisture conditions to give at least 95% of the maximum dry density (proctor density). Cubical quantity of compacted earth only shall be measured and paid. M3 750 0.00 0.00 0.00
2.161 209428 Attaining IGBC Green Service Buildings Certification for Substation Building. The scope of services towards attaining the desired IGBC Rating would include but not limited to the following: i. Project Registration with IGBC ii. Performing the feasibiliy iv. Facilitation, Documentation and Submission of project details for IGBC rating v. Simulation services including Energy Simulation, Day-light Simulation etc. vi. IGBC Review & Comments response to achieve the anticipated rating For detailed scope of work, refer Special Conditions of Contract. The cost shall shall be inclusive of all expenses including Application Fees, Council Fees, Consultancy Fees, Travel, Liasioning with IGBC for Certification and Documentation etc. IGBC Application Fees shall be paid on producing payment receipts by BA and balance payment shall be made after the Certification is received from IGBC. EA 5 0.00 0.00 0.00
2.162 209429 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources and using recycled concrete aggregate (RCA) as coarse aggregate and fine aggregate within permissible utilization of 20% each, Portland Pozzolana /Ordinary Portland/Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum M3 75 0.00 0.00 0.00
2.163 209452 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 1200 mm dia. R.C.C. pipe M 25 0.00 0.00 0.00
2.164 209456 Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.80 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineerin-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. M2 75 0.00 0.00 0.00
2.165 209457 Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. Made of G.I. wire of dia. 4 mm, PVC coated to achieve outer dia not less than 5 mm in required colour and shade M2 154 0.00 0.00 0.00
2.166 new-1 Finishing walls with readymix Premium acrylic emulsion paint (Company Depot Tinted) having VOC less than 50 gm/litre and UV resistance as per IS:15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade with silicon additives. New work (Two or more coats applied @ 1.43 litre/ 10 sqm Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm. M2 8075 0.00 0.00 0.00
B Total All Inclusive Amount (Rs) - Civil Services 0.00
A+B Total All Inclusive Amount (Rs.) Electrical + Civil Services 0.00
Annexure-1 (Schedule of Item)
NIT No - TPDDL/ENGG/ENQ/200001981/26-27
NIT Description - 1 Year Rate Contract (RC) for 66kV & 33kV EHV Bay Extension with associated Electrical & Civil works at Various Locations in TPDDL area
S. NO. TPDDL Service Code Item Descr. UOM Quantity "A" Unit Rate (Rs.) "a" Applicable GST (in Rs.) "b" Price per Unit (in Rs.) "B"= a+b TPDDL Amt (in Rs.) C=A*B HSN/ SAC code
Electrical Services
1.001 ITC of TRANSFORMER POWER 25/31.5MVA-9 NORMALTAP:Installation ,testing & commissioning of 3 Ph, 'Dyn11 ONAN/ ONAF power Transformer with OLTC including fixing of all loose accessories/parts of transformer (supplied along with the transformer), pre-commissioning checks. There shall be outdoor bushings on HV side which shall be connected with over head conductors or power cables through external open bus bar arrangement comprising of brass palm connectors, 100mm X 10mm Tinned Copper Flat with HS Insulating Sleeve Busbar and on LV side cable box will be available. LV side busbars shall connect to 1CX1000sqmm 3 runs of 11kV Al XLPE cable per phase. This item includes the jumpering/connections/termination on both sides. It also includes testing of transformer at site as per TATA Power-DDL power transformer specifications. This includes oil filtration of transformer. EA 21 0.00 0.00 0.00
1.002 Dragging of TRANSFORMER POWER upto 25/31.5MVA-9 NORMALTAP from unloading point to foundation ( up to 20 meters) or vice versa with complete safety measures as per TATA Power-DDL project in-charge instructions. M 300 0.00 0.00 0.00
1.003 Installation ,testing & commissioning of outdoor neutral CT (NCT) for PTR including its connections with PTR/Reactor & NGR/Earth Pit, etc.. EA 22 0.00 0.00 0.00
1.004 To provide brazing for all joints/connections required as per site condition between NCT and Copper earth plate, for earthing of NCT at as per TATA Power-DDL earthing philosophy. One set means all requirements for one NCT. EA 22 0.00 0.00 0.00
1.005 Installation ,testing & commissioning of LA 60KV 10KA, heavy duty, station class, lightning arrestor(LA) & surge counter including laying & connection of 1CX50 sqmm copper flexible cable with LA surge counter. This item includes jumpering/connections. EA 66 0.00 0.00 0.00
1.006 Installation ,testing & commissioning of 66kV Post Insulator including jumpering/connections. EA 66 0.00 0.00 0.00
1.007 SITC of clamp & connectors required for connection of 66kV BPI with 2.5 inch IPS tube EA 66 0.00 0.00 0.00
1.008 SITC of clamp & connectors required for connection of 66kV LA with 2.5 inch IPS tube EA 36 0.00 0.00 0.00
1.009 SITC of connector for connection of 66kV cable termination lug with 2.5 inch IPS tube EA 36 0.00 0.00 0.00
1.01 LTC of CABLE 66KV AL 1X1000 SQMM ARM XLPE along with trefoil clamp in already excavated trench/available trench/vertical mounting.(cable shall be Free Issued by TATA Power-DDL). Application of Fire paint(including supply) at transformer end it shall be up to sand filling in trench, and in switchgear room it shall be from switchgear to building entry point. Sealing of cable to be provided at entries as per TATA Power-DDL Standard Drawing . Quantity shall be paid per meter of each cable laid. M 4930 0.00 0.00 0.00
1.011 LTC of CABLE 11KV AL 1X1000 SQMM ARM XLPE along with trefoil clamp in already excavated trench/available trench/vertical mounting.(cable shall be Free Issued by TATA Power-DDL.Cable shall be 2 runs / Phase for 20/25 , 16/20 MVA and 3 runs/phase for 25/31.5 MVA power Transformer to 11 kV Switchgear Panel ). Application of Fire paint(including supply) at transformer end it shall be up to sand filling in trench, and in switchgear room it shall be from switchgear to building entry point. Sealing of cable to be provided at entries as per TATA Power-DDL Standard Drawing . Quantity shall be paid per meter of each cable laid M 25820 0.00 0.00 0.00
1.012 LTC of CABLE 1.1KV AL 4CX95 SQMM ARM (For AC & DC Supply) for ACDB to Battery charger & Filtration industrial socket M 1450 0.00 0.00 0.00
1.013 LTC of CABLE 1.1KV AL 4CX16 SQMM ARM M 4100 0.00 0.00 0.00
1.014 LTC of CABLE 1.1KV AL 4CX25 SQMM ARM M 6750 0.00 0.00 0.00
1.015 LTC of CABLE 11KV AL 3CX300/400 SQMM XLPE ARM (cable shall be Free Issued by TATA Power-DDL). From 11 kV Switchgear to 250kVA/160 KVA Transformer in already excavated trench/available trench/vertical mounting. Application of Fire paint(including supply) in cable trench portion shall be in scope of this activity. M 1400 0.00 0.00 0.00
1.016 LTC of CABLE 1.1KV AL 3.5CX300 SQMM XLPE ARM or CABLE 1.1KV AL 4CX300 SQMM XLPE ARM for station transformer M 950 0.00 0.00 0.00
1.017 LTC of CABLE CONTROL 1.1KV CU 4CX2.5 SQMM ARM M 16000 0.00 0.00 0.00
1.018 LTC of CABLE CONTROL 1.1KV CU 12CX2.5 SQMM ARM M 9850 0.00 0.00 0.00
1.019 LTC of CABLE CONTROL 1.1KV CU 19CX2.5 SQMM ARM M 10750 0.00 0.00 0.00
1.02 LTC of CABLE CONTROL 1.1KV CU 6CX4 SQMM ARM M 11950 0.00 0.00 0.00
1.021 LTC of CABLE CONTROL 1.1KV CU 2CX6 SQMM ARM (For D.C.) M 6300 0.00 0.00 0.00
1.022 LTC of CABLE CONTROL 1.1KV CU 2CX50SQ.MM FLEX. M 300 0.00 0.00 0.00
1.023 SITC of 50x6mm CU flat for Transformer neutral earthing including required earth excavation for laying earth flat. This item excludes brazing activity. M 525 0.00 0.00 0.00
1.024 SITC of Earthing with Electrolytic grade copper plate 600mmx600mmx6mm including 50x6mm copper flat and other accessories and providing masonry enclosure with cover plate to be provided in 6 mtr deep earth pit to be filled With earth enhancement material as per IEEE80:2000,14.5(D) and TATA Power-DDL standard earthing philosophy. Earth Enhancement material approval is mandatory before erection activity. EA 44 0.00 0.00 0.00
1.025 SITC of 100 mm dia GI pipe-6 meter length earth electrode with treated earth Pit heavy class with Treated Earth Pits. With earth enhancement material as per IEEE80:2000,14.5(D). This item includes civil goomties required for earth pit as per TATA Power-DDL standard earthing philosophy and specification. Earth Enhancement compound (Minimum Terec-5 KG and Earthcon-12.5KG) is to be used for every earth pit till the earthing value of each pit is achieved below 02 Ohms EA 74 0.00 0.00 0.00
1.026 SITC of 100 mm dia GI pipe-3 meter length earth electrode with treated earth Pit heavy class with Treated Earth Pits. With earth enhancement material as per IEEE80:2000,14.5(D). This item includes civil goomties required for earth pit as per TATA Power-DDL standard earthing philosophy and specification. Earth Enhancement compound (Minimum Terec-5 KG and Earthcon-12.5KG) is to be used for every earth pit till the earthing value of each pit is achieved below 02 Ohms EA 56 0.00 0.00 0.00
1.027 SITC of 100 mm dia GI pipe-6 meter length earth electrode with treated earth Pit heavy class with Treated Earth Pits without goomty. With earth enhancement material as per IEEE80:2000,14.5(D).. Earth Enhancement compound (Minimum Terec-5 KG and Earthcon-12.5KG) is to be used for every earth pit till the earthing value of each pit is achieved below 02 Ohms EA 44 0.00 0.00 0.00
1.028 SITC of 100 mm dia GI pipe-3 meter length earth electrode with treated earth Pit heavy class with Treated Earth Pits without goomty. With earth enhancement material as per IEEE80:2000,14.5(D).. Earth Enhancement compound (Minimum Terec-5 KG and Earthcon-12.5KG) is to be used for every earth pit till the earthing value of each pit is achieved below 02 Ohms EA 36 0.00 0.00 0.00
1.029 SITC of building spikes, 20mm dia GI rod (2.5Meter length) EA 80 0.00 0.00 0.00
1.03 ITC of TRANSFORMER 250KVA 3PH 11KV/433V with cable box on HV/LV sides as per TATA Power-DDL specifications including jumpering/connections. EA 5 0.00 0.00 0.00
1.031 SITC of Double compression glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables of the sizes (diameter between 12mm to 18mm ) EA 280 0.00 0.00 0.00
1.032 SITC of Double compression glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables of the sizes (diameter between 18mm to 24mm ) EA 650 0.00 0.00 0.00
1.033 SITC of Double compression glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables of the sizes (diameter more than 24mm) EA 380 0.00 0.00 0.00
1.034 SITC of Double compression glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore CU conductor control cables of the various sizes up to 12 mm EA 66 0.00 0.00 0.00
1.035 SITC of cable cleat (Nylon-6) size up to 100mm EA 244 0.00 0.00 0.00
1.036 SITC of cable cleat (Nylon-6) size greater than 100mm EA 74 0.00 0.00 0.00
1.037 ITC of Cable Cleats of various size EA 150 0.00 0.00 0.00
1.038 Supply of Trefoil Clamp for suitable for 66kV and/or 11kV 1Cx1000sq.mm Power Cable as per TATA Power-DDL Specification/Drawing EA 315 0.00 0.00 0.00
1.039 SITC of IP54 Lighting junction box for each Light at tower suitable for out door installation comprising of 8 no. CBT M 4 type terminal connector for light connections or loop in / loop out cable EA 35 0.00 0.00 0.00
1.04 SITC of AC Distribution Board AC 415V, 400A cubicle type Indoor, floor mounted, auxiliary service board as per TATA Power-DDL specification EA 7 0.00 0.00 0.00
1.041 SITC of astro timer control for lighting arrangement. This item shall be executed as per TATA Power-DDL Engineering In-charge. EA 6 0.00 0.00 0.00
1.042 SITC of industrial type Control room lighting including all accessories:- LED luminaire 2x16/18/20W industrial type fitting with LED luminaire. Suitable for Surface/Suspended mounting EA 84 0.00 0.00 0.00
1.043 SITC of industrial type Control room lighting including all accessories:- LED luminaire 2x36/40W industrial type fitting with LED luminaire. Suitable for Surface/Suspended mounting EA 118 0.00 0.00 0.00
1.044 SITC of flame proof fluorescent fitting including all accessories:-LED luminaire 2x36/40W flame proof acid proof fitting with LED lamp for Battery Room/Cable cellar room. Suitable for Surface/Suspended mounting EA 24 0.00 0.00 0.00
1.045 SITC Installation of LED 120W luminaire with required fittings and accessories as per TATA Power-DDL specifications. EA 177 0.00 0.00 0.00
1.046 Supply, Installation ,testing & commissioning of AC 415V 400A Street Light panel AC 415V, 400A ,50 KA for 1 Sec cubicle type Outdoor, Plinth mounted, Street light panel as per specification comprising of the following: Incomer 63A TTPNMCCB -1 No. Metering with RYB indicating lamp LED type, Voltmeter with selector switch, ammeter with selector switch , suitable CT's & 2A TPNMCB for backup protection of voltmeter & indication light. 1 No. 70A FP CONTACTOR -1 No. 24 Hr. timer for auto Operation Auto manual selector switch , I set push button for on/off operation.Outgoing feeder 25A TPNMCB 4 Nos. 63A Power industrial socket with "C" series TPNMCB for Protection & provision of up to 3.5c X 50 sqmm Al Arm cable Termination as per TATA Power-DDL specifications. EA 6 0.00 0.00 0.00
1.047 SITC of IP 54 Lighting Distribution Board for control room lighting control comprising of one no, incomer 63 A TPN MCB & 18 no. out going as 10-32A SP MCB. EA 25 0.00 0.00 0.00
1.048 SITCof Power Distribution Board for control room air conditioner comprising of one no, incomer 63 A TPN MCB & 6 no. out going as 32A TPN MCB. With auto changeover for Air conditioner EA 14 0.00 0.00 0.00
1.049 SITC of IP 54 protected 150A three phase industrial socket with 150A TPN MCB for oil filtration machine with 3x6.0 sqmm PVC insulated copper conductor stranded insulated wires & 2x1.5sqmm Stranded Green earth wire in recessed and/or on surface 40mm dia GI conduit including chasing of wall, filling of chases etc. complete in all respect. EA 6 0.00 0.00 0.00
1.05 SITC of 32A three phase industrial socket with 32A TPN MCB AC power point with 3x6.0 sqmm PVC insulated copper conductor stranded insulated wires & 2x1.5sqmm Stranded Green earth wire in recessed and/or on surface 40mm dia GI/PVC conduit including chasing of wall, filling of chases etc. complete in all respect. EA 42 0.00 0.00 0.00
1.051 Supply & laying of HDPE Pipe Size 200 mm dia (PN-4 PE80) as per TATA Power-DDL specifications M 660 0.00 0.00 0.00
1.052 Supply & laying of HDPE Pipe Size 100 mm dia (PN-4 PE80) for control cables in the out door yard M 350 0.00 0.00 0.00
1.053 Supply, Fabrication and installation of GI structural steel material for gantry tower, beam, equipment's, cable mounting structure, tower mounting structure, LA Structure,BPI , drain crossing structure etc., where ever required as per approved drawing including nuts, bolts, washer & clamps. TON 132 0.00 0.00 0.00
1.054 SITC of 75 x 12 mm G I flat Main Earth mat, Aux Earth mat & Earthing Risers for Main Equipment's & structures etc. This item includes required earth excavation & backfilling for laying earth flat including exothermic wielding ,anticorrosive coatings i.e. red oxide and bitumen KG 38900 0.00 0.00 0.00
1.055 SITC of 50x6 GI flat for Aux earth material Earthing conductor for connection of , L.T panel, Junction box, & building Lightning risers & peak Connection etc. This item includes required earth excavation & backfilling for laying earth flat including exothermic wielding ,anticorrosive coatings i.e. red oxide and bitumen. KG 26300 0.00 0.00 0.00
1.056 Supply and Installation of GI PERFORATED TRAY 150MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 230 0.00 0.00 0.00
1.057 Supply and Installation of GI PERFORATED TRAY 300MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 1050 0.00 0.00 0.00
1.058 Supply and Installation of GI PERFORATED TRAY 600MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 600 0.00 0.00 0.00
1.059 Supply and Installation of GI LADDER CABLE TRAY 300MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 950 0.00 0.00 0.00
1.06 Supply and Installation of GI LADDER CABLE TRAY 600MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 950 0.00 0.00 0.00
1.061 SITC of aluminum IPS tube busbar with endcaps of 2.5 inches suitable for minimum 1600A Rated Current of required length with insulated Raychem BPTM sleeves of 66kV class. The IPS tube shall conform to IS:5082 and IS:2673. M 198 0.00 0.00 0.00
1.062 SITC of One light point by One Switch wiring of above light point, with 1.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 62 0.00 0.00 0.00
1.063 SITC of Two light point by One Switch wiring of above light point, with 1.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1.0 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 51 0.00 0.00 0.00
1.064 SITC of Three light point by One switch wiring of above light point, with 1.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1.0 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 40 0.00 0.00 0.00
1.065 SITC Flood light point -2.5 sqmm cu wiring wiring of above light point, with 2.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1.0 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 90 0.00 0.00 0.00
1.066 SITC of Exhaust fan point wiring of above exhaust fan point, with 1.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1.0 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 45 0.00 0.00 0.00
1.067 SITC of wiring of General power point with 4.0 sq.mm PVC insulated copper conductor single core stranded wires in GI/pVC conduit with 2.5 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling of chases etc. com EA 47 0.00 0.00 0.00
1.068 Supply of Fire barriers at cable entrances in control room ( EA means each entry) for 4 hrs. rating as per TATA Power-DDL specifications EA 22 0.00 0.00 0.00
1.069 SITC of Fire retardant coating on cables with required accessories as per TATA Power-DDL specifications (this item to be used only if not covered in other line items activity) KG 600 0.00 0.00 0.00
1.07 SITC of EPDM based cable entry/exits sealing system for 11kv power cables (for one PTR - 9 cables) including required minor civil works as per TATA Power-DDL specifications. This also includes provision of 20% spares modules for future cables laying or replacement activity EA 23 0.00 0.00 0.00
1.071 SITC of EPDM based cable entry/exits sealing system for 11 kV outgoing power cables for (10 cables) including required minor civil works as per TATA Power-DDL specifications. This also includes provision of 20% spares modules for future cables laying or replacement activity EA 8 0.00 0.00 0.00
1.072 FIRE EXTINGUISHER CO2 CAP 6.5 KG SITC of Fire Extinguishers CO2 type 6.5Kg for switchgear room, control room, engineer room with required accessories as per latest TATA Power-DDL latest specifications. EA 40 0.00 0.00 0.00
1.073 SITC of Fire Extinguishers Dry powder chemical type 25 kg with required accessories as per TPDDL specifications.(For PTR) EA 22 0.00 0.00 0.00
1.074 SITC of Fire Extinguishers CO2 type 22.5 kg with required accessories as per TPDDL specifications.(For PTR) EA 14 0.00 0.00 0.00
1.075 SITC of ISI marked Fire Extinguishers -ABC Type 9 Kg for Switch room and other locations (IS:15683) Approved Make : Ceasefire / Minimax / Safex with required accessories as per TPDDL specifications. EA 36 0.00 0.00 0.00
1.076 SITC of ISI marked Fire Extinguishers -ABC Type 6 Kg for Switch room and other locations (IS:13849) Approved Make : Ceasefire / Minimax / Safex EA 28 0.00 0.00 0.00
1.077 SITC of wall mounted type Micro Processor based fire alarm panel with made of 16 SWG CRCA sheet, inbuilt Battery Box, comprising of Audio/ visual alarm indication of fire & fault etc., min. 16X2 line LCD display, time and date on LCD, complete with 100 event data logger with date and time stamp, indications for fire, fault, main power and battery as per ENG-GEN-4046. The panel shall also contain annunciation, window type indicators for fire and fault. Panel should support (a) NO-NC contact for fire alarm communication to BCPU (b) Capability of Ethernet Communication though RTU to centralized monitoring system (c) Data download to PC through USB. (c) ATX key board for field programming (d) PA system connectivity for announcement and altering (e) GSM functionality as per TPDDL specifications. Panel shall contain built-in battery charger and battery (Approved makes: Exide / Amaron / APC / Su-kam) for 48 hrs. back up in normal case and 30 min back up in case of alarm.Approved Make: Ravel / System Sensor / Agni Suraksha / ASES / Honeywell EA 10 0.00 0.00 0.00
1.078 SITC of Installation, Testing and Commissioning of Manual Call box with push button reset type as per IS 2189 Approved Make : Ravel / System Sensor / Agni Suraksha / ASES / Honeywell with required accessories as per TPDDL specifications. EA 13 0.00 0.00 0.00
1.079 SITC of Electronic Hooters (min 110 db intensity required) made out of ABS (colour RED) Approved Make : Ravel / System Sensor / Agni Suraksha / ASES / Honeywell with required accessories as per TPDDL specifications. EA 13 0.00 0.00 0.00
1.08 SITC of Installation, Testing and Commissioning of Response indicator as per IS 2189 Approved Make : Ravel / System Sensor / Agni Suraksha / ASES / Honeywell with required accessories as per TPDDL specifications. EA 54 0.00 0.00 0.00
1.081 SITC of Cable (FRLS in PO Red Color) cable 2 core* 1.5mm. Approved Makes: Polycab / Finolex / Gloster / RR Kabel / Havells M 2300 0.00 0.00 0.00
1.082 SITC of All safety items like First aid box - 1 no., safety Gloves - 2 pair., Safety Display board / Warning signs - 1 lot, accident prevention chart - 1 nos., shock treatment chart - 2 no., Grid SLD on wooden board- 1 no. on A0 size, (For complete grid) SET 16 0.00 0.00 0.00
1.083 SITC of Sand Bucket along with stand(8 buckets) as per IS2546.The sand bucket should be clearly labeled and contain only clean, dry sand. Fire buckets should be made of heavy gauge galvanized steel, have a 9/10 liter capacity, and be painted red on the outside and white on the inside with the word "FIRE" stamped in large letters EA 22 0.00 0.00 0.00
1.084 SITC of LOTO station as per TATA Power-DDL project In-Charge EA 16 0.00 0.00 0.00
1.085 ITC of electrical panel lock out base with cover as per TATA Power-DDL project In-Charge EA 16 0.00 0.00 0.00
1.086 Supply and Laying of insulated mat Class-A ,IS 15652:2006 as per TATA Power-DDL Specifications. (1 meter wide by 2 meters long) LV(3.3kV)/DC EA 42 0.00 0.00 0.00
1.087 Supply and Laying of insulated mat Class-B ,IS 15652:2006as per TATA Power-DDL Specifications. (1 meter wide by 2 meters long) 11KV EA 122 0.00 0.00 0.00
1.088 SITC of asset numbering- Complete identification of all the assets/equipment’s, RCC cable trench cover marking in the approve color and numbering to be done with detailed description of the asset as per the requirement of project in-charge. This includes Supply of paints and other required material to complete the activity. (This item shall be paid per PTR Bay/ Line Bay,) LOT 22 0.00 0.00 0.00
1.089 SITC of Grid signs boards i.e. safety notices such as "Danger of Death," "High Voltage," and "No Trespassing," along with fire safety signs like "Fire Alarm" and "Fire Exit Keep Clear," and protective equipment information like "Wear Safety Helmet" and "First Aid", Prohibition signs, Hazard signs, Emergency information signs, Fire Equipment signs at various locations. The exact signs may vary by location, but the purpose is to warn of hazards, instruct on safety procedures. LOT 16 0.00 0.00 0.00
1.09 Supply and Fixing of the Danger plates on the poles/tower/structure including fabrication of clamp etc. EA 64 0.00 0.00 0.00
1.091 SITC of Earth Insulator (DMC) EA 205 0.00 0.00 0.00
1.092 Transportation of various items from stores to site or from site to site or from site to store including loading and unloading: with tempo 709/410 EA 28 0.00 0.00 0.00
1.093 Supply of Vacuum Cleaner as per TATA Power-DDL project in-charge instructions. Approved make : Eureka Forbes Pro Vac WD 77 EA 5 0.00 0.00 0.00
1.094 SITC of industrial type continuous heavy duty Exhaust fan with louvers, 18 inches including auto-changeover facility. Approved make: Bajaj/Crompton/Havells EA 61 0.00 0.00 0.00
1.095 SITC of Industrial type Dewatering/submersible/sewage pump (fixed type) 415 V, 2 HP, automatic ON/OFF feature,Pre-fitted float switch ensure that the pump start and stop automatically as per need and including required plumbing items(union, valves, sockets, CPVC pipe etc.) & connections along with outlet flexible nylon braided PVC pipe - 30 meters. including all accessories if required. Approved make - Crompton/Kirloskar EA 7 0.00 0.00 0.00
1.096 SITCof Industrial type Dewatering/submersible/sewage pump (portable type) 415 V, 1 HP, automatic ON/OFF facility and including required plumbing connections along with outlet flexible nylon braided PVC pipe - 30 meters. - Approved make - Crompton/Kirloskar EA 18 0.00 0.00 0.00
1.097 SITC of BLDC ceiling fan, 48 '' as per TATA Power-DDL project in-charge instructions. Approved Make : Crompton/Bajaj/Havells EA 47 0.00 0.00 0.00
1.098 SITC of BLDC wall mounted fan 400 mm, 1350 rpm, auto swing. Approved make : Bajaj/Havells/Crompton EA 14 0.00 0.00 0.00
1.099 Supply of platform type FRP ladder 3M height, extra heavy duty ladder for all industrial application as per TATA Power-DDL specifications. EA 6 0.00 0.00 0.00
1.1 Mounting of 66/33 KV 1Cx1000sqmm & 33KV 3Cx400sqmm Cable on pole,Structure,tower etc. M 155 0.00 0.00 0.00
1.101 Supply of Linear Heat sensing (LHS) cable as per TPDDL SpecificationsApproved Makes: Patol, Alankar, Ravel M 700 0.00 0.00 0.00
1.102 SITC of Multi - Heat and Smoke -Type Fire detectors as per IS 2189.Blinking Type for health indication. Approved Make : Ravel / System Sensor / Agni Suraksha /ASES / Honeywell with required accessories as per TPDDL specifications. EA 130 0.00 0.00 0.00
1.103 SITC of 1-PhLink Box SVL EA 36 0.00 0.00 0.00
1.104 ITC of 3.3 kv XLPE insulated AL watertig M 180 0.00 0.00 0.00
1.105 Supply of 3.3 kv insulated 1CX300 M 180 0.00 0.00 0.00
1.106 ITC of TRANSFORMER 1.6 MVA 3PH11KV/433V CU on existing plinth and making all connection on 11kV & LV side along with associated works EA 2 0.00 0.00 0.00
1.107 Installation ,testing & commissioning of CIRCUIT BREAKER SF6 66KV 1600A with operating mechanism, GI structure, jumpering/connections grouting works and other accessories as per the approved drawing. All the Electrical and mechanical interlock of breaker should be available in working condition and should be checked before commissioning. This item also includes ITC of castle key & interlocking arrangement for breakers & isolators supplied with the equipment. SET 11 0.00 0.00 0.00
1.108 Installation ,testing & commissioning of CT 66KV 750-500-250/1/1/1/1A 0.2CLASS OD including jumpering/connections. EA 33 0.00 0.00 0.00
1.109 Installation ,testing & commissioning of PT RATIO 66KV/1.73 110V/1.73 O/D 0.2 CLA to be used as line PT/bus PT. This items includes jumpering/connections. EA 15 0.00 0.00 0.00
1.11 Installation ,testing & commissioning of ISOLATOR 66KV 1600A 3PH 25KA CB W/O E/S along with gear box arrangement and other accessories including , jumpering/connections. This item also includes ITC of castle key & interlocking arrangement for breakers & isolators supplied with the equipment. EA 26 0.00 0.00 0.00
1.111 301001440 Supply of 72.5KV ,1600A, 3 Ph gang operated , Manual Operated, Center Break Disconnector (Isolator) with solid core post insulator - Without earth switch with gear box arrangement and other accessories including castle key & interlocking arrangement as per latest TATA Power-DDL specifications. SET 26 0.00 0.00 0.00
1.112 Installation ,testing & commissioning of ISOLATOR 66KV 1600A 3PH 25KA CB WITH E/S With earth switch along with gear box arrangement and other accessories including jumpering/connections. this item also includes ITC of castle key & interlocking arrangement for breakers & isolators supplied with the equipment. EA 11 0.00 0.00 0.00
1.113 301001441 Supply of 72.5KV ,1600A, 3 Ph gang operated , Manual Operated, Center Break Disconnector (Isolator) with solid core post insulator - With earth switch with gear box arrangement and other accessories including castle key & interlocking arrangement as per latest TATA Power-DDL specifications. Castle Lock Earth Switch and Isolator (Castle Lock For Mechanical interlock between Isolator main switch and earth switch )- 1 set SET 11 0.00 0.00 0.00
1.114 Stringing of ACSR conductor and its connection with bus ACSR conductor and those equipment which are not covered under other line items of tender BoM. M 3750 0.00 0.00 0.00
1.115 Installation, Testing & Commissioning of SPACER (Rigid & Flexible) as per TATA Power-DDL standard drawing and project in-charge instructions EA 150 0.00 0.00 0.00
1.116 SITC of High Mast (motorized) 16m as per TATA Power-DDL specifications. Approved Makes : Bajaj/Philips/Surya. This item includes SITC of all required accessories including LED lights & structure etc. but excluding civil works. EA 5 0.00 0.00 0.00
1.117 SITC of Industrial type Air-conditioning package unit (capacity 2 x 2 tonnes) make with auto changeover with required accessories (complete wiring and piping) floor standing type as per TATA Power-DDL latest specifications and site requirement. Refrigerant type shall be R32 or R40 only" shall be as per actual. EA 4 0.00 0.00 0.00
1.118 SITC of 1.5 Ton 5 Star Inverter Split AC as per TATA Power-DDL approved make with auto changeover facility. It also includes the arrangement of AC waste water disposal arrangement (including minor plumbing/civil work) EA 2 0.00 0.00 0.00
1.119 SITC of Bay marshalling kiosk made of 2.5 mm. Thick sheet steel , IP 55 enclosure protection as per specification. EA 12 0.00 0.00 0.00
1.12 SITC of CT/PT Junction Box of 2.5 mm thick sheet steel, IP 55 enclosure protection as per specification. EA 15 0.00 0.00 0.00
1.121 ITC of Single anchoring point single tension line hardware fitting compression type with polymeric/Disc insulators suitable for 66KV tension polymeric insulators, Shackle suitable for 20 mm anchoring hole on beam side, without turn buckle for SINGLE ACSR ZEBRA conductor Complete as per specification. EA 21 0.00 0.00 0.00
1.122 ITC of Single anchoring point single tension line hardware fitting compression type with polymeric/Disc insulators suitable for 66KV tension polymeric insulators, Shackle suitable for 20 mm anchoring hole on beam side, with turn buckle for SINGLE ACSR ZEBRA conductor Complete as per specification. EA 21 0.00 0.00 0.00
1.123 ITC of Single anchoring point Double tension line hardware fitting compression type with polymeric/Disc insulators suitable for 2 x 66KV tension polymeric insulators, Shackle suitable for 20 mm anchoring hole on beam side, without turn buckle for TWIN ACSR ZEBRA conductor Complete as per specification. EA 27 0.00 0.00 0.00
1.124 ITC of Single anchoring point Double tension line hardware fitting compression type with polymeric/Disc insulators suitable for 2 x 66KV tension polymeric insulators, Shackle suitable for 20 mm anchoring hole on beam side, with turn buckle for TWIN ACSR ZEBRA conductor Complete as per specification. EA 27 0.00 0.00 0.00
1.125 ITC of Single suspension Hardware fitting complete with Shackle & polymeric/Disc insulators suitable for 20 mm anchoring hole, all hardware suitable for SINGLE ACSR ZEBRA conductor with through clamp suitable for 66KV suspension polymeric Insulators, complete assembly as per specification. EA 30 0.00 0.00 0.00
1.126 ITC of Single suspension Hardware fitting complete with Shackle & polymeric/Disc insulators suitable for 20 mm anchoring hole, all hardware suitable for TWIN ACSR ZEBRA conductor with through clamp suitable for 66KV suspension polymeric Insulators, complete assembly as per specification. EA 30 0.00 0.00 0.00
1.127 ITC of Single suspension hardware fitting complete with Shackle & polymeric/Disc insulators suitable for 20 mm anchoring hole, all hardware suitable for TWIN ACSR ZEBRA conductor with drop clamp suitable for 66KV suspension polymeric Insulators, complete assembly as per specification. EA 21 0.00 0.00 0.00
1.128 ITC of Single suspension hardware fitting complete with Shackle & polymeric/Disc insulators suitable for 20 mm anchoring hole, all hardware suitable for SINGLE ACSR ZEBRA conductor with drop clamp suitable for 66KV suspension polymeric Insulators, complete assembly as per specification. EA 21 0.00 0.00 0.00
1.129 Dismantling of GI/MS structure as per TATA Power-DDL project in-charge. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. TON 3.9 0.00 0.00 0.00
1.13 Dismantling of Steel tubular pole 8/9/10 mtr long with base plate & cross arm with other arrangement EA 15 0.00 0.00 0.00
1.131 SITC of extension module for AC Distribution Board AC 415V, 400A cubicle type Indoor, floor mounted, auxiliary service board as per TATA Power-DDL specification. (O/G MCBs: 150 A x 1; 63 A x 2, 32 A x 2, 16 A x 4) EA 3 0.00 0.00 0.00
1.132 ITC of 11kV 5 MVAR Reactor Installation ,testing & commissioning of as per TATA Power-DDL specifications. There shall be outdoor bushings on HV side which shall be connected with the overhead bus through brass palm connectors and on LV side shorted . Bushing palm connectors shall be provided for HV bushing. This includes oil filtration of reactor also. EA 6 0.00 0.00 0.00
1.133 ITC of CAPACITOR BANK 7.2MVAR 12.65KV O/D along with Capacitor units, support Structure,NCT,Reactor,Interconnecting Bus-Bar/cable, Lightning Arrestor,Insulators,insulation sleaves,cage fencing & other accessories etc. excluding civil works. as per TATA Power-DDL specifications. EA 2 0.00 0.00 0.00
1.134 SITC of 1-PhLink Box EA 1 0.00 0.00 0.00
1.135 ITC of High Mast (motorized) 12/16m as per TATA Power-DDL specifications. Approved Makes : Bajaj/Philips/Surya. This item includes ITC of all required accessories including LED lights & structure etc. but excluding civil works. EA 1 0.00 0.00 0.00
1.136 Dismantling of High Mast (motorized) 12/16m as per TATA Power-DDL specifications.Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site EA 1 0.00 0.00 0.00
1.137 Dismantling of TRANSFORMER POWER upto 20/25MVA 66/11KV including all accessories & cable mounting structure, BPI, bus bar arrangement, MB,opening of HV/LV connections/jumpers/earthing connection,Fan&stand and dragging up to 30m from the foundation to loading point by using required T&P and wooden sleepers. Loading point may be low bed trailer. The scope of work also includes drain of oil & storage into drums. EA 3 0.00 0.00 0.00
1.138 Dismantling of outdoor neutral CT (NCT) for PTR including its disconnections with PTR/Reactor & NGR/Earth Pit, etc..Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. EA 3 0.00 0.00 0.00
1.139 Dismantling and removing of control cables for grid works including rewounding back on drums or in coils. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. M 2000 0.00 0.00 0.00
1.14 Dismantling of Conductor with insulators & hardware (per mtr per conductor) including stacking at site/store. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. M 30 0.00 0.00 0.00
1.141 Dismantling of CIRCUIT BREAKER 66/33KV including structure as per TATA Power-DDL Project in-charge instructions. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. EA 1 0.00 0.00 0.00
1.142 Dismantling of NIFPS system including pipe arrangement and staking at site EA 1 0.00 0.00 0.00
1.143 Dismantling of Equipment like CT, PT, LA & Isolator Loading, Scope of work also include loading, unloading of material/equipment & transportation up to TPDDL Store/site.Dismantling of healthy equipment's also includes the testing of the equipment before handed over to TATA Power-DDL engineer In charge EA 3 0.00 0.00 0.00
1.144 Dismantling and removing of EHV/HT U/G cables for grid works from the earth or existing power cable trench. This also includes earth excavation (if required) to dismantle the cable and rewounding the cable back on drums or in coils .Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. M 1300 0.00 0.00 0.00
1.145 Dismantling of TRANSFORMER POWER upto 20/25 MVA 33/11KV including all accessories & cable mounting structure, BPI,MB, bus bar arrangement, opening of HV/LV connections/jumpers/earthing connection,Fan&stand and dragging up to 30m from the foundation to loading point by using required T&P and wooden sleepers. Loading point may be low bed trailor.The scope of work also includes drain of oil & storage into drums. EA 1 0.00 0.00 0.00
1.146 ITC of TRANSFORMER POWER 20/25 MVA 33/11KV Installation ,testing & commissioning of 3 Ph, 'Dyn11 ONAN/ ONAF power Transformer with OLTC including fixing of all loose accessories/parts of transformer (supplied with the transformer) ,pre-commissioning checks. Transformer shall be equipped with cable boxes on both the primary and secondary sides. This item includes jumpering/connections on both sides. It also includes testing of transformer at site as per TATA Power-DDL power transformer specifications. This includes oil filtration of transformer. EA 1 0.00 0.00 0.00
1.147 LTC of CABLE 33KV AL 3CX400 SQ MM XLPE ARM (as per TPDDL's specification) already in the excavated trench/already laid pipe M 400 0.00 0.00 0.00
1.148 ITC of Distribution Box 160A TP MCCB EA 1 0.00 0.00 0.00
1.149 Supply of TEREC+ earthing compound KG 100 0.00 0.00 0.00
1.15 ITC of 7/3.15 mm GSS wire including clamps as per TATA Power-DDL approved drawings. M 150 0.00 0.00 0.00
1.151 Dismantling and re-installation of switchyard fence including allied civil works as per TATA Power-DDL Project In-charge. M2 350 0.00 0.00 0.00
1.152 Supply and Laying of insulated mat Class-C ,IS 15652:2006 as per TATA Power-DDL Specifications. (1 meter wide by 2 meters long) 33KV EA 2 0.00 0.00 0.00
1.153 Dismantling of existing 11kV, 7.2 MVAR Cap Bank including accessories,Cage fencing, structure etc. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. EA 1 0.00 0.00 0.00
1.154 Installation ,testing & commissioning of 30KV,10KA, heavy duty, station class, lightning arrestor(LA) & surge counter including laying & connection of 1CX50 sqmm copper flexible cable with LA surge counter. This item includes jumpering/connections. EA 3 0.00 0.00 0.00
1.155 Installation ,testing & commissioning of CT 33KV 750-500/1/1/1/1A CLASS 0.2 O/D including jumpering/connections. EA 3 0.00 0.00 0.00
1.156 Installation ,testing & commissioning of PT RATIO 33KV/1.732(110/1.732) OD 0.2 CL to be used as line PT/bus PT. This items includes jumpering/connections. EA 3 0.00 0.00 0.00
1.157 SITC of beam detectors as per IS 2189. Approved Make : System sensor / Apollo / Edward with required accessories as per TPDDL specifications. EA 5 0.00 0.00 0.00
1.158 SITC of 200MM GI Pipe Class C M 10 0.00 0.00 0.00
1.159 Disconnection, lower down of cables & reconnection of 11kV 3Run/Phase of 1Cx1000sqmm cable in11kV Incomer panel along with other associated works.(Per Panel) EA 2 0.00 0.00 0.00
1.16 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. M2 50 0.00 0.00 0.00
1.161 Dismantling of CT JB,MB EA 5 0.00 0.00 0.00
1.162 SITC of castle key lock arrangement for CB, Isolators (CB to bus isolators & line isolators and between isolators) as per TATA Power-DDL project in-charge instructions (this line item will be executed whenever castle key lock arrangement not available with CB/isolator) EA 2 0.00 0.00 0.00
1.163 Dismantling & re fixing of cable tray M 50 0.00 0.00 0.00
A Total All Inclusive Amount (Rs) - Civil Services 0.00
2.001 205894 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. M2 1815 0.00 0.00 0.00
2.002 205895 Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) M3 1561.6 0.00 0.00 0.00
2.003 205896 Demolishing cement concrete manually/ by mechanical mEAns including disposal of material within 50 metres lEAd as per direction of Engineer - in - charge. Nominal concrete 1:4:8 or lEAner mix (i/c equivalent design mix) M3 27.5 0.00 0.00 0.00
2.004 205897 Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge. M3 315.4 0.00 0.00 0.00
2.005 205898 Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. In cement mortar M3 291.662 0.00 0.00 0.00
2.006 205900 Dismantling stone slab flooring laid in cement mortar including stacking of serviceable material and disposal of unserviceable material within 50 metres lead. M2 13.2 0.00 0.00 0.00
2.007 205913 Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Cost should include breaking of 1m of top pile head. Note: Truck Mounted rotary/TMR/Tubewell boring mchine shall not be used. (Note :- Min. Cement content shall be 400 KG/M3.) 450 mm dia piles M 3000 0.00 0.00 0.00
2.008 205918 Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections M 1498.4229 0.00 0.00 0.00
2.009 205919 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete at all levels. Thermo-Mechanically Treated bars of grade Fe-500D or more. KG 622235.9347 0.00 0.00 0.00
2.01 205920 Extra for making pointed edge of square bars by hEAting & hammering. EA 100 0.00 0.00 0.00
2.011 205921 Structural steel work in single section fixed with or without connecting plate including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. KG 31988.84 0.00 0.00 0.00
2.012 205922 Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. KG 90953.8593 0.00 0.00 0.00
2.013 205923 Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete. KG 25190.0103 0.00 0.00 0.00
2.014 205924 Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. KG 12585 0.00 0.00 0.00
2.015 205925 P/F 2mm thick MS sheet including welding cutting assembling and erection including a coat of primer as directed by Eng. In charge KG 13191.1366 0.00 0.00 0.00
2.016 205926 Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying a priming coat of approved steel primer. M.S. tube. KG 500 0.00 0.00 0.00
2.017 205927 Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. Fixed to openings /wooden frames with rawl plugs screws etc. KG 623.8839 0.00 0.00 0.00
2.018 205928 Providing and fixing IRC fabric (welded mesh) of desired size to the frame of MS angles, channels, tees, flats etc. including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer as required. In frames, gates etc. (Cost of MS frame will be paid separately). Fixed to steel frames by welding. KG 3105.102 0.00 0.00 0.00
2.019 205929 Providing and fixing concertina coil fencing with punched tape concertina coil 600 mm dia 10 metre openable length ( total length 90 m) having 50 no rounds per 6 metre length, upto 3m height of wall with existing angle iron 'Y' shaped placed 2.4m or 3.00m apart and with 9 horizontal R.B.T. reinforced barbed wire, stud tied with G.I. staples and G.I. clips to retain horizontal including necessary bolts or G.I. barbed wire tied to angle iron, all complete as per direction of Engineer-in-charge, with reinforced barbed tape(R.B.T.) /Spring core (2.5mm thick) wire of high tensile strength of 165 KG/ sq.mm with tape (0.52 mm thick) and weight 43.478gm/ metre (cost of M.S. angle, C.C. blocks shall be paid separately) M 399.89 0.00 0.00 0.00
2.02 205930 Providing and fixing T-iron frames for doors, windows and ventilators of mild steel Tee-sections, joints mitred and welded, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with 15x3 mm lugs 10 cm. long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size). KG 969.5603 0.00 0.00 0.00
2.021 205931 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) KG 897.4816 0.00 0.00 0.00
2.022 205932 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately). :Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) KG 85.5499 0.00 0.00 0.00
2.023 205935 Extra for pre finished nosing in treads of steps of Kota stone/ sand stone slab. M 250 0.00 0.00 0.00
2.024 205937 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 150 mm dia. R.C.C. pipe M 63.9496 0.00 0.00 0.00
2.025 205938 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete: 250 mm dia. R.C.C. pipe M 254.45 0.00 0.00 0.00
2.026 205939 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 300 mm dia. R.C.C. pipe M 259 0.00 0.00 0.00
2.027 205956 Providing and fixing G.I. Pipes complete with G.I. fittings and clamps i/c making good the walls etc. concealed pipe including painting with anti corrosive bitumastic paint, cutting chases and making good the wall - 20 mm dia. nominal bore M 83.7909 0.00 0.00 0.00
2.028 205957 Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work - 25 mm dia. nominal bore M 183.5334 0.00 0.00 0.00
2.029 205962 Providing and fixing soil, waste and vent pipes (Sand cast iron S&S pipe as per IS: 1729)b) 75mm dia M 50 0.00 0.00 0.00
2.03 205973 Dismantling barbed/RBT/concertina wire or flexible wire rope in fencing including making rolls and stacking within 50 metres lead. KG 57.112 0.00 0.00 0.00
2.031 205974 Dismantling expanded metal including chain link fencing or I.R.C. fabrics with necessary battens and beading including stacking the serviceable material within 50 metres lead. M2 781.638 0.00 0.00 0.00
2.032 205975 Dismantling steel work in built up sections in angles, tees, flats and channels including all gusset plates, bolts, nuts, cutting rivets, welding etc. including dismembering and stacking within 50metres lead. KG 1305.92 0.00 0.00 0.00
2.033 205978 Collecting, stacking , screening & respreading of existing yard gravel stone. M3 602.272 0.00 0.00 0.00
2.034 205981 Earth work in excavation for all depths in all kinds of soil by mechanical means (Hydraulic excavator) / manual means including dressing of sides and ramming of bottoms including dewatering of water coming from any source such as rains, accumulated rain water, floods, leakages from sewer, drains, water lines, ground water table being high or due to any other cause whatsoever wherever required by means of suitable capacity of pumps and pipe lines etc. or by any other method during excavation, concreting and also keeping the area dry till the construction is over including close timbering including strutting, shoring and packing cavities, soldier piling, sheet piling or by any other suitable method (wherever required) etc. complete and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed. No additional payment shall be made on account of dewatering and method of shoring/piling adopted for retaining earth whatsoever. M3 18211.8095 0.00 0.00 0.00
2.035 205982 Extra over item for "Earthwork in excavation..... adopted whatsoever" in all kinds of soils for every additional lift of 1.5 m or part thereof. No additional payment shall be made on account of dewatering and method of shoring/piling adopted for retaining earth whatsoever. M3 7515.049 0.00 0.00 0.00
2.036 205983 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and for all lifts. M3 17002.7148 0.00 0.00 0.00
2.037 205985 Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. M3 30.273 0.00 0.00 0.00
2.038 205986 Supplying, diluting and injecting chemical emulsion for Pre-constructional Anti-Termite Treatment and creating a continuous chemical barrier under and all around the column pits, wall trenches, basement excavation, top surface of plinth filling, junction of wall and floor, along the external perimeter of building, expansion joints, over the top surface of consolidated earth on which apron is to be laid, surrounding of pipes and conduits etc. complete as per IS codes & specifications (plinth area of the building at ground floor only shall be measured for payment) with Chlorphyriphos Emulsifiable concentrate 20% with 1% concentration. M2 1780.872 0.00 0.00 0.00
2.039 205989 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) M3 8.8 0.00 0.00 0.00
2.04 205991 Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 12.5mm nominal size derived from natural sources) M2 3.3 0.00 0.00 0.00
2.041 205993 Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth. M2 42.35 0.00 0.00 0.00
2.042 205994 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. All works upto plinth level. Concrete of M25 grade with minimum cement content of 330 kg /cum M3 3934.3965 0.00 0.00 0.00
2.043 205995 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. All works above plinth level upto floor V level. Concrete of M25 grade with minimum cement content of 330 kg /cum M3 816.7482 0.00 0.00 0.00
2.044 205996 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 cement : 2 coarse sand (zone-III) including manufactured sand derived from Recycled Concrete Aggregate (RCA) upto 25% : 4 graded stone aggregate 20 mm nominal size Recycled Concrete Aggregate (RCA) upto 25%) M3 71.4535 0.00 0.00 0.00
2.045 205998 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Foundations, footings, bases of columns, etc. for mass concrete. M2 3162.1558 0.00 0.00 0.00
2.046 205999 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. M2 10347.1507 0.00 0.00 0.00
2.047 206000 Centering and shuttering including strutting, propping etc. and removal of form for all heights: Suspended floors, roofs, landings, balconies and access platform. M2 2216.6694 0.00 0.00 0.00
2.048 206001 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Lintels, beams, plinth beams, girders, bressumers and cantilevers. M2 4031.5867 0.00 0.00 0.00
2.049 206002 Centering and shuttering including strutting, propping etc. and removal of form for for all heights : Columns, Pillars, Piers, Abutments, Posts and Struts. M2 6414.6442 0.00 0.00 0.00
2.05 206003 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Stairs, (excluding landings) except spiral-staircases. M2 125 0.00 0.00 0.00
2.051 206004 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Weather shade, Chajjas, Corbels etc., including edges. M2 44.2187 0.00 0.00 0.00
2.052 206005 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) M3 247.0193 0.00 0.00 0.00
2.053 206007 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) M3 1252.0608 0.00 0.00 0.00
2.054 206009 Extra for providing and placing in position 2 Nos. 6mm dia. M.S. bars at every third course of half brick masonry. M2 50 0.00 0.00 0.00
2.055 206010 12 mm cement plaster of mix for all heights: 1:4 (1 cement: 4 fine sand) M2 8705.5604 0.00 0.00 0.00
2.056 206012 15 mm cement plaster on the rough side of single or half brick wall of mix for all heights: 1:4 (1 cement: 4 fine sand) M2 7638.5668 0.00 0.00 0.00
2.057 206014 6 mm cement plaster of mix for all heights: 1:3 (1 cement: 3 fine sand) M2 1153.9891 0.00 0.00 0.00
2.058 206016 Providing and fixing Chicken-mesh of 1.5 mm dia. steel wire with hexagonal or rectangular openings of 20-25 mm 150 mm wide fixed with U nails at 150 mm centre to centre placed and held properly in position at brick and R.C.C joints as per direction of engineer-in-charge. M2 250 0.00 0.00 0.00
2.059 206017 Neat cement punning M2 605.0145 0.00 0.00 0.00
2.06 206018 Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 -part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25mm M.S. laths with 1.25 mm thick top cover. M2 100.92 0.00 0.00 0.00
2.061 206019 Providing and fixing GI chain link fabric fencing of required width in mesh size 75x75 mm, 3.15 mm dia. mesh wire as per drawing conforming to IS:2721, MS stirrups wire 2.5 mm dia. with tying wire 1.6 mm dia. including providing 25x4.75 mm stretcher bars, eye bolt 85 mm half round staples etc. including nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. (MS Flat, angle etc. will be paid separately). M2 349.25 0.00 0.00 0.00
2.062 206021 Providing and fixing stainless steel (SS 304 grade) adjustable friction windows stays of approved quality with necessary stainless steel screws etc. to the side hung windows as per direction of Engineerin-charge complete.255 X 19 mm EA 17.6 0.00 0.00 0.00
2.063 206023 Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 KG., for doors, including cost of cutting floors ,embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. With stainless steel cover plate minimum 1.25 mm thickness. EA 5 0.00 0.00 0.00
2.064 206024 Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS:12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides. M2 125 0.00 0.00 0.00
2.065 206027 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 4.0 mm thickness (weight not less than 10 kg/ sqm) M2 73.7022 0.00 0.00 0.00
2.066 206028 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5 mm thickness (weight not less than 12.50 kg/ sqm) M2 93.47 0.00 0.00 0.00
2.067 206029 Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/M2 (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the rate of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm or both sides of joint and two coats of primer suitable for board, all as per manufacture's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : 12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- Part I.: 2011 (Board with BIS certification marks) M2 129.4046 0.00 0.00 0.00
2.068 206031 Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 KG/M2. of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto300mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to115mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand)admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with waterproofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs c)After two days of proper curing applying a second coat of cement slurry using 2.75KG/ M2 of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge. d)Finishing the surface with 20 mm thick jointless cement mortar of mix1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : With average thickness of 120mm and minimum thickness at khurra as 65 mm. M2 2181.9531 0.00 0.00 0.00
2.069 206033 Providing and fixing GI chain link fabric fencing of required width in mesh size 75x75 mm, 3.15 mm dia. mesh wire PVC coated to achieve outer dia. not less than 4.15 mm in required colour and shadeas per drawing conforming to IS:2721, MS stirrups wire 2.5 mm dia. with tying wire 1.6 mm dia. including providing 25x4.75 mm stretcher bars, eye bolt 85 mm half round staples etc. including nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. (MS Flat, angle etc. will be paid separately). M2 375 0.00 0.00 0.00
2.07 206035 Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet1mx1mx400micron, finished with 12mm cement plaster 1:3 (1 cement :3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. EA 115 0.00 0.00 0.00
2.071 206037 Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade New work (two or more coats) over and including water thinnable priming coat with cement primer. M2 2481.8244 0.00 0.00 0.00
2.072 206039 Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 KG/10 M2). M2 3331.5714 0.00 0.00 0.00
2.073 206040 Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade: Two or more coats on new work. M2 29.3282 0.00 0.00 0.00
2.074 206041 Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work. M2 6207.4005 0.00 0.00 0.00
2.075 206044 Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick. M2 1174.9407 0.00 0.00 0.00
2.076 206045 Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. M2 129.5853 0.00 0.00 0.00
2.077 206046 Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer ) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3KG per M2 including pointing in white cement mixed with pigment of matching shade complete. M2 37.9698 0.00 0.00 0.00
2.078 206047 Providing and laying Ceramic glazed floor tiles 300x300 or 400x400 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS :15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4Coarse sand) including pointing the joints with white cement and matching pigment etc., complete. M2 6.9773 0.00 0.00 0.00
2.079 206053 Supplying, laying & spreading machine crushed 65 mm good quality stone aggregates including compacing the same. M3 130.658 0.00 0.00 0.00
2.08 206054 Disposal of all debris/rubbish/malba/surplus excavated earth/similar unserviceable, dismantled or waste materials arising out of demolition and construction activities, by mechanical means, including loading, transporting, unloading to authorized Construction and Demolition (C&D) waste recycling plant or approved municipal dumping ground as per the directions of TPDDL Engineer-in-charge, for all leads including all lifts involved. Bidder solely shall be responsible for identifying such area and bear all costs involved, TPDDL shall not be liable for the same. Bidder shall clear the site thoroughly of such unwanted materials and rubbish etc. left out of his work and dress the site to the satisfaction of the TPDDL Engineer-in-Charge in all respects before the final handing over. Nothing additional shall be paid on account of disposal of waste material to construction and demolition (C&D) waste recycling plant. M3 4243.3873 0.00 0.00 0.00
2.081 206055 Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. L 8542 0.00 0.00 0.00
2.082 206058 Providing and fixing aluminium tower bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade with necessary screws etc. complete : 200x10 mm EA 50 0.00 0.00 0.00
2.083 206059 Providing and fixing aluminium handles ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete : 125 mm EA 23.2 0.00 0.00 0.00
2.084 206060 Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. EA 5 0.00 0.00 0.00
2.085 206068 Supplying and fixing C.I. cover without frame for manholes : 610x610 mm rectangular C.I. cover (light duty) the weight of the cover to be not less than 23 KG. EA 19.9 0.00 0.00 0.00
2.086 206070 Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm. depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earth with lead upto 50 metres. M2 429 0.00 0.00 0.00
2.087 206071 Supplying and stacking at site. 90 mm to 45 mm size stone aggregate. M3 42.9 0.00 0.00 0.00
2.088 206072 Supplying and stacking at site. 63 mm to 45 mm size stone aggregate. M3 32.175 0.00 0.00 0.00
2.089 206073 Supplying and stacking at site. Stone screening 13.2 mm nominal size (Type A) M3 6.435 0.00 0.00 0.00
2.09 206074 Laying, spreading and compacting stone aggregate of specified sizes to WBM specifications in uniform thickness, hand picking, rolling with 3 wheeled road / vibratory roller 8-10 tonne capacity in stages to proper grade and camber, applying and brooming requisite type of screening / binding material to fill up interstices of coarse aggregate, watering and compacting to the required density M3 75.075 0.00 0.00 0.00
2.091 206075 Providing and laying R.C.C./ C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator, vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-incharge. (The panel shuttering work and steel reinforcement shall be paid for separately). (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately). M3 95.7 0.00 0.00 0.00
2.092 206076 Providing and fixing in position 12mm thick bitumen impregnated per cm fiber board conforming to IS: 1838, including cost of primer, sealing depth per compound Grade-A in expansion joints M2 9.9 0.00 0.00 0.00
2.093 206077 Providing and filling in position bitumen mix filler of proportion 80 KG. of hot bitumen, 1 KG. of cement and 0.25 cubic metre of coarse sand for expansion joints. M3 2.475 0.00 0.00 0.00
2.094 206079 Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge M3 155.7696 0.00 0.00 0.00
2.095 206081 Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -in -charge. M3 5 0.00 0.00 0.00
2.096 206087 Providing and fixing 20 mm dia., 1.2 mtr long each GI rungs as per the directions of Engineer-In-Charge EA 166.6 0.00 0.00 0.00
2.097 206091 Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreouschina flushing cistern & C.P. flush bend with fittings & C.I.brackets,40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal designcomplete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : W.C. pan with ISI marked white solid plastic seat and lid EA 2.2 0.00 0.00 0.00
2.098 206092 Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with white PVC automatic flushing cistern,with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS :2556, C.I. trap with outlet grating and other couplings in C.P. brass, including painting of fittings and cutting and making good the walls and floors wherever required : Single half stall urinal with 5 litre P.V.C. automatic flushing cistern EA 2.2 0.00 0.00 0.00
2.099 206093 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require : White Vitreous China Flat back wash basin size 550x400 mm with single 15 mm C.P. brass pillar tap EA 7.2 0.00 0.00 0.00
2.1 206094 Providing and fixing 600 x 450 mm bevelled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board sheet ground fixed to wooden cleats with C.P. brass screws and washers complete. EA 7.2 0.00 0.00 0.00
2.101 206095 P/F CP brass toilet paper holder of approved quality and make. EA 2.2 0.00 0.00 0.00
2.102 206096 Providing and fixing brass bib cock of approved quality: 15 mm nominal bore EA 2.2 0.00 0.00 0.00
2.103 206104 Providing and filling the joints with spun yarn cement, slurry and cement mortar 1:2 ( 1 cement: 2 fine sand) in S.C.I/C.I pipes b) 75mm dia EA 10 0.00 0.00 0.00
2.104 206105 Providing and fixing plain bend of required degree (Sand cast iron S&S as per IS 1729)a) 100mm EA 10 0.00 0.00 0.00
2.105 206108 P/F PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fitting of approved quality and colour weighing not less than 105 gms. EA 7.2 0.00 0.00 0.00
2.106 206109 Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour 450 mm long towel rail with total length of 495 mm,78 mm wide and effective height of 88 mm, weighing not less than 170 gms EA 7.2 0.00 0.00 0.00
2.107 206110 P/f CP jali for nahni trap with or without hole using white cement and pigment to match the tile colour, complete. EA 13.8 0.00 0.00 0.00
2.108 206112 Providing and fixing gun metal non-return valve of approved quality (screwed end) 25mm nominal bore. Horizontal (ISI) EA 5 0.00 0.00 0.00
2.109 206113 Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 KG and frame to be not less than 2.70 KG as per standard design : 150x100 mm P type. With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 EA 5 0.00 0.00 0.00
2.11 206126 Fencing with angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and end post on one side only and provided with horizontal lines and two diagonals interwoven with horizontal wires, of barbed wire weighing 9.38 KG per 100 m (minimum), between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete. (Cost of posts, struts, earth work and concrete work to be paid for separately) :-Payment to be made per metre cost of total length of barbed wire used. With G.I. barbed wire M 381.7 0.00 0.00 0.00
2.111 206163 Dismantling manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge : Water bound macadam road, Wet mix macadam road, Granular sub-base or any type of base and sub base course laid in between wearing course and subgrade. M2 3725.4 0.00 0.00 0.00
2.112 206174 Dismantling steel work in single sections including dismembering and stacking within 50 metres lead in: Channels, angles, tees an d flats KG 330 0.00 0.00 0.00
2.113 206241 Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter M 633.1468 0.00 0.00 0.00
2.114 206270 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer’s specifications including appropriate priming coat, preparation of surface, etc. complete. On steel work M2 1000 0.00 0.00 0.00
2.115 206352 Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. M2 2513 0.00 0.00 0.00
2.116 206353 Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. EA 102.504 0.00 0.00 0.00
2.117 206373 Providing & fixing mild steel round holding down bolts including nuts & washer plates complete KG 125 0.00 0.00 0.00
2.118 206482 Providing and fixing expansion hold fasteners on C.C. /R.C.C./Brick masonry surface backing including drilling necessary holes and the cost of bolt etc complete. Wedge expansion type Fastener with threaded dia 10 mm EA 50 0.00 0.00 0.00
2.119 206495 Providing & Laying C.C in brick ballast in 1:6:12 (1 Cement : 6 Coarse Sand : 12 Brick aggregate) mix. ( E ) M3 771.242 0.00 0.00 0.00
2.12 206496 Supplying, laying & spreading machine crushed 20 mm good quality blue colour stone aggregates including compacting the same. M3 1098.56 0.00 0.00 0.00
2.121 206497 Supplying chemical emulsion in sealed containers including delivery, diluting and applying for antiweed treatment in yard as specified by manufacturer. M2 3971.664 0.00 0.00 0.00
2.122 206536 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion powder coated aluminium (minimum thickness of powder coating 50 micron) KG 16.5 0.00 0.00 0.00
2.123 206537 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coating 50 micron) KG 16.5 0.00 0.00 0.00
2.124 206624 Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design : With common burnt clay F.P.S. (non-modular) bricks of class designation 7.5 EA 9.4 0.00 0.00 0.00
2.125 206628 Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour : Two coats M2 151.195 0.00 0.00 0.00
2.126 206631 Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. Flexible pipe 40 mm dia EA 5 0.00 0.00 0.00
2.127 206659 Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) : 25 mm nominal bore EA 5 0.00 0.00 0.00
2.128 206660 Providing and fixing GI union in GI pipe including cutting & threading the pipe & making long screws etc. complete (new work). 20mm nominal bore EA 5 0.00 0.00 0.00
2.129 206698 Making construction joint, first cutting groove 5x30 mm deep with special blade in concrete road and then filling the grooves 5x15 mm deep with polysulphide sealant over an expanded polyethene backer rod including rounding of the edges, etc. all complete. M 99 0.00 0.00 0.00
2.13 206853 Add for using extra cement in the items of design mix over and above the specified cement content therein. KG 75484.144 0.00 0.00 0.00
2.131 206871 Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) including manufactured and derived from Recycled Concrete Aggregate (RCA) upto 25% : 4 graded stone aggregate 12.5mm nominal size inclcuding (Recycled Conceret Aggregate (RCA) upto 25%)) M2 50 0.00 0.00 0.00
2.132 206921 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement,water tanks, roof slabs, podiums, reservior,sewage & water treatment plant, tunnels/subway and bridge deck etc., prepared by mixing in the ratio of 5:2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3:1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative ( internal) side with the help of synthetic fibre brush.The material shall meet the requirements as specified in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure in negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry for 10 years against any leakage. For horizontal surface one [email protected] per sqm. M2 250 0.00 0.00 0.00
2.133 206922 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement,water tanks, roof slabs, podiums, reservior,sewage & water treatment plant, tunnels/subway and bridge deck etc., prepared by mixing in the ratio of 5:2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3:1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative ( internal) side with the help of synthetic fibre brush.The material shall meet the requirements as specified in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure in negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry for 10 years against any leakage. For vertical surface two [email protected] kg per sqm per coat M2 250 0.00 0.00 0.00
2.134 206923 Providing and mixing integral crystalline admixture for waterproofing treatment to RCC structures like basement raft, retaining walls, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc. at the time of transporting of concrete into the drum of the ready mixed truck, using integral crystalline admixture @0.80% (minimum) to the weight of cement content per cubic meter of concrete)or heigher as recommended by the manufacturer's specification in reinforced cement concrete at site of work. the material shall meet the requirements as specified in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90%, compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure. The crystalline admixture shall be capable of self- healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the Engineer-in-charge. The product performance shall carry gurantee for 10 years against any leakage. KG 250 0.00 0.00 0.00
2.135 207033 Providing and laying autoclaved aerated concrete (AAC) blocks masonry 100mm/125mm thick with Grade-1 AAC blocks of density 551 to 650 KG/CUM conforming to IS:2185 (Part 3) in super structure above plinth level up to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rate includes providing and placing in position 2 Nos 6 mm dia M.S. bars at every third course of masonry work. M3 50 0.00 0.00 0.00
2.136 207113 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design :150 mm diameter S.W. pipe M 25 0.00 0.00 0.00
2.137 207442 Extra for providing mechanical device chain and crank operation for operating rolling shutters - upto 16.80 sqm in the area M2 7.2 0.00 0.00 0.00
2.138 207462 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 cement : 4 manufactured sand derived from Recycled Concrete Aggregate (RCA) : 8 graded stone aggregate 40 mm nominal size Recycled Aggregate (RCA) M3 728.9509 0.00 0.00 0.00
2.139 207465 Cutting of cores in reinforced concrete structures upto 200 mm dia. and 300 mm depth EA 140.7 0.00 0.00 0.00
2.14 207501 Providing and fixing 25 mm thick Fibreglass Reinforced Plastic grating of mesh size 38X38 mm, rib thickness 5-7 mm complete as per approved drawings in colour as approved by TPDDL EIC. M2 250 0.00 0.00 0.00
2.141 207525 Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 manufactured sand derived from Recycled Concrete Aggregate (RCA) : 6 graded stone aggregate 20 mm nominal size (Recycled Aggregate (RA) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth M2 102.7 0.00 0.00 0.00
2.142 207538 Providing and fixing unplasticised P.V.C. in Stainless Steel finished connection pipe with brass unions: 45 cm length-15 mm nominal bore. EA 5 0.00 0.00 0.00
2.143 208350 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 manufactured sand derived from Recycled Concrete Aggregate (RCA) : 6 graded stone aggregate 20 mm nominal size Recycled Concrete Aggregate (RCA) M3 75.611 0.00 0.00 0.00
2.144 208351 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:5:10 (1 cement : 5 manufactured sand derived from Recycled Concrete Aggregate (RCA) : 10 graded stone aggregate 40 mm nominal size Recycled Aggregate (RCA) ) M3 25 0.00 0.00 0.00
2.145 208352 Providing and fixing precast reinforced cement concrete work in cable trench covers, including the cost of required centering, shuttering but, excluding cost of reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). M3 214.692 0.00 0.00 0.00
2.146 208401 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 200 mm dia (OD-200 mm & ID-175 mm nominal) M3 71.6 0.00 0.00 0.00
2.147 208411 Providing and laying 60mm thick factory made cement concrete paver block of approved shape and colour of M -30 grade made of C&D waste by block making machine with vibratory compaction laid in required pattern and including over 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge. M2 250 0.00 0.00 0.00
2.148 208892 Providing and laying Geotextile membrane, 120 gsm non woven, 100% polyester of thickness 1 to 1.25 mm. M2 15 0.00 0.00 0.00
2.149 208893 Providing and filling Brick bats of 40 mm nominal size under flooring etc. i/c compaction by ramming and levelling top surface complete M3 10 0.00 0.00 0.00
2.15 208894 Supplying and laying charcoal in rain water harvesting recharge pit. M3 5 0.00 0.00 0.00
2.151 208922 Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). KG 500 0.00 0.00 0.00
2.152 208923 Providing and fixing stainless steel (SS-304 grade) friction hinges to the side/ top hung uPVC windows, of approved quality, with necessary stainless steel screws etc. as per direction of Engineer-in-charge. 200 x 19 x 1.9 mm EA 20 0.00 0.00 0.00
2.153 209063 Providing and applying two coats of High Albedo paint having minimum Solar Reflective Index (SRI) 108 (with solar reflectance & thermal emittance tested as per ASTM) C 1549 and ASTM C 1371 respectively), VOC less than 10 cc/gm. The coating thickness and the methodology of application shall strctly as per manufacturer's specifications and as approved by Engineer-in-Charge. Surface preparation includes cleaning with metal wire brush to remove all dust, fungus etc., washing with water all complete. The contractor shall give guarantee for the perfomance of SRI and also the durabitity of coating, all complete as per direction of Engineer-in-Charge. M2 1059.8 0.00 0.00 0.00
2.154 209064 Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour all complete to achieve even shade and colour: new work (two or more coats) over and including water thinnable priming coat with cement primer having COC content less than 50g/L M2 2488.8 0.00 0.00 0.00
2.155 209065 Finishing walls with readymix Premium acrylic emulsion paint (Company Depot Tinted) having VOC less than 50 gm/litre and UV resis tance as per IS:15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade with silicon additives. N ew work (Two or more coats applied @ 1.43 litre/ 10 sqm Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm. M2 71.5 0.00 0.00 0.00
2.156 209068 Brickwork with Recycled CC Bricks of size 230x110x75 mm (M10 Grade) in foundation and plinth in :- (a) Cement Mortar 1:6 (1 cement : 6 coarse sand) M3 205.5 0.00 0.00 0.00
2.157 209069 Brickwork with Recycled CC Bricks of size 230x110x75 mm (M10 Grade) in superstructure above plinth level upto floor V level in all shapes and sizes :- (a) Cement Mortar 1:4 (1 cement : 4 coarse sand) M3 50 0.00 0.00 0.00
2.158 209412 Drilling suitable holes in reinforced or plain cement concrete with power driven drill machine to a minimum depth of 100mm upto 2 00mm in RCC beams, lintels, columns and slabs to introduce steel bars for sunshades/balconies including fixing the steel bars in p osition using epoxy resin anchor grout of approved make but excluding the cost of reinforcement, all complete as per direction of Engineer-In-Charge. Upto and including 12mm dia. (approved make HILTI) EA 275 0.00 0.00 0.00
2.159 209413 Design & detailing, testing and installation of appropriate sizes of reinforcement anchorages or splices fixed into existing hard ened concrete by injecting adhesives in drilled holes after cleaning of the holes to connect new reinforcement to existing walls a nd slab. BA shall visit the site and collect necessary details required for carrying out the work and submit complete proposal for TPDDL approval before execution of work at site. (approved make HILTI) - 16 to 28 dia. bar EA 825 0.00 0.00 0.00
2.16 209415 Supplying and Filling screened soil procured from MCD approved C&D waste recycling plant and carriage for all leads including spreading in required thickness as per the directions of TPDDL Engineer-In-Charge and compacting under optimum moisture conditions to give at least 95% of the maximum dry density (proctor density). Cubical quantity of compacted earth only shall be measured and paid. M3 750 0.00 0.00 0.00
2.161 209428 Attaining IGBC Green Service Buildings Certification for Substation Building. The scope of services towards attaining the desired IGBC Rating would include but not limited to the following: i. Project Registration with IGBC ii. Performing the feasibiliy iv. Facilitation, Documentation and Submission of project details for IGBC rating v. Simulation services including Energy Simulation, Day-light Simulation etc. vi. IGBC Review & Comments response to achieve the anticipated rating For detailed scope of work, refer Special Conditions of Contract. The cost shall shall be inclusive of all expenses including Application Fees, Council Fees, Consultancy Fees, Travel, Liasioning with IGBC for Certification and Documentation etc. IGBC Application Fees shall be paid on producing payment receipts by BA and balance payment shall be made after the Certification is received from IGBC. EA 5 0.00 0.00 0.00
2.162 209429 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources and using recycled concrete aggregate (RCA) as coarse aggregate and fine aggregate within permissible utilization of 20% each, Portland Pozzolana /Ordinary Portland/Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum M3 75 0.00 0.00 0.00
2.163 209452 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 1200 mm dia. R.C.C. pipe M 25 0.00 0.00 0.00
2.164 209456 Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.80 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineerin-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. M2 75 0.00 0.00 0.00
2.165 209457 Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. Made of G.I. wire of dia. 4 mm, PVC coated to achieve outer dia not less than 5 mm in required colour and shade M2 154 0.00 0.00 0.00
2.166 new-1 Finishing walls with readymix Premium acrylic emulsion paint (Company Depot Tinted) having VOC less than 50 gm/litre and UV resistance as per IS:15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade with silicon additives. New work (Two or more coats applied @ 1.43 litre/ 10 sqm Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm. M2 8075 0.00 0.00 0.00
B Total All Inclusive Amount (Rs) - Civil Services 0.00
A+B Total All Inclusive Amount (Rs.) Electrical + Civil Services 0.00
Annexure-1 (Schedule of Item)
NIT No - TPDDL/ENGG/ENQ/200001981/26-27
NIT Description - 1 Year Rate Contract (RC) for 66kV & 33kV EHV Bay Extension with associated Electrical & Civil works at Various Locations in TPDDL area
S. NO. TPDDL Service Code Item Descr. UOM Quantity "A" Unit Rate (Rs.) "a" Applicable GST (in Rs.) "b" Price per Unit (in Rs.) "B"= a+b TPDDL Amt (in Rs.) C=A*B HSN/ SAC code PR/D0000/00263 66/11 kV Kanjhawala DTC EV Grid to supply load of 6.975MVA to EV depot PR/D0000/00260 66/11 kV Rohini-III DTC EV Grid to supply load of 7 MVA to EV depot PR/D0000/00259 66/11 kV Rohini-IV DTC EV Grid to supply load of 6 MVA to EV depot. PR/D0000/00264 66/11 kV Ghevra Savda DTC EV Grid to supply load of 10 MVA to EV depot. PR/D0000/00261 66/11 kV Narela A-3 DTC EV Grid to supply load of 6MVA to EV Depot. Installation of two 66/11kV 31.5MVA PTR including line bay Equipment and PTR bays with associated 11kV Switchgear Panels Equipment at Rohini Sec-11 Grid for Power Evacuation from BESS Station Addition 66/11kV 31.5MVA PTR4 @ Bawana-1 Grid Addition 66/11kV 31.5MVA PTR4 @ Bawana-6 Addition 66/11kV 31.5MVA PTR4 @ RG24 Grid Addition 66/11kV 31.5MVA PTR3@ Bhalswa-2 Addition 66/11kV 31.5MVA PTR3@Bawana1Ph2 AUGMENTATION OF PTR-4 AT DSIDC NARELA-1 GRID Augmentation of 20MVA PTR-3 AT RG-4 GRID RG-6 PTR-3 Augmentation 20 to 31.5MVA Augmentation of 16MVA PTR-2 at 33/11kV Saraswati Garden Grid Emergency
1.001 ITC of TRANSFORMER POWER 25/31.5MVA-9 NORMALTAP:Installation ,testing & commissioning of 3 Ph, 'Dyn11 ONAN/ ONAF power Transformer with OLTC including fixing of all loose accessories/parts of transformer (supplied along with the transformer), pre-commissioning checks. There shall be outdoor bushings on HV side which shall be connected with over head conductors or power cables through external open bus bar arrangement comprising of brass palm connectors, 100mm X 10mm Tinned Copper Flat with HS Insulating Sleeve Busbar and on LV side cable box will be available. LV side busbars shall connect to 1CX1000sqmm 3 runs of 11kV Al XLPE cable per phase. This item includes the jumpering/connections/termination on both sides. It also includes testing of transformer at site as per TATA Power-DDL power transformer specifications. This includes oil filtration of transformer. EA 21 0.00 0.00 0.00 2 2 2 2 2 2 1 1 1 1 1 1 1 1 0 1
1.002 Dragging of TRANSFORMER POWER upto 25/31.5MVA-9 NORMALTAP from unloading point to foundation ( up to 20 meters) or vice versa with complete safety measures as per TATA Power-DDL project in-charge instructions. M 300 0.00 0.00 0.00 20 20 20 20 20 20 20 20 20 20 20 20 20 20 0 20
1.003 Installation ,testing & commissioning of outdoor neutral CT (NCT) for PTR including its connections with PTR/Reactor & NGR/Earth Pit, etc.. EA 22 0.00 0.00 0.00 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1
1.004 To provide brazing for all joints/connections required as per site condition between NCT and Copper earth plate, for earthing of NCT at as per TATA Power-DDL earthing philosophy. One set means all requirements for one NCT. EA 22 0.00 0.00 0.00 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1
1.005 Installation ,testing & commissioning of LA 60KV 10KA, heavy duty, station class, lightning arrestor(LA) & surge counter including laying & connection of 1CX50 sqmm copper flexible cable with LA surge counter. This item includes jumpering/connections. EA 66 0.00 0.00 0.00 6 6 6 6 6 15 3 3 3 3 3 0 0 3 0 3
1.006 Installation ,testing & commissioning of 66kV Post Insulator including jumpering/connections. EA 66 0.00 0.00 0.00 12 12 12 12 12 0 0 0 0 6 0 0 0 0 0 0
1.007 SITC of clamp & connectors required for connection of 66kV BPI with 2.5 inch IPS tube EA 66 0.00 0.00 0.00 12 12 12 12 12 0 0 0 0 6 0 0 0 0 0 0
1.008 SITC of clamp & connectors required for connection of 66kV LA with 2.5 inch IPS tube EA 36 0.00 0.00 0.00 6 6 6 6 6 0 0 0 0 6 0 0 0 0 0 0
1.009 SITC of connector for connection of 66kV cable termination lug with 2.5 inch IPS tube EA 36 0.00 0.00 0.00 6 6 6 6 6 0 0 0 0 6 0 0 0 0 0 0
1.01 LTC of CABLE 66KV AL 1X1000 SQMM ARM XLPE along with trefoil clamp in already excavated trench/available trench/vertical mounting.(cable shall be Free Issued by TATA Power-DDL). Application of Fire paint(including supply) at transformer end it shall be up to sand filling in trench, and in switchgear room it shall be from switchgear to building entry point. Sealing of cable to be provided at entries as per TATA Power-DDL Standard Drawing . Quantity shall be paid per meter of each cable laid. M 4930 0.00 0.00 0.00 650 1000 1100 900 480 0 0 0 0 800 0 0 0 0 0 0
1.011 LTC of CABLE 11KV AL 1X1000 SQMM ARM XLPE along with trefoil clamp in already excavated trench/available trench/vertical mounting.(cable shall be Free Issued by TATA Power-DDL.Cable shall be 2 runs / Phase for 20/25 , 16/20 MVA and 3 runs/phase for 25/31.5 MVA power Transformer to 11 kV Switchgear Panel ). Application of Fire paint(including supply) at transformer end it shall be up to sand filling in trench, and in switchgear room it shall be from switchgear to building entry point. Sealing of cable to be provided at entries as per TATA Power-DDL Standard Drawing . Quantity shall be paid per meter of each cable laid M 25820 0.00 0.00 0.00 720 1200 1050 1200 500 2250 2025 2025 2100 1500 2025 1800 1800 1800 1800 2025
1.012 LTC of CABLE 1.1KV AL 4CX95 SQMM ARM (For AC & DC Supply) for ACDB to Battery charger & Filtration industrial socket M 1450 0.00 0.00 0.00 250 250 250 250 250 100 0 0 0 0 0 0 0 0 100 0
1.015 LTC of CABLE 11KV AL 3CX300/400 SQMM XLPE ARM (cable shall be Free Issued by TATA Power-DDL). From 11 kV Switchgear to 250kVA/160 KVA Transformer in already excavated trench/available trench/vertical mounting. Application of Fire paint(including supply) in cable trench portion shall be in scope of this activity. M 1400 0.00 0.00 0.00 100 100 100 100 100 300 75 75 75 75 75 50 50 50 0 75
1.016 LTC of CABLE 1.1KV AL 3.5CX300 SQMM XLPE ARM or CABLE 1.1KV AL 4CX300 SQMM XLPE ARM for station transformer M 950 0.00 0.00 0.00 150 150 150 150 150 200 0 0 0 0 0 0 0 0 0 0
1.023 SITC of 50x6mm CU flat for Transformer neutral earthing including required earth excavation for laying earth flat. This item excludes brazing activity. M 525 0.00 0.00 0.00 50 50 50 50 50 50 25 25 25 25 25 25 25 25 0 25
1.024 SITC of Earthing with Electrolytic grade copper plate 600mmx600mmx6mm including 50x6mm copper flat and other accessories and providing masonry enclosure with cover plate to be provided in 6 mtr deep earth pit to be filled With earth enhancement material as per IEEE80:2000,14.5(D) and TATA Power-DDL standard earthing philosophy. Earth Enhancement material approval is mandatory before erection activity. EA 44 0.00 0.00 0.00 4 4 4 4 4 4 2 2 2 2 2 2 2 2 2 2
1.025 SITC of 100 mm dia GI pipe-6 meter length earth electrode with treated earth Pit heavy class with Treated Earth Pits. With earth enhancement material as per IEEE80:2000,14.5(D). This item includes civil goomties required for earth pit as per TATA Power-DDL standard earthing philosophy and specification. Earth Enhancement compound (Minimum Terec-5 KG and Earthcon-12.5KG) is to be used for every earth pit till the earthing value of each pit is achieved below 02 Ohms EA 74 0.00 0.00 0.00 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5
1.026 SITC of 100 mm dia GI pipe-3 meter length earth electrode with treated earth Pit heavy class with Treated Earth Pits. With earth enhancement material as per IEEE80:2000,14.5(D). This item includes civil goomties required for earth pit as per TATA Power-DDL standard earthing philosophy and specification. Earth Enhancement compound (Minimum Terec-5 KG and Earthcon-12.5KG) is to be used for every earth pit till the earthing value of each pit is achieved below 02 Ohms EA 56 0.00 0.00 0.00 6 6 6 6 6 6 2 2 2 2 2 2 2 2 2 2
1.027 SITC of 100 mm dia GI pipe-6 meter length earth electrode with treated earth Pit heavy class with Treated Earth Pits without goomty. With earth enhancement material as per IEEE80:2000,14.5(D).. Earth Enhancement compound (Minimum Terec-5 KG and Earthcon-12.5KG) is to be used for every earth pit till the earthing value of each pit is achieved below 02 Ohms EA 44 0.00 0.00 0.00 4 4 4 4 4 4 2 2 2 2 2 2 2 2 2 2
1.028 SITC of 100 mm dia GI pipe-3 meter length earth electrode with treated earth Pit heavy class with Treated Earth Pits without goomty. With earth enhancement material as per IEEE80:2000,14.5(D).. Earth Enhancement compound (Minimum Terec-5 KG and Earthcon-12.5KG) is to be used for every earth pit till the earthing value of each pit is achieved below 02 Ohms EA 36 0.00 0.00 0.00 6 6 6 6 6 6 0 0 0 0 0 0 0 0 0 0
1.029 SITC of building spikes, 20mm dia GI rod (2.5Meter length) EA 80 0.00 0.00 0.00 6 6 6 6 6 10 6 6 6 6 6 0 0 4 0 6
1.03 ITC of TRANSFORMER 250KVA 3PH 11KV/433V with cable box on HV/LV sides as per TATA Power-DDL specifications including jumpering/connections. EA 5 0.00 0.00 0.00 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0
1.031 SITC of Double compression glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables of the sizes (diameter between 12mm to 18mm ) EA 280 0.00 0.00 0.00 30 30 30 30 30 30 10 10 10 10 10 10 10 10 10 10
1.032 SITC of Double compression glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables of the sizes (diameter between 18mm to 24mm ) EA 650 0.00 0.00 0.00 60 60 60 60 60 60 30 30 30 30 30 30 30 30 20 30
1.033 SITC of Double compression glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables of the sizes (diameter more than 24mm) EA 380 0.00 0.00 0.00 30 30 30 30 30 30 20 20 20 20 20 20 20 20 20 20
1.034 SITC of Double compression glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore CU conductor control cables of the various sizes up to 12 mm EA 66 0.00 0.00 0.00 6 6 6 6 6 6 0 0 0 0 0 10 10 10 0 0
1.036 SITC of cable cleat (Nylon-6) size greater than 100mm EA 74 0.00 0.00 0.00 4 4 4 4 4 4 0 0 0 10 0 10 10 10 10 0
1.038 Supply of Trefoil Clamp for suitable for 66kV and/or 11kV 1Cx1000sq.mm Power Cable as per TATA Power-DDL Specification/Drawing EA 315 0.00 0.00 0.00 25 25 25 25 25 30 20 20 20 20 20 10 10 10 10 20
1.039 SITC of IP54 Lighting junction box for each Light at tower suitable for out door installation comprising of 8 no. CBT M 4 type terminal connector for light connections or loop in / loop out cable EA 35 0.00 0.00 0.00 5 5 5 5 5 4 1 1 1 1 1 0 0 0 0 1
1.04 SITC of AC Distribution Board AC 415V, 400A cubicle type Indoor, floor mounted, auxiliary service board as per TATA Power-DDL specification EA 7 0.00 0.00 0.00 1 1 1 2 0 0 1 0 1 0 0 0 0 0
1.041 SITC of astro timer control for lighting arrangement. This item shall be executed as per TATA Power-DDL Engineering In-charge. EA 6 0.00 0.00 0.00 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0
1.042 SITC of industrial type Control room lighting including all accessories:- LED luminaire 2x16/18/20W industrial type fitting with LED luminaire. Suitable for Surface/Suspended mounting EA 84 0.00 0.00 0.00 12 12 12 12 12 12 2 2 2 2 2 0 0 0 0 2
1.043 SITC of industrial type Control room lighting including all accessories:- LED luminaire 2x36/40W industrial type fitting with LED luminaire. Suitable for Surface/Suspended mounting EA 118 0.00 0.00 0.00 6 20 20 20 20 20 2 2 2 2 2 0 0 0 0 2
1.044 SITC of flame proof fluorescent fitting including all accessories:-LED luminaire 2x36/40W flame proof acid proof fitting with LED lamp for Battery Room/Cable cellar room. Suitable for Surface/Suspended mounting EA 24 0.00 0.00 0.00 4 4 4 4 4 4 0 0 0 0 0 0 0 0 0 0
1.045 SITC Installation of LED 120W luminaire with required fittings and accessories as per TATA Power-DDL specifications. EA 177 0.00 0.00 0.00 15 12 12 12 12 20 10 10 20 15 10 2 2 10 5 10
1.046 Supply, Installation ,testing & commissioning of AC 415V 400A Street Light panel AC 415V, 400A ,50 KA for 1 Sec cubicle type Outdoor, Plinth mounted, Street light panel as per specification comprising of the following: Incomer 63A TTPNMCCB -1 No. Metering with RYB indicating lamp LED type, Voltmeter with selector switch, ammeter with selector switch , suitable CT's & 2A TPNMCB for backup protection of voltmeter & indication light. 1 No. 70A FP CONTACTOR -1 No. 24 Hr. timer for auto Operation Auto manual selector switch , I set push button for on/off operation.Outgoing feeder 25A TPNMCB 4 Nos. 63A Power industrial socket with "C" series TPNMCB for Protection & provision of up to 3.5c X 50 sqmm Al Arm cable Termination as per TATA Power-DDL specifications. EA 6 0.00 0.00 0.00 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0
1.047 SITC of IP 54 Lighting Distribution Board for control room lighting control comprising of one no, incomer 63 A TPN MCB & 18 no. out going as 10-32A SP MCB. EA 25 0.00 0.00 0.00 3 3 3 3 3 4 1 1 1 1 1 0 0 0 0 1
1.048 SITCof Power Distribution Board for control room air conditioner comprising of one no, incomer 63 A TPN MCB & 6 no. out going as 32A TPN MCB. With auto changeover for Air conditioner EA 14 0.00 0.00 0.00 1 1 1 1 1 4 1 1 1 0 1 0 0 0 0 1
1.049 SITC of IP 54 protected 150A three phase industrial socket with 150A TPN MCB for oil filtration machine with 3x6.0 sqmm PVC insulated copper conductor stranded insulated wires & 2x1.5sqmm Stranded Green earth wire in recessed and/or on surface 40mm dia GI conduit including chasing of wall, filling of chases etc. complete in all respect. EA 6 0.00 0.00 0.00 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0
1.05 SITC of 32A three phase industrial socket with 32A TPN MCB AC power point with 3x6.0 sqmm PVC insulated copper conductor stranded insulated wires & 2x1.5sqmm Stranded Green earth wire in recessed and/or on surface 40mm dia GI/PVC conduit including chasing of wall, filling of chases etc. complete in all respect. EA 42 0.00 0.00 0.00 5 5 5 5 5 5 2 2 2 2 2 0 0 0 0 2
1.051 Supply & laying of HDPE Pipe Size 200 mm dia (PN-4 PE80) as per TATA Power-DDL specifications M 660 0.00 0.00 0.00 50 50 50 50 50 50 50 50 50 50 50 20 20 20 0 50
1.052 Supply & laying of HDPE Pipe Size 100 mm dia (PN-4 PE80) for control cables in the out door yard M 350 0.00 0.00 0.00 50 50 50 50 50 100 0 0 0 0 0 0 0 0 0 0
1.053 Supply, Fabrication and installation of GI structural steel material for gantry tower, beam, equipment's, cable mounting structure, tower mounting structure, LA Structure,BPI , drain crossing structure etc., where ever required as per approved drawing including nuts, bolts, washer & clamps. TON 132 0.00 0.00 0.00 5 5 5 5 5 11 17 17 8 4 17 2 2 7 5 17
1.054 SITC of 75 x 12 mm G I flat Main Earth mat, Aux Earth mat & Earthing Risers for Main Equipment's & structures etc. This item includes required earth excavation & backfilling for laying earth flat including exothermic wielding ,anticorrosive coatings i.e. red oxide and bitumen KG 38900 0.00 0.00 0.00 3000 3000 3000 3000 3000 10500 2000 2000 1200 1000 2000 500 500 1200 1000 2000
1.055 SITC of 50x6 GI flat for Aux earth material Earthing conductor for connection of , L.T panel, Junction box, & building Lightning risers & peak Connection etc. This item includes required earth excavation & backfilling for laying earth flat including exothermic wielding ,anticorrosive coatings i.e. red oxide and bitumen. KG 26300 0.00 0.00 0.00 1500 1500 1500 1500 1500 6000 2000 2000 1500 1000 2000 250 250 1500 300 2000
1.056 Supply and Installation of GI PERFORATED TRAY 150MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 230 0.00 0.00 0.00 10 10 10 10 10 20 20 20 20 20 20 10 10 10 10 20
1.057 Supply and Installation of GI PERFORATED TRAY 300MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 1050 0.00 0.00 0.00 50 50 50 50 50 200 100 100 100 100 100 0 0 0 0 100
1.058 Supply and Installation of GI PERFORATED TRAY 600MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 600 0.00 0.00 0.00 50 50 50 50 50 300 0 0 0 50 0 0 0 0 0 0
1.059 Supply and Installation of GI LADDER CABLE TRAY 300MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 950 0.00 0.00 0.00 50 50 50 50 50 100 100 100 100 100 100 0 0 0 0 100
1.06 Supply and Installation of GI LADDER CABLE TRAY 600MMX100MM along with its accessories to be laid in outdoor and indoor cable trenches M 950 0.00 0.00 0.00 50 50 50 50 50 100 100 100 100 100 100 0 0 0 0 100
1.061 SITC of aluminum IPS tube busbar with endcaps of 2.5 inches suitable for minimum 1600A Rated Current of required length with insulated Raychem BPTM sleeves of 66kV class. The IPS tube shall conform to IS:5082 and IS:2673. M 198 0.00 0.00 0.00 36 36 36 36 36 0 0 0 0 18 0 0 0 0 0 0
1.062 SITC of One light point by One Switch wiring of above light point, with 1.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 62 0.00 0.00 0.00 5 5 5 5 5 10 5 5 5 2 5 0 0 0 0 5
1.063 SITC of Two light point by One Switch wiring of above light point, with 1.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1.0 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 51 0.00 0.00 0.00 5 5 5 5 5 15 2 2 2 1 2 0 0 0 0 2
1.064 SITC of Three light point by One switch wiring of above light point, with 1.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1.0 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 40 0.00 0.00 0.00 5 5 5 5 5 15 0 0 0 0 0 0 0 0 0 0
1.065 SITC Flood light point -2.5 sqmm cu wiring wiring of above light point, with 2.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1.0 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 90 0.00 0.00 0.00 10 10 10 10 10 10 5 5 5 5 5 0 0 0 0 5
1.066 SITC of Exhaust fan point wiring of above exhaust fan point, with 1.5 sq.mm PVC insulated copper conductor single core stranded wires in GI/PVC conduit with 1.0 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling with cement mortar etc. complete in all respect. EA 45 0.00 0.00 0.00 4 2 2 2 2 12 4 4 0 0 2 0 0 2 5 4
1.067 SITC of wiring of General power point with 4.0 sq.mm PVC insulated copper conductor single core stranded wires in GI/pVC conduit with 2.5 sq. mm PVC insulated Stranded Green earth wire in recessed and/or on surface including chasing of wall, filling of chases etc. com EA 47 0.00 0.00 0.00 4 4 4 4 4 5 4 4 4 2 4 0 0 0 0 4
1.068 Supply of Fire barriers at cable entrances in control room ( EA means each entry) for 4 hrs. rating as per TATA Power-DDL specifications EA 22 0.00 0.00 0.00 2 2 2 2 2 2 1 1 1 1 1 0 0 0 4 1
1.069 SITC of Fire retardant coating on cables with required accessories as per TATA Power-DDL specifications (this item to be used only if not covered in other line items activity) KG 600 0.00 0.00 0.00 50 50 50 50 50 50 50 50 50 50 50 0 0 0 0 50
1.07 SITC of EPDM based cable entry/exits sealing system for 11kv power cables (for one PTR - 9 cables) including required minor civil works as per TATA Power-DDL specifications. This also includes provision of 20% spares modules for future cables laying or replacement activity EA 23 0.00 0.00 0.00 2 2 2 2 2 2 2 2 2 1 2 0 0 0 0 2
1.071 SITC of EPDM based cable entry/exits sealing system for 11 kV outgoing power cables for (10 cables) including required minor civil works as per TATA Power-DDL specifications. This also includes provision of 20% spares modules for future cables laying or replacement activity EA 8 0.00 0.00 0.00 1 1 1 1 1 0 0 0 0 0 0 0 1 1 1 0
1.072 FIRE EXTINGUISHER CO2 CAP 6.5 KG SITC of Fire Extinguishers CO2 type 6.5Kg for switchgear room, control room, engineer room with required accessories as per latest TATA Power-DDL latest specifications. EA 40 0.00 0.00 0.00 2 2 2 2 4 4 4 4 4 4 4 0 0 0 0 4
1.073 SITC of Fire Extinguishers Dry powder chemical type 25 kg with required accessories as per TPDDL specifications.(For PTR) EA 22 0.00 0.00 0.00 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1
1.074 SITC of Fire Extinguishers CO2 type 22.5 kg with required accessories as per TPDDL specifications.(For PTR) EA 14 0.00 0.00 0.00 1 1 1 1 1 2 1 1 1 1 1 0 0 0 1 1
1.075 SITC of ISI marked Fire Extinguishers -ABC Type 9 Kg for Switch room and other locations (IS:15683) Approved Make : Ceasefire / Minimax / Safex with required accessories as per TPDDL specifications. EA 36 0.00 0.00 0.00 4 4 4 4 4 4 2 2 2 2 2 0 0 0 0 2
1.076 SITC of ISI marked Fire Extinguishers -ABC Type 6 Kg for Switch room and other locations (IS:13849) Approved Make : Ceasefire / Minimax / Safex EA 28 0.00 0.00 0.00 2 2 2 2 2 2 2 2 2 2 2 1 1 1 1 2
1.077 SITC of wall mounted type Micro Processor based fire alarm panel with made of 16 SWG CRCA sheet, inbuilt Battery Box, comprising of Audio/ visual alarm indication of fire & fault etc., min. 16X2 line LCD display, time and date on LCD, complete with 100 event data logger with date and time stamp, indications for fire, fault, main power and battery as per ENG-GEN-4046. The panel shall also contain annunciation, window type indicators for fire and fault. Panel should support (a) NO-NC contact for fire alarm communication to BCPU (b) Capability of Ethernet Communication though RTU to centralized monitoring system (c) Data download to PC through USB. (c) ATX key board for field programming (d) PA system connectivity for announcement and altering (e) GSM functionality as per TPDDL specifications. Panel shall contain built-in battery charger and battery (Approved makes: Exide / Amaron / APC / Su-kam) for 48 hrs. back up in normal case and 30 min back up in case of alarm.Approved Make: Ravel / System Sensor / Agni Suraksha / ASES / Honeywell EA 10 0.00 0.00 0.00 1 1 1 1 1 1 1 1 0 0 1 0 0 0 0 1
1.078 SITC of Installation, Testing and Commissioning of Manual Call box with push button reset type as per IS 2189 Approved Make : Ravel / System Sensor / Agni Suraksha / ASES / Honeywell with required accessories as per TPDDL specifications. EA 13 0.00 0.00 0.00 1 1 1 1 1 4 1 1 0 0 1 0 0 0 1
1.079 SITC of Electronic Hooters (min 110 db intensity required) made out of ABS (colour RED) Approved Make : Ravel / System Sensor / Agni Suraksha / ASES / Honeywell with required accessories as per TPDDL specifications. EA 13 0.00 0.00 0.00 1 1 1 1 1 4 1 1 0 0 1 0 0 0 1
1.08 SITC of Installation, Testing and Commissioning of Response indicator as per IS 2189 Approved Make : Ravel / System Sensor / Agni Suraksha / ASES / Honeywell with required accessories as per TPDDL specifications. EA 54 0.00 0.00 0.00 4 4 4 4 4 10 4 4 4 4 4 0 0 0 4
1.081 SITC of Cable (FRLS in PO Red Color) cable 2 core* 1.5mm. Approved Makes: Polycab / Finolex / Gloster / RR Kabel / Havells M 2300 0.00 0.00 0.00 300 300 300 300 300 500 50 50 50 50 50 0 0 0 50
1.082 SITC of All safety items like First aid box - 1 no., safety Gloves - 2 pair., Safety Display board / Warning signs - 1 lot, accident prevention chart - 1 nos., shock treatment chart - 2 no., Grid SLD on wooden board- 1 no. on A0 size, (For complete grid) SET 16 0.00 0.00 0.00 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1.083 SITC of Sand Bucket along with stand(8 buckets) as per IS2546.The sand bucket should be clearly labeled and contain only clean, dry sand. Fire buckets should be made of heavy gauge galvanized steel, have a 9/10 liter capacity, and be painted red on the outside and white on the inside with the word "FIRE" stamped in large letters EA 22 0.00 0.00 0.00 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1
1.084 SITC of LOTO station as per TATA Power-DDL project In-Charge EA 16 0.00 0.00 0.00 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1.085 ITC of electrical panel lock out base with cover as per TATA Power-DDL project In-Charge EA 16 0.00 0.00 0.00 1 1 1 1 1 1 0 0 0 0 0 0 0 0 10 0
1.086 Supply and Laying of insulated mat Class-A ,IS 15652:2006 as per TATA Power-DDL Specifications. (1 meter wide by 2 meters long) LV(3.3kV)/DC EA 42 0.00 0.00 0.00 2 2 2 2 2 10 2 2 2 2 2 0 0 0 10 2
1.087 Supply and Laying of insulated mat Class-B ,IS 15652:2006as per TATA Power-DDL Specifications. (1 meter wide by 2 meters long) 11KV EA 122 0.00 0.00 0.00 10 10 10 10 10 10 10 10 10 10 10 0 0 2 10
1.088 SITC of asset numbering- Complete identification of all the assets/equipment’s, RCC cable trench cover marking in the approve color and numbering to be done with detailed description of the asset as per the requirement of project in-charge. This includes Supply of paints and other required material to complete the activity. (This item shall be paid per PTR Bay/ Line Bay,) LOT 22 0.00 0.00 0.00 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1
1.089 SITC of Grid signs boards i.e. safety notices such as "Danger of Death," "High Voltage," and "No Trespassing," along with fire safety signs like "Fire Alarm" and "Fire Exit Keep Clear," and protective equipment information like "Wear Safety Helmet" and "First Aid", Prohibition signs, Hazard signs, Emergency information signs, Fire Equipment signs at various locations. The exact signs may vary by location, but the purpose is to warn of hazards, instruct on safety procedures. LOT 16 0.00 0.00 0.00 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1.09 Supply and Fixing of the Danger plates on the poles/tower/structure including fabrication of clamp etc. EA 64 0.00 0.00 0.00 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
1.092 Transportation of various items from stores to site or from site to site or from site to store including loading and unloading: with tempo 709/410 EA 28 0.00 0.00 0.00 2 2 2 2 2 2 2 2 2 2 2 1 1 1 1 2
1.093 Supply of Vacuum Cleaner as per TATA Power-DDL project in-charge instructions. Approved make : Eureka Forbes Pro Vac WD 77 EA 5 0.00 0.00 0.00 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0
1.094 SITC of industrial type continuous heavy duty Exhaust fan with louvers, 18 inches including auto-changeover facility. Approved make: Bajaj/Crompton/Havells EA 61 0.00 0.00 0.00 4 4 4 4 4 12 4 4 4 2 4 0 0 2 5 4
1.095 SITC of Industrial type Dewatering/submersible/sewage pump (fixed type) 415 V, 2 HP, automatic ON/OFF feature,Pre-fitted float switch ensure that the pump start and stop automatically as per need and including required plumbing items(union, valves, sockets, CPVC pipe etc.) & connections along with outlet flexible nylon braided PVC pipe - 30 meters. including all accessories if required. Approved make - Crompton/Kirloskar EA 7 0.00 0.00 0.00 1 1 1 1 1 1 0 0 0 0 0 1 0 0 0
1.096 SITCof Industrial type Dewatering/submersible/sewage pump (portable type) 415 V, 1 HP, automatic ON/OFF facility and including required plumbing connections along with outlet flexible nylon braided PVC pipe - 30 meters. - Approved make - Crompton/Kirloskar EA 18 0.00 0.00 0.00 1 1 1 1 1 1 2 2 2 1 2 0 0 1 2
1.097 SITC of BLDC ceiling fan, 48 '' as per TATA Power-DDL project in-charge instructions. Approved Make : Crompton/Bajaj/Havells EA 47 0.00 0.00 0.00 4 4 4 4 4 4 5 5 4 0 2 0 0 2 5
1.098 SITC of BLDC wall mounted fan 400 mm, 1350 rpm, auto swing. Approved make : Bajaj/Havells/Crompton EA 14 0.00 0.00 0.00 2 2 2 2 2 4 0 0 0 0 0 0 0 0 0
1.099 Supply of platform type FRP ladder 3M height, extra heavy duty ladder for all industrial application as per TATA Power-DDL specifications. EA 6 0.00 0.00 0.00 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0
1.1 Mounting of 66/33 KV 1Cx1000sqmm & 33KV 3Cx400sqmm Cable on pole,Structure,tower etc. M 155 0.00 0.00 0.00 25 25 25 25 25 0 0 0 0 10 0 0 0 0 20 0
1.101 Supply of Linear Heat sensing (LHS) cable as per TPDDL SpecificationsApproved Makes: Patol, Alankar, Ravel M 700 0.00 0.00 0.00 50 50 50 50 50 150 50 50 50 50 50 0 0 0 50
1.102 SITC of Multi - Heat and Smoke -Type Fire detectors as per IS 2189.Blinking Type for health indication. Approved Make : Ravel / System Sensor / Agni Suraksha /ASES / Honeywell with required accessories as per TPDDL specifications. EA 130 0.00 0.00 0.00 12 12 12 12 12 20 10 10 5 5 10 0 0 0 10
1.104 ITC of 3.3 kv XLPE insulated AL watertig M 180 0.00 0.00 0.00 30 30 30 30 30 0 0 0 0 30 0 0 0 0 0
1.106 ITC of TRANSFORMER 1.6 MVA 3PH11KV/433V CU on existing plinth and making all connection on 11kV & LV side along with associated works EA 2 0.00 0.00 0.00 2 0 0 0 0 0 0 0 0 0
1.107 Installation ,testing & commissioning of CIRCUIT BREAKER SF6 66KV 1600A with operating mechanism, GI structure, jumpering/connections grouting works and other accessories as per the approved drawing. All the Electrical and mechanical interlock of breaker should be available in working condition and should be checked before commissioning. This item also includes ITC of castle key & interlocking arrangement for breakers & isolators supplied with the equipment. SET 11 0.00 0.00 0.00 5 1 1 1 0 1 0 0 1 1
1.108 Installation ,testing & commissioning of CT 66KV 750-500-250/1/1/1/1A 0.2CLASS OD including jumpering/connections. EA 33 0.00 0.00 0.00 18 3 3 3 0 3 0 0 0 3
1.109 Installation ,testing & commissioning of PT RATIO 66KV/1.73 110V/1.73 O/D 0.2 CLA to be used as line PT/bus PT. This items includes jumpering/connections. EA 15 0.00 0.00 0.00 15 0 0 0 0 0 0 0 0 0
1.11 Installation ,testing & commissioning of ISOLATOR 66KV 1600A 3PH 25KA CB W/O E/S along with gear box arrangement and other accessories including , jumpering/connections. This item also includes ITC of castle key & interlocking arrangement for breakers & isolators supplied with the equipment. EA 26 0.00 0.00 0.00 14 2 2 2 0 2 0 0 2 2
1.111 301001440 Supply of 72.5KV ,1600A, 3 Ph gang operated , Manual Operated, Center Break Disconnector (Isolator) with solid core post insulator - Without earth switch with gear box arrangement and other accessories including castle key & interlocking arrangement as per latest TATA Power-DDL specifications. SET 26 0.00 0.00 0.00 14 2 2 2 0 2 0 0 2 0 2
1.112 Installation ,testing & commissioning of ISOLATOR 66KV 1600A 3PH 25KA CB WITH E/S With earth switch along with gear box arrangement and other accessories including jumpering/connections. this item also includes ITC of castle key & interlocking arrangement for breakers & isolators supplied with the equipment. EA 11 0.00 0.00 0.00 5 1 1 1 0 1 0 0 1 1
1.113 301001441 Supply of 72.5KV ,1600A, 3 Ph gang operated , Manual Operated, Center Break Disconnector (Isolator) with solid core post insulator - With earth switch with gear box arrangement and other accessories including castle key & interlocking arrangement as per latest TATA Power-DDL specifications. Castle Lock Earth Switch and Isolator (Castle Lock For Mechanical interlock between Isolator main switch and earth switch )- 1 set SET 11 0.00 0.00 0.00 5 1 1 1 0 1 0 0 1 0 1
1.114 Stringing of ACSR conductor and its connection with bus ACSR conductor and those equipment which are not covered under other line items of tender BoM. M 3750 0.00 0.00 0.00 1250 400 400 300 0 400 200 200 200 400
1.115 Installation, Testing & Commissioning of SPACER (Rigid & Flexible) as per TATA Power-DDL standard drawing and project in-charge instructions EA 150 0.00 0.00 0.00 50 20 20 20 0 20 0 0 0 20
1.116 SITC of High Mast (motorized) 16m as per TATA Power-DDL specifications. Approved Makes : Bajaj/Philips/Surya. This item includes SITC of all required accessories including LED lights & structure etc. but excluding civil works. EA 5 0.00 0.00 0.00 1 1 1 0 0 0 1 0 0 1
1.117 SITC of Industrial type Air-conditioning package unit (capacity 2 x 2 tonnes) make with auto changeover with required accessories (complete wiring and piping) floor standing type as per TATA Power-DDL latest specifications and site requirement. Refrigerant type shall be R32 or R40 only" shall be as per actual. EA 4 0.00 0.00 0.00 4 0 0 0 0 0 0 0 0 0
1.118 SITC of 1.5 Ton 5 Star Inverter Split AC as per TATA Power-DDL approved make with auto changeover facility. It also includes the arrangement of AC waste water disposal arrangement (including minor plumbing/civil work) EA 2 0.00 0.00 0.00 2 0 0 0 0 0 0 0 0 0
1.119 SITC of Bay marshalling kiosk made of 2.5 mm. Thick sheet steel , IP 55 enclosure protection as per specification. EA 12 0.00 0.00 0.00 6 1 1 1 0 1 0 0 1 1
1.12 SITC of CT/PT Junction Box of 2.5 mm thick sheet steel, IP 55 enclosure protection as per specification. EA 15 0.00 0.00 0.00 9 1 1 1 0 1 0 0 1 1
1.121 ITC of Single anchoring point single tension line hardware fitting compression type with polymeric/Disc insulators suitable for 66KV tension polymeric insulators, Shackle suitable for 20 mm anchoring hole on beam side, without turn buckle for SINGLE ACSR ZEBRA conductor Complete as per specification. EA 21 0.00 0.00 0.00 6 3 3 3 0 3 0 0 0 3
1.122 ITC of Single anchoring point single tension line hardware fitting compression type with polymeric/Disc insulators suitable for 66KV tension polymeric insulators, Shackle suitable for 20 mm anchoring hole on beam side, with turn buckle for SINGLE ACSR ZEBRA conductor Complete as per specification. EA 21 0.00 0.00 0.00 6 3 3 3 0 3 0 0 0 3
1.123 ITC of Single anchoring point Double tension line hardware fitting compression type with polymeric/Disc insulators suitable for 2 x 66KV tension polymeric insulators, Shackle suitable for 20 mm anchoring hole on beam side, without turn buckle for TWIN ACSR ZEBRA conductor Complete as per specification. EA 27 0.00 0.00 0.00 12 3 3 3 0 3 0 0 0 3
1.124 ITC of Single anchoring point Double tension line hardware fitting compression type with polymeric/Disc insulators suitable for 2 x 66KV tension polymeric insulators, Shackle suitable for 20 mm anchoring hole on beam side, with turn buckle for TWIN ACSR ZEBRA conductor Complete as per specification. EA 27 0.00 0.00 0.00 12 3 3 3 0 3 0 0 0 3
1.125 ITC of Single suspension Hardware fitting complete with Shackle & polymeric/Disc insulators suitable for 20 mm anchoring hole, all hardware suitable for SINGLE ACSR ZEBRA conductor with through clamp suitable for 66KV suspension polymeric Insulators, complete assembly as per specification. EA 30 0.00 0.00 0.00 6 3 3 3 0 3 3 3 3 3
1.126 ITC of Single suspension Hardware fitting complete with Shackle & polymeric/Disc insulators suitable for 20 mm anchoring hole, all hardware suitable for TWIN ACSR ZEBRA conductor with through clamp suitable for 66KV suspension polymeric Insulators, complete assembly as per specification. EA 30 0.00 0.00 0.00 6 3 3 3 0 3 3 3 3 3
1.127 ITC of Single suspension hardware fitting complete with Shackle & polymeric/Disc insulators suitable for 20 mm anchoring hole, all hardware suitable for TWIN ACSR ZEBRA conductor with drop clamp suitable for 66KV suspension polymeric Insulators, complete assembly as per specification. EA 21 0.00 0.00 0.00 6 3 3 3 0 3 0 0 0 3
1.128 ITC of Single suspension hardware fitting complete with Shackle & polymeric/Disc insulators suitable for 20 mm anchoring hole, all hardware suitable for SINGLE ACSR ZEBRA conductor with drop clamp suitable for 66KV suspension polymeric Insulators, complete assembly as per specification. EA 21 0.00 0.00 0.00 6 3 3 3 0 3 0 0 0 3
1.129 Dismantling of GI/MS structure as per TATA Power-DDL project in-charge. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. TON 3.9 0.00 0.00 0.00 2 0.2 0.4 0.4 0.4 0.5
1.13 Dismantling of Steel tubular pole 8/9/10 mtr long with base plate & cross arm with other arrangement EA 15 0.00 0.00 0.00 0 3 3 3 3 0 0 0 0 3
1.131 SITC of extension module for AC Distribution Board AC 415V, 400A cubicle type Indoor, floor mounted, auxiliary service board as per TATA Power-DDL specification. (O/G MCBs: 150 A x 1; 63 A x 2, 32 A x 2, 16 A x 4) EA 3 0.00 0.00 0.00 1 1 0 0 0 0 1
1.132 ITC of 11kV 5 MVAR Reactor Installation ,testing & commissioning of as per TATA Power-DDL specifications. There shall be outdoor bushings on HV side which shall be connected with the overhead bus through brass palm connectors and on LV side shorted . Bushing palm connectors shall be provided for HV bushing. This includes oil filtration of reactor also. EA 6 0.00 0.00 0.00 1 1 1 1 1 0 0 0 1
1.133 ITC of CAPACITOR BANK 7.2MVAR 12.65KV O/D along with Capacitor units, support Structure,NCT,Reactor,Interconnecting Bus-Bar/cable, Lightning Arrestor,Insulators,insulation sleaves,cage fencing & other accessories etc. excluding civil works. as per TATA Power-DDL specifications. EA 2 0.00 0.00 0.00 1 1 0 0 0 0
1.134 SITC of 1-PhLink Box EA 1 0.00 0.00 0.00 1 0 0 0 0
1.135 ITC of High Mast (motorized) 12/16m as per TATA Power-DDL specifications. Approved Makes : Bajaj/Philips/Surya. This item includes ITC of all required accessories including LED lights & structure etc. but excluding civil works. EA 1 0.00 0.00 0.00 1 0 0 0
1.136 Dismantling of High Mast (motorized) 12/16m as per TATA Power-DDL specifications.Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site EA 1 0.00 0.00 0.00 1 0 0 0
1.137 Dismantling of TRANSFORMER POWER upto 20/25MVA 66/11KV including all accessories & cable mounting structure, BPI, bus bar arrangement, MB,opening of HV/LV connections/jumpers/earthing connection,Fan&stand and dragging up to 30m from the foundation to loading point by using required T&P and wooden sleepers. Loading point may be low bed trailer. The scope of work also includes drain of oil & storage into drums. EA 3 0.00 0.00 0.00 1 1 1
1.138 Dismantling of outdoor neutral CT (NCT) for PTR including its disconnections with PTR/Reactor & NGR/Earth Pit, etc..Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. EA 3 0.00 0.00 0.00 1 1 1
1.139 Dismantling and removing of control cables for grid works including rewounding back on drums or in coils. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. M 2000 0.00 0.00 0.00 500 500 500 500
1.14 Dismantling of Conductor with insulators & hardware (per mtr per conductor) including stacking at site/store. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. M 30 0.00 0.00 0.00 30
1.141 Dismantling of CIRCUIT BREAKER 66/33KV including structure as per TATA Power-DDL Project in-charge instructions. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. EA 1 0.00 0.00 0.00 1
1.142 Dismantling of NIFPS system including pipe arrangement and staking at site EA 1 0.00 0.00 0.00 1
1.143 Dismantling of Equipment like CT, PT, LA & Isolator Loading, Scope of work also include loading, unloading of material/equipment & transportation up to TPDDL Store/site.Dismantling of healthy equipment's also includes the testing of the equipment before handed over to TATA Power-DDL engineer In charge EA 3 0.00 0.00 0.00 3
1.144 Dismantling and removing of EHV/HT U/G cables for grid works from the earth or existing power cable trench. This also includes earth excavation (if required) to dismantle the cable and rewounding the cable back on drums or in coils .Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. M 1300 0.00 0.00 0.00 300 500 500
1.145 Dismantling of TRANSFORMER POWER upto 20/25 MVA 33/11KV including all accessories & cable mounting structure, BPI,MB, bus bar arrangement, opening of HV/LV connections/jumpers/earthing connection,Fan&stand and dragging up to 30m from the foundation to loading point by using required T&P and wooden sleepers. Loading point may be low bed trailor.The scope of work also includes drain of oil & storage into drums. EA 1 0.00 0.00 0.00 1
1.146 ITC of TRANSFORMER POWER 20/25 MVA 33/11KV Installation ,testing & commissioning of 3 Ph, 'Dyn11 ONAN/ ONAF power Transformer with OLTC including fixing of all loose accessories/parts of transformer (supplied with the transformer) ,pre-commissioning checks. Transformer shall be equipped with cable boxes on both the primary and secondary sides. This item includes jumpering/connections on both sides. It also includes testing of transformer at site as per TATA Power-DDL power transformer specifications. This includes oil filtration of transformer. EA 1 0.00 0.00 0.00 1
1.147 LTC of CABLE 33KV AL 3CX400 SQ MM XLPE ARM (as per TPDDL's specification) already in the excavated trench/already laid pipe M 400 0.00 0.00 0.00 400
1.148 ITC of Distribution Box 160A TP MCCB EA 1 0.00 0.00 0.00 1
1.149 Supply of TEREC+ earthing compound KG 100 0.00 0.00 0.00 100
1.15 ITC of 7/3.15 mm GSS wire including clamps as per TATA Power-DDL approved drawings. M 150 0.00 0.00 0.00 50 50 50
1.151 Dismantling and re-installation of switchyard fence including allied civil works as per TATA Power-DDL Project In-charge. M2 350 0.00 0.00 0.00 100 25 25 25 25 25 25 25 25 25 25
1.152 Supply and Laying of insulated mat Class-C ,IS 15652:2006 as per TATA Power-DDL Specifications. (1 meter wide by 2 meters long) 33KV EA 2 0.00 0.00 0.00 2
1.153 Dismantling of existing 11kV, 7.2 MVAR Cap Bank including accessories,Cage fencing, structure etc. Scope of work also include loading, unloading of material & transportation up to TPDDL Store/site. EA 1 0.00 0.00 0.00 1
1.154 Installation ,testing & commissioning of 30KV,10KA, heavy duty, station class, lightning arrestor(LA) & surge counter including laying & connection of 1CX50 sqmm copper flexible cable with LA surge counter. This item includes jumpering/connections. EA 3 0.00 0.00 0.00 3
1.155 Installation ,testing & commissioning of CT 33KV 750-500/1/1/1/1A CLASS 0.2 O/D including jumpering/connections. EA 3 0.00 0.00 0.00 3
1.156 Installation ,testing & commissioning of PT RATIO 33KV/1.732(110/1.732) OD 0.2 CL to be used as line PT/bus PT. This items includes jumpering/connections. EA 3 0.00 0.00 0.00 3
1.157 SITC of beam detectors as per IS 2189. Approved Make : System sensor / Apollo / Edward with required accessories as per TPDDL specifications. EA 5 0.00 0.00 0.00 5
1.158 SITC of 200MM GI Pipe Class C M 10 0.00 0.00 0.00 10
1.159 Disconnection, lower down of cables & reconnection of 11kV 3Run/Phase of 1Cx1000sqmm cable in11kV Incomer panel along with other associated works.(Per Panel) EA 2 0.00 0.00 0.00 2
1.16 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. M2 50 0.00 0.00 0.00 50
1.161 Dismantling of CT JB,MB EA 5 0.00 0.00 0.00 5
1.162 SITC of castle key lock arrangement for CB, Isolators (CB to bus isolators & line isolators and between isolators) as per TATA Power-DDL project in-charge instructions (this line item will be executed whenever castle key lock arrangement not available with CB/isolator) EA 2 0.00 0.00 0.00 2
1.163 Dismantling & re fixing of cable tray M 50 0.00 0.00 0.00 50
Total All Inclusive Amount (Rs) - Civil Services 0.00 Khanjawala Rohini-3 Rohini-4 Shavda Narela-A-3
2.001 205894 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. M2 1815 0.00 0.00 0.00 1815
2.002 205895 Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) M3 1561.6 0.00 0.00 0.00 223 223 223 223 223 330 12.1 5.5 6.6 12.1 46.2 8.8 12.1 6.6 6.6
2.003 205896 Demolishing cement concrete manually/ by mechanical mEAns including disposal of material within 50 metres lEAd as per direction of Engineer - in - charge. Nominal concrete 1:4:8 or lEAner mix (i/c equivalent design mix) M3 27.5 0.00 0.00 0.00 27.5
2.004 205897 Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge. M3 315.4 0.00 0.00 0.00 5 5 5 5 5 220 17.6 11 2.2 3.3 11 7.7 3.3 2.2 12.1
2.005 205898 Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. In cement mortar M3 291.662 0.00 0.00 0.00 5 5 5 5 5 177.1 10.362 22 2.2 4.4 27.5 7.7 4.4 2.2 8.8
2.006 205900 Dismantling stone slab flooring laid in cement mortar including stacking of serviceable material and disposal of unserviceable material within 50 metres lead. M2 13.2 0.00 0.00 0.00 12.1 1.1
2.007 205913 Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Cost should include breaking of 1m of top pile head. Note: Truck Mounted rotary/TMR/Tubewell boring mchine shall not be used. (Note :- Min. Cement content shall be 400 KG/M3.) 450 mm dia piles M 3000 0.00 0.00 0.00 1500 0 0 1500 0
2.008 205918 Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections M 1498.4229 0.00 0.00 0.00 151 151 151 151 151 657.1829 86.24
2.009 205919 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete at all levels. Thermo-Mechanically Treated bars of grade Fe-500D or more. KG 622235.9347 0.00 0.00 0.00 89062.5 59625 59625 89062.5 59625 132326.3117 51784.623 28875 3245 5445 22825 4152.5 5087.5 4345 7150
2.01 205920 Extra for making pointed edge of square bars by hEAting & hammering. EA 100 0.00 0.00 0.00 20 20 20 20 20
2.011 205921 Structural steel work in single section fixed with or without connecting plate including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. KG 31988.84 0.00 0.00 0.00 250 250 250 250 250 8121.08 9709.26 220 12100 220 55 313.5
2.012 205922 Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. KG 90953.8593 0.00 0.00 0.00 3000 3000 3000 3000 3000 34177.2453 13781.614 12100 3300 2530 2860 2310 2750 2145
2.013 205923 Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete. KG 25190.0103 0.00 0.00 0.00 2500 2500 2500 2500 2500 6827.4173 4102.593 220 1540
2.014 205924 Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. KG 12585 0.00 0.00 0.00 2000 2000 2000 2000 2000 220 2365
2.015 205925 P/F 2mm thick MS sheet including welding cutting assembling and erection including a coat of primer as directed by Eng. In charge KG 13191.1366 0.00 0.00 0.00 2500 2500 2500 2500 2500 679.0366 12.1
2.016 205926 Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying a priming coat of approved steel primer. M.S. tube. KG 500 0.00 0.00 0.00 100 100 100 100 100
2.017 205927 Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. Fixed to openings /wooden frames with rawl plugs screws etc. KG 623.8839 0.00 0.00 0.00 40 40 40 40 40 121.3839 302.5
2.018 205928 Providing and fixing IRC fabric (welded mesh) of desired size to the frame of MS angles, channels, tees, flats etc. including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer as required. In frames, gates etc. (Cost of MS frame will be paid separately). Fixed to steel frames by welding. KG 3105.102 0.00 0.00 0.00 550 550 550 550 550 88.726 110 101.376 55
2.019 205929 Providing and fixing concertina coil fencing with punched tape concertina coil 600 mm dia 10 metre openable length ( total length 90 m) having 50 no rounds per 6 metre length, upto 3m height of wall with existing angle iron 'Y' shaped placed 2.4m or 3.00m apart and with 9 horizontal R.B.T. reinforced barbed wire, stud tied with G.I. staples and G.I. clips to retain horizontal including necessary bolts or G.I. barbed wire tied to angle iron, all complete as per direction of Engineer-in-charge, with reinforced barbed tape(R.B.T.) /Spring core (2.5mm thick) wire of high tensile strength of 165 KG/ sq.mm with tape (0.52 mm thick) and weight 43.478gm/ metre (cost of M.S. angle, C.C. blocks shall be paid separately) M 399.89 0.00 0.00 0.00 25 25 25 25 25 208.89 60.5 5.5
2.02 205930 Providing and fixing T-iron frames for doors, windows and ventilators of mild steel Tee-sections, joints mitred and welded, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with 15x3 mm lugs 10 cm. long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size). KG 969.5603 0.00 0.00 0.00 111 111 111 111 111 392.5603 22
2.021 205931 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) KG 897.4816 0.00 0.00 0.00 91 91 91 91 91 321.6136 109.868 11
2.022 205932 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately). :Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) KG 85.5499 0.00 0.00 0.00 8 8 8 8 8 25.7499 8.8 11
2.023 205935 Extra for pre finished nosing in treads of steps of Kota stone/ sand stone slab. M 250 0.00 0.00 0.00 50 50 50 50 50
2.024 205937 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 150 mm dia. R.C.C. pipe M 63.9496 0.00 0.00 0.00 43.5666 14.883 5.5
2.025 205938 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete: 250 mm dia. R.C.C. pipe M 254.45 0.00 0.00 0.00 40 40 40 40 40 54.45
2.026 205939 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 300 mm dia. R.C.C. pipe M 259 0.00 0.00 0.00 10 10 10 10 10 5.5 33 33 11 16.5 33 16.5 33 11 16.5
2.027 205956 Providing and fixing G.I. Pipes complete with G.I. fittings and clamps i/c making good the walls etc. concealed pipe including painting with anti corrosive bitumastic paint, cutting chases and making good the wall - 20 mm dia. nominal bore M 83.7909 0.00 0.00 0.00 10 10 10 10 10 33.7909
2.028 205957 Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work - 25 mm dia. nominal bore M 183.5334 0.00 0.00 0.00 10 10 10 10 10 133.5334
2.029 205962 Providing and fixing soil, waste and vent pipes (Sand cast iron S&S pipe as per IS: 1729)b) 75mm dia M 50 0.00 0.00 0.00 10 10 10 10 10
2.03 205973 Dismantling barbed/RBT/concertina wire or flexible wire rope in fencing including making rolls and stacking within 50 metres lead. KG 57.112 0.00 0.00 0.00 8.712 37.4 11
2.031 205974 Dismantling expanded metal including chain link fencing or I.R.C. fabrics with necessary battens and beading including stacking the serviceable material within 50 metres lead. M2 781.638 0.00 0.00 0.00 669.438 16.5 16.5 46.2 16.5 16.5
2.032 205975 Dismantling steel work in built up sections in angles, tees, flats and channels including all gusset plates, bolts, nuts, cutting rivets, welding etc. including dismembering and stacking within 50metres lead. KG 1305.92 0.00 0.00 0.00 82.72 110 948.2 55 55 55
2.033 205978 Collecting, stacking , screening & respreading of existing yard gravel stone. M3 602.272 0.00 0.00 0.00 429 68.772 5.5 11 66 5.5 11 5.5
2.034 205981 Earth work in excavation for all depths in all kinds of soil by mechanical means (Hydraulic excavator) / manual means including dressing of sides and ramming of bottoms including dewatering of water coming from any source such as rains, accumulated rain water, floods, leakages from sewer, drains, water lines, ground water table being high or due to any other cause whatsoever wherever required by means of suitable capacity of pumps and pipe lines etc. or by any other method during excavation, concreting and also keeping the area dry till the construction is over including close timbering including strutting, shoring and packing cavities, soldier piling, sheet piling or by any other suitable method (wherever required) etc. complete and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed. No additional payment shall be made on account of dewatering and method of shoring/piling adopted for retaining earth whatsoever. M3 18211.8095 0.00 0.00 0.00 1706 1706 1706 1706 1706 4234.2685 2059.541 1292.5 137.5 253 1072.5 110 170.5 137.5 214.5
2.035 205982 Extra over item for "Earthwork in excavation..... adopted whatsoever" in all kinds of soils for every additional lift of 1.5 m or part thereof. No additional payment shall be made on account of dewatering and method of shoring/piling adopted for retaining earth whatsoever. M3 7515.049 0.00 0.00 0.00 853 853 853 853 853 1569.634 900.515 269.5 57.2 275 22 57.2 22 77
2.036 205983 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and for all lifts. M3 17002.7148 0.00 0.00 0.00 1706 1706 1706 1706 1706 3569.6738 2059.541 1292.5 137.5 154 742.5 110 55 137.5 214.5
2.037 205985 Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. M3 30.273 0.00 0.00 0.00 2 2 2 2 2 5.313 13.86 1.1
2.038 205986 Supplying, diluting and injecting chemical emulsion for Pre-constructional Anti-Termite Treatment and creating a continuous chemical barrier under and all around the column pits, wall trenches, basement excavation, top surface of plinth filling, junction of wall and floor, along the external perimeter of building, expansion joints, over the top surface of consolidated earth on which apron is to be laid, surrounding of pipes and conduits etc. complete as per IS codes & specifications (plinth area of the building at ground floor only shall be measured for payment) with Chlorphyriphos Emulsifiable concentrate 20% with 1% concentration. M2 1780.872 0.00 0.00 0.00 175 175 175 175 175 765.072 121 19.8
2.039 205989 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) M3 8.8 0.00 0.00 0.00 5.5 3.3
2.04 205991 Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 12.5mm nominal size derived from natural sources) M2 3.3 0.00 0.00 0.00 3.3
2.041 205993 Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth. M2 42.35 0.00 0.00 0.00 42.35
2.042 205994 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. All works upto plinth level. Concrete of M25 grade with minimum cement content of 330 kg /cum M3 3934.3965 0.00 0.00 0.00 350 350 350 350 350 1015.8764 432.487 247.5 41.2731 59.4 203.5 33.66 40.7 38.5 71.5
2.043 205995 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. All works above plinth level upto floor V level. Concrete of M25 grade with minimum cement content of 330 kg /cum M3 816.7482 0.00 0.00 0.00 102 102 102 102 102 241.8482 41.8 5.5 5.5 12.1
2.044 205996 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 cement : 2 coarse sand (zone-III) including manufactured sand derived from Recycled Concrete Aggregate (RCA) upto 25% : 4 graded stone aggregate 20 mm nominal size Recycled Concrete Aggregate (RCA) upto 25%) M3 71.4535 0.00 0.00 0.00 6 6 6 6 6 20.1135 7.942 2.2 1.1 1.1 5.5 0.198 3.3
2.045 205998 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Foundations, footings, bases of columns, etc. for mass concrete. M2 3162.1558 0.00 0.00 0.00 240 240 240 240 240 805.0108 517.385 242 13.2 33 181.5 33 33 43.56 60.5
2.046 205999 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. M2 10347.1507 0.00 0.00 0.00 690 690 690 690 690 3288.5237 1636.327 588.5 55 154 660 74.8 154 55 231
2.047 206000 Centering and shuttering including strutting, propping etc. and removal of form for all heights: Suspended floors, roofs, landings, balconies and access platform. M2 2216.6694 0.00 0.00 0.00 198 198 198 198 198 863.8234 308.946 13.2 27.5 13.2
2.048 206001 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Lintels, beams, plinth beams, girders, bressumers and cantilevers. M2 4031.5867 0.00 0.00 0.00 477 477 477 477 477 1246.1207 334.466 16.5 16.5 33
2.049 206002 Centering and shuttering including strutting, propping etc. and removal of form for for all heights : Columns, Pillars, Piers, Abutments, Posts and Struts. M2 6414.6442 0.00 0.00 0.00 633 633 633 633 633 2083.6442 528.44 181.5 63.8 64.9 159.5 32.56 25.3 74.8 35.2
2.05 206003 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Stairs, (excluding landings) except spiral-staircases. M2 125 0.00 0.00 0.00 25 25 25 25 25
2.051 206004 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Weather shade, Chajjas, Corbels etc., including edges. M2 44.2187 0.00 0.00 0.00 4 4 4 4 4 13.9557 4.763 5.5
2.052 206005 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) M3 247.0193 0.00 0.00 0.00 129.2093 62.81 13.2 14.3 16.5 3.3 7.7
2.053 206007 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) M3 1252.0608 0.00 0.00 0.00 152 152 152 152 152 329.7008 98.56 39.6 6.6 12.1 5.5
2.054 206009 Extra for providing and placing in position 2 Nos. 6mm dia. M.S. bars at every third course of half brick masonry. M2 50 0.00 0.00 0.00 10 10 10 10 10
2.056 206012 15 mm cement plaster on the rough side of single or half brick wall of mix for all heights: 1:4 (1 cement: 4 fine sand) M2 7638.5668 0.00 0.00 0.00 965 965 965 965 965 2141.4448 287.122 38.5 22 33 82.5 93.5 22 44 49.5
2.057 206014 6 mm cement plaster of mix for all heights: 1:3 (1 cement: 3 fine sand) M2 1153.9891 0.00 0.00 0.00 1013.1891 121 19.8
2.058 206016 Providing and fixing Chicken-mesh of 1.5 mm dia. steel wire with hexagonal or rectangular openings of 20-25 mm 150 mm wide fixed with U nails at 150 mm centre to centre placed and held properly in position at brick and R.C.C joints as per direction of engineer-in-charge. M2 250 0.00 0.00 0.00 50 50 50 50 50
2.06 206018 Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 -part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25mm M.S. laths with 1.25 mm thick top cover. M2 100.92 0.00 0.00 0.00 12 12 12 12 12 13.2 14.52 13.2
2.061 206019 Providing and fixing GI chain link fabric fencing of required width in mesh size 75x75 mm, 3.15 mm dia. mesh wire as per drawing conforming to IS:2721, MS stirrups wire 2.5 mm dia. with tying wire 1.6 mm dia. including providing 25x4.75 mm stretcher bars, eye bolt 85 mm half round staples etc. including nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. (MS Flat, angle etc. will be paid separately). M2 349.25 0.00 0.00 0.00 115.5 121 13.75 82.5 16.5
2.062 206021 Providing and fixing stainless steel (SS 304 grade) adjustable friction windows stays of approved quality with necessary stainless steel screws etc. to the side hung windows as per direction of Engineerin-charge complete.255 X 19 mm EA 17.6 0.00 0.00 0.00 13.2 4.4
2.063 206023 Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 KG., for doors, including cost of cutting floors ,embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. With stainless steel cover plate minimum 1.25 mm thickness. EA 5 0.00 0.00 0.00 1 1 1 1 1
2.064 206024 Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS:12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides. M2 125 0.00 0.00 0.00 25 25 25 25 25
2.065 206027 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 4.0 mm thickness (weight not less than 10 kg/ sqm) M2 73.7022 0.00 0.00 0.00 54.9362 18.766
2.066 206028 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5 mm thickness (weight not less than 12.50 kg/ sqm) M2 93.47 0.00 0.00 0.00 17 17 17 17 17 4.675 1.595 2.2
2.067 206029 Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/M2 (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the rate of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm or both sides of joint and two coats of primer suitable for board, all as per manufacture's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : 12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- Part I.: 2011 (Board with BIS certification marks) M2 129.4046 0.00 0.00 0.00 10 10 10 10 10 59.1866 20.218
2.068 206031 Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 KG/M2. of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto300mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to115mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand)admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with waterproofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs c)After two days of proper curing applying a second coat of cement slurry using 2.75KG/ M2 of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge. d)Finishing the surface with 20 mm thick jointless cement mortar of mix1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : With average thickness of 120mm and minimum thickness at khurra as 65 mm. M2 2181.9531 0.00 0.00 0.00 215 215 215 215 215 935.9031 151.25 19.8
2.069 206033 Providing and fixing GI chain link fabric fencing of required width in mesh size 75x75 mm, 3.15 mm dia. mesh wire PVC coated to achieve outer dia. not less than 4.15 mm in required colour and shadeas per drawing conforming to IS:2721, MS stirrups wire 2.5 mm dia. with tying wire 1.6 mm dia. including providing 25x4.75 mm stretcher bars, eye bolt 85 mm half round staples etc. including nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. (MS Flat, angle etc. will be paid separately). M2 375 0.00 0.00 0.00 75 75 75 75 75
2.07 206035 Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet1mx1mx400micron, finished with 12mm cement plaster 1:3 (1 cement :3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. EA 115 0.00 0.00 0.00 12 12 12 12 12 39.6 13.2 2.2
2.071 206037 Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade New work (two or more coats) over and including water thinnable priming coat with cement primer. M2 2481.8244 0.00 0.00 0.00 2118.8244 363
2.072 206039 Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 KG/10 M2). M2 3331.5714 0.00 0.00 0.00 60 60 60 60 60 2498.2694 373.802 27.5 33 33 38.5 27.5
2.073 206040 Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade: Two or more coats on new work. M2 29.3282 0.00 0.00 0.00 29.3282
2.074 206041 Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work. M2 6207.4005 0.00 0.00 0.00 300 300 300 300 300 1733.8255 2000.075 275 33 55 165 99 77 22 247.5
2.075 206044 Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick. M2 1174.9407 0.00 0.00 0.00 112 112 112 112 112 487.6267 108.614 13.2 5.5
2.076 206045 Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. M2 129.5853 0.00 0.00 0.00 15 15 15 15 15 37.4033 12.782 2.2 2.2
2.077 206046 Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer ) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3KG per M2 including pointing in white cement mixed with pigment of matching shade complete. M2 37.9698 0.00 0.00 0.00 37.9698
2.078 206047 Providing and laying Ceramic glazed floor tiles 300x300 or 400x400 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS :15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4Coarse sand) including pointing the joints with white cement and matching pigment etc., complete. M2 6.9773 0.00 0.00 0.00 6.9773
2.079 206053 Supplying, laying & spreading machine crushed 65 mm good quality stone aggregates including compacing the same. M3 130.658 0.00 0.00 0.00 11 11 11 11 11 26.158 6.6 6.6 6.6 6.6 6.6 16.5
2.08 206054 Disposal of all debris/rubbish/malba/surplus excavated earth/similar unserviceable, dismantled or waste materials arising out of demolition and construction activities, by mechanical means, including loading, transporting, unloading to authorized Construction and Demolition (C&D) waste recycling plant or approved municipal dumping ground as per the directions of TPDDL Engineer-in-charge, for all leads including all lifts involved. Bidder solely shall be responsible for identifying such area and bear all costs involved, TPDDL shall not be liable for the same. Bidder shall clear the site thoroughly of such unwanted materials and rubbish etc. left out of his work and dress the site to the satisfaction of the TPDDL Engineer-in-Charge in all respects before the final handing over. Nothing additional shall be paid on account of disposal of waste material to construction and demolition (C&D) waste recycling plant. M3 4243.3873 0.00 0.00 0.00 400 400 400 400 400 1209.3873 110 110 49.5 159.5 385 38.5 132 11 38.5
2.081 206055 Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. L 8542 0.00 0.00 0.00 1000 1000 1000 1000 1000 3542
2.082 206058 Providing and fixing aluminium tower bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade with necessary screws etc. complete : 200x10 mm EA 50 0.00 0.00 0.00 10 10 10 10 10
2.083 206059 Providing and fixing aluminium handles ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete : 125 mm EA 23.2 0.00 0.00 0.00 2 2 2 2 2 6.6 2.2 4.4
2.084 206060 Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. EA 5 0.00 0.00 0.00 1 1 1 1 1
2.085 206068 Supplying and fixing C.I. cover without frame for manholes : 610x610 mm rectangular C.I. cover (light duty) the weight of the cover to be not less than 23 KG. EA 19.9 0.00 0.00 0.00 2 2 2 2 2 4.4 1.1 1.1 1.1 1.1 1.1
2.086 206070 Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm. depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earth with lead upto 50 metres. M2 429 0.00 0.00 0.00 429
2.087 206071 Supplying and stacking at site. 90 mm to 45 mm size stone aggregate. M3 42.9 0.00 0.00 0.00 42.9
2.088 206072 Supplying and stacking at site. 63 mm to 45 mm size stone aggregate. M3 32.175 0.00 0.00 0.00 32.175
2.089 206073 Supplying and stacking at site. Stone screening 13.2 mm nominal size (Type A) M3 6.435 0.00 0.00 0.00 6.435
2.09 206074 Laying, spreading and compacting stone aggregate of specified sizes to WBM specifications in uniform thickness, hand picking, rolling with 3 wheeled road / vibratory roller 8-10 tonne capacity in stages to proper grade and camber, applying and brooming requisite type of screening / binding material to fill up interstices of coarse aggregate, watering and compacting to the required density M3 75.075 0.00 0.00 0.00 75.075
2.091 206075 Providing and laying R.C.C./ C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator, vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-incharge. (The panel shuttering work and steel reinforcement shall be paid for separately). (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately). M3 95.7 0.00 0.00 0.00 52.8 42.9
2.092 206076 Providing and fixing in position 12mm thick bitumen impregnated per cm fiber board conforming to IS: 1838, including cost of primer, sealing depth per compound Grade-A in expansion joints M2 9.9 0.00 0.00 0.00 9.9
2.093 206077 Providing and filling in position bitumen mix filler of proportion 80 KG. of hot bitumen, 1 KG. of cement and 0.25 cubic metre of coarse sand for expansion joints. M3 2.475 0.00 0.00 0.00 2.475
2.094 206079 Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge M3 155.7696 0.00 0.00 0.00 17 17 17 17 17 70.7696
2.095 206081 Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -in -charge. M3 5 0.00 0.00 0.00 1 1 1 1 1
2.096 206087 Providing and fixing 20 mm dia., 1.2 mtr long each GI rungs as per the directions of Engineer-In-Charge EA 166.6 0.00 0.00 0.00 10 10 10 10 10 41.8 11 17.6 8.8 17.6 8.8 11
2.097 206091 Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreouschina flushing cistern & C.P. flush bend with fittings & C.I.brackets,40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal designcomplete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : W.C. pan with ISI marked white solid plastic seat and lid EA 2.2 0.00 0.00 0.00 2.2
2.098 206092 Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with white PVC automatic flushing cistern,with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS :2556, C.I. trap with outlet grating and other couplings in C.P. brass, including painting of fittings and cutting and making good the walls and floors wherever required : Single half stall urinal with 5 litre P.V.C. automatic flushing cistern EA 2.2 0.00 0.00 0.00 2.2
2.099 206093 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require : White Vitreous China Flat back wash basin size 550x400 mm with single 15 mm C.P. brass pillar tap EA 7.2 0.00 0.00 0.00 1 1 1 1 1 2.2
2.1 206094 Providing and fixing 600 x 450 mm bevelled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board sheet ground fixed to wooden cleats with C.P. brass screws and washers complete. EA 7.2 0.00 0.00 0.00 1 1 1 1 1 2.2
2.101 206095 P/F CP brass toilet paper holder of approved quality and make. EA 2.2 0.00 0.00 0.00 2.2
2.102 206096 Providing and fixing brass bib cock of approved quality: 15 mm nominal bore EA 2.2 0.00 0.00 0.00 2.2
2.103 206104 Providing and filling the joints with spun yarn cement, slurry and cement mortar 1:2 ( 1 cement: 2 fine sand) in S.C.I/C.I pipes b) 75mm dia EA 10 0.00 0.00 0.00 2 2 2 2 2
2.104 206105 Providing and fixing plain bend of required degree (Sand cast iron S&S as per IS 1729)a) 100mm EA 10 0.00 0.00 0.00 2 2 2 2 2
2.105 206108 P/F PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fitting of approved quality and colour weighing not less than 105 gms. EA 7.2 0.00 0.00 0.00 1 1 1 1 1 2.2
2.106 206109 Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour 450 mm long towel rail with total length of 495 mm,78 mm wide and effective height of 88 mm, weighing not less than 170 gms EA 7.2 0.00 0.00 0.00 1 1 1 1 1 2.2
2.107 206110 P/f CP jali for nahni trap with or without hole using white cement and pigment to match the tile colour, complete. EA 13.8 0.00 0.00 0.00 1 1 1 1 1 8.8
2.108 206112 Providing and fixing gun metal non-return valve of approved quality (screwed end) 25mm nominal bore. Horizontal (ISI) EA 5 0.00 0.00 0.00 1 1 1 1 1
2.109 206113 Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 KG and frame to be not less than 2.70 KG as per standard design : 150x100 mm P type. With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 EA 5 0.00 0.00 0.00 1 1 1 1 1
2.11 206126 Fencing with angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and end post on one side only and provided with horizontal lines and two diagonals interwoven with horizontal wires, of barbed wire weighing 9.38 KG per 100 m (minimum), between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete. (Cost of posts, struts, earth work and concrete work to be paid for separately) :-Payment to be made per metre cost of total length of barbed wire used. With G.I. barbed wire M 381.7 0.00 0.00 0.00 220 161.7
2.111 206163 Dismantling manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge : Water bound macadam road, Wet mix macadam road, Granular sub-base or any type of base and sub base course laid in between wearing course and subgrade. M2 3725.4 0.00 0.00 0.00 742 742 742 742 742 12.1 3.3
2.112 206174 Dismantling steel work in single sections including dismembering and stacking within 50 metres lead in: Channels, angles, tees an d flats KG 330 0.00 0.00 0.00 220 110
2.113 206241 Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter M 633.1468 0.00 0.00 0.00 66 66 66 66 66 231.6468 60.5 11
2.114 206270 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer’s specifications including appropriate priming coat, preparation of surface, etc. complete. On steel work M2 1000 0.00 0.00 0.00 200 200 200 200 200
2.115 206352 Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. M2 2513 0.00 0.00 0.00 485 485 485 485 485 88
2.116 206353 Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. EA 102.504 0.00 0.00 0.00 12 12 12 12 12 42.504
2.117 206373 Providing & fixing mild steel round holding down bolts including nuts & washer plates complete KG 125 0.00 0.00 0.00 25 25 25 25 25
2.118 206482 Providing and fixing expansion hold fasteners on C.C. /R.C.C./Brick masonry surface backing including drilling necessary holes and the cost of bolt etc complete. Wedge expansion type Fastener with threaded dia 10 mm EA 50 0.00 0.00 0.00 10 10 10 10 10
2.119 206495 Providing & Laying C.C in brick ballast in 1:6:12 (1 Cement : 6 Coarse Sand : 12 Brick aggregate) mix. ( E ) M3 771.242 0.00 0.00 0.00 31 31 31 31 31 485.1 11.572 49.5 18.04 7.7 19.8 3.63 4.4 13.2 3.3
2.12 206496 Supplying, laying & spreading machine crushed 20 mm good quality blue colour stone aggregates including compacting the same. M3 1098.56 0.00 0.00 0.00 46 46 46 46 46 726 18.15 77 21.56 4.4 5.5 0.55 13.2 2.2
2.121 206497 Supplying chemical emulsion in sealed containers including delivery, diluting and applying for antiweed treatment in yard as specified by manufacturer. M2 3971.664 0.00 0.00 0.00 305 305 305 305 305 5.5 115.764 1815 158.4 49.5 110 16.5 22 132 22
2.122 206536 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion powder coated aluminium (minimum thickness of powder coating 50 micron) KG 16.5 0.00 0.00 0.00 16.5
2.123 206537 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coating 50 micron) KG 16.5 0.00 0.00 0.00 16.5
2.124 206624 Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design : With common burnt clay F.P.S. (non-modular) bricks of class designation 7.5 EA 9.4 0.00 0.00 0.00 1 1 1 1 1 4.4
2.125 206628 Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour : Two coats M2 151.195 0.00 0.00 0.00 151.195
2.126 206631 Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. Flexible pipe 40 mm dia EA 5 0.00 0.00 0.00 1 1 1 1 1
2.127 206659 Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) : 25 mm nominal bore EA 5 0.00 0.00 0.00 1 1 1 1 1
2.128 206660 Providing and fixing GI union in GI pipe including cutting & threading the pipe & making long screws etc. complete (new work). 20mm nominal bore EA 5 0.00 0.00 0.00 1 1 1 1 1
2.129 206698 Making construction joint, first cutting groove 5x30 mm deep with special blade in concrete road and then filling the grooves 5x15 mm deep with polysulphide sealant over an expanded polyethene backer rod including rounding of the edges, etc. all complete. M 99 0.00 0.00 0.00 99
2.13 206853 Add for using extra cement in the items of design mix over and above the specified cement content therein. KG 75484.144 0.00 0.00 0.00 8380 8380 8380 8380 8380 12262.404 9485.74 5060 4180 506 770 1320
2.131 206871 Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) including manufactured and derived from Recycled Concrete Aggregate (RCA) upto 25% : 4 graded stone aggregate 12.5mm nominal size inclcuding (Recycled Conceret Aggregate (RCA) upto 25%)) M2 50 0.00 0.00 0.00 10 10 10 10 10
2.132 206921 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement,water tanks, roof slabs, podiums, reservior,sewage & water treatment plant, tunnels/subway and bridge deck etc., prepared by mixing in the ratio of 5:2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3:1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative ( internal) side with the help of synthetic fibre brush.The material shall meet the requirements as specified in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure in negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry for 10 years against any leakage. For horizontal surface one [email protected] per sqm. M2 250 0.00 0.00 0.00 50 50 50 50 50
2.133 206922 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement,water tanks, roof slabs, podiums, reservior,sewage & water treatment plant, tunnels/subway and bridge deck etc., prepared by mixing in the ratio of 5:2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3:1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative ( internal) side with the help of synthetic fibre brush.The material shall meet the requirements as specified in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure in negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry for 10 years against any leakage. For vertical surface two [email protected] kg per sqm per coat M2 250 0.00 0.00 0.00 50 50 50 50 50
2.134 206923 Providing and mixing integral crystalline admixture for waterproofing treatment to RCC structures like basement raft, retaining walls, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc. at the time of transporting of concrete into the drum of the ready mixed truck, using integral crystalline admixture @0.80% (minimum) to the weight of cement content per cubic meter of concrete)or heigher as recommended by the manufacturer's specification in reinforced cement concrete at site of work. the material shall meet the requirements as specified in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90%, compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure. The crystalline admixture shall be capable of self- healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the Engineer-in-charge. The product performance shall carry gurantee for 10 years against any leakage. KG 250 0.00 0.00 0.00 50 50 50 50 50
2.135 207033 Providing and laying autoclaved aerated concrete (AAC) blocks masonry 100mm/125mm thick with Grade-1 AAC blocks of density 551 to 650 KG/CUM conforming to IS:2185 (Part 3) in super structure above plinth level up to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rate includes providing and placing in position 2 Nos 6 mm dia M.S. bars at every third course of masonry work. M3 50 0.00 0.00 0.00 10 10 10 10 10
2.136 207113 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design :150 mm diameter S.W. pipe M 25 0.00 0.00 0.00 5 5 5 5 5
2.137 207442 Extra for providing mechanical device chain and crank operation for operating rolling shutters - upto 16.80 sqm in the area M2 7.2 0.00 0.00 0.00 1 1 1 1 1 1.1 1.1
2.138 207462 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 cement : 4 manufactured sand derived from Recycled Concrete Aggregate (RCA) : 8 graded stone aggregate 40 mm nominal size Recycled Aggregate (RCA) M3 728.9509 0.00 0.00 0.00 52 52 52 52 52 205.3469 99.044 44 11 12.1 49.5 17.16 7.7 9.9 13.2
2.139 207465 Cutting of cores in reinforced concrete structures upto 200 mm dia. and 300 mm depth EA 140.7 0.00 0.00 0.00 20 20 20 20 20 31.9 5.5 3.3
2.14 207501 Providing and fixing 25 mm thick Fibreglass Reinforced Plastic grating of mesh size 38X38 mm, rib thickness 5-7 mm complete as per approved drawings in colour as approved by TPDDL EIC. M2 250 0.00 0.00 0.00 50 50 50 50 50
2.141 207525 Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 manufactured sand derived from Recycled Concrete Aggregate (RCA) : 6 graded stone aggregate 20 mm nominal size (Recycled Aggregate (RA) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth M2 102.7 0.00 0.00 0.00 19 19 19 19 19 7.7
2.142 207538 Providing and fixing unplasticised P.V.C. in Stainless Steel finished connection pipe with brass unions: 45 cm length-15 mm nominal bore. EA 5 0.00 0.00 0.00 1 1 1 1 1
2.143 208350 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 manufactured sand derived from Recycled Concrete Aggregate (RCA) : 6 graded stone aggregate 20 mm nominal size Recycled Concrete Aggregate (RCA) M3 75.611 0.00 0.00 0.00 5 5 5 5 5 8.074 17.787 3.3 11 0.55 3.3 3.3 3.3
2.144 208351 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:5:10 (1 cement : 5 manufactured sand derived from Recycled Concrete Aggregate (RCA) : 10 graded stone aggregate 40 mm nominal size Recycled Aggregate (RCA) ) M3 25 0.00 0.00 0.00 5 5 5 5 5
2.145 208352 Providing and fixing precast reinforced cement concrete work in cable trench covers, including the cost of required centering, shuttering but, excluding cost of reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). M3 214.692 0.00 0.00 0.00 10 10 10 10 10 87.45 37.642 13.2 1.1 2.2 15.4 1.1 2.2 1.1 3.3
2.146 208401 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 200 mm dia (OD-200 mm & ID-175 mm nominal) M3 71.6 0.00 0.00 0.00 2 2 2 2 2 6.6 55
2.147 208411 Providing and laying 60mm thick factory made cement concrete paver block of approved shape and colour of M -30 grade made of C&D waste by block making machine with vibratory compaction laid in required pattern and including over 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge. M2 250 0.00 0.00 0.00 50 50 50 50 50
2.148 208892 Providing and laying Geotextile membrane, 120 gsm non woven, 100% polyester of thickness 1 to 1.25 mm. M2 15 0.00 0.00 0.00 3 3 3 3 3
2.149 208893 Providing and filling Brick bats of 40 mm nominal size under flooring etc. i/c compaction by ramming and levelling top surface complete M3 10 0.00 0.00 0.00 2 2 2 2 2
2.15 208894 Supplying and laying charcoal in rain water harvesting recharge pit. M3 5 0.00 0.00 0.00 1 1 1 1 1
2.151 208922 Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). KG 500 0.00 0.00 0.00 100 100 100 100 100
2.152 208923 Providing and fixing stainless steel (SS-304 grade) friction hinges to the side/ top hung uPVC windows, of approved quality, with necessary stainless steel screws etc. as per direction of Engineer-in-charge. 200 x 19 x 1.9 mm EA 20 0.00 0.00 0.00 4 4 4 4 4
2.153 209063 Providing and applying two coats of High Albedo paint having minimum Solar Reflective Index (SRI) 108 (with solar reflectance & thermal emittance tested as per ASTM) C 1549 and ASTM C 1371 respectively), VOC less than 10 cc/gm. The coating thickness and the methodology of application shall strctly as per manufacturer's specifications and as approved by Engineer-in-Charge. Surface preparation includes cleaning with metal wire brush to remove all dust, fungus etc., washing with water all complete. The contractor shall give guarantee for the perfomance of SRI and also the durabitity of coating, all complete as per direction of Engineer-in-Charge. M2 1059.8 0.00 0.00 0.00 175 175 175 175 175 55 55 55 19.8
2.154 209064 Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour all complete to achieve even shade and colour: new work (two or more coats) over and including water thinnable priming coat with cement primer having COC content less than 50g/L M2 2488.8 0.00 0.00 0.00 485 485 485 485 485 63.8
2.155 209065 Finishing walls with readymix Premium acrylic emulsion paint (Company Depot Tinted) having VOC less than 50 gm/litre and UV resis tance as per IS:15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade with silicon additives. N ew work (Two or more coats applied @ 1.43 litre/ 10 sqm Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm. M2 71.5 0.00 0.00 0.00 71.5
2.156 209068 Brickwork with Recycled CC Bricks of size 230x110x75 mm (M10 Grade) in foundation and plinth in :- (a) Cement Mortar 1:6 (1 cement : 6 coarse sand) M3 205.5 0.00 0.00 0.00 40 40 40 40 40 2.2 3.3
2.157 209069 Brickwork with Recycled CC Bricks of size 230x110x75 mm (M10 Grade) in superstructure above plinth level upto floor V level in all shapes and sizes :- (a) Cement Mortar 1:4 (1 cement : 4 coarse sand) M3 50 0.00 0.00 0.00 10 10 10 10 10
2.158 209412 Drilling suitable holes in reinforced or plain cement concrete with power driven drill machine to a minimum depth of 100mm upto 2 00mm in RCC beams, lintels, columns and slabs to introduce steel bars for sunshades/balconies including fixing the steel bars in p osition using epoxy resin anchor grout of approved make but excluding the cost of reinforcement, all complete as per direction of Engineer-In-Charge. Upto and including 12mm dia. (approved make HILTI) EA 275 0.00 0.00 0.00 275
2.159 209413 Design & detailing, testing and installation of appropriate sizes of reinforcement anchorages or splices fixed into existing hard ened concrete by injecting adhesives in drilled holes after cleaning of the holes to connect new reinforcement to existing walls a nd slab. BA shall visit the site and collect necessary details required for carrying out the work and submit complete proposal for TPDDL approval before execution of work at site. (approved make HILTI) - 16 to 28 dia. bar EA 825 0.00 0.00 0.00 825
2.16 209415 Supplying and Filling screened soil procured from MCD approved C&D waste recycling plant and carriage for all leads including spreading in required thickness as per the directions of TPDDL Engineer-In-Charge and compacting under optimum moisture conditions to give at least 95% of the maximum dry density (proctor density). Cubical quantity of compacted earth only shall be measured and paid. M3 750 0.00 0.00 0.00 150 150 150 150 150
2.161 209428 Attaining IGBC Green Service Buildings Certification for Substation Building. The scope of services towards attaining the desired IGBC Rating would include but not limited to the following: i. Project Registration with IGBC ii. Performing the feasibiliy iv. Facilitation, Documentation and Submission of project details for IGBC rating v. Simulation services including Energy Simulation, Day-light Simulation etc. vi. IGBC Review & Comments response to achieve the anticipated rating For detailed scope of work, refer Special Conditions of Contract. The cost shall shall be inclusive of all expenses including Application Fees, Council Fees, Consultancy Fees, Travel, Liasioning with IGBC for Certification and Documentation etc. IGBC Application Fees shall be paid on producing payment receipts by BA and balance payment shall be made after the Certification is received from IGBC. EA 5 0.00 0.00 0.00 1 1 1 1 1
2.162 209429 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources and using recycled concrete aggregate (RCA) as coarse aggregate and fine aggregate within permissible utilization of 20% each, Portland Pozzolana /Ordinary Portland/Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum M3 75 0.00 0.00 0.00 15 15 15 15 15
2.163 209452 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 1200 mm dia. R.C.C. pipe M 25 0.00 0.00 0.00 5 5 5 5 5
2.164 209456 Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.80 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineerin-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. M2 75 0.00 0.00 0.00 15 15 15 15 15
2.165 209457 Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. Made of G.I. wire of dia. 4 mm, PVC coated to achieve outer dia not less than 5 mm in required colour and shade M2 154 0.00 0.00 0.00 137.5 16.5
2.166 new-1 Finishing walls with readymix Premium acrylic emulsion paint (Company Depot Tinted) having VOC less than 50 gm/litre and UV resistance as per IS:15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade with silicon additives. New work (Two or more coats applied @ 1.43 litre/ 10 sqm Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm. M2 8075 0.00 0.00 0.00 1615 1615 1615 1615 1615
Total All Inclusive Amount (Rs) - Civil Services 0.00
Total All Inclusive Amount (Rs.) Electrical + Civil Services 0.00
TENDER NO: TPDDL/ENGG/ENQ/200001981/26-27
DESCRIPTION: 1 Year RC for EHV Bay Extension with associated Electrical & Civil works for Deposit & CAPEX Schemes
TYPE OF TENDER: OPEN TENDER
Last Date of receipt of pre-bid queries, if any
Sr. No. Detailed Reference to Tata Power Technical Document. Please specify Document No / Clause No / Page No Description as per Bid Document Query / Clarification Tata Power DDL Reply Vendor name Email ID phone number
Supplier Sustainability Index Questionnaire
Vendor Name : Vendor Code : Date : Vendor Code
Parameter Category (Marks) S. No. Questions Detail Description Max Score Scoring Criteria
Marks Gain Response by BA Remark By BA
Environment (100) Carbon Footprint (20) 1 Does your organization calculate GHG emissions? Please select the suitable option (Select any one response): a) Yes, we calculate the GHG emissions and data is available since FY ….... b) No, but we have plans to start GHG inventorization from FY ….... c) No, we do not compute GHG emissions, nor we have any plans in near future to do so. 5 a) 5 b) 2 c) 0
2 Which GHG emissions your organization has computed and what is their value? Please select the suitable option (multiple responses can be selected): a) Scope-1 (Direct GHG emissions from sources owned or controlled by the organization); Emissions for FY 25: .................. b) Scope-2 (Indirect GHG emissions from the generation of purchased electricity, steam, heating, and cooling consumed by the organization) Emissions for FY 25: .................. c) Scope-3 (Indirect emissions from activities upstream and downstream of the value chain, i.e. with purchasers and suppliers) Emissions for FY 25: .................. 10 a) 4 b) 4 c) 2
3 Has your organization set targets & programs to reduce carbon footprint in its overall logistic operation? Please select the suitable option (Select any one response): a) Yes, our organization has set targets and programs to reduce carbon footprint. b) No, our organization does not have set targets and programs to reduce carbon footprint. c) Partially, our organization has some initiatives but no specific targets or programs in place. d) Unsure/ Not applicable 5 a) 5 b) 0 c) 3 d) 0
Energy Consumption and Efficiency (10) 4 How does your organization manage and optimize energy consumption? Please select the suitable option (multiple responses can be selected): a) We regularly conduct energy audits and implement energy-efficient technologies. b) We have designated energy management teams to monitor and improve energy usage. c) We actively promote energy-saving practices and provide employee training on energy conservation. d) We have implemented automated systems to track and control energy consumption. e) Our organization does not have specific measures in place to manage or optimize energy consumption. 5 a) 2 b) 1 c) 1 d) 1 e) 0
5 Does the organization monitor Stack Emissions (source specific) and/ or Ambient Air Emissions (area wide) in its premises? a) Yes, the organization regularly monitors both Stack and Ambient Air Emissions b) Yes, the organization monitors Stack Air Emissions only c) Yes, the organization monitors Ambient Air Emissions only d) No, the organization does not monitor Stack or Ambient Air Emissions 5 a) 5 b) 3 c) 3 d) 0
Waste Management/ Packaging (10) 6 What are the different categories of waste which your organization generates? Please select the suitable option (multiple responses can be selected): a) Hazardous Waste and/or Battery Waste b) Plastic Waste c) Metal Waste d) Biomedical Waste e) Municipal Soild Waste & other waste streams 5 a) 1 b) 1 c) 1 d) 1 e) 1
7 Does your organization has a process to recycle these waste categories either in-house or through external agency? a) Yes, all types of waste generated by us is recycled b) Yes, ....% of our waste goes for recycling c) We are not aware if any of our waste is recycled 2 a) 2 b) 1 c) 0
8 How does the organization incorporate packaging reduction, reuse, and recycling in its purchasing practices? Please select the suitable option (multiple responses can be selected): a) We actively seek suppliers who offer minimal packaging or sustainable packaging options b) We prioritize reusable packaging solutions when available and feasible c) We have established policies to encourage recycling of packaging materials d) Our organization does not specifically address packaging reduction, reuse, or recycling in purchasing practices 3 a) 1 b) 1 c) 1 d) 0
Water Management (15) 9 Has your organization set specific targets to reduce water consumption? a) Yes, our organization has set specific targets to reduce water consumption b) Our organization has some standalone initiatives to reduce water consumption, but no specific targets are set c) No standalone initiatives or targets are there to reduce water consumption 3 a) 3 b) 2 c) 0
10 Do you have a functional Rainwater Harvesting System at your facility? a) Yes with a capacity of …….KLD in …... sqm of catchment area b) No, but we have plans to put a RWH system by …..... c) No, we do not have any plans of putting up RWH in our premises 2 a) 2 b) 1 c) 0
11 What is the source wise consumption of water in your organization? Please select the suitable option (multiple responses can be selected): a) Underground Borewell approved by local authority; ..... KL b) Underground Borewell not approved by local authority; ..... KL c) Piped Municipal water supply; ..... KL d) Water Tanker; ...... KL e) Packaged Drinking Water; ...... KL f) Treated Waste Water; ..... KL g) Water consumption is not monitored in our organization 7 a) 1 b) 1 c) 1 d) 1 e) 1 f) 2 e) 0
12 Do you have any waste water treatment facility in your organization? a) Yes, we have waste water treatment facility of ….... KLD b) No, we do not have waste water treatment facility 3 a) 3 b) 0
Innovation for Sustainability (20) 13 How is your organization fostering innovation to address sustainability challenges? Please select the suitable option (multiple responses can be selected): a) By investing in internal R&D initiatives focused on sustainability. b) By establishing cross-functional teams dedicated to innovation in sustainability. c) By partnering with external stakeholders such as startups, research institutions, or NGOs. d) By encouraging employee-led sustainability projects and ideas. e) By participating in industry collaborations or consortia focused on sustainability innovation. f) Unsure/ Not applicable 10 a) 2 b) 2 c) 2 d) 2 e) 2 f) 0
14 Please share examples in support of the above. free text 10 5 marks of each example (mention any two examples)
Continuous Improvement (15) 15 Has your organization set specific ESG targets, and how are they monitored? a) Yes, our organization has set specific ESG targets, and they are monitored through regular performance assessments via well defined KPIs. b) Partial - While we do not have specific targets, but we monitor key parameters related to ESG. c) No, our organization has not set any specific ESG targets. 5 a) 5 b) 2 c) 0
16 How does your organization engage in continuous improvement in sustainability practices? Please select the suitable option (multiple responses can be selected): a) By conducting regular sustainability audits and assessments. b) By implementing feedback mechanisms from stakeholders on sustainability initiatives. c) By setting and reviewing sustainability goals on a regular basis. d) By participating in sustainability-focused training and education programs. e) By benchmarking against industry best practices on sustainability. f) By integrating sustainability considerations into decision-making processes. g) Other (Please specify) ________________________ 5 1 mark for each response with a maximum of 5 marks
17 Has the organization taken any initiative(s) to improve the Recyclability Ration of its products (End of Life Treatment) to reduce the impact of manufactured products on the environment and society? a) Yes [please share the details] b) No 5 a) 5 b)0
Renewable Energy (10) 18 Has your organization installed solar panels in the facility for renewable power generation? a) Yes for ….. KW b) No, but we purchase solar power from outside c) No, we do not have solar power in our energy mix 5 5 if details are provided else 0
19 Please provide the % share of solar in overall energy consumption (if response to previous question is Yes) …. %
20 Are you using Electric Vehicles in your organization setup? a) Yes, we have …... nos. of EVs deployed b) No, we do not have any EV in our setup 5 5 if details are provided else 0
21 In case response to previous question is "Yes", please share the details of EVs deployed in your organization setup with respect to type of usage etc. free text
Social (50) Labor Practices (20) 22 How does your organization ensure fair wages, working hours, and safe working conditions? Please select the suitable options (multiple responses can be selected): a) By implementing regular wage reviews and adjustments to ensure fair compensation. b) By adhering to legal regulations and industry standards regarding working hours. c) By conducting regular workplace inspections and safety audits to maintain safe working conditions. d) By providing training and education on labor rights and safety protocols to employees. e) By establishing grievance mechanisms for employees to report concerns about wages or working conditions. f) By collaborating with labor unions or worker advocacy groups to address labor-related issues. 10 a) 2 b) 2 c) 2 d) 1 e)2 f) 1 Maximum 10 marks
23 Does your organization have a presence of an Internal Review Committee and Policies to ensure the workplace is free of physical abuse, corporal punishment, physical contact with the intent to injure or intimidate, and disciplinary measures that cause physical discomfort? a) Yes, our organization has an Internal Review Committee and Policies in place to ensure the workplace is free from physical abuse and corporal punishment. b) Yes, our organization has Policies in place to ensure the workplace is free from physical abuse and corporal punishment, but there is no specific Internal Review Committee. c) No, our organization does not have specific Policies or an Internal Review Committee addressing physical abuse and corporal punishment. 5 a) 5 b) 3 c) 0
24 Can you provide information on diversity, equity, and inclusion within your workforce? a) Yes, our organization actively collects and reports data on diversity, equity, and inclusion metrics within our workforce. b) Yes, our organization has implemented initiatives and programs to promote diversity, equity, and inclusion within our workforce but does not currently collect or report data on diversity, equity, and inclusion within our workforce. c) No, our organization does not have specific initiatives or programs focused on diversity, equity, and inclusion within our workforce. 5 a) 5 b) 3 c) 0
Supply Chain Labor Standards (10) 25 How do you ensure that your suppliers adhere to fair labor practices? Please select the suitable option (multiple responses can be selected): a) By conducting regular audits or assessments of suppliers' labor practices. b) By requiring suppliers to sign agreements or contracts that include provisions for fair labor practices. c) By providing training and guidance to suppliers on fair labor standards and expectations. d) By engaging with suppliers in dialogue and collaboration to address any issues related to fair labor practices. e) By sourcing from suppliers with recognized certifications or accreditations related to fair labor practices. 5 a) 1 b) 1 c) 1 d) 1 e) 1
26 What steps are taken to address human rights issues in your supply chain? Please select the suitable option (multiple responses can be selected): a) Regular audits or assessments of suppliers' human rights practices. b) Requiring suppliers to adhere to codes of conduct or standards that include human rights provisions. c) Providing training and guidance to suppliers on human rights standards and expectations. d) Engaging with suppliers in dialogue and collaboration to address human rights issues. e) Sourcing from suppliers with recognized certifications or accreditations related to human rights practices. 5 a) 1 b) 1 c) 1 d) 1 e) 1
Community Engagement (20) 27 To promote social responsibility in its value (supply) chain, is there any visible commitment from the Top Management of the organization to integrate ESG criteria under a Responsible Supply Chain Policy/Program such as but not limited to Ethical, Social, Environmental and Gender Equality criteria, and health and safety, in its purchasing, distribution and contracting policies and practices to improve consistency with social responsibility objectives. a) Yes, there is visible commitment from Top Management to integrate ESG criteria into a Responsible Supply Chain Policy/ Program. b) Partially, there is some commitment from Top Management, but not all aspects of ESG criteria are integrated into the Responsible Supply Chain Policy/Program. c) No, there is no visible commitment from Top Management to integrate ESG criteria into a Responsible Supply Chain Policy/Program. 10 a) 10 b) 5 c) 0
28 Describe your organization's initiatives for supporting local communities where you operate. Please select the suitable option (multiple responses can be selected): a) We actively participate in community outreach programs and events. b) We contribute to local charities or nonprofits through donations or volunteer work. c) We collaborate with local stakeholders to address community needs and concerns. d) We provide employment opportunities and skill development programs for community members. e) We sponsor or support local educational or environmental initiatives. 10 a) 2 b) 2 c) 2 d) 2 e) 2
Governance (50) Ethics and Anti-Corruption (20) 29 Does the organization measure the following information:- Total number of substantiated complaints received concerning breaches of customer privacy? a) Yes, it is measured, there were ….. nos. in FY 25 b) No, it is not measured 5 a) 5 b) 0
30 Does the organization measures the following information:- Total number of identified leaks, thefts, or losses of customer data? a) Yes, it is measured, there were ….. nos. in FY 25 b) No, it is not measured 5 a) 5 b) 0
31 How does your organization prevent and address corruption risks? Please select the suitable option (multiple responses can be selected): a) By implementing robust anti-corruption policies and procedures. b) By conducting regular training on anti-corruption measures for employees. c) By establishing clear channels for reporting corruption concerns. d) By conducting periodic risk assessments to identify and mitigate corruption risks. e) By collaborating with law enforcement agencies or regulatory bodies to address corruption issues. 5 a) 1 b) 1 c) 1 d) 1 e) 1
32 Has the organization established a Code of Business Ethics, endorsed by senior management indicating organization’s values, principles, standards, and norms of behavior? a) Yes, our organization has established a Code of Business Ethics endorsed by senior management. b) No, we do not have any Code of Business Ethics endorsed by our senior management as of now, but we plan to introduce it by FY ...... c) No, we do not have any Code of Business Ethics endorsed by our senior management, nor we have any immediate plans for the same. d) Unsure/ Not applicable. 5 a) 5 b) 2 c) 0 d) 0
Transparency and Reporting (15) 33 How does your organization communicate its ESG efforts to stakeholders? Please select the suitable option (multiple responses can be selected): a) Through regular reports or publications dedicated to ESG initiatives. b) By hosting stakeholder meetings or forums specifically focused on ESG topics. c) Via dedicated sections on the company website or sustainability reports. d) Through social media platforms or other digital communication channels. e) By participating in industry conferences or events focused on sustainability. 5 a) 1 b) 1 c) 1 d) 1 e) 1
34 Is there a well-established governance structure for regulating/governing its policies? a) Yes, there is a well-established governance structure in place. b) Partially, there is some governance structure, but it's not well-established. c) No, there is no well-established governance structure in place, but we intend to establish the same by FY ..... d) No, there is no well-established governance structure in place, nor do we have any plans to establish the same in near future. 5 a) 5 b) 3 c) 1 d) 0
35 Are all labor, health, and safety policies, practices, and expectations communicated to all employees and suppliers in local or appropriate languages? a) Yes, all policies, practices, and expectations are communicated in local or appropriate languages. b) Partially, some policies, practices, and expectations are communicated in local or appropriate languages, but not all. c) No, not all policies, practices, and expectations are communicated in local or appropriate languages. 5 a) 5 b) 3 c) 0
Certifications (15) 36 Does your organization have following certifications (valid till date-please mention validity) Please select the suitable option (multiple responses can be selected): a) ISO 9001 accreditation b) ISO 20400:2017 or equivalent c) SA 8000 or equivalent d) ISO 14001 certification e) ISO 18001/45001 or equivalent f) ISO/IEC 27001 or equivalent g) Other (Please specify) ________________________ 15 a) 1 b) 5 c) 4 d) 2 e) 1 f) 1 g) 1
What is GHG emission?
GHG emission stands for Greenhouse Gas emission, which refers to the release of gases into the Earth's atmosphere that trap heat and contribute to global warming and climate change.
Key Greenhouse Gases (GHGs):
1. Carbon dioxide (CO₂) – from burning fossil fuels like coal, oil, and gas.
2. Methane (CH₄) – from agriculture (e.g., livestock), landfills, and natural gas leaks.
3. Nitrous oxide (N₂O) – from fertilizers, agricultural activities, and combustion.
4. Fluorinated gases – synthetic gases from industrial processes (e.g., HFCs, PFCs, SF₆).
🔥 Why GHG Emissions Matter:
GHGs act like a blanket around the Earth. They trap heat in the atmosphere, which leads to:
· Rising global temperatures
· Melting glaciers and rising sea levels
· More extreme weather (storms, droughts, floods)
· Disruption of ecosystems and food supply
📏 Measuring GHG Emissions:
GHG emissions are usually measured in tonnes of carbon dioxide equivalent (tCO₂e) to account for the different warming potentials of each gas.
· 1 tonne of methane (CH₄) = ~28–36 tonnes of CO₂e over 100 years
· 1 tonne of nitrous oxide (N₂O) = ~265–298 tonnes of CO₂e
📊 Types of GHG Emissions (Scopes):
Scope Description Examples
Scope 1 Direct emissions from owned/controlled sources Company vehicles, fuel combustion on-site
Scope 2 Indirect emissions from purchased energy Electricity used in buildings or factories
Scope 3 All other indirect emissions in the value chain Business travel, waste, supply chain emissions
🏭 Why Are GHG Emissions Important?
Climate Change: GHGs are the primary drivers of global warming.
Regulatory Compliance: Many countries require GHG reporting.
Sustainability Goals: Companies track emissions to reduce their carbon footprint.
Investor & Customer Pressure: Transparency and climate responsibility matter.
Scope 1 Emission:
Scope 1 emissions refer to direct greenhouse gas (GHG) emissions from sources that are owned or controlled by an organization. These include:
Sources of Scope 1 Emissions:
1. Stationary Combustion – e.g., fuel burned in boilers, furnaces, generators.
2. Mobile Combustion – e.g., fuel used in company-owned vehicles.
3. Process Emissions – e.g., emissions from chemical processes in manufacturing.
4. Fugitive Emissions – e.g., leakage from refrigerants or gas pipelines.
Scope 1 Emission Calculation Formula:
Scope 1 Emissions (tCO₂e)=∑(Fuel Quantity×Emission Factor)
Fuel Quantity is the amount of fuel used (in litres, m³, kg, etc.).
Emission Factor is a standard value indicating how much CO₂ (or CO₂e) is emitted per unit of fuel used. These values are typically provided by:
IPCC (Intergovernmental Panel on Climate Change)
National databases (e.g., US EPA, UK DEFRA, India’s CEA)
Example Calculation:
Scenario: A company uses 10,000 litres of diesel in generators annually.
Emission Factor (diesel): ~2.68 kg CO₂/litre
10,000 litres×2.68 kg CO₂/litre=26,800 kg CO₂=26.8 tCO₂
So, the Scope 1 emissions from diesel use = 26.8 tonnes CO₂e
Scope 2 Emission:
🔌 Scope 2 Emissions – What Are They?
Scope 2 emissions are indirect greenhouse gas emissions from the generation of purchased electricity, steam, heating, or cooling consumed by your organization.
Even though these emissions occur at the power plant (not on-site), they are accounted for by the buyer of the energy to reflect true carbon responsibility.
📐 Scope 2 Emission Calculation Formula
Scope 2 Emissions (tCO₂e)=Electricity Consumed(kWh)×Emission Factor (kg CO₂e/kWh)÷1000
Electricity Consumed: in kilowatt-hours (kWh)
Emission Factor: varies by country and source (coal, gas, hydro, renewables, etc.)
Conversion factor ÷ 1000 to convert kg to tonnes (tCO₂e)
📊 Example Calculation
Your organization consumes 100,000 kWh of grid electricity annually
Emission factor for your grid = 0.82 kg CO₂e/kWh (common in coal-heavy grids like India)
📌 Emission Factor References (Typical Values)*:
Region Grid Emission Factor (kg CO₂e/kWh)
India (CEA, 2023) ~0.82
USA (EPA Avg.) ~0.40
Renewable Energy ~0.0
Scope 2 GHG emission calculation:
If require want help of chatgpt for calculation:
e.g. type below sentence in chatgpt
“My factory annual electricity consumption is 12000 kwh in india. calculate scope 2 GHG emission value for me.”
It will give below reply:
Thanks! Based on your input:
Annual electricity consumption = 12,000 kWh
Location = India
Grid Emission Factor (India, CEA 2023) = 0.82 kg CO₂e/kWh
📊 Scope 2 Emissions Calculation:
Scope 2 Emissions = 12,000 kWh×0.82 kg CO₂e/kWh=9,840 kg CO₂e
9,840kg CO₂e ÷ 1000 = 9.84tonnes CO₂e (tCO₂e)
Your factory’s Scope 2 GHG emissions = 9.84 tCO₂e per year
Scope 3 Emission:
🌐 Scope 3 Emissions – What Are They?
Scope 3 emissions are all other indirect GHG emissions that occur in your value chain — both upstream (supplier side) and downstream (customer side). These do not come from owned or directly controlled sources but are a major part of your overall carbon footprint.
🔍 Examples of Scope 3 Activities:
Category Examples
Upstream Purchased goods & services, transportation, business travel, waste
Downstream Use of sold products, product disposal, downstream transport, franchises
Employee-related Commuting, leased assets
📐 How to Calculate Scope 3 Emissions
Because Scope 3 involves many sources, each category may use a different approach:
✅ General Formula:
Emissions (tCO₂e)=Activity Data×Emission Factor
· Activity Data = e.g., amount of goods purchased, km traveled, tonnes of waste
· Emission Factor = standard GHG factor for that activity (from sources like DEFRA, GHG Protocol, etc.)
📊 Example Calculation – Purchased Goods
· Your factory purchases 5 tonnes of steel per year
· Emission factor for steel production = 1.9 tCO₂e per tonne
5 tonnes×1.9 tCO₂e/tonne=9.5 tCO₂e5
You would repeat this process for each major activity under Scope 3.
✏️ To Calculate Scope 3 for Your Factory, if require you can use open source available on web & provide below detail for calculation of scope 3:
1. Purchased goods (type and quantity)
2. Waste generated (in tonnes or kg)
3. Business travel data (km, flights, etc.)
4. Employee commuting (approximate number, distance, transport type)
5. Transport of goods (inbound/outbound, km and tonnes)
6. Other relevant Scope 3 activities
🌫️ Stack and Ambient Air Emissions – Overview
In air pollution control and environmental compliance, stack emissions and ambient air emissions refer to two key concepts for monitoring and managing air quality.
🔥 1. Stack Emissions (Point Source Emissions)
These are air pollutants emitted from a fixed source, such as a chimney, furnace, or exhaust stack of a factory, boiler, or power plant.
🏭 Key Characteristics:
· Controlled and measurable
· Emitted directly into the atmosphere
· Subject to environmental regulation and pollution control norms
📋 Typical Stack Pollutants:
· Particulate Matter (PM10, PM2.5)
· Sulphur Dioxide (SO₂)
· Nitrogen Oxides (NOx)
· Carbon Monoxide (CO)
· Carbon Dioxide (CO₂)
· Volatile Organic Compounds (VOCs)
· Heavy metals (e.g., lead, mercury, cadmium)
· Dioxins and furans
🧪 Measurement Method:
· Stack monitoring is done using Continuous Emission Monitoring Systems (CEMS) or manual stack sampling as per CPCB/MoEF norms.
· Results are usually reported in mg/Nm³ or ppm.
🌍 2. Ambient Air Emissions (Ambient Air Quality)
These refer to the quality of the air in the environment outside the facility — i.e., the air people breathe in surrounding areas. These include emissions from multiple sources (industry, vehicles, construction, etc.).
📋 Key Ambient Pollutants Monitored:
· NH₃ (Ammonia)
· Benzene, Benzo(a)pyrene
🧪 Measurement Method:
· Ambient Air Quality Monitoring is done using Ambient Air Quality Monitoring Stations (AAQMS).
· Reported in µg/m³ as per National Ambient Air Quality Standards (NAAQS) in India.
✅ Regulatory Standards (India – CPCB):
Pollutant Stack Limit (Typical) Ambient Air Limit (24-hr avg, Industrial Area)
PM 150 mg/Nm³ (stack) 100 µg/m³ (PM10), 60 µg/m³ (PM2.5)
SO₂ 100 mg/Nm³ 80 µg/m³
NOx 50–300 mg/Nm³ 80 µg/m³
CO 100 mg/Nm³ 2 mg/m³ (1-hr avg)
Limits vary by industry type, fuel, and state-specific rules.
Aspect Stack Emissions Ambient Air Emissions
Source From industrial stacks or chimneys From all sources in the open environment
Purpose Regulatory compliance & pollution control Public health & environmental monitoring
Monitoring Stack analyzers or sampling Ambient air monitoring stations
ESG stands for Environmental, Social, and Governance — a framework used to assess an organization’s sustainability, ethical impact, and corporate responsibility beyond traditional financial metrics.
📊 The Three Pillars of ESG:
1. Environmental (E)
Focuses on how a company impacts the natural environment.
· Carbon footprint (GHG emissions)
· Energy and water usage
· Waste management
· Pollution control (air, water, soil)
· Biodiversity and conservation
· Climate risk and adaptation
Looks at how a company manages relationships with employees, communities, and stakeholders.
· Labor practices and human rights
· Health and safety
· Diversity, equity & inclusion (DEI)
· Community engagement
· Customer satisfaction
· Supply chain responsibility
3. Governance (G)
Relates to the structure, ethics, and accountability of corporate leadership.
· Board composition and diversity
· Business ethics and anti-corruption
· Transparency and disclosure
· Executive compensation
· Shareholder rights
· Compliance and risk management
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_ENG-EHV-1016_Approved Make List - New Grid & Bay Extension Jobs.pdf
Tender Document • 1.18 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_ENG-EHV-1019_MS & GI Structural Steel for Electrical Works.pdf
Tender Document • 0.56 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_ENG-EHV-1026_AC Distribution Board Panel for Grids.pdf
Tender Document • 0.87 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_ENG-EHV-1034_33kV & 66kV Isolator.pdf
Tender Document • 0.72 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_ENG-GEN-4007_Earth Enhancement Compound.pdf
Tender Document • 2.00 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_ENG-GEN-4008-01_Cable Cleat (Two-Bolt Type).pdf
Tender Document • 0.84 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_ENG-GEN-4023_HDPE Pipes.pdf
Tender Document • 0.74 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_ENG-GEN-4024_Galvanized Iron(GI) Pipes.pdf
Tender Document • 1.29 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_ENG-GEN-4038_Danger Notice Plate.pdf
Tender Document • 1.00 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_ENG-GEN-68_Fire retardant coating for cable.pdf
Tender Document • 0.19 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_ENG-HV-2001 GI earth pipe.pdf
Tender Document • 2.60 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_ENG-LV-3037_High Mast Lighting with LED Flood Lights.pdf
Tender Document • 0.20 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_TPDDL-SID-1012_Trefoil Clamp for Single Core 1000 sqmm Cables.pdf
Tender Document • 0.41 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_TPDDL-SID-1016_Earthing Philosophy for EHV Project Jobs.pdf
Tender Document • 1.97 MB
Tender Document_20260726205826606_Tender Document_Annexure II – Technical Specifications_TPDDL-SID-1027_Cable Mounting Structure for 66kV Cable.pdf
Tender Document • 3.45 MB
Tender Document_20260726205826606_Tender Document_Annexure X – GCC_Composite Work.pdf
Tender Document • 2.87 MB
Tender Document_20260726205826606_Tender Document_Annexure XIV – Safety Bid Document.pdf
Tender Document • 0.28 MB
Tender Document_20260726205826606_Tender Document_Annexure-1 Schedule of Item_Price Bid (BOQ).pdf
Tender Document • 0.57 MB
Tender Document_20260726205826606_Tender Document_Annexure-I Schedule of Item_BOQ.xlsx
Tender Document • 0.21 MB
Tender Document_20260726205826606_Tender Document_Isolator Make Preference.pdf
Tender Document • 0.23 MB
Tender Document_20260726205826606_Tender Document_Location-Scheme wise Detail BOQ.xlsx
Tender Document • 0.22 MB
Tender Document_20260726205826606_Tender Document_Pre-Bid_Query_Format_TPDDL-ENGG-ENQ-200001981-26-27.xlsx
Tender Document • 0.01 MB
Tender Document_20260726205826606_Tender Document_Supplier Sustainability Index (SSI) Questionnaire Format.xlsx
Tender Document • 0.03 MB
Tender Document_20260726205826606_Tender Document_TPDDL-ENGG-ENQ-200001981-26-27_Bay Extension Works.pdf
Tender Document • 1.04 MB
Prebid Query Reponses_20260823140543096_Prebid Query Reponses_Annexure-1 Schedule of Item_Price Bid (BOQ)_Revise.pdf
Corrigendum • 0.57 MB
Prebid Query Reponses_20260823140543096_Prebid Query Reponses_Annexure-I Schedule of Item_BOQ.xlsx
Corrigendum • 0.21 MB
Prebid Query Reponses_20260823140543096_Prebid Query Reponses_ENG-EHV-1042_Technical Specification of 3.3kV Sheath Bonding Cable.pdf
Corrigendum • 0.39 MB
Prebid Query Reponses_20260823140543096_Prebid Query Reponses_Prebid Query Responses.pdf
Corrigendum • 0.56 MB
Corrigendum Notification_20260826102522544.pdf
Corrigendum • 0.24 MB
Notification of Technically Qualified BAs_20260921203122674.pdf
Corrigendum • 0.19 MB
Notification of Technically Qualified BAs_20260921203122674.pdf
Corrigendum • 0.19 MB
Corrigendum Notification_20260826102522544.pdf
Corrigendum • 0.24 MB
Prebid Query Reponses_20260823140543096.zip
Corrigendum • 1.64 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .