Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.4 CrAccepted-AOC | ₹3.4 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹3.4 Cr+₹1.1 L (0.34%)Rejected-Finance | ₹3.4 Cr+₹1.1 L (0.34%) | L2 | Rejected-Finance L2 |
| 3 | L3₹3.6 Cr+₹28.4 L (8.45%)Rejected-Finance | ₹3.6 Cr+₹28.4 L (8.45%) | L3 | Rejected-Finance L3 |
| 4 | L4₹3.7 Cr+₹28.5 L (8.48%)Rejected-Finance | ₹3.7 Cr+₹28.5 L (8.48%) | L4 | Rejected-Finance L4 |
| 5 | L5₹4.2 Cr+₹81.8 L (24.3%)Rejected-Finance | ₹4.2 Cr+₹81.8 L (24.3%) | L5 | Rejected-Finance L5 |
Tender Value
₹4.0 Cr
EMD Value
₹8.0 L
Closing Date
9 Mar 2020, 6:00 pmClosed
Sr. Manager (E-E) Gaya Airport, Gaya
Sr. Manager (E-E), Airports Authority of India, Gaya Airport, Gaya
Construction of Technical Block cum Control Tower at Gaya Airport Gaya. SH Provision of D.G Sets and substation equipments
2020_AAI_43578_1
AAI/GY/SME (E)/Tech. Block/ DG sets/eNIT-07/19-20/
Open Tender
Electrical Works
Item Rate
180 days
Gaya Airport
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,120
Airports Authority of India
₹8.0 L
15 Jul 2020
19 Feb 2020
16 Mar 2020
20 Feb 2020
9 Mar 2020
20 Feb 2020
20 Feb 2020 - 2 Mar 2020
Amount
Supplying of following size of XLPE insulated PVC sheathed armoured power cable of aluminium conductor confirming to IS: 7098 Part - II -1985 with latest amendments etc. as required. (a) 3 core X 300 Sqmm. - 33 KV Grade (E).
Supply of HDPE Pipes of 160 mm dia as per IS: 4984 : 2016 of Material Grade : PE 63 & Pressure Rating of PN 8 etc as required.
Making horizontal boring by HDD method suitable for laying of 160 mm dia. (min.) HDPE Pipe at a min. depth of 1.2 meter below the common ground surface level i/c drawing & laying of HDPE Pipe etc complete as required ( Supply of HDPE pipe not included).
Laying of one no. XLPE/PVC insulated PVC sheathed power cable of 33 KV of size exceeding 120 Sqmm but not exceeding 400 Sqmm in the existing RCC/hume/stone ware/GI/HDPE Pipe as required
Laying of one no. XLPE/PVC insulated PVC sheathed power cable of 33 KV of size exceeding 120 Sqmm but not exceeding 400 Sqmm in the existing masonary open duct.
Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 33 kV grade as required.
3 core X 300 Sqmm.
Supplying and making cable route marker with cement concrete 1:2:4 (1 cement: 2 coarse: 4 graded stone aggregate 20 mm niminal size) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10 cm including inscription duly engraved as required.
Constructing masonry Chamber 120x120x100 cm inside, in brick work with common burnt clay F.P.S bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design.
Supply, Installation, testing and Commissioning of indoor type 500 KVA,3 Phase oil immersed natural cooled (ONAN) double wound with copper wire, continuous rated core type 33 KV/433 V, 50 Hz with off load tap changer +/- 7.5 % in 2.5% step transformer, delta connected on HT side and Star connected on LT side with vector group DYn11, cable box for HT & MV termination suitable for 33 KV, 3 core x 300 Sq.mm.XLPE cable on HT side and 1.1 KV, 3.5 core upto 400 Sq. mm cable connection arrangement on LT side complete with all accessories. Buchnolz relay and first fill of filtered oil and confirming to IS:1180 Level 2 & additional specifications etc as required.
SITC of Adapter Panel for extension of/ integration with the existing 33 KV VCB Panel board of Siemens make outgoings including complete connections,interconnections & other provisions whatever required as per site condition (If required)
Supplying of following size of 1.1 KV grade XLPE insulated PVC sheathed armoured power cable of aluminium conductor confirming to IS: 7098 Part - I-1988 with latest amendments etc. as required.
3.5 Core X 400 Sq. mm Cable
3.5 Core X 240 Sq. mm Cable
3.5 Core X 185 Sq. mm Cable
3.5 Core X 120 Sq. mm Cable
3.5 Core X 70 Sq. mm Cable
3.5 Core X 50 Sq. mm Cable
Supplying and Making end terminations with brass compression gland and aluminium lugs for following size of PVC insulated and PVC SHEATHED/XLPE aluminium conductor cable of 1.1 KV grade as required.
3.5 Core X 400 Sq. mm Cable
3.5 Core X 240 Sq. mm Cable
3.5 Core X185 Sq. mm Cable
3.5 Core X 120 Sq. mm Cable
3.5 Core X 70 Sq. mm Cable
3.5 Core X 50 Sq. mm Cable
Supply and Making end terminations for the following size of 33 KV grade Aluminium conductor XLPE insulated cable with heat shrinkable jointing kits etc. Complete with all accessories as required.
3 core X 300 Sqmm. indoor end termination.
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
450 mm width X 50 mm depth X 2.0 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “bends” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
450 mm width X 50 mm depth X 2.0 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc.
450 mm width X 50 mm depth X 2.0 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Above 95 sq. mm and upto 185 sq. mm size in the existing RCC/HUME/ METAL pipe as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Above 185 sq. mm and upto 400 sq. mm size in the existing RCC/HUME/ METAL pipe as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Above 35 sq. mm and upto 95 sq. mm size in the existing RCC/HUME/ METAL pipe as required.
Laying of one number XLPE insulated and PVC sheathed power cable of 1.1 KV grade in the existing open duct as required.
Above 35 Sq. mm upto 95 Sq. mm
Above 95 Sq. mm upto 185 Sq. mm
Above 185 Sq. mm upto 400 Sq. mm
Laying of one number XLPE insulated and PVC sheathed aluminium conductor cable of 1.1KV grade of following size on surface/ cable tray as required.
Above 35 sq. mm and upto 95 Sq. mm
Above 95 sq. mm and upto 185 sq. mm
Earthing with Copper earth plate 600 mm X 600 mm X 3 mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe 2.7 mtr. long etc. with charcoal and salt complete as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal and salt complete as required.
Providing and fixing 25 mm x 5 mm Copper strip in 40 mm dia G. I. pipe from earth electrode including connection with brass nut, bolts, spring, washer excavations and refilling etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in reces for connections etc. as required.
Providing and fixing 25 mm x 5 mm G. I. strip in 40 mm dia G. I. pipe from earth electrode including connection with G.I. nut, bolts, spring, washer excavation and refilling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in reces for connections etc. as required.
Supplying and fixing in position 3 Nos. of 9 ltr.. Capacity G.I. fire buckets duly painted with red oxicle and red paint and text. "FIRE" in white mounted on suitable size MS angle frame including grouting in floor or wall and filling dry sand etc. as required.
Supply, installation, testing and commissioning ISI maked (IS:15683) Fire Extinguisher, Carbon-di-oxide type capacity 4.5 kg. Flat base including valve, discharge hose of not less than 10mm dia, 1M long, and complete in all respects including initial fill with CO2 gas conforming to IS:307-1966 and wall suspension braket as required as per specification.
Supply,installation,testing and commissioning of 6kg ABC (Powder Type) Fire Extinguisher,Mild Steel Cylinders ISI marked fitted with pressure indicating gauge,internal tube,squeeze lever type valve fully charged with ABC 90 Powder (Monoammonium phoshate) pressured by Nitrogen complete in all respects including wall suspension bracket and conforming to IS:15683 as required as per specification.
Supply and fixing in position shock treatment charts written in "English" and "Hindi" duly mounted on wooden frame with glass covering / in fiber board etc. complete as required.
Supply and Fixing First Aid box made of MS with powder coating, front door transparent Made of Acrylic sheet of size 15"x11"x4" with two compartments, hinged cover with locking arrangement with necessary general medical grade tools and medicines.
Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc. as required.
250 mm dia.
Supply & fixing of fire retardant / extinguishing Electrical Insulated synthetic mat of 3 mm thick + 10% conforming to IS 15652: 2006, & other applicable standards, suitable for all voltages upto 33 KV AC and having minimum width of 1000 mm +/- 20 mm and including fixing the same at site by using adhesive/compound as per site requirement.
Supply & fixing of fire retardant / extinguishing Electrical Insulated synthetic mat of 2 mm thick + 10% conforming to IS 15652: 2006, & other applicable standards, suitable for all voltages upto 3.3 KV AC and having minimum width of 1000 mm +/- 20 mm and including fixing the same at site by using adhesive/compound as per site requirement.
Supply, Installation, Testing and Commissioning of 500 KVA (Minimum) Silent type D.G Set with DG set controller module mounted on DG set having AMF control, auto synchronizing, auto load sharing, auto load management, inbuilt metering & protection, communicable port (RS485) etc. and acoustic enclosure conforming to latest environment protection regulations for emmission and noise levels complete with Diesel Engine of suitable BHP (considering de-rating factor if any) at 1500 RPM, water cooled, (Radiator type), four stroke, electric start, turbo-charged & after cooled conforming to BS: 5514 with all standard accessories,coupled with Alternator of 500 KVA rating (minimum), brushless, self excited, self regulated and suitable for continuous operation , generating 415 V+/-5% Volts at 0.8 PF ( lag), 50Hz, 3 phase, 4 wire system generally conforming to BS: 2613 & IS: 4722. Both Engine and Alternator shall be mounted on common channel iron base frame, with fuel pipe line upto 10 meter ( to be concealed under floor), exhaust pipe line upto 15 meter ( to be erected with sufficient M.S supports and insulated, hood on top) , Antivibration mountings, residential type silencer, electric starter, batteries & battery charger, fuel tank of 990 ltrs. capacity with level indicator, other standard accessories etc complete as required. ( Refer Technical specification)
AT AND T ENGINEERS PVT LTD
UNIQUE TRANSFORMER SERVICE INDUSTRIES
Konstelec Engineers Pvt. Ltd.
CANELA ENTERPRISES PVT LTD
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .